Improve Material Balance by Using Proper Flowmeter Corrections - Hydrocarbon Processing - October 2011

This document discusses improving the accuracy of flow measurements by applying proper flowmeter corrections. It provides guidelines for selecting flowmeters based on process conditions and calibration requirements. While flowmeters are installed correctly according to standards, errors can be introduced if flow conditions are not understood and correction factors not applied. The article then describes sources of measurement errors and the importance of uncertainties for mass balancing and reconciliation. It provides equations to correct differential pressure, volumetric and mass flow measurements and derive uncertainty equations for various flowmeter types. Accurate interpretation of stream flows is critical for process control, production accounting and regulatory reporting.

Uploaded by

Marco L. Lanteri
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
352 views

Improve Material Balance by Using Proper Flowmeter Corrections - Hydrocarbon Processing - October 2011

This document discusses improving the accuracy of flow measurements by applying proper flowmeter corrections. It provides guidelines for selecting flowmeters based on process conditions and calibration requirements. While flowmeters are installed correctly according to standards, errors can be introduced if flow conditions are not understood and correction factors not applied. The article then describes sources of measurement errors and the importance of uncertainties for mass balancing and reconciliation. It provides equations to correct differential pressure, volumetric and mass flow measurements and derive uncertainty equations for various flowmeter types. Accurate interpretation of stream flows is critical for process control, production accounting and regulatory reporting.

Uploaded by

Marco L. Lanteri
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 25

16/5/2016

Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011

COPYINGANDDISTRIBUTINGAREPROHIBITEDWITHOUTPERMISSIONOFTHEPUBLISHER

Improvematerialbalancebyusingproper
flowmetercorrections
10.01.2011|Peramanu,S.,CanadianNaturalResourcesLtd.,Calgary,CanadaWah,J.C.,CanadianNatural
ResourcesLtd.,Calgary,Canada
Hereareguidelinestoincreaseaccuracyforflowmeasurements
Keywords:
Processplantsfrequentlyencountermassimbalances.Thesecanbeattributedtovariousfactors,butoftentheylead
backtoinappropriatemeasuringdevices,impropercalibration,incorrectinstallationorincorrectinterpretationofthe
measuredflows.Therearewellestablishedguidelinesavailabletoensureappropriateflowmeterselectionbasedon
theprocessconditionsandcontrolrequirements.
Instrumentvendorsfollowtheindustrystandardsandapprovedproceduresforflowmetercalibration,calculatingthe
calibrationfactorsbasedonthedataprovidedintheflowmeterspecificationdatasheets.Engineeringand
constructionservicecontractorsoftenfollowvendorguidelinesandstandardpracticestocorrectlyinstallthe
flowmeters.Thismeansthatmostflowmeterinstallations,therefore,meetacceptedprojectstandardsand
specifications.
Whatstheflowrate?
However,measuredflowinterpretation,normallyaprocessorproductionengineersresponsibility,isoftendone
withoutproperdirectionsorguidelines.Althoughitappearsstraightforwardthattheflowmetermeasurestheflowrate
andtheflowratevalueisreadfromthedisplay,significanterrorcanbeintroducediftheflowmeasurementconditions
arenotunderstoodandappropriatecorrectionfactorsarenotapplied.Accuratestreamflowinterpretationandcritical
massbalancereconciliationrequireunderstandingflowmetercharacteristicsandtheirassociatedmeasurement
uncertainties.Thisisofparticularimportancewheremassbalancesmaybeusedforhighlysensitiveprocesscontrol
operations,productionaccountingorgovernmentreportingonroyaltiesandemissions.
Thisarticleprovidesabackgroundontheimportanceofaccuratemeasurements,adescriptionofmeasurementerrors
andtheroleofuncertaintiesinmassbalanceandreconciliation.Flowmetercorrectionequationsarederivedfor
differentialpressureflow,volumetricflowandmassflowmeters,andflowcorrectionfactorsareprovidedforvarious
unitsofmeasurements(UOM).Flowmeteruncertaintyequationsarederivedfordifferentialpressureflow,volumetric
flowandmassflowmeters.

METERINGAPPLICATIONS
Toachievethemostaccurateflowmeasurement(minimumuncertainty),properflowsystemoperationand
maintenancemustbepracticedsothatmeteraccuracycapabilitiesarerealized.Periodicmaintenance,testingand
recalibrationareessentialbecausethecalibrationwillshiftovertimeduetowear,damageorcontamination.
Themaintenancemaybeonlyasecondaryequipmentcalibration,acompletesystemmechanicalinspection,an
actualthroughputtestagainstsomeagreeduponstandardsoranycombinationofthese.Theequipmentusedtotest
themeter,suchasthermometers,deadweighttests,pressuregauges,differentialpressuregauges,chromatographs
andprovers(usedforthroughputtests),musthaveaccuracycertificationandshouldbeapprovedandagreeduponby
theinterestedparties.Havingoperatorswhohavehadexperiencewithsimilarmeteringsystemsalsoincreasesthe
calibrationandtestprocedureconfidencelevels.Testequipmentitselfshouldberecertifiedperiodicallybytheagency
ormanufacturerthatoriginallycertifiedtheequipment.

http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true

1/25

16/5/2016

Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011

Custodytransferoperations.
Incustodytransfermeasurement,themeasurementfurnishesquantityandqualityinformationthatcanbeusedasthe
basisforachangeinownershipand/orachangeinresponsibilityformaterials.
Custodytransfermeasurementisdistinctfromothermeasurementtypesbecauseofthecontractualnatureofthe
meter.Custodytransfermeteringmayrequireaccuracyof0.1%orbetter,whereascontrolmeasurementmaybe
acceptedata2%accuracyandoperationalmeasurementmayrequirea5%accuracy.Ahighintegritycustody
transfermeasurementsystemisaresultofcarefuldesignbasedonthespecificapplicationrequirementscomprising
fluidcontrol,conditioning,metering,computationandameansoftraceablesitedatavalidation.1,2
Custodytransfermanagementinvolvestheentirechainfromthecustodytransfermeteringconceptualizationtothe
finalproductionorsaledatareporting.Forexample,intheupstreamoilandgassector,measurementincludesall
intermediatestepssuchasmeasurementandsamplingguidelines,operationalprocedures,dataprocessing,data
transmissionandreconciliation,allocationorcustodytransferprocedures.Tosolvetheflowmeasurementequation,
itisimperativethateveryequationparameterbewellunderstoodandrepresented.
Aprimarycustodytransfermeasurementconsiderationistominimizeflowvariationsbymaintainingbetterflow
control.Forsituationswherethismaynotbepossible,ameterwithawiderangingflowcapacityisneeded.Ifasingle
meterwiththerequiredflowcapacitytocovertheintendedoperatingrangewithminimumuncertaintydoesnotexist,
usingmultiplemeterswithsometypeofmeterswitchingcontrolisrequired.Mostmetersoperatewithaspecified
uncertaintywithinthestatedflowcapacitylimitsthatistypicallyfrom25%to95%oftheflowmetermaximum
capacity.Forcustodytransfermeteringandcriticalcontrolmeasurement,itisimportanttomaintainthemeter
operationwithinthestatedflowcapacitylimits.
Errors.
Otherthansomeoperatingproblemsandpoormaintenancethatmayaffectthemeasurement,themaincauseoferror
isthefluidcharacteristicsanderrorsinfluiddensitycalculation.Forgases,mixturesaremoreaccuratelymeasuredif
thestreamhasrelativelyconstantcomposition.ThisallowsspecificPVTteststoberun,ordatamaybeavailablefor
commonmixturesfrompreviouswork.Ifthemixtureischangingrapidly,adensitometeroramassmetermaybe
requiredtodetermineanaccuratemeasurement.
Duringtimeswhenacustodytransfermeterisoutofserviceorregisteringinaccurately,aproceduremustbeinplace
formeasuringorestimatingdeliveries.Thisproceduremayneedtobeinaccordancewithregulatorystandardsifthe
meterflowisusedforregulatoryreporting.AnexampleofthisistherecentUSAEPAGreenhouseGasMandatory
ReportingRuleissuedSept.22,2009.Atypicalaccuracylimitfrom0.5%to2%maybeused,butmaybesetcloser
orwiderdependingonthespecificmetercostsandmeasurementability.
Forcustodytransfermeters,aproversystemormastermetershouldbeusedforthroughputtestingandrecalibration.
Thebestthroughputtestcanberundirectlyinserieswithaprover.Theprovercancomeinmanyforms,but
essentiallyitinvolvesabasicvolumethathasbeencertifiedbyagovernmentorindustrialgroup.Sincemostmeters
arenottotallylinear,testsmayhavetoberunoverthemetersoperatingrangetocalculatethecalibrationfactors
dependentontheflowcapacity.
Commercialmassbalancesoftware.
Thecharacteristicsandstrengthsofcommercialmassbalancesoftwaremayinclude:
Graphicallyaidedinputthatisuserfriendlyandintuitive
Interactivediagnosticsandfeedbackoninputerrors
Flexibilitytoselectthemeasurementunitsdesiredbytheuser
Flexibilityfortheusertoselectstartandendtimestoperformthereconciliation
Facilitytoconstructmassbalanceunitsbasedonplantconfigurationuserinput
Reconciliationprocessesperformlinear,nonlinearandinequalityconstraintsonthemeasurementdatatoproduce
reconciledmeasurementsandunmeasuredflowestimates
Algorithmforefficientiterationandfastconvergencetothesolution.SomealgorithmsmayincludetheMonte
Carlomethodtogeneratesetsofrandomvaluesformeasurementerrorswithinaprescribedrange(%uncertainty)
thataresolvedanditeratedinthereconciliationalgorithm
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true

2/25

16/5/2016

Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011

Algorithmtoensurenumericalrobustnessandpreventnumericalrunaway

Areconciledmassbalanceattheprocessingunitlevelorgroupofprocessingunits,progressingallthewayupto
theplantlevel
Abilitytoreconciletotalmassandselectedcomponentfractionsatthesametime

Reportingtooltoverifythepresenterrorinbalanceforeachnodeandgeneratethecustomizedreports.
Massbalanceandreconciliation.
Datareconciliation 3,4improvesprocessdataaccuracybyadjustingthemeasuredvaluessothattheysatisfythe
processconstraints.Theamountofadjustmentmadetothemeasurementsisminimizedsincetherandomerrorsare
expectedtobesmall.Datareconciliationcanbeformulatedbythefollowingconstrainedweightedleastsquares
optimizationproblem:
Minimizethefunction(knownasobjectivefunction):

Wherenisthenumberofmeasurements,Misthedifferencebetweenthereconciledandmeasuredvaluesof
measurements,iands iisthemeasurementistandarddeviation.Thevalue1/s 2whichisaninverseofvariance
(squareofstandarddeviation)istheweightfactorrepresentingtheaccuracyoftherespectivemeasurements.Sincea
highervalueofstandarddeviationimpliesthatthemeasurementislessaccurate,theabovechoicegiveslargerweights
tomoreaccuratemeasurements.
Theaboveobjectivefunctionminimizationissubjecttoconstraints:
fj(Mi1DMi)=0 j=1,....m
Wherefisthebalanceequationforthemeasurements(i=1,....n)andmisthenumberofbalanceequations.
Duringthereconciliationprocess,themeasurementscontainingsystematicbiasorgrosserrorsaredetectedby
comparingthedifferencebetweenthereconciledandmeasuredvaluestothemeasurementuncertainties.
IfAbs(DMi/Mi)>Uncertainty,measurementihasgrosserror.
Themeasurementscontaininggrosserrorsareeithereliminatedorappropriatelycompensatedfordatareconciliation
tobeeffective,asshowninFig.1.Inthisexample,thereconciliationinvolves:
M1 =stream1cumulativemeasuredmassflowoveraperiod(aday,forexample)
M2=stream2cumulativemeasuredmassflowoveraperiod
M3=stream3cumulativemeasuredmassflowoveraperiod
M4=measuredmassinventorygainordepletionoverthesameperiod

Fig.1.Flowreconciliationexampleforastoragetank.
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true

3/25

16/5/2016

Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011

Itisevidentthatbecauseofmeasurementerrorsthesemeasuredquantitiesdonotbalance,namely:
M1 1M2M31M4
Therefore,reconciliationisrequiredadjustmentstoeachofthemeasuredquantitiesneedtobemadetoobtainamass
balance:
(M1 1DM1 )1(M21DM2)=(M31DM3)1(M41DM4)
whereMiisanadjustment(+veorve)forthemeasuredquantityMi.
ItisevidentthatthereareinfinitesetsofMi,eachofwhichwillgivethedesiredmassbalance,i.e.,theywillsatisfy
theequationabove.OftheinfinitesetsofMi,theoneparticularsetthatcorrespondstotheleastamountoftotal
adjustmentisrequired.ThissuggeststhattheproblemtofindthisparticularsetofMicanbeformulatedasonethat
entailsminimizingafunction(usuallyreferredtoasobjectivefunction)subjecttosomeconstraints(massbalance
equations).Forthesimpleexamplehere,theproblemoffindingthatparticularsetofMicanbeformulatedas:
Minimizetheobjectivefunction:

Subjecttotheconstraint:

(M1 1DM1 )1(M21DM2)


(M31DM3)(M41DM4)=0
Wheres iistheuncertaintyassociatedwiththeinstrumentthatgivesthemeasuredquantity,Mi.
Theuseofuncertaintiesforreconciliationcanbeexplainedwiththisexample.AssumethataflowmeterM1 with
percentuncertaintyat95%confidencelevel(%U95)as2%isreading300kgduringacertaintimeperiod.Sincethe
95%confidencelevelcorrespondstotwostandarddeviations,2s 1 ,thestandarddeviationerror,s 1 ,forthis
measurementcanbecalculatedas3kgas:

Therefore,theweightfactor,(1/s 1 2),formeasurementM1 intheobjectivefunctionaboveis1/9.Supposeifthe


reconciledflowrateforM1 is307kg,thenthereconcilederror(differencebetweenthereconciledvalueandthe
measuredvalue)is7kg.Thisvalueisgreaterthanthe6kgerror(95%confidence)calculated.Thismeansthat
measurementM1 hasagrosserrorandshouldbeeliminatedorproperlycompensatedforeffectivereconciliation.

FLOWCORRECTIONS
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true

4/25

16/5/2016

Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011

Processindustryflowmeterscanbeclassifiedintothreebroadcategoriesthatincludedifferentialpressuremeters,
actualvolumetricflowmetersandmassflowmeters.Thedifferentialpressuremetersincludeorifice,venturi,nozzle,
wedge,pitottubeandannubarvolumetricflowmetersincludevortex,turbine,ultrasonicandmagneticandmass
flowmetersincludeCoriolisandthermalmeters.Themeteroperatingprinciplesandflowequationsareprovidedin
AppendixA.
Foranyoftheseflowmeters,thevendorshouldmakesurethattheflowmetersmeasuredoutputsareintheUOM
requestedintheflowmeterspecificationdatasheet.Forthis,thevendorcalculatestheconversionfactorbyusingthe
designdensitydata(orpressure,temperatureandmolecularweightdataforgases)specifiedonthedatasheetto
outputmeasuredvaluesinthedesiredUOM.
Duringprocessoperation,themeasureddensity(orP,T,MWandzforgases)valuesmaynotbethesameasthe
valuesonthedatasheet.Therefore,themeasuredflowratesshouldbecorrectedtoaccountforthemeasuredprocess
conditions.ThecorrectionfactorsforvariousflowmetersusingdifferentUOMareprovidedinTable1.Thedetailsof
theflowmetercorrectioncalculationareavailableinAppendixB.

Flowuncertaintyequations.Uncertainty,U95,isastatisticalstatementofmeasurementaccuracythatisusefulin:
Definingtolerancesforreconcilingmeasurementswithconcurrentgrosserrordetectionandelimination
Estimatingaccuracieswhenreportingtogovernmentonmeasurementsthatimpactroyaltiesandemissions
Evaluatingcustodytransfermeteringperformance.
Uncertaintyisameasurementprocesscharacteristic.Itprovidesanestimateoftheerrorbandwithinwhichthetrue
valueforthatmeasurementprocessmustfallwithhighprobability.5Itisbasedontheprobabilityof95%thatistwice
thestandarddeviation,2s.The95%confidencelevelfortheestimatedflowmeteruncertaintyisinaccordancewith
prudentstatisticalandengineeringpractice.
Flowmeteruncertaintyisactuallyafunctionofbothbias(systematicorgrosserror)andprecision(randomerror),as
showninFig.2.Flowmeterpartmanufacturersfollowrigoroustestingandcalibrationtoremoveorrandomizethe
measurementbiases.InCanada,theyfollowthestandardsbyMeasurementsCanada,andintheUS,thetestmethod
followstheNationalBureauofStandards(NationalInstituteofStandardsandTechnology).Thevaluesusedforthe
precisionmaybeobtainedfrommanufacturersspecificationsfortherespectiveequipmentprovidedthatthevalues
areadjustedtoreflectoperatingconditions.

http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true

5/25

16/5/2016

Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011

Fig.2.Biasandprecisionerrors.

Tocalculatetheuncertaintyvalues,thesignificanceofeachvariable(parameter)intheflowcalculationequationis
examinedandisrelatedtoflowmeasurement.Itisassumedthatthemeterhasbeenproperlyinstalled,operatedand
maintained.Itisalsoassumedthatthesystematicequipmentbiasesarerandomizedwithinthedatabase,whichmeans
thatvariationsintheequipmentandlaboratorieswillnotimposeanybiasintheequationsabilitytorepresentreality.
Forpracticalconsiderations,thepertinentvariablesareassumedtobeindependenttoenablesimpleruncertainty
calculations.Itwasnotedthatthesimplifieduncertaintyequationswouldprovideverygooduncertaintyestimates.6
Themathematicalrelationshipsamongthevariablesestablishthesensitivityofthemeteredquantitiestoeachofthese
variables.Eachvariablethatinfluencestheflowmeasurementuncertaintyhasaspecificsensitivitycoefficient.The
uncertaintyforageneralequationQ=f(x1 ,x2,.....xN)canbederivedanalyticallybypartialdifferentiationbasedon
propagationofuncertaintybytheTaylorseries.
RefertoAppendixCforderivationusingtheTaylorseries.TheuncertaintyinQcanbegivenas:

Thiscanberepresentedinasimplerformas:

wheredQ/QistheuncertaintyinQ,SxisthesensitivitycoefficientassociatedwiththevariableandUxisthevariable
uncertainty.Theuncertaintyequationsarederivedfordifferentialpressure,volumetricandmassflowmetersin
AppendixDusingtheflowequationsrepresentingthebasicoperatingprinciple.
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true

6/25

16/5/2016

Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011

FLOWMETERUNCERTAINTY
Uncertaintyfororifice,ventureornozzlemetermeasuringinstandardflowisgivenby:

Thesameequationabovecanbeusedforawedgemeterhowever,thedeviationintheequivalentdiameter,d,fora
wedgemeteriscalculatedbyusing:

where:

Uncertainityequationsforvortex,turbinemultrasonicandcoriolisflowmetersareinAppendixD.
Measuredflowratecorrection.
Anorificemeterisusedinarefinerytomeasuretheflowrateofliquidhydrocarbonsanditiscalibratedtoindicate
(readout)flowrateinstandardvolumetricflows.Forexample,designstreamconditionsindicatedontheflowmeter
specificationdatasheetare:
TD=Designtemperature=300C
PD=Designpressure=1,500kPaa
rD_Std=Designstandarddensity=950kg/m3(normallyobtainedfromprocesssimulation)
rD=Designactualdensity=750kg/m3(normallyobtainedfromprocesssimulation).
Duringactualoperation,themeasuredconditionsare:
TM=Measuredtemperature=310C
PM=Measuredpressure=1,500kPaa
rM_Std=Measuredstandarddensity=960kg/m3(measuredinthelaboratoryusingthesample)
rM=Measuredactualdensity=740kg/m3(measured,orcalculatedusinganappropriatecorrelation).
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true

7/25

16/5/2016

Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011

Forliquidflows,ifthemeasureddensitiesarenotavailableattheactualoperatingconditions,theestablished
correlationscanbeused.Itshouldbenotedthatthesecorrelationsmayresultinsomeerrorinthedensity
predictions.
ActualliquidhydrocarbonstreamdensitycanbeestimatedusingtheequationbyYawas:7

ForC20 andheavieralkanes,thedensitiescanbeobtainedusingthemethodbyFisher:8

whereSGmisspecificgravityatmeasuredtemperature
SGristhespecificgravityatreferencetemperature
TmismeasuredtemperatureinKelvin
TrisreferencetemperatureinC.
AmethodforcalculatingactualdensityusingliquidcriticalpropertiesisgivenbyNoor:9

whererm=Densityatmeasuredtemperatureinkg/m3,
M=Molecularweight,
V C=Criticalvolumeinm3/kg
Tm=MeasuredtemperatureinKelvin
TC=CriticaltemperatureinKelvin.
FromTable1,thecorrectionfactorfortheorificemeterwithindicated(readout)liquidflowrateatstandardconditions
isgivenby:

andthecorrectedflowrateatstandardconditionsisgivenby:
QStdVol_Corr=QStdVol_Meas 3CorrectionFactor
Iftheflowmeterindicated(readout)flowis600std.m3/d,thenthecorrectedflowrateatstandardconditionis:
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true

8/25

16/5/2016

Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011

=589.8Stdm3/d~590std.m3/d

Uncertaintycalculation.
A3in.orificemeterrunwithabratioof0.6isselectedforthepreviousliquidhydrocarbonflowmeasurement
exampleatastaticpressureof1,500kPaaandflowingtemperatureof310C.Differentialpressurerecordedforthe
flowis25kPaandtheflowrateis590std.m3/h.
Thevariablesensitivitycoefficientscanbecalculatedusingtheorificeuncertaintyequation:

Theuncertaintyvaluesforthevariablesdx/xat95%confidencelevel,U95,canbeobtainedfromindustrystandards
andprocedures(AGA,API,ASME,ASTM)and/ormanufacturesspecificationsfortheequipmentorparts.Foreach
variable,theuncertaintylistedinTable2representsrandomerrorsonly,whichareobtainedfromAGARP31.

Basedonthecalculations,thestandardvolumetricflowmeasurementuncertaintyat95%confidencelevelis0.76%.
Formassflowmeasurementuncertainty,thestandarddensityvariable,rStd,intheaboveequationisexcluded,which
givesthe%U95valueof0.58%.

APPENDIXA
TheoperatingprinciplesandflowmeterequationsarelistedinthisappendixfortheflowmetersasshowninFig.3.

http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true

9/25

16/5/2016

Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011

Fig.3.Examplesofvariousflowmetersusedbyindustry.

Differentialpressureflowmeters.
Theflowmetersthatmeasuredifferentialpressuretocalculatetheflowratescanbeclassifiedasdifferentialpressure
flowmeters.
Orifice,venturiandnozzleflowmeters.Forfluidflowinanorifice,venturiornozzleflowmeter,theactual
volumetricflowratecanbegivenas:10

wheredistheorificediameterforanorificemeterorthroatdiameterforventuriandnozzlemeters,
P1 =Pressureattheupstreampressuretap,
P2=Pressureatthedownstreampressuretap
r1 =DensityatP1 pressurecondition.
Cd=Dischargecoefficienttoaccountforfrictionallosses(kineticenergyintoheat)duetoviscosityandturbulence
effects.
Euisthevelocityapproachfactorthatrelatestheflowingfluidvelocityinthemeterapproachsection(upstreammeter
tube)totheorifice/throatfluidvelocity:

whereb=d/Distheorificebore(orthroatfortheventuriandnozzle)topipeinnerdiameterratio.
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true

10/25

16/5/2016

Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011

Yistheexpansionfactortoaccountforthegascompressibilitythatisgivenby:

wherekisspecificheatratioCP /CV.Forblessthan0.25,b4valueapproacheszerointheequation.
Pitottubeorannubarflowmeters(forvelocitylessthan30%ofsonicvelocity).ForfluidflowinaPitot
tubeflowmeter,theactualvolumetricflowratecanbegivenas:

Where:K=Instrumentcoefficientthatisusuallydeterminedthroughcalibration,
D=Pipeinsidediameter
P=PressuredropmeasuredbythePitottube,whichisthedifferencebetweenthetotal(stagnation)pressure,Pt,and
thestaticpressure,Ps .
Wedgeflowmeter(usedforliquidflowsonly).Forliquidflowinawedgeflowmeter,actualvolumetricflowrate
canbecalculatedusingtheorificeequation:

wheredisequivalentorificediameterthatiscalculatedusingequivalentbetaratio:

whereH=wedgesegmentopeningheight,
D=Pipeinsidediameter,
P=Pressuredropacrosstheorifice
rAct=Liquiddensityatactualtemperatureandpressureconditions,T,P.
Cdisthewedgemeterdischargecoefficienttoaccountforfrictionallosses(kineticenergyintoheat)duetoviscosity
andturbulenceeffects.
Euisthevelocityapproachfactorthatrelatestheflowingfluidvelocityinthewedgemeterapproachsection(upstream
metertube)tothefluidvelocityinthewedgesection.

http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true

11/25

16/5/2016

Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011

wherebisd/Dwhichisequivalentorificetopipeinnerdiameterratio.
Volumetricflowmeters.
Theflowmetersthatdirectlyinterprettheactualvolumetricflowfromothermeasuredparametersarecalledvolumetric
flowmeters.Tointerpretthevelocity,vortexmetersusevortexsheddingfrequencyultrasonicmetersusesound
transittimeandmagneticmetersusevoltageinducedinthefluid(conductive)flowingthroughanimposedmagnetic
field.
Vortexflowmeter.Avortexflowmetermeasuresthevolumetricflowratebyusingthevortexsheddingfrequency
causedbyaflowbarrier.11
Strouhalnumber,S,isrelatedtovortexsheddingfrequencybyS=fw/u
wheref=Vortexsheddingfrequencythatdependsonflowvelocity,fluidviscosityandflowbarrierdimensions(bluff,
whichiseitheracylinderorasquarecolumn)usedtocreatevortex
w=Flowbarrierwidth(bluff)
u=Fluidvelocityinthebluffsection.
Actualvolumetricflowratecanbegivenby:

whereDisthepipeinnerdiameter
andBistheblockagefactorthatisdefinedasthepipeborearealessthebluffbodyblockagearea,dividedbythepipe
fullborearea:

whereKfactorisusedtocompensateforthepipeflownonuniformprofileinindustrialapplications.Combiningthe
aboveequationstheactualflowrateisgivenas:

TheStrouhalnumber,S,isaboutconstantacrossawideReynoldsnumberrangeof(102107).TheSvaluedepends
onthebluffwidthtothepipeinnerdiameterratio.S=0.18forw/D=0.1S=0.26forw/D=0.3andS=0.44for
w/D=0.5.
Turbineflowmeter.Aturbineflowmetermeasuresthevolumetricflowbycountingtherotorrevolutions(rotor
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true

12/25

16/5/2016

Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011

angularvelocity)thatturnsinproportiontotheflowvelocity.1214Theequationforaturbinemetercanbegivenas:
utan(theta)=Kr(omega)
whereu=Incomingflowvelocity,
Theta=Anglebetweenthepipeaxis(incomingflowdirection)andtheturbineblades,
r=Rootmeansquarevalueofthebladeinnerandouterradiitorepresenttheaverageradius,
K=Instrumentfactortocompensatevelocityloss(nonidealities)duetorotorbladedesignandomegaistherotor
angularvelocity.

wherero=Bladeradiusouteredgeandri=Radiusbladeroot.
Actualvolumetricflowratecanbegivenby:

Ultrasonicflowmeter.Anultrasonicflowmetermeasuresthevolumetricflowbyusingsoundpulsetransittimein
theflowmediumcausedbydoplareffect.1517Atypicalultrasonicflowmeter(transittimeflowmeasurement)system
utilizestwoultrasonictransducersthatfunctionasbothtransmitterandreceiver.Theflowmeteroperatesby
alternatelytransmittingandreceivingasoundenergyburstbetweenthetwotransducersandmeasuringthetransit
timethatittakesforsoundtotravelbetweenthetwotransducers.Thedifferenceinthetransittimemeasuredis
directlyandrelatedtotheliquidvelocityinthepipe.
IftDisthesoundpulsetransittime(ortimeofflight)travelingfromtheupstreamtransducertothedownstream
transducer,andtUisthetransittimefromtheoppositedirection,theequationscanbegivenas:

wheretheta=Anglebetweenthetransduceraxistotheflowdirection,
c=Soundspeedintheliquid,
D=Pipeinsidediameter
u=Flowvelocityaveragedoverthesoundpath.Solvingtheaboveequationsleadsto:

http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true

13/25

16/5/2016

Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011

wheretf =(tUtD)/(tUtD)isthetransittimefunctionandKistheinstrumentfactordeterminedthroughcalibration.
Therefore,byaccuratelymeasuringtheupstreamanddownstreamtransittimes,tUandtD,theflowvelocity,u,canbe
obtained.
Actualvolumetricflowrateiscalculatedas:

whereAisthepipeinnercrosssectionarea.
Magneticflowmeter.MagneticflowmeteroperationisbasedonFaradaysLawthatstatesthatthevoltageinduced
acrossanyconductorasitmovesatrightanglesthroughamagneticfieldisproportionaltotheconductorvelocity.18
Toapplythisprinciplethefluidbeingmeasuredmustbeelectricallyconductive.
Thevoltage,E,generatedinaconductorisgivenby:
E(alpha)BLu
where:
E=Voltagegeneratedinaconductor
B=Magneticfieldstrengthperpendiculartotheflowdirection
L=Distancebetweentheelectrodes(usuallyequaltopipeinsidediameterinmostconstruction)
u=Conductorvelocity.
Thefluidvelocitycanbegivenby:

whereKistheinstrumentcoefficientthatisusuallydeterminedthroughcalibration.
Subsequently,theactualvolumetricflowrateiscalculatedas:

whereAisthepipeinnercrosssectionareaandDisthepipeinsidediameter.
Massflowmeters.
Acoriolisflowmeterdirectlymeasuresthemassflowbasedontheinertialforcesexertedonthetubevibrations.1921
Whenanoscillatingexcitationforceisappliedtothetube,causingittovibrate,thefluidflowingthroughthetubewill
induceatwist(orrotation)tothetubebecauseoftheCoriolisaccelerationactinginoppositedirectionsoneitherside
oftheappliedforce.
InaUtubecoriolismeter,theflowisguidedintotheUshapedtubethatisvibratedusinganactuator.Thevibrationis
commonlyintroducedbyelectriccoilsandmeasuredbymagneticsensors.Whenthetubeismovingupwardduring
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true

14/25

16/5/2016

Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011

thefirsthalfofacycle,thefluidflowingintothemeterresistsbeingforcedupbypushingdownonthetube.Onthe
oppositeside,theliquidflowingoutofthemeterresistshavingitsverticalmotiondecreasedbypushinguponthe
tube.Thisactioncausesthetubetotwist.Whenthetubeismovingdownwardduringthesecondhalfofthevibration
cycle,ittwistsintheoppositedirection.Thetwovibrationsareshiftedinphase(timelag)withrespecttoeachother,
andthedegreeofphaseshiftisdirectlyaffectedbythemasspassingthroughthetube.
AUshapedCoriolisflowmetermassflowisgivenas:

whereKu=Tubestiffness,
K=Ashapedependentfactor
L=Width,
t=Timelag,
omega=Vibrationfrequency
Iu=Tubeinertiathatincludesthetubefluidmass.Theexpressioncanbesimplifiedas:

where:

isthenaturalfrequencyoftheUshapedtubesystem.
Thermalflowmeter.
Athermalflowmetermeasuresthemassflowbasedonheatabsorption.Asmoleculesofamovingfluidcomeinto
contactwithaheatsource,theyabsorbheatandcoolthesource.Atincreasedflowrates,moremoleculescomeinto
contactwiththeheatsourceabsorbingevenmoreheat.Theheatdissipatedfromthesourceinthismanneris
proportionaltothenumberofmoleculesofaparticulargas(itsmass),thegasthermalcharacteristics,anditsflow
characteristics.Themassflowofathermalmassflowmetercanbegivenas:
QMass =KH
whereKistheinstrumentcoefficientwhichisusuallydeterminedthroughcalibration,andHistheamountofheat
dissipatedfromtheheatsource.
APPENDIXB:FLOWMETERCORRECTIONCALCULATIONS
Flowcorrectionfordifferentialpressureflowmeters.
Actualflowfordifferentialpressuremetersiscalculatedusing:
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true

15/25

16/5/2016

Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011

Assumingincompressiblefluidintherangeofinterest(constantfluiddensitybetweentheflowmeterpressuretaps)
theactualflowratemeasuredbytheflowmetercanbegivenas:

Liquidflowmeter(actualvolumetricflowmeasurementact.m3/h).Theequationforcorrectedflowis:

Liquidflowmeter(standardvolumetricflowmeasurementstd.m3/h).Standardvolumetricflowiscalculated
using:

Theequationforcorrectedflowis:

Liquidflowmeter(massflowmeasurementkg/h).Massflowiscalculatedusing:

http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true

16/25

16/5/2016

Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011

Theequationforcorrectedflowisgivenby:

Gasflowmeter(actualvolumetricflowmeasurementact.m3/h).Theequationforcorrectedflowis:

Gasflowmeter(standardvolumetricflowmeasurementstd.m3/h).Standardflowrateis:

Theequationforcorrectedflowisgivenby:

Gas/steamflowmeter(massflowmeasurementkg/h).Theequationformassflowis:

Theequationforcorrectedflowis:

http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true

17/25

16/5/2016

Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011

Flowcorrectionforvolumetricflowmeters.
Actualflowmeasuredbythevolumetricflowis:
Vortexmeter:QActVolfv
Turbinemeter:QActVolomega
Ultrasonicmeter:QActVolf(TUP ,TDown)
Magneticmeter:QActVolE
Liquidflowmeter(actualvolumetricflowmeasurementact.m3/h).Theequationforcorrectedflowis:

Liquidflowmeter(standardvolumetricflowmeasurementstd.m3/h).Standardvolumetricflowiscalculated
using:

Theequationforcorrectedflowis:

Liquidflowmeter(massflowmeasurementkg/h).Massflowiscalculatedusing:

Theequationforcorrectedflowis:

Gasflowmeter(actualvolumetricflowmeasurementact.m3/h).Theequationforcorrectedflowis:
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true

18/25

16/5/2016

Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011

Gasflowmeter(standardvolumetricflowmeasurementstd.m3/h).Standardvolumetricflowiscalculatedusing:

Theequationforcorrectedflowis:

Gas/steamflowmeter(massflowmeasurementkg/h).Theequationformassflowis:

Theequationforcorrectedflowis:

Flowcorrectionformassflowmeters.
Massflowratesforthemassflowmetersis:
Coriolismeter:QMass t
Thermalmeter:QMass DH
Liquidflowmeter(actualvolumetricflowact.m3/h).Actualvolumetricflowiscalculatedusing:

Theequationforcorrectedflowis:

http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true

19/25

16/5/2016

Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011

Ifthecoriolismeterhasanintegraldensitymeasurementandusestheoperatingdensity(orflowingdensity)instead
ofdesigndensity,rD,intheaboveequations,thencorrectionfactorisequalto1.
Liquidflowmeter(standardvolumetricflowstd.m3/h).Standardvolumetricflowiscalculatedusing:

Theequationforcorrectedflowis:

Liquidflowmeter(massflowmeterkg/h).Equationforcorrectedflowis:
QMass_Corr=QMass_Meas
Thecorrectionfactorrequiredforcorrectingtheflowmeterreadingisequalto1.
Gasflowmeter(actualvolumetricflowmeasurementact.m3/h).Actualvolumetricflowiscalculatedusing:

Theequationforcorrectedflowis:

Ifthecoriolismeterhasanintegraldensitymeasurementandusestheoperatingdensity(orflowingdensity)inthe
aboveequationsinsteadofdesigndensity,thencorrectionfactorisequalto1.
Gasflowmeter(standardvolumetricflowmeasurementstd.m3/h).Standardvolumetricflowis:

http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true

20/25

16/5/2016

Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011

Theequationforcorrectedflowis:

Gasflowmeter(massflowmeterkg/h).Theequationforcorrectedflowis:
QMass_Corr=QMass_Meas

APPENDIXC:PROPAGATIONOFUNCERTAINTYBYTAYLORSERIES
Thesensitivitycoefficientassociatedwitheachflowvariableisderivedanalyticallybypartialdifferentiationbasedon
uncertaintypropagationbytheTaylorseries[ASMEMFC2M,1983].TherelationshipofdependentvariableQwith
independentvariablesx1,x2,...,xNcanbeexpressedinageneralformas:
Q=f(x1 ,x2,...,xN)
UsingtheTaylorseriestheuncertaintyinQcanbeexpressedas:

Squaringonbothsides,theequationcanbewrittenas:

Giventhatthevariablesareuncorrelated(independent),i.e.,(delta)xi(delta)xj=0(ij),allthevaluesofthe
summationintheaboveequationwillbezero.Therefore,theuncertaintyinQcanbegivenas:

http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true

21/25

16/5/2016

Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011

whichcanberepresentedinasimplerformas:

where(delta)Q/QistheuncertaintyinQ,Sxisthesensitivitycoefficientassociatedwiththevariable,andUxisthe
uncertaintyofthevariable.

APPENDIXD:UNCERTAINITYEQUATIONSFORVORTEX,TURBINE,ULTRASONIC
ANDCORIOLIS
Vortexflowmeteruncertaintyis:

Turbineflowmeteruncertaintyis:

Ultrasonicflowmeteruncertaintyis:

http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true

22/25

16/5/2016

Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011

Coriolisflowmeteruncertaintyis:

NOMENCLATURE
SubscriptDDesignvaluesfromflowmeterspecificationdatasheet
SubscriptMMeasuredvaluesduringplantoperation
MMolecularweight
PPressure,kPaa
PPressuredrop,kPa
QFlowrate
QMass Massflowrate,kg/h
QActVolVolumetricflowrateatactualoperatingconditions,act.m3/h
QStdVolVolumetricflowrateatstandardconditions(15Cand1atm.),std.m3/h
QMass_Meas Measured(readout)massflowratefromtheflowmeter,kg/h
QActVol_Meas Measuredactualvolumetricflowrate(readout)fromtheflowmeter,act.m3/h
QStdVol_Meas Measuredstandardvolumetricflowrate(readout)fromtheflowmeter,std.m3/h
QMass_CorrCorrectedmassflowratefortheflowmeter,kg/h
QActVol_CorrCorrectedactualvolumetricflowratefortheflowmeter,act.m3/h
QStdVol_CorrCorrectedstandardvolumetricflowratefortheflowmeter,std.m3/h
RUniversalgasconstant(R=8.3145kPaam3/kmolK)
SSensitivitycoefficient
TTemperature,K
UUncertainty
U95Uncertaintyat95%confidencelevel
ZCompressibilityfactorforgases(Z=1foridealgas)
sStandarddeviation
rMassdensity,kg/m3
rDDesigndensityatactualconditionsfromflowmeterspecificationdatasheet
rMMeasured(orcalculated)densityatactualconditionsduringoperation
rD_StdDesigndensityatstandardconditionsfromflowmeterspecificationdatasheet
rM_StdMeasureddensityatstandardconditionsduringoperation
Acknowledgments
TheauthorsthanktheircolleagueKenFernie,P.Eng.,forreviewandvaluablecommentsoncustodytransfer
metering,andAndrewNelson,ProductionmanagementmanagerfromMatrikonInc.,hisforreviewandvaluable
inputonflowmeteruncertainties.
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true

23/25

16/5/2016

Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011

LITERATURECITED
1 Spitzer,D.W.,FlowMeasurement:PracticalGuidesforMeasurementandControl,2ndEdition,Research

TrianglePark,NC:ISA,2001.
2Upp,E.L.andP.J.LaNasa,FluidFlowMeasurement:APracticalGuidetoAccurateFlowMeasurement,Gulf

ProfessionalPublishing,2ndEdition,2002.
3Romagnoli,J.A.andM.C.Sanchez,DataProcessingandReconciliationforChemicalProcessOperations,

ProcessSystemsEngineering,Vol.2,AcademicPress,1stEdition,1999.
4Ozyurt,D.B.andR.W.Pike,TheoryandPracticesofSimultaneousDataReconciliationandGrossErrorDetection

forChemicalProcesses,ComputersandChemicalEngineering,28,pp.381402,2004.
5 ASMEMFC2M,MeasurementUncertaintyforFluidFlowinClosedConduits,AmericanNationalStandard,1983

(Revised2006).
6AGARP31,OrificeMeteringofNaturalGasandOtherRelatedHydrocarbonFluidsPart1GeneralEquations

andUncertaintyGuidelines,AmericanGasAssociation,June2003.(APIMPMS14.31ANSI/API253091Part1
GasProcessorsAssociationGPA8185Part1).
7Yawas,C.L.,etal,EquationforLiquidDensity,HydrocarbonProcessing,Vol.70,No1,January1991,pp.103

106.
8Fisher,C.H.,HowtoPredictnAlkaneDensities,ChemicalEngineering,Vol.96,No10,pp.195,October1989.
9Noor,A.,QuickEstimateofLiquidDensities,ChemicalEngineering,Vol.88,No.7,pp.111,6thApril1981.
10 ASMEMFC3M,MeasurementofFluidFlowinPipesUsingOrifice,NozzleandVenturi,AmericanNational

Standard,2004.
11 ASMEMFC6M,MeasurementofFluidFlowinPipesusingVortexFlowmeters,AmericanNationalStandard,

1998(Revised2005).
12AGARP7,MeasurementofNaturalGasbyTurbineMeters,AmericanGasAssociation,February2006.
13APIMPMS5.3,MeasurementofLiquidHydrocarbonsbyTurbineMeters,AmericanPetroleumInstitute,

September2000.
14ASMEMFC4M,MeasurementofGasFlowbyTurbineMeters,AmericanNationalStandard,1986(Revised

2008).
15 AGARP9,MeasurementofGasbyMultipathUltrasonicMeters,AmericanGasAssociation,April2007.
16APIMPMS5.8,MeasurementofLiquidHydrocarbonsbyUltrasonicFlowMetersUsingTransitTime

Technology,AmericanPetroleumInstitute,February2005.
17ASMEMFC5M,MeasurementofLiquidFlowinClosedConduitsUsingTransitTimeUltrasonicFlowmeters,

AmericanNationalStandard,1985(Revised2006).
18ASMEMFC16M,MeasurementofLiquidFlowinClosedConduitswithElectromagneticFlowmeters,American

NationalStandard,1995(Revised2006).
19AGARP11,MeasurementofNaturalGasbyCoriolisMeter,AmericanGasAssociation,January2003.
20 APIMPMS5.6,MeasurementofLiquidHydrocarbonsbyCoriolisMeters,AmericanPetroleumInstitute,

October2002.
21 ASMEMFC11M,MeasurementofFluidFlowbyMeansofCoriolisMassFlowmeters,AmericanNational

Standard,1989(Revised2003).

Theauthors

SubodhsenPeramanuhasmorethan15yearsofexperienceinconceptual,frontenddesignand
detailedengineeringofupgradingandrefiningprocesses.Hehasauthoredpapersontopicsincluding
hydrogenseparationandeconomics,bitumencharacterization,andasphaltenesolubilityand
reversibility.Dr.PeramanuwasinvolvedincommissioningandstartupofCNRLHorizonUpgrader
andisworkingwithCNRLThermalTeamasaseniorengineeringspecialistoninsituoilrecovery.He
holdsaBChemEngdegreeinchemicalengineeringfromInstituteofChemicalTechnology(formerly
UDCT),Mumbai,MTechdegreefromIndianInstituteTechnology,KanpurandPhDfromUniversityof
http://www.hydrocarbonprocessing.com/Article/2913712/Improvematerialbalancebyusingproperflowmetercorrections.html?Print=true

24/25

16/5/2016

Improvematerialbalancebyusingproperflowmetercorrections|HydrocarbonProcessing|October2011

Calgary.

JuonWahscareerinprocessengineeringspansmorethan30yearsandcoversconceptualdesign,
FEED,EPCanddetailedprocessandequipmentdesignofmajorprojectsinrefining,bitumen
upgradingandoilandgasproductionfacilities.Atpresent,Mr.Wahisaconsultantonprocessdesign
andplantoperations.Atthetimeofwriting,hewasworkingonanexpansionprojectfortheHorizon
UpgradingcomplexofCNRL.Mr.WahholdsaBScdegreeinchemicalengineeringfromtheUniversity
ofBirmingham,UK,andaDiplmedIngnieurinchemicalengineeringandpetroleumrefiningfrom
theIFP,France.

AnatoliyPavlov
10.12.2015
Iwouldliketosuggestuseofanewheattype(noknownThermalMass)fastactinggasliquidMASSFLOWMETER
forimmersioninunsteadyflow.DetailsinEmail:[email protected].
C.Voigt
11.11.2014
DearSir,
couldyoupleasesentmethroughthenamesofthestandardswhichhavebeenusedtocalculatethecorrectionfactor
forgasflowatstdm3/hrintable1?Thankyouverymuchinadvance,
C.Voigt
SHASHIKANTDAWALKAR
02.23.2014
DearSir,
Pleaseletmeknowtheprincipleofcorrectionfactorappliedinthemeasurementofcorrectionfactorandthe
calculationofcorrectionfactorforvolumentricflowthroughorificemeter.
WithRegards
RichardvonBrecht
01.20.2013
Thisisanamazingarticle.tome.I'munfamiliarwithsomeofthenomenclature.I'dbeinterestedseeinganexpanded
versionofyourpaper.
MuhammadFarhatUllah
12.19.2011
Itisreallyhandyandvaluablearticle.Thanks