Improvematerialbalancebyusingproper
flowmetercorrections
10.01.2011|Peramanu,S.,CanadianNaturalResourcesLtd.,Calgary,CanadaWah,J.C.,CanadianNatural
ResourcesLtd.,Calgary,Canada
Hereareguidelinestoincreaseaccuracyforflowmeasurements
Keywords:
Processplantsfrequentlyencountermassimbalances.Thesecanbeattributedtovariousfactors,butoftentheylead
backtoinappropriatemeasuringdevices,impropercalibration,incorrectinstallationorincorrectinterpretationofthe
measuredflows.Therearewellestablishedguidelinesavailabletoensureappropriateflowmeterselectionbasedon
theprocessconditionsandcontrolrequirements.
Instrumentvendorsfollowtheindustrystandardsandapprovedproceduresforflowmetercalibration,calculatingthe
calibrationfactorsbasedonthedataprovidedintheflowmeterspecificationdatasheets.Engineeringand
constructionservicecontractorsoftenfollowvendorguidelinesandstandardpracticestocorrectlyinstallthe
flowmeters.Thismeansthatmostflowmeterinstallations,therefore,meetacceptedprojectstandardsand
specifications.
Whatstheflowrate?
However,measuredflowinterpretation,normallyaprocessorproductionengineersresponsibility,isoftendone
withoutproperdirectionsorguidelines.Althoughitappearsstraightforwardthattheflowmetermeasurestheflowrate
andtheflowratevalueisreadfromthedisplay,significanterrorcanbeintroducediftheflowmeasurementconditions
arenotunderstoodandappropriatecorrectionfactorsarenotapplied.Accuratestreamflowinterpretationandcritical
massbalancereconciliationrequireunderstandingflowmetercharacteristicsandtheirassociatedmeasurement
uncertainties.Thisisofparticularimportancewheremassbalancesmaybeusedforhighlysensitiveprocesscontrol
operations,productionaccountingorgovernmentreportingonroyaltiesandemissions.
Thisarticleprovidesabackgroundontheimportanceofaccuratemeasurements,adescriptionofmeasurementerrors
andtheroleofuncertaintiesinmassbalanceandreconciliation.Flowmetercorrectionequationsarederivedfor
differentialpressureflow,volumetricflowandmassflowmeters,andflowcorrectionfactorsareprovidedforvarious
unitsofmeasurements(UOM).Flowmeteruncertaintyequationsarederivedfordifferentialpressureflow,volumetric
flowandmassflowmeters.
METERINGAPPLICATIONS
Toachievethemostaccurateflowmeasurement(minimumuncertainty),properflowsystemoperationand
maintenancemustbepracticedsothatmeteraccuracycapabilitiesarerealized.Periodicmaintenance,testingand
recalibrationareessentialbecausethecalibrationwillshiftovertimeduetowear,damageorcontamination.
Themaintenancemaybeonlyasecondaryequipmentcalibration,acompletesystemmechanicalinspection,an
actualthroughputtestagainstsomeagreeduponstandardsoranycombinationofthese.Theequipmentusedtotest
themeter,suchasthermometers,deadweighttests,pressuregauges,differentialpressuregauges,chromatographs
andprovers(usedforthroughputtests),musthaveaccuracycertificationandshouldbeapprovedandagreeduponby
theinterestedparties.Havingoperatorswhohavehadexperiencewithsimilarmeteringsystemsalsoincreasesthe
calibrationandtestprocedureconfidencelevels.Testequipmentitselfshouldberecertifiedperiodicallybytheagency
ormanufacturerthatoriginallycertifiedtheequipment.
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true
1/25
16/5/2016
Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011
Custodytransferoperations.
Incustodytransfermeasurement,themeasurementfurnishesquantityandqualityinformationthatcanbeusedasthe
basisforachangeinownershipand/orachangeinresponsibilityformaterials.
Custodytransfermeasurementisdistinctfromothermeasurementtypesbecauseofthecontractualnatureofthe
meter.Custodytransfermeteringmayrequireaccuracyof0.1%orbetter,whereascontrolmeasurementmaybe
acceptedata2%accuracyandoperationalmeasurementmayrequirea5%accuracy.Ahighintegritycustody
transfermeasurementsystemisaresultofcarefuldesignbasedonthespecificapplicationrequirementscomprising
fluidcontrol,conditioning,metering,computationandameansoftraceablesitedatavalidation.1,2
Custodytransfermanagementinvolvestheentirechainfromthecustodytransfermeteringconceptualizationtothe
finalproductionorsaledatareporting.Forexample,intheupstreamoilandgassector,measurementincludesall
intermediatestepssuchasmeasurementandsamplingguidelines,operationalprocedures,dataprocessing,data
transmissionandreconciliation,allocationorcustodytransferprocedures.Tosolvetheflowmeasurementequation,
itisimperativethateveryequationparameterbewellunderstoodandrepresented.
Aprimarycustodytransfermeasurementconsiderationistominimizeflowvariationsbymaintainingbetterflow
control.Forsituationswherethismaynotbepossible,ameterwithawiderangingflowcapacityisneeded.Ifasingle
meterwiththerequiredflowcapacitytocovertheintendedoperatingrangewithminimumuncertaintydoesnotexist,
usingmultiplemeterswithsometypeofmeterswitchingcontrolisrequired.Mostmetersoperatewithaspecified
uncertaintywithinthestatedflowcapacitylimitsthatistypicallyfrom25%to95%oftheflowmetermaximum
capacity.Forcustodytransfermeteringandcriticalcontrolmeasurement,itisimportanttomaintainthemeter
operationwithinthestatedflowcapacitylimits.
Errors.
Otherthansomeoperatingproblemsandpoormaintenancethatmayaffectthemeasurement,themaincauseoferror
isthefluidcharacteristicsanderrorsinfluiddensitycalculation.Forgases,mixturesaremoreaccuratelymeasuredif
thestreamhasrelativelyconstantcomposition.ThisallowsspecificPVTteststoberun,ordatamaybeavailablefor
commonmixturesfrompreviouswork.Ifthemixtureischangingrapidly,adensitometeroramassmetermaybe
requiredtodetermineanaccuratemeasurement.
Duringtimeswhenacustodytransfermeterisoutofserviceorregisteringinaccurately,aproceduremustbeinplace
formeasuringorestimatingdeliveries.Thisproceduremayneedtobeinaccordancewithregulatorystandardsifthe
meterflowisusedforregulatoryreporting.AnexampleofthisistherecentUSAEPAGreenhouseGasMandatory
ReportingRuleissuedSept.22,2009.Atypicalaccuracylimitfrom0.5%to2%maybeused,butmaybesetcloser
orwiderdependingonthespecificmetercostsandmeasurementability.
Forcustodytransfermeters,aproversystemormastermetershouldbeusedforthroughputtestingandrecalibration.
Thebestthroughputtestcanberundirectlyinserieswithaprover.Theprovercancomeinmanyforms,but
essentiallyitinvolvesabasicvolumethathasbeencertifiedbyagovernmentorindustrialgroup.Sincemostmeters
arenottotallylinear,testsmayhavetoberunoverthemetersoperatingrangetocalculatethecalibrationfactors
dependentontheflowcapacity.
Commercialmassbalancesoftware.
Thecharacteristicsandstrengthsofcommercialmassbalancesoftwaremayinclude:
Graphicallyaidedinputthatisuserfriendlyandintuitive
Interactivediagnosticsandfeedbackoninputerrors
Flexibilitytoselectthemeasurementunitsdesiredbytheuser
Flexibilityfortheusertoselectstartandendtimestoperformthereconciliation
Facilitytoconstructmassbalanceunitsbasedonplantconfigurationuserinput
Reconciliationprocessesperformlinear,nonlinearandinequalityconstraintsonthemeasurementdatatoproduce
reconciledmeasurementsandunmeasuredflowestimates
Algorithmforefficientiterationandfastconvergencetothesolution.SomealgorithmsmayincludetheMonte
Carlomethodtogeneratesetsofrandomvaluesformeasurementerrorswithinaprescribedrange(%uncertainty)
thataresolvedanditeratedinthereconciliationalgorithm
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true
2/25
16/5/2016
Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011
Algorithmtoensurenumericalrobustnessandpreventnumericalrunaway
Areconciledmassbalanceattheprocessingunitlevelorgroupofprocessingunits,progressingallthewayupto
theplantlevel
Abilitytoreconciletotalmassandselectedcomponentfractionsatthesametime
Reportingtooltoverifythepresenterrorinbalanceforeachnodeandgeneratethecustomizedreports.
Massbalanceandreconciliation.
Datareconciliation 3,4improvesprocessdataaccuracybyadjustingthemeasuredvaluessothattheysatisfythe
processconstraints.Theamountofadjustmentmadetothemeasurementsisminimizedsincetherandomerrorsare
expectedtobesmall.Datareconciliationcanbeformulatedbythefollowingconstrainedweightedleastsquares
optimizationproblem:
Minimizethefunction(knownasobjectivefunction):
Wherenisthenumberofmeasurements,Misthedifferencebetweenthereconciledandmeasuredvaluesof
measurements,iands iisthemeasurementistandarddeviation.Thevalue1/s 2whichisaninverseofvariance
(squareofstandarddeviation)istheweightfactorrepresentingtheaccuracyoftherespectivemeasurements.Sincea
highervalueofstandarddeviationimpliesthatthemeasurementislessaccurate,theabovechoicegiveslargerweights
tomoreaccuratemeasurements.
Theaboveobjectivefunctionminimizationissubjecttoconstraints:
fj(Mi1DMi)=0 j=1,....m
Wherefisthebalanceequationforthemeasurements(i=1,....n)andmisthenumberofbalanceequations.
Duringthereconciliationprocess,themeasurementscontainingsystematicbiasorgrosserrorsaredetectedby
comparingthedifferencebetweenthereconciledandmeasuredvaluestothemeasurementuncertainties.
IfAbs(DMi/Mi)>Uncertainty,measurementihasgrosserror.
Themeasurementscontaininggrosserrorsareeithereliminatedorappropriatelycompensatedfordatareconciliation
tobeeffective,asshowninFig.1.Inthisexample,thereconciliationinvolves:
M1 =stream1cumulativemeasuredmassflowoveraperiod(aday,forexample)
M2=stream2cumulativemeasuredmassflowoveraperiod
M3=stream3cumulativemeasuredmassflowoveraperiod
M4=measuredmassinventorygainordepletionoverthesameperiod
Fig.1.Flowreconciliationexampleforastoragetank.
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true
3/25
16/5/2016
Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011
Itisevidentthatbecauseofmeasurementerrorsthesemeasuredquantitiesdonotbalance,namely:
M1 1M2M31M4
Therefore,reconciliationisrequiredadjustmentstoeachofthemeasuredquantitiesneedtobemadetoobtainamass
balance:
(M1 1DM1 )1(M21DM2)=(M31DM3)1(M41DM4)
whereMiisanadjustment(+veorve)forthemeasuredquantityMi.
ItisevidentthatthereareinfinitesetsofMi,eachofwhichwillgivethedesiredmassbalance,i.e.,theywillsatisfy
theequationabove.OftheinfinitesetsofMi,theoneparticularsetthatcorrespondstotheleastamountoftotal
adjustmentisrequired.ThissuggeststhattheproblemtofindthisparticularsetofMicanbeformulatedasonethat
entailsminimizingafunction(usuallyreferredtoasobjectivefunction)subjecttosomeconstraints(massbalance
equations).Forthesimpleexamplehere,theproblemoffindingthatparticularsetofMicanbeformulatedas:
Minimizetheobjectivefunction:
Subjecttotheconstraint:
FLOWCORRECTIONS
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true
4/25
16/5/2016
Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011
Processindustryflowmeterscanbeclassifiedintothreebroadcategoriesthatincludedifferentialpressuremeters,
actualvolumetricflowmetersandmassflowmeters.Thedifferentialpressuremetersincludeorifice,venturi,nozzle,
wedge,pitottubeandannubarvolumetricflowmetersincludevortex,turbine,ultrasonicandmagneticandmass
flowmetersincludeCoriolisandthermalmeters.Themeteroperatingprinciplesandflowequationsareprovidedin
AppendixA.
Foranyoftheseflowmeters,thevendorshouldmakesurethattheflowmetersmeasuredoutputsareintheUOM
requestedintheflowmeterspecificationdatasheet.Forthis,thevendorcalculatestheconversionfactorbyusingthe
designdensitydata(orpressure,temperatureandmolecularweightdataforgases)specifiedonthedatasheetto
outputmeasuredvaluesinthedesiredUOM.
Duringprocessoperation,themeasureddensity(orP,T,MWandzforgases)valuesmaynotbethesameasthe
valuesonthedatasheet.Therefore,themeasuredflowratesshouldbecorrectedtoaccountforthemeasuredprocess
conditions.ThecorrectionfactorsforvariousflowmetersusingdifferentUOMareprovidedinTable1.Thedetailsof
theflowmetercorrectioncalculationareavailableinAppendixB.
Flowuncertaintyequations.Uncertainty,U95,isastatisticalstatementofmeasurementaccuracythatisusefulin:
Definingtolerancesforreconcilingmeasurementswithconcurrentgrosserrordetectionandelimination
Estimatingaccuracieswhenreportingtogovernmentonmeasurementsthatimpactroyaltiesandemissions
Evaluatingcustodytransfermeteringperformance.
Uncertaintyisameasurementprocesscharacteristic.Itprovidesanestimateoftheerrorbandwithinwhichthetrue
valueforthatmeasurementprocessmustfallwithhighprobability.5Itisbasedontheprobabilityof95%thatistwice
thestandarddeviation,2s.The95%confidencelevelfortheestimatedflowmeteruncertaintyisinaccordancewith
prudentstatisticalandengineeringpractice.
Flowmeteruncertaintyisactuallyafunctionofbothbias(systematicorgrosserror)andprecision(randomerror),as
showninFig.2.Flowmeterpartmanufacturersfollowrigoroustestingandcalibrationtoremoveorrandomizethe
measurementbiases.InCanada,theyfollowthestandardsbyMeasurementsCanada,andintheUS,thetestmethod
followstheNationalBureauofStandards(NationalInstituteofStandardsandTechnology).Thevaluesusedforthe
precisionmaybeobtainedfrommanufacturersspecificationsfortherespectiveequipmentprovidedthatthevalues
areadjustedtoreflectoperatingconditions.
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true
5/25
16/5/2016
Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011
Fig.2.Biasandprecisionerrors.
Tocalculatetheuncertaintyvalues,thesignificanceofeachvariable(parameter)intheflowcalculationequationis
examinedandisrelatedtoflowmeasurement.Itisassumedthatthemeterhasbeenproperlyinstalled,operatedand
maintained.Itisalsoassumedthatthesystematicequipmentbiasesarerandomizedwithinthedatabase,whichmeans
thatvariationsintheequipmentandlaboratorieswillnotimposeanybiasintheequationsabilitytorepresentreality.
Forpracticalconsiderations,thepertinentvariablesareassumedtobeindependenttoenablesimpleruncertainty
calculations.Itwasnotedthatthesimplifieduncertaintyequationswouldprovideverygooduncertaintyestimates.6
Themathematicalrelationshipsamongthevariablesestablishthesensitivityofthemeteredquantitiestoeachofthese
variables.Eachvariablethatinfluencestheflowmeasurementuncertaintyhasaspecificsensitivitycoefficient.The
uncertaintyforageneralequationQ=f(x1 ,x2,.....xN)canbederivedanalyticallybypartialdifferentiationbasedon
propagationofuncertaintybytheTaylorseries.
RefertoAppendixCforderivationusingtheTaylorseries.TheuncertaintyinQcanbegivenas:
Thiscanberepresentedinasimplerformas:
wheredQ/QistheuncertaintyinQ,SxisthesensitivitycoefficientassociatedwiththevariableandUxisthevariable
uncertainty.Theuncertaintyequationsarederivedfordifferentialpressure,volumetricandmassflowmetersin
AppendixDusingtheflowequationsrepresentingthebasicoperatingprinciple.
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true
6/25
16/5/2016
Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011
FLOWMETERUNCERTAINTY
Uncertaintyfororifice,ventureornozzlemetermeasuringinstandardflowisgivenby:
Thesameequationabovecanbeusedforawedgemeterhowever,thedeviationintheequivalentdiameter,d,fora
wedgemeteriscalculatedbyusing:
where:
Uncertainityequationsforvortex,turbinemultrasonicandcoriolisflowmetersareinAppendixD.
Measuredflowratecorrection.
Anorificemeterisusedinarefinerytomeasuretheflowrateofliquidhydrocarbonsanditiscalibratedtoindicate
(readout)flowrateinstandardvolumetricflows.Forexample,designstreamconditionsindicatedontheflowmeter
specificationdatasheetare:
TD=Designtemperature=300C
PD=Designpressure=1,500kPaa
rD_Std=Designstandarddensity=950kg/m3(normallyobtainedfromprocesssimulation)
rD=Designactualdensity=750kg/m3(normallyobtainedfromprocesssimulation).
Duringactualoperation,themeasuredconditionsare:
TM=Measuredtemperature=310C
PM=Measuredpressure=1,500kPaa
rM_Std=Measuredstandarddensity=960kg/m3(measuredinthelaboratoryusingthesample)
rM=Measuredactualdensity=740kg/m3(measured,orcalculatedusinganappropriatecorrelation).
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true
7/25
16/5/2016
Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011
Forliquidflows,ifthemeasureddensitiesarenotavailableattheactualoperatingconditions,theestablished
correlationscanbeused.Itshouldbenotedthatthesecorrelationsmayresultinsomeerrorinthedensity
predictions.
ActualliquidhydrocarbonstreamdensitycanbeestimatedusingtheequationbyYawas:7
ForC20 andheavieralkanes,thedensitiescanbeobtainedusingthemethodbyFisher:8
whereSGmisspecificgravityatmeasuredtemperature
SGristhespecificgravityatreferencetemperature
TmismeasuredtemperatureinKelvin
TrisreferencetemperatureinC.
AmethodforcalculatingactualdensityusingliquidcriticalpropertiesisgivenbyNoor:9
whererm=Densityatmeasuredtemperatureinkg/m3,
M=Molecularweight,
V C=Criticalvolumeinm3/kg
Tm=MeasuredtemperatureinKelvin
TC=CriticaltemperatureinKelvin.
FromTable1,thecorrectionfactorfortheorificemeterwithindicated(readout)liquidflowrateatstandardconditions
isgivenby:
andthecorrectedflowrateatstandardconditionsisgivenby:
QStdVol_Corr=QStdVol_Meas 3CorrectionFactor
Iftheflowmeterindicated(readout)flowis600std.m3/d,thenthecorrectedflowrateatstandardconditionis:
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true
8/25
16/5/2016
Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011
=589.8Stdm3/d~590std.m3/d
Uncertaintycalculation.
A3in.orificemeterrunwithabratioof0.6isselectedforthepreviousliquidhydrocarbonflowmeasurement
exampleatastaticpressureof1,500kPaaandflowingtemperatureof310C.Differentialpressurerecordedforthe
flowis25kPaandtheflowrateis590std.m3/h.
Thevariablesensitivitycoefficientscanbecalculatedusingtheorificeuncertaintyequation:
Theuncertaintyvaluesforthevariablesdx/xat95%confidencelevel,U95,canbeobtainedfromindustrystandards
andprocedures(AGA,API,ASME,ASTM)and/ormanufacturesspecificationsfortheequipmentorparts.Foreach
variable,theuncertaintylistedinTable2representsrandomerrorsonly,whichareobtainedfromAGARP31.
Basedonthecalculations,thestandardvolumetricflowmeasurementuncertaintyat95%confidencelevelis0.76%.
Formassflowmeasurementuncertainty,thestandarddensityvariable,rStd,intheaboveequationisexcluded,which
givesthe%U95valueof0.58%.
APPENDIXA
TheoperatingprinciplesandflowmeterequationsarelistedinthisappendixfortheflowmetersasshowninFig.3.
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true
9/25
16/5/2016
Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011
Fig.3.Examplesofvariousflowmetersusedbyindustry.
Differentialpressureflowmeters.
Theflowmetersthatmeasuredifferentialpressuretocalculatetheflowratescanbeclassifiedasdifferentialpressure
flowmeters.
Orifice,venturiandnozzleflowmeters.Forfluidflowinanorifice,venturiornozzleflowmeter,theactual
volumetricflowratecanbegivenas:10
wheredistheorificediameterforanorificemeterorthroatdiameterforventuriandnozzlemeters,
P1 =Pressureattheupstreampressuretap,
P2=Pressureatthedownstreampressuretap
r1 =DensityatP1 pressurecondition.
Cd=Dischargecoefficienttoaccountforfrictionallosses(kineticenergyintoheat)duetoviscosityandturbulence
effects.
Euisthevelocityapproachfactorthatrelatestheflowingfluidvelocityinthemeterapproachsection(upstreammeter
tube)totheorifice/throatfluidvelocity:
whereb=d/Distheorificebore(orthroatfortheventuriandnozzle)topipeinnerdiameterratio.
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true
10/25
16/5/2016
Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011
Yistheexpansionfactortoaccountforthegascompressibilitythatisgivenby:
wherekisspecificheatratioCP /CV.Forblessthan0.25,b4valueapproacheszerointheequation.
Pitottubeorannubarflowmeters(forvelocitylessthan30%ofsonicvelocity).ForfluidflowinaPitot
tubeflowmeter,theactualvolumetricflowratecanbegivenas:
Where:K=Instrumentcoefficientthatisusuallydeterminedthroughcalibration,
D=Pipeinsidediameter
P=PressuredropmeasuredbythePitottube,whichisthedifferencebetweenthetotal(stagnation)pressure,Pt,and
thestaticpressure,Ps .
Wedgeflowmeter(usedforliquidflowsonly).Forliquidflowinawedgeflowmeter,actualvolumetricflowrate
canbecalculatedusingtheorificeequation:
wheredisequivalentorificediameterthatiscalculatedusingequivalentbetaratio:
whereH=wedgesegmentopeningheight,
D=Pipeinsidediameter,
P=Pressuredropacrosstheorifice
rAct=Liquiddensityatactualtemperatureandpressureconditions,T,P.
Cdisthewedgemeterdischargecoefficienttoaccountforfrictionallosses(kineticenergyintoheat)duetoviscosity
andturbulenceeffects.
Euisthevelocityapproachfactorthatrelatestheflowingfluidvelocityinthewedgemeterapproachsection(upstream
metertube)tothefluidvelocityinthewedgesection.
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true
11/25
16/5/2016
Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011
wherebisd/Dwhichisequivalentorificetopipeinnerdiameterratio.
Volumetricflowmeters.
Theflowmetersthatdirectlyinterprettheactualvolumetricflowfromothermeasuredparametersarecalledvolumetric
flowmeters.Tointerpretthevelocity,vortexmetersusevortexsheddingfrequencyultrasonicmetersusesound
transittimeandmagneticmetersusevoltageinducedinthefluid(conductive)flowingthroughanimposedmagnetic
field.
Vortexflowmeter.Avortexflowmetermeasuresthevolumetricflowratebyusingthevortexsheddingfrequency
causedbyaflowbarrier.11
Strouhalnumber,S,isrelatedtovortexsheddingfrequencybyS=fw/u
wheref=Vortexsheddingfrequencythatdependsonflowvelocity,fluidviscosityandflowbarrierdimensions(bluff,
whichiseitheracylinderorasquarecolumn)usedtocreatevortex
w=Flowbarrierwidth(bluff)
u=Fluidvelocityinthebluffsection.
Actualvolumetricflowratecanbegivenby:
whereDisthepipeinnerdiameter
andBistheblockagefactorthatisdefinedasthepipeborearealessthebluffbodyblockagearea,dividedbythepipe
fullborearea:
whereKfactorisusedtocompensateforthepipeflownonuniformprofileinindustrialapplications.Combiningthe
aboveequationstheactualflowrateisgivenas:
TheStrouhalnumber,S,isaboutconstantacrossawideReynoldsnumberrangeof(102107).TheSvaluedepends
onthebluffwidthtothepipeinnerdiameterratio.S=0.18forw/D=0.1S=0.26forw/D=0.3andS=0.44for
w/D=0.5.
Turbineflowmeter.Aturbineflowmetermeasuresthevolumetricflowbycountingtherotorrevolutions(rotor
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true
12/25
16/5/2016
Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011
angularvelocity)thatturnsinproportiontotheflowvelocity.1214Theequationforaturbinemetercanbegivenas:
utan(theta)=Kr(omega)
whereu=Incomingflowvelocity,
Theta=Anglebetweenthepipeaxis(incomingflowdirection)andtheturbineblades,
r=Rootmeansquarevalueofthebladeinnerandouterradiitorepresenttheaverageradius,
K=Instrumentfactortocompensatevelocityloss(nonidealities)duetorotorbladedesignandomegaistherotor
angularvelocity.
wherero=Bladeradiusouteredgeandri=Radiusbladeroot.
Actualvolumetricflowratecanbegivenby:
Ultrasonicflowmeter.Anultrasonicflowmetermeasuresthevolumetricflowbyusingsoundpulsetransittimein
theflowmediumcausedbydoplareffect.1517Atypicalultrasonicflowmeter(transittimeflowmeasurement)system
utilizestwoultrasonictransducersthatfunctionasbothtransmitterandreceiver.Theflowmeteroperatesby
alternatelytransmittingandreceivingasoundenergyburstbetweenthetwotransducersandmeasuringthetransit
timethatittakesforsoundtotravelbetweenthetwotransducers.Thedifferenceinthetransittimemeasuredis
directlyandrelatedtotheliquidvelocityinthepipe.
IftDisthesoundpulsetransittime(ortimeofflight)travelingfromtheupstreamtransducertothedownstream
transducer,andtUisthetransittimefromtheoppositedirection,theequationscanbegivenas:
wheretheta=Anglebetweenthetransduceraxistotheflowdirection,
c=Soundspeedintheliquid,
D=Pipeinsidediameter
u=Flowvelocityaveragedoverthesoundpath.Solvingtheaboveequationsleadsto:
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true
13/25
16/5/2016
Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011
wheretf =(tUtD)/(tUtD)isthetransittimefunctionandKistheinstrumentfactordeterminedthroughcalibration.
Therefore,byaccuratelymeasuringtheupstreamanddownstreamtransittimes,tUandtD,theflowvelocity,u,canbe
obtained.
Actualvolumetricflowrateiscalculatedas:
whereAisthepipeinnercrosssectionarea.
Magneticflowmeter.MagneticflowmeteroperationisbasedonFaradaysLawthatstatesthatthevoltageinduced
acrossanyconductorasitmovesatrightanglesthroughamagneticfieldisproportionaltotheconductorvelocity.18
Toapplythisprinciplethefluidbeingmeasuredmustbeelectricallyconductive.
Thevoltage,E,generatedinaconductorisgivenby:
E(alpha)BLu
where:
E=Voltagegeneratedinaconductor
B=Magneticfieldstrengthperpendiculartotheflowdirection
L=Distancebetweentheelectrodes(usuallyequaltopipeinsidediameterinmostconstruction)
u=Conductorvelocity.
Thefluidvelocitycanbegivenby:
whereKistheinstrumentcoefficientthatisusuallydeterminedthroughcalibration.
Subsequently,theactualvolumetricflowrateiscalculatedas:
whereAisthepipeinnercrosssectionareaandDisthepipeinsidediameter.
Massflowmeters.
Acoriolisflowmeterdirectlymeasuresthemassflowbasedontheinertialforcesexertedonthetubevibrations.1921
Whenanoscillatingexcitationforceisappliedtothetube,causingittovibrate,thefluidflowingthroughthetubewill
induceatwist(orrotation)tothetubebecauseoftheCoriolisaccelerationactinginoppositedirectionsoneitherside
oftheappliedforce.
InaUtubecoriolismeter,theflowisguidedintotheUshapedtubethatisvibratedusinganactuator.Thevibrationis
commonlyintroducedbyelectriccoilsandmeasuredbymagneticsensors.Whenthetubeismovingupwardduring
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true
14/25
16/5/2016
Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011
thefirsthalfofacycle,thefluidflowingintothemeterresistsbeingforcedupbypushingdownonthetube.Onthe
oppositeside,theliquidflowingoutofthemeterresistshavingitsverticalmotiondecreasedbypushinguponthe
tube.Thisactioncausesthetubetotwist.Whenthetubeismovingdownwardduringthesecondhalfofthevibration
cycle,ittwistsintheoppositedirection.Thetwovibrationsareshiftedinphase(timelag)withrespecttoeachother,
andthedegreeofphaseshiftisdirectlyaffectedbythemasspassingthroughthetube.
AUshapedCoriolisflowmetermassflowisgivenas:
whereKu=Tubestiffness,
K=Ashapedependentfactor
L=Width,
t=Timelag,
omega=Vibrationfrequency
Iu=Tubeinertiathatincludesthetubefluidmass.Theexpressioncanbesimplifiedas:
where:
isthenaturalfrequencyoftheUshapedtubesystem.
Thermalflowmeter.
Athermalflowmetermeasuresthemassflowbasedonheatabsorption.Asmoleculesofamovingfluidcomeinto
contactwithaheatsource,theyabsorbheatandcoolthesource.Atincreasedflowrates,moremoleculescomeinto
contactwiththeheatsourceabsorbingevenmoreheat.Theheatdissipatedfromthesourceinthismanneris
proportionaltothenumberofmoleculesofaparticulargas(itsmass),thegasthermalcharacteristics,anditsflow
characteristics.Themassflowofathermalmassflowmetercanbegivenas:
QMass =KH
whereKistheinstrumentcoefficientwhichisusuallydeterminedthroughcalibration,andHistheamountofheat
dissipatedfromtheheatsource.
APPENDIXB:FLOWMETERCORRECTIONCALCULATIONS
Flowcorrectionfordifferentialpressureflowmeters.
Actualflowfordifferentialpressuremetersiscalculatedusing:
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true
15/25
16/5/2016
Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011
Assumingincompressiblefluidintherangeofinterest(constantfluiddensitybetweentheflowmeterpressuretaps)
theactualflowratemeasuredbytheflowmetercanbegivenas:
Liquidflowmeter(actualvolumetricflowmeasurementact.m3/h).Theequationforcorrectedflowis:
Liquidflowmeter(standardvolumetricflowmeasurementstd.m3/h).Standardvolumetricflowiscalculated
using:
Theequationforcorrectedflowis:
Liquidflowmeter(massflowmeasurementkg/h).Massflowiscalculatedusing:
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true
16/25
16/5/2016
Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011
Theequationforcorrectedflowisgivenby:
Gasflowmeter(actualvolumetricflowmeasurementact.m3/h).Theequationforcorrectedflowis:
Gasflowmeter(standardvolumetricflowmeasurementstd.m3/h).Standardflowrateis:
Theequationforcorrectedflowisgivenby:
Gas/steamflowmeter(massflowmeasurementkg/h).Theequationformassflowis:
Theequationforcorrectedflowis:
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true
17/25
16/5/2016
Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011
Flowcorrectionforvolumetricflowmeters.
Actualflowmeasuredbythevolumetricflowis:
Vortexmeter:QActVolfv
Turbinemeter:QActVolomega
Ultrasonicmeter:QActVolf(TUP ,TDown)
Magneticmeter:QActVolE
Liquidflowmeter(actualvolumetricflowmeasurementact.m3/h).Theequationforcorrectedflowis:
Liquidflowmeter(standardvolumetricflowmeasurementstd.m3/h).Standardvolumetricflowiscalculated
using:
Theequationforcorrectedflowis:
Liquidflowmeter(massflowmeasurementkg/h).Massflowiscalculatedusing:
Theequationforcorrectedflowis:
Gasflowmeter(actualvolumetricflowmeasurementact.m3/h).Theequationforcorrectedflowis:
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true
18/25
16/5/2016
Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011
Gasflowmeter(standardvolumetricflowmeasurementstd.m3/h).Standardvolumetricflowiscalculatedusing:
Theequationforcorrectedflowis:
Gas/steamflowmeter(massflowmeasurementkg/h).Theequationformassflowis:
Theequationforcorrectedflowis:
Flowcorrectionformassflowmeters.
Massflowratesforthemassflowmetersis:
Coriolismeter:QMass t
Thermalmeter:QMass DH
Liquidflowmeter(actualvolumetricflowact.m3/h).Actualvolumetricflowiscalculatedusing:
Theequationforcorrectedflowis:
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true
19/25
16/5/2016
Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011
Ifthecoriolismeterhasanintegraldensitymeasurementandusestheoperatingdensity(orflowingdensity)instead
ofdesigndensity,rD,intheaboveequations,thencorrectionfactorisequalto1.
Liquidflowmeter(standardvolumetricflowstd.m3/h).Standardvolumetricflowiscalculatedusing:
Theequationforcorrectedflowis:
Liquidflowmeter(massflowmeterkg/h).Equationforcorrectedflowis:
QMass_Corr=QMass_Meas
Thecorrectionfactorrequiredforcorrectingtheflowmeterreadingisequalto1.
Gasflowmeter(actualvolumetricflowmeasurementact.m3/h).Actualvolumetricflowiscalculatedusing:
Theequationforcorrectedflowis:
Ifthecoriolismeterhasanintegraldensitymeasurementandusestheoperatingdensity(orflowingdensity)inthe
aboveequationsinsteadofdesigndensity,thencorrectionfactorisequalto1.
Gasflowmeter(standardvolumetricflowmeasurementstd.m3/h).Standardvolumetricflowis:
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true
20/25
16/5/2016
Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011
Theequationforcorrectedflowis:
Gasflowmeter(massflowmeterkg/h).Theequationforcorrectedflowis:
QMass_Corr=QMass_Meas
APPENDIXC:PROPAGATIONOFUNCERTAINTYBYTAYLORSERIES
Thesensitivitycoefficientassociatedwitheachflowvariableisderivedanalyticallybypartialdifferentiationbasedon
uncertaintypropagationbytheTaylorseries[ASMEMFC2M,1983].TherelationshipofdependentvariableQwith
independentvariablesx1,x2,...,xNcanbeexpressedinageneralformas:
Q=f(x1 ,x2,...,xN)
UsingtheTaylorseriestheuncertaintyinQcanbeexpressedas:
Squaringonbothsides,theequationcanbewrittenas:
Giventhatthevariablesareuncorrelated(independent),i.e.,(delta)xi(delta)xj=0(ij),allthevaluesofthe
summationintheaboveequationwillbezero.Therefore,theuncertaintyinQcanbegivenas:
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true
21/25
16/5/2016
Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011
whichcanberepresentedinasimplerformas:
where(delta)Q/QistheuncertaintyinQ,Sxisthesensitivitycoefficientassociatedwiththevariable,andUxisthe
uncertaintyofthevariable.
APPENDIXD:UNCERTAINITYEQUATIONSFORVORTEX,TURBINE,ULTRASONIC
ANDCORIOLIS
Vortexflowmeteruncertaintyis:
Turbineflowmeteruncertaintyis:
Ultrasonicflowmeteruncertaintyis:
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true
22/25
16/5/2016
Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011
Coriolisflowmeteruncertaintyis:
NOMENCLATURE
SubscriptDDesignvaluesfromflowmeterspecificationdatasheet
SubscriptMMeasuredvaluesduringplantoperation
MMolecularweight
PPressure,kPaa
PPressuredrop,kPa
QFlowrate
QMass Massflowrate,kg/h
QActVolVolumetricflowrateatactualoperatingconditions,act.m3/h
QStdVolVolumetricflowrateatstandardconditions(15Cand1atm.),std.m3/h
QMass_Meas Measured(readout)massflowratefromtheflowmeter,kg/h
QActVol_Meas Measuredactualvolumetricflowrate(readout)fromtheflowmeter,act.m3/h
QStdVol_Meas Measuredstandardvolumetricflowrate(readout)fromtheflowmeter,std.m3/h
QMass_CorrCorrectedmassflowratefortheflowmeter,kg/h
QActVol_CorrCorrectedactualvolumetricflowratefortheflowmeter,act.m3/h
QStdVol_CorrCorrectedstandardvolumetricflowratefortheflowmeter,std.m3/h
RUniversalgasconstant(R=8.3145kPaam3/kmolK)
SSensitivitycoefficient
TTemperature,K
UUncertainty
U95Uncertaintyat95%confidencelevel
ZCompressibilityfactorforgases(Z=1foridealgas)
sStandarddeviation
rMassdensity,kg/m3
rDDesigndensityatactualconditionsfromflowmeterspecificationdatasheet
rMMeasured(orcalculated)densityatactualconditionsduringoperation
rD_StdDesigndensityatstandardconditionsfromflowmeterspecificationdatasheet
rM_StdMeasureddensityatstandardconditionsduringoperation
Acknowledgments
TheauthorsthanktheircolleagueKenFernie,P.Eng.,forreviewandvaluablecommentsoncustodytransfer
metering,andAndrewNelson,ProductionmanagementmanagerfromMatrikonInc.,hisforreviewandvaluable
inputonflowmeteruncertainties.
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true
23/25
16/5/2016
Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011
LITERATURECITED
1 Spitzer,D.W.,FlowMeasurement:PracticalGuidesforMeasurementandControl,2ndEdition,Research
TrianglePark,NC:ISA,2001.
2Upp,E.L.andP.J.LaNasa,FluidFlowMeasurement:APracticalGuidetoAccurateFlowMeasurement,Gulf
ProfessionalPublishing,2ndEdition,2002.
3Romagnoli,J.A.andM.C.Sanchez,DataProcessingandReconciliationforChemicalProcessOperations,
ProcessSystemsEngineering,Vol.2,AcademicPress,1stEdition,1999.
4Ozyurt,D.B.andR.W.Pike,TheoryandPracticesofSimultaneousDataReconciliationandGrossErrorDetection
forChemicalProcesses,ComputersandChemicalEngineering,28,pp.381402,2004.
5 ASMEMFC2M,MeasurementUncertaintyforFluidFlowinClosedConduits,AmericanNationalStandard,1983
(Revised2006).
6AGARP31,OrificeMeteringofNaturalGasandOtherRelatedHydrocarbonFluidsPart1GeneralEquations
andUncertaintyGuidelines,AmericanGasAssociation,June2003.(APIMPMS14.31ANSI/API253091Part1
GasProcessorsAssociationGPA8185Part1).
7Yawas,C.L.,etal,EquationforLiquidDensity,HydrocarbonProcessing,Vol.70,No1,January1991,pp.103
106.
8Fisher,C.H.,HowtoPredictnAlkaneDensities,ChemicalEngineering,Vol.96,No10,pp.195,October1989.
9Noor,A.,QuickEstimateofLiquidDensities,ChemicalEngineering,Vol.88,No.7,pp.111,6thApril1981.
10 ASMEMFC3M,MeasurementofFluidFlowinPipesUsingOrifice,NozzleandVenturi,AmericanNational
Standard,2004.
11 ASMEMFC6M,MeasurementofFluidFlowinPipesusingVortexFlowmeters,AmericanNationalStandard,
1998(Revised2005).
12AGARP7,MeasurementofNaturalGasbyTurbineMeters,AmericanGasAssociation,February2006.
13APIMPMS5.3,MeasurementofLiquidHydrocarbonsbyTurbineMeters,AmericanPetroleumInstitute,
September2000.
14ASMEMFC4M,MeasurementofGasFlowbyTurbineMeters,AmericanNationalStandard,1986(Revised
2008).
15 AGARP9,MeasurementofGasbyMultipathUltrasonicMeters,AmericanGasAssociation,April2007.
16APIMPMS5.8,MeasurementofLiquidHydrocarbonsbyUltrasonicFlowMetersUsingTransitTime
Technology,AmericanPetroleumInstitute,February2005.
17ASMEMFC5M,MeasurementofLiquidFlowinClosedConduitsUsingTransitTimeUltrasonicFlowmeters,
AmericanNationalStandard,1985(Revised2006).
18ASMEMFC16M,MeasurementofLiquidFlowinClosedConduitswithElectromagneticFlowmeters,American
NationalStandard,1995(Revised2006).
19AGARP11,MeasurementofNaturalGasbyCoriolisMeter,AmericanGasAssociation,January2003.
20 APIMPMS5.6,MeasurementofLiquidHydrocarbonsbyCoriolisMeters,AmericanPetroleumInstitute,
October2002.
21 ASMEMFC11M,MeasurementofFluidFlowbyMeansofCoriolisMassFlowmeters,AmericanNational
Standard,1989(Revised2003).
Theauthors
SubodhsenPeramanuhasmorethan15yearsofexperienceinconceptual,frontenddesignand
detailedengineeringofupgradingandrefiningprocesses.Hehasauthoredpapersontopicsincluding
hydrogenseparationandeconomics,bitumencharacterization,andasphaltenesolubilityand
reversibility.Dr.PeramanuwasinvolvedincommissioningandstartupofCNRLHorizonUpgrader
andisworkingwithCNRLThermalTeamasaseniorengineeringspecialistoninsituoilrecovery.He
holdsaBChemEngdegreeinchemicalengineeringfromInstituteofChemicalTechnology(formerly
UDCT),Mumbai,MTechdegreefromIndianInstituteTechnology,KanpurandPhDfromUniversityof
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true
24/25
16/5/2016
Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011
Calgary.
JuonWahscareerinprocessengineeringspansmorethan30yearsandcoversconceptualdesign,
FEED,EPCanddetailedprocessandequipmentdesignofmajorprojectsinrefining,bitumen
upgradingandoilandgasproductionfacilities.Atpresent,Mr.Wahisaconsultantonprocessdesign
andplantoperations.Atthetimeofwriting,hewasworkingonanexpansionprojectfortheHorizon
UpgradingcomplexofCNRL.Mr.WahholdsaBScdegreeinchemicalengineeringfromtheUniversity
ofBirmingham,UK,andaDiplmedIngnieurinchemicalengineeringandpetroleumrefiningfrom
theIFP,France.
AnatoliyPavlov
10.12.2015
Iwouldliketosuggestuseofanewheattype(noknownThermalMass)fastactinggasliquidMASSFLOWMETER
forimmersioninunsteadyflow.DetailsinEmail:[email protected].
C.Voigt
11.11.2014
DearSir,
couldyoupleasesentmethroughthenamesofthestandardswhichhavebeenusedtocalculatethecorrectionfactor
forgasflowatstdm3/hrintable1?Thankyouverymuchinadvance,
C.Voigt
SHASHIKANTDAWALKAR
02.23.2014
DearSir,
Pleaseletmeknowtheprincipleofcorrectionfactorappliedinthemeasurementofcorrectionfactorandthe
calculationofcorrectionfactorforvolumentricflowthroughorificemeter.
WithRegards
RichardvonBrecht
01.20.2013
Thisisanamazingarticle.tome.I'munfamiliarwithsomeofthenomenclature.I'dbeinterestedseeinganexpanded
versionofyourpaper.
MuhammadFarhatUllah
12.19.2011
Itisreallyhandyandvaluablearticle.Thanks
WilliamBlanco
12.07.2011
Tobothofyou,excellentandvaluablework
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true
25/25