Analog Control System
Analog Control System
KORBA SIMULATOR
223
KORBA SIMULATOR
224
2.
3.
4.
5.
SH temperature control
6.
Draft control
Acs has got two operating channels which are simultaneously active i.e.
Teleperm - M & Teleperm - C
Teleperm C - is the control system which is purely hardware based electronic wherein
controls all the related logics & computation are done through electronic
cards/modules only.
Teleperm M - This the control which uses software in addition to hardware electronic
cards. Wherein part of the computation logics are performed through software. During
KORBA SIMULATOR
225
normal operation if Tel. C fails for a particular system, that control will transfer to Tel
M automatically however reverse is not possible. Selection of any of these two channel
can be done from UCB depending on the healthiness of control system.
Hotwell Level Control
Condenser hotwell level shall be controlled by regulating the make up water flow to the
condenser. The make up to condenser is primarily provided through the make up line
from demineralisation plant. If the condenser make up demand exceeds the flow in
DM water make up line ,the additional requirement of make up water shall be
supplied from condensate storage tank. Accordingly ,the low level in hotwell shall be
controlled by modulating:
(a)
(b)
Hotwell level control system is provided with three separate controllers termed as
Hotwell high level controller, Hotwell normal level controller and Hotwell low level
controller. For high level and normal or low level there are two separate level
transmitters. In all the three controllers actual Hotwell level is measured through
level transmitters, Output of which is inturn converted into corresponding current
signal and then voltage signal through two converters .The available voltage signal is
compared with Hotwell level set value in terms of voltage. Net available voltage is fed to
a PI controller and output of this used for opening or closing of respective pneumatic
control valves provided for Normal, Emergency or spill control thereby controlling the
makeup flow as per the demand. Actual position feed back of the valve is available in
the UCB. Control circuit is provided with hard hold memory card which retains the
last available value and provides smooth change over to manual whenever auto control
fails.
Auto control fails giving a flashing lamp on the controller module when actual level
goes beyond the level transmitter range.
Drum Level Control / Feed Water Control
This control loop is used for controlling of drum level. Depending on the feed water
flow path two separate control loops are used.
Namely, single element control & three element control.
Single element control :- This control system gets selected when BLI(Boiler load
index)is below < 20 % and feed water flow is controlled through low range line. In this
control system actual level of drum, after pressure correction, is compared with the set
point and available net voltage is processed through a PID controller. Output of this
controller is used for generation of pneumatic pressure for actuation of low range feed
water control valve. Actual valve position is displayed in UCB. If running BFP
scoop/speed is kept on auto it will slowly bring the speed to a constant value which is
already preset in the control system and the feed flow will be controlled through
pneumatic control valves.
KORBA SIMULATOR
226
Three element control :- Three element control is selected for higher load operation.
In this control the feed flow is controlled by varying BFP speed. The set demand for
scoop is achieved as follows Actual drum level and set point difference, after taking into account input of BLI, is
compared with sum of feed water flow & SH spray flow signal . The net resultant
output is fed to a PI controller and subsequently the output of feed master controller
sets the speed demand for TDBFP and MDBFP.
Primary Air Pressure Control
It is needed to maintain sufficient primary air pressure under all condition as this is
essential for carrying coal from pulveriser to furnace. Under this control system
actual pressure developed by PA fans is converted into voltage and is compared with
the set voltage (in terms of PA header pressure)then the net available output is
separately processed through two PI controllers meant for individual control loop, the
output of these controllers is used to set the demand position of blade pitch of each
fans. Actual position of blade pitch is available in UCB. Moreover biasing is provided
for adjusting the loading between two fans. Control loop includes following interlocks
1.
Control system is released for auto operation only after outlet damper has opened
fully.
2.
3.
227
processed through separate PID controllers for spray control & the demand position of
spray valve and burner tilt. Demand position of RH spray valves are displayed on the
panel and average tilt position along with the position feedback of all the four corners
tilt position is shown separately on UCB panel.
SH temperature Control
In this control system SH steam outlet temp. is maintained at set point which is equal
to the minimum of
(1)
(2)
Set point derived through a function generator based on BLI (Boiler Load Index).
Thus derived temp. set point is compared with signal corresponding to actual main
steam temp. measured through thermocouple at SH outlet. Separate comparison is
done for SH left and right streams . Error signals thus developed are further
influenced by feedforward signals from burner tilt position and BLI.
These corrected error signals are now compared with respective error signals derived
by desuperheater control loop and the final error signals are given as input to two
separated PID controllers ,one each for left and right streams, for finally controlling
the superheater spray through pneumatically operated control valves. The controler
output is displayed in UCB. An interlock is provided for closing the inlet block valve
below 5% opening of control valves..
Co - ordinated Control System :
As electrical energy cannot be stored in a large quantity it is necessary to balance its
generation with momentary consumption. The grid frequency is the factor which
indicates the degree of balance between production (generation) and the consumption.
In absence of storage capacity for electrical energy it is a must for a modern power
plant to have adequate control system to respond to rapid load changes and at the
same time control the process/the equipments so that no part of the plant runs into a
dangerous operating state i.e. the pressure, temperature and other process
parameters must not cross the designed/safe limits of a particular equipment ,
otherwise, the availability and required safety of the man and machine will be
reduced / endangered.
In order to achieve best efficiency and best availability with requisite safety, it is
necessary that operation of both the main plant equipments ( i.e. Boiler and Turbine)
is co-ordinated using suitable control system and there should be a possibility of
decoupling them during disturbances by means of bypass system.
Boiler and Turbine have a number of equipments which must be able to follow their
demands during unit start-up / shutdown and load variations. As a result, the power
plant process has a hierarchial structure and in order to match with the process best
KORBA SIMULATOR
228
KORBA SIMULATOR
229
To ensure that the unit is following the load set point closely, an inhibit increase /
decrease feature is provided. If any of MW, Throttle steam pressure, FW flow, Fuel
flow & PA Header pressuredeviates from set point significantly or has reached the
MAX/MIN limits, the load demand is inhibited from increasing or decreasing as the
case may be. Air flow & turbine load limit active are two additional signals to inhibit
increase of load demand.
Boiler master and generation of fuel / air set point:
The function of the boiler master auto / manual station in CMC Console is to provide
a set point for fuel and air flow i.e. fuel demand and air demand signals. In Coordinated mode, it is equal to sum of boiler load set point and master controller (PID)
output. In this mode Boiler master controller acts on DP error. The fuel demand as
generated is compared with actual air flow and a minimum of the two is selected as
the fuel set point.
The air demand as generated is compared with fuel flow & 30 % of air flow and
maximum is selected as air set point. This MIN/MAX selection ensures an air rich
furnace. When fuel/air demand increases the MAX gate first increases the air set
point and when fuel demand decreases the MAX gate permits reduction of air flow only
after fuel has decreased.
Fuel Flow control :
Oil flow to burners and feeders speed (which is the measure of coal flow) along with
Calorific Value(C.V) corrections added to get total fuel flow. Cabinet adjustments are
provided to take care of individual calorific values to obtain total fuel flow as fuel oil
equivalent (FOE). The total fuel flow (FOE) is compared with fuel set point to
generated fuel control error. This control error is fed through (Pl) controller (Master
Fuel Controller) to all feeders in auto and Each feeder is provided with a bias and an
auto /manual station.
Secondary Air Flow Control
As mentioned earlier, air demand is generated as the MAX of the following:1)
2)
3)
At SSTPS secondary air flow is measured by aerofoil near the windbox (left & right) by
two transmitters, sum of the two transmitters give the secondary air flow. Primary air
flow is added to this to give total air flow which is used for combustion control, purge
logic & SADC (Secondary Air Damper Control). This actual air flow is compared with
the air set point and then modified by O2 trim to generate the air flow control error.
This signal is doubled in case only one, out of two running fans available for automatic
control. An equalising and biasing signal is added to equalise and bias the individual
fan air flows. Control signal thus formed operates on the individual controller (for
KORBA SIMULATOR
230
each fan) whose output fires the thyristor drives of the 415 V AC motors for blade
pitch control. An auto / manual station is provided for each fan.
O2 TRIM
A selection station and a setter for oxygen set point are provided to achieve the desired
excess air. If variable O2 set point (SP) is selected, set point is generated by a function
generator which is a function of MAX (air flow SP and total air flow). In other mode SP
is set from UCB. O2 in flue gas is compared with this SP and error is fed to PI
controller, output of which is limited between 0.8 and 1.2 times of total air flow. O2 PI
controller output is now multiplied by total air flow and the resultant O / P signal is
given to makes the FD fans blade pitch controllers for achieving desired air flow. O2
probes are provided at the outlet of economiser for measurement and control of the
flue gas O2. These probes are zirconium oxide probes working on the principle of
partial pressure of oxygen.Thus the input signal to FD Fan blade pitch controllers is
trimmed by O2 signal to get desired Excess air / O2 set point
Generation of DP / DMW Signals
The pressure set point compared with actual throttle steam pressure to obtain the
control error signal DP. Three pressure transmitters are provided for redundancy
along with deviation monitoring and middle of the three is selected as actual pressure.
In case of two transmitters fault, the control is put to manual. The pressure set point
generated in this circuit is also sent to HP Bypass Control. Actual MW signal (middle
value of O/P of 3 transducer) is sent from turbine control panel to CMC console where
DMW signal is formed as the difference between load demand and actual MW.
Selection of CMC
1.
Put Air Master on Auto i.e. atleast one FD fan blade pitch controller on auto.
2.
Put feeders speed control on auto after varying Fuel Master (FM) output and
making feeder speed controller error zero.
3.
Vary Boiler Master Output so that FM error becomes zero. Then put FM on auto.
4.
Make throttle pre. set point and actual pr. difference zero .
5.
Put BM on auto
6.
Increase / decrease unit master output so that it becomes equal to actual load.
(wait until load set value and load actual value matches as shown in the CMC
console digital indicator)
7.
8.
Press co-ordinated push button along with manual release on CMC desk.
KORBA SIMULATOR
231
2)
If the unit is in co-ordinated mode automatic change over to Boiler Follow Mode occurs
under following conditions
a)
b)
(PrCMC - Pr lim) > 60 MW [i.e. when difference between set point guidance signal
and load set point for EHC is more than 60 MW ]
2)
3)
KORBA SIMULATOR
232
4)
Press Turbine follow push button along with manual release on CMC desk and
turbine goes to
initial pressure mode from limit pressure modes by itself.
5)
Now load set point can be changed by varying the boiler master manually.
Runback Mode
Under runback condition the firing rate for the boiler must be reduced to pre-set
values, as close as possible to the tolerable limits. Therefore the swings of firing rate
caused by the action of the PID controller must be avoided. As consequence of this
condition the system has to be switched to pure feed forward control, where the firing
rate set point is directly proportional to the load capability signal. To avoid any
mismatch between steam production of the boiler and the turbine load, the turbine
has to be switched to initial pressure control, as with TFM.
Runback Resetting
1)
2)
Reduce load set point from the turbine desk to a value slightly less than Unit
capability so that 1 0 Runback in Operation resets.
KORBA SIMULATOR
233