ISeries Instruments Addendum 104633-00 16aug2012
ISeries Instruments Addendum 104633-00 16aug2012
iSeries Instruments
Part Number 104633-00
16Aug2012
This section describes the updates and corrections that apply to the
Introduction chapter.
In the features list, replace the associated feature with the following:
Analog
outputs
Chapter 2 - Installation
1 RS-232 or RS-485 with two connectors, baud rate 1200115200, data bits, parity,
and stop bits, protocols: C-Link, MODBUS, Geysitech (Bayern-Hessen), and
streaming data (all user selectable)
This section describes the updates and corrections that apply to the
Installation chapter.
In the Setup section, add the following reference in the step for
connecting a recording device to the rear panel connector:
Instrument Controls > I/O Configuration in the Operation chapter.
Connecting External
Devices
Figure x-x shows the recommended method for attaching the cable to the
terminal board using the included tie-down and spacer. Table x-x identifies
the connector pins and associated signals.
Note Not all of the I/O available in the instrument is brought out on this
terminal board, if more I/O is desired, an alternative means of connection
is required.
See Detail B
See Detail A
Detail B
Assembled Connector
Pin
Signal Description
Pin
Signal Description
Analog1
13
Power_Fail_NC
Analog ground
14
Power_Fail_COM
Analog2
15
Power_Fail_NO
Analog ground
16
TTL_Input1
Analog3
17
TTL_Input2
Analog ground
18
TTL_Input3
Analog4
19
TTL_Input4
Analog ground
20
Digital ground
Pin
Signal Description
Pin
Signal Description
Analog5
21
TTL_Input5
10
Analog ground
22
TTL_Input6
11
Analog6
23
TTL_Input7
12
Analog ground
24
Digital ground
Figure x-x shows the recommended method for attaching the cable to the
terminal board using the included tie-down and spacer. Table x-x identifies
the connector pins and associated signals.
See Detail A
See Detail B
Detail B
Assembled Connector
Pin
Signal Description
Pin
Signal Description
Relay1_ContactA
13
Relay7_ContactA
Relay1_ContactB
14
Relay7_ContactB
Relay2_ContactA
15
Relay8_ContactA
Relay2_ContactB
16
Relay8_ContactB
Relay3_ContactA
17
Relay9_ContactA
Relay3_ContactB
18
Relay9_ContactB
Pin
Signal Description
Pin
Signal Description
Relay4_ContactA
19
Relay10_ContactA
Relay4_ContactB
20
Relay10_ContactB
Relay5_ContactA
21
Solenoid_Drive_Output1
10
Relay5_ContactB
22
+24V
11
Relay6_ContactA
23
Solenoid_Drive_Output2
12
Relay6_ContactB
24
+24V
The 25-pin terminal board is included with the I/O Expansion Board.
See Detail A
See Detail B
Detail B
Assembled Connector
Pin
Signal Description
Pin
Signal Description
IOut1
13
Analog_In1
GND_ISO
14
Analog_In2
IOut2
15
Analog_In3
GND_ISO
16
GNDD
Chapter 3 - Operation
Power-Up Screen
Pin
Signal Description
Pin
Signal Description
IOut3
17
Analog_In4
GND_ISO
18
Analog_In5
IOut4
19
Analog_In6
GND_ISO
20
GNDD
IOut5
21
Analog_In7
10
GND_ISO
22
Analog_In8
11
IOut6
23
GNDD
12
GND_ISO
24
GNDD
This section describes the updates and corrections that apply to the
Operation chapter.
Replace the Thermo Electron Corporation power-up screen with the
Thermo Scientific power-up screen.
Status Bar In the Run Screen section, add the following that describes the new
status bar icons.
The status bar displays the time, the password (lock) icon, service
(wrench) icon, alarm (bell) icon, and optional zero/span sample solenoid
valve status, if installed.
Note Time is always displayed in 24-hour format.
Degree Symbol
Change the Alarm references on the status bar to the bell icon or remove
the reference. The Alarm references have been replaced with status bar
icons described previously in this document.
Screens which show temperature values should include the degree symbol
not just the C for Celsius units. The degree symbol has been added to
all screens that were missing it.
The iSeries instruments include a built-in data logging capability as a
standard feature. The operator is allowed to create two different types of
records, which for historical reasons are named lrecs and srecs. Each record
can contain up to 32 different fields or data items, and records can be
created at user-defined intervals ranging from 1 to 60 minutes.
Record generation is tied to the instruments real-time clock. For example,
if the logging period for srecs is set to 30 minutes, a new srec will be
generated on every hour and every half hour (10:00, 10:30, 11:00 ).
Lrecs and srecs can be interleaved. For example, an srec containing just the
current concentration level could be generated every five minutes while an
lrec containing a full set of diagnostic data could be generated once every
hour.
The analyzers computer system includes three megabytes of flash memory
which is enough to store a full lrec containing 32 data items and a full srec
containing 32 items once each minute for a week (>20,000 total records).
If logging is limited to the minimum content of date, time, concentration
and error flags, the analyzer can store data once each minute for four
months (>190,000 records).
Add Span and BKG
Reset to Default Content
AVG
DIAGS ALARM
Add Serial Settings descriptions and menu including Data Bits, Parity, and
Stop Bits.
Note The Baud Rate and RS-232/485 selections were moved from the
Communications Settings menu to the Serial Settings screen.
Serial Settings
The Serial Settings menu is used for serial communications control and
configuration. In the Main Menu, choose Instrument Controls >
Communication Settings > Serial Settings.
SERIAL SETTINGS:
>BAUD RATE
DATA BITS
PARITY
STOP BITS
RS-232/485 SEL
RANGE
Baud Rate
AVG
9600
8
NONE
1
RS-232
DIAGS ALARM
The Baud Rate screen is used to set the RS-232/RS485 interface baud rate.
Baud rates of 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200
are available. The analyzers default baud rate is set to 9600 to provide
backwards compatibility with the older C-series analyzers.
BAUD RATE:
CURRENTLY:
SET TO:
9600
19200 ?
CHANGE VALUE
SAVE VALUE
RANGE
Data Bits
AVG
DIAGS ALARM
The Data Bits Screen is used to set the number of serial data bits.
Selections of 7 or 8 are available (defaults to 8).
DATA BITS:
CURRENTLY:
SET TO:
8
7
CHANGE VALUE
SAVE VALUE
RANGE
Parity
AVG
DIAGS ALARM
The Parity screen is used to select the parity bit for the serial port.
Selections of NONE, EVEN, or ODD are available (defaults to NONE).
PARITY:
CURRENTLY:
SET TO:
NONE
NONE
CHANGE VALUE
SAVE VALUE
RANGE
Stop Bits
AVG
DIAGS ALARM
The Stop Bits screen is used to select the number of stop bits for the serial
port. Selections of 1 and 2 are available (defaults to 1).
STOP BITS:
CURRENTLY:
SET TO:
1
2
CHANGE VALUE
SAVE VALUE
RANGE
Replace Equipment
Damage Alert
AVG
DIAGS ALARM
Add Network Time Protocol Server (NTP SVR) to the TCP/IP Settings
menu as follows:
Main Menu > Instrument Controls > Communication Settings > TCP/IP
Settings.
TCP/IP SETTINGS:
>USE DHCP
OFF
IP ADDR
192.168.1.200
NETMASK
255.255.255.0
GATEWAY
192.168.1.15
HOST NAME
iSeries
NTP SVR
192.168.1.15
RANGE
10
AVG
DIAGS ALARM
DIAGS ALARM
Main Menu > Instrument Controls > I/O Configuration > Output Relay
Settings > Relay 1-10 > Instrument State > Non-Alarm, add Local/Remote
to the Non Alarm Status Items menu.
RANGE
AVG
AVG
DIAGS ALARM
In the Digital Input Settings section, under Instrument Controls, add the
following note, if it is not already included:
Note Not all of the I/O available in the instrument is brought out on the
supplied terminal board, if more I/O is desired, an alternative means of
connection is required.
Add Allow Over/Under Range to Output Channels Screen and add the
Allow Over/Under Range screen as follows:
Main Menu > Instrument Controls > I/O Configuration > Analog Output
Config.
11
OUTPUT CHANNELS:
>ALLOW OVER/UNDER RANGE
ALL VOLTAGE CHANNELS
ALL CURRENT CHANNELS
VOLTAGE CHANNEL 1
VOLTAGE CHANNEL 2
VOLTAGE CHANNEL 3
VOLTAGE CHANNEL 4
RANGE
AVG
DIAGS ALARM
TOGGLE VALUE
RANGE
AVG
DIAGS ALARM
Screen Contrast
12
The optimal contrast will change from one LCD screen to another. If the
LCD screen is replaced, the contrast may need to be reset.
If the display contrast is not optimal, but the content on the screen is
visible, select Instrument Controls > Screen Contrast and adjust the screen
contrast. If the content on the screen is not visible, use the set contrast 10
C-Link command to set screen contrast to mid range, then optimize the
contrast. See Contrast Levels in the C-Link Protocol Commands
Appendix section of this document for more information on this
command.
AVG
DIAGS ALARM
SCREEN CONTRAST
SERVICE MODE
DATE/TIME
TIMEZONE
13
SAVE VALUE
RANGE
Digital Inputs
AVG
DIAGS ALARM
Replace the Digital Inputs description, under the Diagnosis menu, with the
following:
The Digital Inputs screen (read only) displays the state of the 16 digital
inputs. Pull-ups are provided on all the inputs, so if nothing is connected
they will read (1), if an input is brought to ground, it will read (0).
Replace the Zero and Span Check description, under the Alarms menu,
with the following:
The Zero and Span Check screen allows the user to view the status of the
most recent zero/span checks and set the maximum check offsets. An alarm
will be triggered if a zero or span check indicates drift that exceeds the
offset value. The zero and span check screens are visible only if the
zero/span check option is enabled. Their functions are similar.
Replace the Zero and Span Auto Calibration description, under the Alarms
menu, with the following:
The Zero and Span Auto Calibration screens (read only) allow the user to
view the status of the most recent auto background calibration or span
calibrations. The zero and span auto calibration screens are visible only if
the zero/span check option is enabled and the zero or span cal reset
function is enabled.
Add the following note to all pressure, flow, and temperature sensor
calibration screens in the Service menu.
Note Wait at least 30 seconds for the reading to stabilize before saving the
value.
Lock/Unlock and
Local/Remote Operation
14
mode, the keypad is locked, data can be viewed but not changed using the
front panel interface, and the remote Set commands are active.
If the instrument keyboard is unlocked via the front panel using Password
> Unlock Instrument, the instrument reports being in Local mode, the
front panel interface is unlocked, and data can be changed from the front
panel.
Refer to the C-Link Protocol Commands appendix for detailed
information about mode, allow mode, and power up mode
commands.
Add Ext Alarms
Chapter 6 Troubleshooting
Add Cause and Action
Descriptions
This section describes the updates and corrections that apply to the
Troubleshooting chapter.
Possible Cause
Action
Analog signal
doesnt match
expected value.
Analog output
goes above fullscale value or
below zero
15
Chapter 7 Servicing
Equipment Damage Static Electricity Damage
This section describes the updates and corrections that apply to the
Servicing chapter.
16
External Device
Connection
Components
Table x-x lists the standard and optional cables and components used for
connecting external devices such as PCs and data loggers to an iSeries
instrument.
Table x-x. External Device Connection Components
Replace Fan
Replacement Procedure
Fan/Filter
Replacement
Part
Number
Description
102562-00
102556-00
102645-00
102646-00
102659-00
6279
102888-00
102891-00
103084-00
Terminal Board PCB Assembly, DB25M (included with optional I/O Expansion
Board)
Use the following procedure to replace the rear panel fan and the filter.
Equipment Required:
Fan
Fan filter
Philips screwdriver
17
2. Remove the fan guard and filter from the rear of the instrument by
unsnapping it.
3. If the fan is not being replaced, install the new filter, snap it into place,
and skip the remaining steps.
4. If possible, disconnect the fan power cable from the fan, otherwise
disconnect the cable from the measurement interface board.
5. Remove the four fan mounting screws along with nuts and washers and
remove the fan.
6. Install a new fan following the previous steps in reverse order.
Correct Pin Designations on
I/O Expansion Connector
18
Chapter 8 System
Description
Add Connection Information
This section describes the updates and corrections that apply to the
System Description chapter.
Add the following to the Ethernet Connection section:
Up to three simultaneous connections are allowed per protocol.
Add the following to the Analog Voltage Outputs and Analog Current
Outputs (Optional) sections.
At least 5% of full-scale over and under range are also supported, but may
be overridden in software if required.
RS-232 Connection
Change the caption of Table 8-1 to: RS-232 DB9 Connector Pin
Configuration.
RS-485 Connection
Change the caption of Table 8-2 to: RS-485 DB9 Connector Pin
Configuration.
Chapter 9 Optional
Equipment
Change the description of the retrofit rack in Table 9-3 to the following:
If your manual does not include the 25-Pin Terminal Board Assembly
reference, add the following information after I/O Expansion Board
Assembly.
19
25-Pin Terminal
Board Assembly
The 25-pin terminal board assembly is included with the I/O expansion
board. Refer Terminal Board PCB Assemblies in the Installation
chapter for information on attaching the cable to the connector board. For
associated part numbers, refer to External Device Connection
Components in the Servicing chapter.
If your manual does not include the Cables reference, add the following
information after I/O Expansion Board Assembly. Change the table
numbering as appropriate for your manual.
Cables
Table x-x identifies the optional individual cables that are available for the
instrument and provides the cable color codes. For associated part
numbers, refer to External Device Connection Components in the
Servicing chapter.
Note Table x-x provides the color coding for both 25-pin cables and 37pin cables. Color codes for pins 1-25 are for 25-pin cables; color codes for
pins 1-37 are for 37-pin cables.
Table x-x. Cable Options
Description
Cable Length
Six feet
Six feet
Six feet
RS-232
20
Pin
Color
Pin
Color
BLACK
20
RED/BLACK
BROWN
21
ORANGE/BLACK
RED
22
YELLOW/BLACK
ORANGE
23
GREEN/BLACK
YELLOW
24
GRAY/BLACK
GREEN
25
PINK/BLACK
BLUE
VIOLET
26
PINK/GREEN
Pin
Color
Pin
Color
GRAY
27
PIND/RED
19
WHITE
28
PINK/VIOLET
11
PINK
29
LIGHT BLUE
12
LIGHT GREEN
30
LIGHT BLUE/BROWN
13
BLACK/WHITE
31
LIGHT BLUE/RED
14
BROWN/WHITE
32
LIGHT BLUE/VIOLET
15
RED/WHITE
33
LIGHT BLUE/BLACK
16
ORANGE/WHITE
34
GRAY/GREEN
17
GREEN/WHITE
35
GRAY/RED
18
BLUE/WHITE
36
GRAY/VIOLET
19
VIOLET/WHITE
37
LIGHT GREEN/BLACK
CLink Protocol
Commands Appendix
This section describes the updates and corrections that apply to the CLink Protocol Commands appendix.
Add the following new command response table to the C-Link Protocol
Commands appendix under Commands:
Table x-x. Command Response Error Descriptions
Command Response
Description
too high
too low
invalid string
Add the following to the end of the first paragraph and to the Accessing
Streaming Data section:
Up to three simultaneous connections are allowed per protocol.
21
Add /sets following Reports in the analog iout range and analog vout
range command descriptions.
Replace the alarm trig conc description with the following:
Reports/sets current concentration alarm trigger sense.
22
Replace the set layout ack description with the following and add the table:
This command disables the stale layout/layout change indicator (*) that is
attached to each response if the erec layout has changed since the last time
erec layout was requested.
Table x-x. Set Layout Ack Values
Value
Function
Do nothing (default)
Append *
Add the following note to the addr gw, addr IP, and addr nm commands:
Note This command cannot be used when DHCP is on. Refer to the
DHCP command that follows for additional information.
Change alarm internal temp command format from internal alarm temp
to alarm internal temp in the examples and associated set commands.
Change alarm pressure command format from pressure alarm in the
example to alarm pressure.
iSeries Manual Update Addendum
23
Alarm Sample Flow Command If the instrument includes the alarm sample flow command, the response is
formatted to be three digits to the right of the decimal, such as 0.350 lpm
instead of one digit to the right of the decimal.
Clr Records Command Change clear records command format from clear records to clr records
in the example.
Contrast Levels
24
Level
Contrast Level
0%
5%
10%
15%
20%
25%
30%
35%
40%
45%
10
50%
11
55%
12
60%
13
65%
14
70%
15
75%
16
80%
17
85%
18
90%
19
95%
20
100%
Add the following scratch pad description to the list sp, set copy sp to
lrec/srec/stream, set copy lrec/srec/stream to sp, sp field, and set sp field
commands:
The scratch pad is a temporary memory area which is used to set up lists of
selections for lrec, srec, or streaming data items. The user can copy any of
these lists to the scratch pad, modify individual elements in the list, then
save the scratch pad back to the original list. Refer to the sp field
command for information on how to edit the scratch pad.
Add the Allow Mode command to the Commands List section and the
Communications Configuration section as follows:
allow mode cmd
25
Note The instrument will always respond to the command mode with
the status of the password lock as mode local or mode remote
regardless of the above setting.
The example that follows sets the instrument to accept the set mode local
or set mode remote commands.
Send:
Receive:
Value
Ignore (default)
Accept
Add the Power Up Mode command to the Commands List section and
the Communications Configuration section as follows:
power up mode
power up mode
This command reports the current power up mode setting, where value, is
either 0 = local/unlocked or 1 = remote/locked. The default value is 0;
power up in local/unlocked mode. The example that follows shows that the
instrument is configured to power up in the remote/locked mode.
Send:
Receive:
power up mode
power up mode 1
26
Send:
Receive:
Value
Local/Unlocked (default)
Remote/Locked Mode
Add the Addr NTP command to the Commands List section and the
Communications Configuration section as follows:
addr ntp
addr ntp
This command reports the IP address for the NTP time server. See
"Network Time Protocol Server in the Communications Settings
section of the Operation chapter for more information.
Send:
Receive:
addr ntp
addr ntp 192.168.1.2
tz
This command reports the tz timezone string for the NTP server. See
Network Time Protocol Server in the Communications Settings
section of the Operation chapter for more information.
Send:
Receive:
tz
tz EST+5EDT
27
set tz string
This command sets the timezone string for the instrument for use with the
NTP time server, where string is a standard timezone string. Common
strings are listed in the timezone screen description in Chapter 3.
Send:
Receive:
set tz EST+5EDT
set tz EST+5EDT ok
Add the Menutext command to the Commands List section and the
Keys Display section as follows:
menutext
Displays the text of the menu item where the cursor is currently
positioned
menutext
This command displays the text of the menu item where the cursor is
currently positioned. The example that follows shows that the cursor is
positioned at the instrument controls menu item.
Send:
Receive:
menutext
menutext
main menu
instrument controls
Sets the current state of the MODBUS coil coil (digital input)
28
mb read coils 1 15
mb read coils 1 15 000000100000001
mb read registers 5 4
mb read registers 5 4 552629.000000 55998800.000000
Add the following zero and span commands to the Commands List
section and to the Calibration section as follows:
span dev
zero dev
span dur
zero dur
zs period
zs avg time
span dev
This command reports the span deviation (span check offset). The example
that follows reports that the span deviation is 1 ppb.
Send:
Receive:
span dev
span dev 1.000 E+00
29
zero dev
This command reports the zero deviation (maximum zero check offset).
The example that follows reports that the zero deviation is 10 ppb.
Send:
Receive:
zero dev
zero dev 1.000 E+01
30
span dur
This command reports the span duration. The example that follows reports
that the span duration min is 10 minutes.
Send:
Receive:
span dur
span dur 10 min
zero dur
This command reports the zero duration. The example that follows reports
that the zero duration is 10 minutes.
Send:
Receive:
zero dur 10
zero dur 10 ok
zs period
This command reports the zero/span (zs) period. The example that follows
reports that the zero/span period is 24 hours.
Send:
Receive:
zs period
zs period 24 hr
31
set zs period 24
set zs period 24 hr ok
zs avg time
This command reports the zero/span (zs) averaging time in seconds. The
example that follows reports that the zero/span averaging time is 30
seconds, according to the Averaging Times table in this appendix.
Send:
Receive:
zs avg time
zs avg time 5:30 sec
Add the Version command to the Commands List section and the
Diagnostics section as follows:
version
version
This command reports the version of all the firmware components. The
example that follows shows a list of firmware components that were
displayed by issuing the version command. The components displayed will
vary depending on the configuration of the instrument.
Send:
Receive:
version
version
Program = 01.05.79.225
Library = 01.01.60.167
Kernel = 2.4.24-uc0-003-Thermo
Board = 81, File = /usr/application.hex
Board App = 11.3.100 Bl 4.0.97
File App = 11.3.100 Bl 4.0.97
Board = 84, File = /usr/application.hex
Board App = 11.3.100 Bl 4.0.97
32
MODBUS Protocol
Appendix
Update Serial Communication
Parameters
This section describes the updates and corrections that apply to the
MODBUS Protocol appendix.
: 7 or 8
: 1 or 2
Parity
Data rate
Add the following note to the (0x05) Force (Write) Single Coil section:
Note This function will not work if the instrument is in service mode.
Coil Number
Status
Invalid
33
Coil Number
Status
(end)
(end)
In addition to the coils listed in the Read Coils table, coils in the Write
Coils table can also be read.
IMPORTANT NOTE The addresses in the following tables are Protocol
Data Unit (PDU) addresses. Verify the register number on your
MODBUS master to ensure that it matches the register number on the
instrument.
Note For additional information on how to read registers and interpret the
data, refer to the (0x03/0x04) Read Holding Registers / Read Input
Registers section in this appendix.
Table C2. Read Registers for xxi
Register Number
Variable
Invalid
1&2
(end)
(end)
34
Coil Number
Action Triggered
100
Invalid
101
Coil Number
Action Triggered
(end)
(end)
In addition to the coils listed in the Write Coils table, coils in the Read
Coils table can also be read.
Reading a Write Coil
Replace Tables in the
MODBUS Commands
Supported Section
To read a write coil, issue a read coil command for that coil. For example
to view the state of write coil 101, issue a read coil 101.
In the MODBUS Commands Supported section (also shown as the
MODBUS Addresses Supported section in some manuals) replace the
appropriate Tables in your manual with the following Tables and
associated text:
42i Series
In the following Tables, repeated numbers are used to indicate different
functions based on the instrument used.
Read Registers for 42i
Register Number
Variable
Used Exclusively In
NONE
1&2
NO
42i, 42i HL, 42i LS, 42i TL, 42i J, 17i, 42i Y
3&4
NO2
3&4
DIF
42i Y
5&6
NOx
42i, 42i HL, 42i LS, 42i TL, 42i J, 17i, 42i D
5&6
NOy
42i Y
7&8
NH3
17i
9&10
NT
17i
11&12
LOW NO
13&14
LOW NO2
13&14
LOW DIF
42i Y
15&16
LOW NOx
15&16
LOW NOy
42i Y
17&18
LO NH3
17i
19&20
LO NT
17i
21&22
HIGH NO
42i, 42i HL, 42i LS, 42i TL, 42i J, 17i, 42i Y
23&24
HIGH NO2
35
36
Register Number
Variable
Used Exclusively In
23&24
HIGH DIF
42i Y
25&26
HIGH NOx
25&26
HIGH NOy
42i Y
27&28
HI NH3
17i
29&30
HI NT
17i
31&32
RANGE
33&34
RANGE
35&36
INTERNAL
TEMPERATURE
37&38
CHAMBER
TEMPERATURE
39&40
COOLER
TEMPERATURE
41&42
NO2 CONVERTER
TEMP
42i, 42i HL, 42i LS, 42i TL, 42i J, 17i, 42i D
43&44
17i, 42i Y
45&46
47&48
PERM OVEN
HEATER
49&50
CHAMBER
PRESSURE
51&52
SAMPLE FLOW
53&54
PMT VOLTS
55&56
ANALOG IN 1
57&58
ANALOG IN 2
59&60
ANALOG IN 3
61&62
ANALOG IN 4
63&64
ANALOG IN 5
65&66
ANALOG IN 6
67&68
ANALOG IN 7
69&70
ANALOG IN 8
71&72
OZONATOR FLOW
73&74
PREREACTOR
75&76
LO PREREACT
77&78
HI PREREACT
Register Number
Variable
Used Exclusively In
79&80
NO CORRECTION
CONC
O2 Sensor Option
81&82
NO2 CORRECTION
CONC
O2 Sensor Option
83&84
NOx CORRECTION
CONC
O2 Sensor Option
85&86
NH3 CORRECTION
CONC
O2 Sensor Option
87&88
NT CORRECTION
CONC
O2 Sensor Option
89&90
LOW NO
CORRECTION
CONC
O2 Sensor Option
91&92
LOW NO2
CORRECTION
CONC
O2 Sensor Option
93&94
LOW NOx
CORRECTION
CONC
O2 Sensor Option
95&96
LO NH3
CORRECTION
CONC
O2 Sensor Option
97&98
LO NT
CORRECTION
CONC
O2 Sensor Option
99&100
HIGH NO
CORRECTION
CONC
O2 Sensor Option
101&102
HIGH NO2
CORRECTION
CONC
O2 Sensor Option
103&104
HIGH NOx
CORRECTION
CONC
O2 Sensor Option
105&106
HI NH3
CORRECTION
CONC
O2 Sensor Option
107&108
HI NT
CORRECTION
CONC
O2 Sensor Option
109&110
CAPILLARY TEMP
17i
111&112
O2 %
37
Register Number
Variable
Used Exclusively In
113&114
O2 SENS TEMP
115&116
NO HOURLY
42i J
117&118
NO2 HOURLY
42i J
119&120
NOX HOURLY
42i J
121&122
EXT ALARMS
38
Coil Number
Status
Used Exclusively In
NONE
AUTORANGE
LOCAL/REMOTE
SERVICE
UNITS
ZERO MODE
Zero/Span Option
SPAN MODE
Zero/Span Option
NO MODE
42i, 42i HL, 42i LS, 42i TL, 42i J, 17i, 42i Y
NOx MODE
42i, 42i HL, 42i LS, 42i TL, 42i J, 17i, 42i D
NOy MODE
42i Y
Nt MODE
17i
10
PRE MODE
11
GEN ALARM
12
NO CONC MAX
ALARM
42i, 42i HL, 42i LS, 42i TL, 42i J, 17i, 42i Y
13
NO CONC MIN
ALARM
42i, 42i HL, 42i LS, 42i TL, 42i J, 17i, 42i Y
14
14
42i Y
15
15
42i Y
16
42i, 42i HL, 42i LS, 42i TL, 42i J, 17i, 42i D
Coil Number
Status
Used Exclusively In
16
42i Y
17
42i, 42i HL, 42i LS, 42i TL, 42i J, 17i, 42i D
17
42i Y
18
17i
19
17i
20
Nt CONC MAX
17i
21
Nt CONC MIN
17i
22
23
CHAMB TEMP
ALARM
24
COOLER TEMP
ALARM
25
NO2 CONVERTER
TEMP ALARM
42i, 42i HL, 42i LS, 42i TL, 42i J, 17i, 42i D
26
17i, 42i Y
27
28
PRESSURE ALARM
29
FLOW ALARM
30
OZONE FLOW
ALARM
31
MOTHERBOARD
STATUS ALARM
32
INTERFACE BD
STATUS ALARM
33
34
AUTORANGE
35
CONC ALARM
36
SAMPLE MODE
37
PURGE MODE
Zero/Span Option
38
17i, 42i Y
39
ZERO CHECK/CAL
ALARM
Zero/Span Option
42i, 42i HL with Bypass Flow Option, 42i LS, 42i TL,
42i J, 17i, 42i Y, 42i D
39
Coil Number
Status
Used Exclusively In
40
SPAN CHECK/CAL
ALARM
Zero/Span Option
41
O2 SENSOR
ALARM
42
CONC ERROR
42i J
43
NO RANGE 1
42i J
44
NO RANGE 2
42i J
45
NO RANGE 3
42i J
46
NO RANGE 4
42i J
47
NO RANGE 5
42i J
48
NO2 RANGE 1
42i J
49
NO2 RANGE 2
42i J
50
NO2 RANGE 3
42i J
51
NO2 RANGE 4
42i J
52
NO2 RANGE 5
42i J
53
NOx RANGE 1
42i J
54
NOx RANGE 2
42i J
55
NOx RANGE 3
42i J
56
NOx RANGE 4
42i J
57
NOx RANGE 5
42i J
58
CALIBRATION
42i J
59
42i J
60
EXT ALARM 1
62
EXT ALARM 2
63
EXT ALARM 3
40
Coil
Number
Action Triggered
Coil Group
Used Exclusively In
100
NONE
101
ZERO MODE
Zero/Span Mode
Zero/Span Option
102
SPAN MODE
Zero/Span Mode
Zero/Span Option
103
NO MODE
Measure Mode
Coil
Number
Action Triggered
Coil Group
Used Exclusively In
104
NOX MODE
Measure Mode
104
NOy MODE
Measure Mode
42i Y
105
Nt MODE
Measure Mode
17i
106
PRE MODE
Measure Mode
107
SET BACKGROUND
108
CAL TO LO SPAN
109
AOUTS TO ZERO
110
AOUTS TO FS
111
CAL TO HI SPAN
112
TELEM TROUBLE
42i J
113
42i J
114
ZERO/PURGE CAL
42i J
115
SPAN/PURGE CAL
42i J
116
ZERO/SPAN/PURGE
42i J
117
EXT ALARM 1
118
EXT ALARM 1
119
EXT ALARM 1
120
PURGE MODE
42i J
43i Series
In the following Table, repeated numbers are used to indicate different
functions based on the instrument used.
Read Registers for 43i
Register
Number
Variable
Used Exclusively In
NONE
1&2
SO2 CONC
3&4
H2S
5&6
CS
5&6
H2S
7&8
41
Register
Number
42
Variable
Used Exclusively In
Range mode)
Scrubber Option
9&10
LO H2S
11&12
LO CS
11&12
LO H2S
13&14
15&16
HI H2S
17&18
HI CS
17&18
HI H2S
19&20
21&22
INTERNAL TEMP
23&24
CHAMBER TEMP
25&26
27&28
29&30
31&32
CHAMBER PRESSURE
33&34
SAMPLE FLOW
35&36
PMT VOLTS
37&38
FLASH VOLTS
39&40
FLASH REF
41&42
ANALOG IN 1
43&44
ANALOG IN 2
45&46
ANALOG IN 3
47&48
ANALOG IN 4
49&50
ANALOG IN 5
51&52
ANALOG IN 6
53&54
ANALOG IN 7
55&56
ANALOG IN 8
57&58
SO2 HOURLY
43i J
59&60
H2S HOURLY
43i J
61&62
CS HOURLY
43i J
63&64
EXT ALARMS
Register
Number
Variable
Used Exclusively In
65&66
O2 %
67&68
O2 SENS TEMP
69&70
H2S SCRUB
71&72
LO H2S SCRUB
73&74
HI H2S SCRUB
75&76
SO2 COR
77&78
LO SO2 COR
79&80
HI SO2 COR
Coil
Number
Status
Used Exclusively In
NONE
AUTORANGE
LOCAL/REMOTE
SERVICE
ZERO MODE
Zero/Span Option
SPAN MODE
Zero/Span Option
SAMPLE MODE
SO2 MODE
CS MODE
10
GEN ALARM
11
12
13
14
15
CS CONC MAX
16
CS CONC MIN
17
43
44
Coil
Number
Status
Used Exclusively In
18
19
CONVERTER TEMP
20
21
PRESSURE ALARM
22
23
24
25
MOTHERBOARD STATUS
ALARM
26
MEASUREMENT INTERFACE
BOARD STATUS ALARM
27
28
CONC ALARM
29
PURGE MODE
Zero/Span Option
30
Zero/Span Option
31
Zero/Span Option
32
SPAN 1 MODE
33
SPAN 2 MODE
34
CONC ERROR
43i J
35
SO2 RANGE 1
43i J
36
SO2 RANGE 2
43i J
37
SO2 RANGE 3
43i J
38
SO2 RANGE 4
43i J
39
SO2 RANGE 5
43i J
40
CALIBRATION
43i J
41
43i J
42
EXT ALARM 1
43
EXT ALARM 2
44
EXT ALARM 3
Action Triggered
Coil Group
Used Exclusively In
100
NONE
101
ZERO MODE
Zero/Span Mode
Zero/Span Option
102
SPAN MODE
Zero/Span Mode
Zero/Span Option
103
SO2 MODE
Measure Mode
104
CS MODE
Measure Mode
105
SET BACKGROUND
106
107
AOUTS TO ZERO
108
AOUTS TO FS
109
110
SPAN 1 MODE
Zero/Span Mode
111
SPAN 2 MODE
Zero/Span Mode
112
TELEM TROUBLE
43i J
113
43i J
114
ZERO/PURGE CAL
43i J
115
SPAN/PURGE CAL
43i J
116
ZERO/SPAN/PURGE
43i J
117
EXT ALARM 1
118
EXT ALARM 2
119
EXT ALARM 3
120
PURGE MODE
Zero/Span Mode
43i J
48i Series
Read Registers for 48i
Register
Number
Variable
Used Exclusively In
NONE
1&2
CO
3&4
LO CO
5&6
HI CO
7&8
RANGE STATUS
45
46
Register
Number
Variable
Used Exclusively In
9&10
S/R
11&12
LO S/R
13&14
HI S/R
15&16
INT TEMP
17&18
BENCH TEMP
19&20
NONE
21&22
23&24
25&26
BENCH PRES
27&28
SAMPLE FLOW
29&30
INTENSITY
31&32
MOTOR SPEED
33&34
ANALOG IN 1
35&36
ANALOG IN 2
37&38
ANALOG IN 3
39&40
ANALOG IN 4
41&42
ANALOG IN 5
43&44
ANALOG IN 6
45&46
ANALOG IN 7
47&48
ANALOG IN 8
49&50
CO2
410i
51&52
LO CO2
410i
53&54
HI CO2
410i
55&56
BIAS SUPPLY
57&58
HCl
15i
59&60
LO HCl
15i
61&62
HI HCl
15i
63&64
SCRUBBER EFF
65&66
LO CO HOURLY
48i J
67&68
EXT ALARMS
69&70
O2 %
71&72
O2 SENS TEMP
73&74
N2O
46i
Register
Number
Variable
Used Exclusively In
75&76
LO N2O
46i
77&78
HI N2O
46i
79&80
CO COR
81&82
LO CO COR
83&84
HI CO COR
85&86
CO2 COR
87&88
LO CO2 COR
89&90
HI CO2 COR
Coil
Number
Status
Used Exclusively In
NONE
AUTORANGE
LOCAL/REMOTE
SERVICE
UNITS
ZERO MODE
Zero/Span Option
SPAN MODE
Zero/Span Option
SAMPLE MODE
GEN ALARM
CONC MAX
10
CONC MIN
11
INT TEMP
12
BENCH TEMP
13
PRESSURE
14
SAMPLE FLOW
15
INTENSITY
16
MOTOR SPEED
17
BIAS VOLTAGE
18
MB STATUS
19
MIB STATUS
20
I/O BD STATUS
47
Coil
Number
Status
Used Exclusively In
21
CONC ALARM
22
PURGE MODE
Zero/Span Option
23
SCRUB TST
MODE
24
ZERO CHK/CAL
ALARM
Zero/Span Option
25
SPAN CHK/CAL
ALARM
Zero/Span Option
26
CONC ERROR
48i J
27
CO RANGE 1
48i J
28
CO RANGE 2
48i J
29
CO RANGE 3
48i J
30
CO RANGE 4
48i J
31
CO RANGE 5
48i J
32
CALIBRATION
48i J
33
48i J
34
EXT ALARM 1
35
EXT ALARM 2
36
EXT ALARM 3
48
Coil
Number
Action Triggered
Coil Group
Used Exclusively In
100
NONE
101
ZERO MODE
Zero/Span Mode
Zero/Span Option
102
SPAN MODE
Zero/Span Mode
Zero/Span Option
103
SET BACKGROUND
104
CAL TO LO SPAN
105
AOUTS TO ZERO
106
AOUTS TO FS
107
CAL TO HI SPAN
108
SCRUBBER TEST
Coil
Number
Action Triggered
Coil Group
Used Exclusively In
109
TELEM TROUBLE
48i J
110
48i J
111
ZERO/PURGE CAL
48i J
112
SPAN/PURGE CAL
48i J
113
ZERO/SPAN/PURGE
48i J
114
EXT ALARM 1
115
EXT ALARM 2
116
EXT ALARM 3
117
PURGE MODE
48i J
Register
Number
Variable
Used Exclusively In
NONE
1&2
O3
49i
3&4
LO O3
49i
5&6
HI O3
49i
7&8
RANGE STATUS
9&10
INTENSITY A
11&12
INTENSITY B
13&14
NOISE A
15&16
NOISE B
17&18
FLOW A
19&20
FLOW B
21&22
PRESSURE
23&24
BENCH TEMP
25&26
LAMP TEMP
27&28
O3 LAMP TEMP
29&30
ANALOG IN 1
31&32
ANALOG IN 2
33&34
ANALOG IN 3
49
Register
Number
Variable
Used Exclusively In
35&36
ANALOG IN 4
37&38
ANALOG IN 5
39&40
ANALOG IN 6
41&42
ANALOG IN 7
43&44
ANALOG IN 8
45&46
O3 OUT CONC
49i PS
47&48
O3 HOURLY
49i J
49&50
EXT ALARMS
50
Status
Used Exclusively In
NONE
AUTORANGE
SERVICE
UNITS
ZERO MODE
Sample/Cal Option
SPAN MODE
Sample/Cal Option
SAMPLE MODE
O3 LEVEL 1
O3 LEVEL 2
O3 LEVEL 3
10
O3 LEVEL 4
11
O3 LEVEL 5
12
PURGE MODE
13
GEN ALARM
14
CONC MAX
15
CONC MIN
16
BENCH TEMP
17
18
O3 LAMP TEMP
19
PRESSURE
20
FLOW A
Sample/Cal Option
Coil
Number
Status
Used Exclusively In
21
FLOW B
22
INTENSITY A
23
INTENSITY B
24
CONC ALARM
25
ZERO CHK/CAL
Sample/Cal Option
26
SPAN CHK/CAL
Sample/Cal Option
27
O3 LEVEL 1 CHK
28
O3 LEVEL 2CHK
29
O3 LEVEL 3 CHK
30
O3 LEVEL 4CHK
31
O3 LEVEL 5 CHK
32
MB STATUS
33
MIB STATUS
34
I/O BD STATUS
35
LOCAL/REMOTE
36
CONC ERROR
49i J
37
O3 RANGE 1
49i J
38
O3 RANGE 2
49i J
39
O3 RANGE 3
49i J
40
O3 RANGE 4
49i J
41
O3 RANGE 5
49i J
42
CALIBRATION
49i J
43
49i J
44
EXT ALARM 1
45
EXT ALARM 2
46
EXT ALARM 3
Coil
Number
Action Triggered
Coil Group
Used Exclusively In
100
NONE
101
ZERO MODE
Zero/Span Mode
Sample/Cal Option
102
SPAN MODE
Zero/Span Mode
Sample/Cal Option
51
Coil
Number
Action Triggered
Coil Group
Used Exclusively In
103
OZONATOR LVL 1
104
OZONATOR LVL 2
105
OZONATOR LVL 3
106
OZONATOR LVL 4
107
OZONATOR LVL 5
108
SET BACKGROUND
109
CAL TO LO SPAN
110
CAL TO HI SPAN
111
OZONATOR SLND
112
AOUTS TO ZERO
113
AOUTS TO FS
114
PUMP OFF
115
TELEM TROUBLE
49i J
116
49i J
117
ZERO/PURGE CAL
49i J
118
SPAN/PURGE CAL
49i J
119
ZERO/SPAN/PURGE
49i J
120
EXT ALARM 1
121
EXT ALARM 2
122
EXT ALARM 3
123
PURGE MODE
49i J
51i
Read Registers for 51i
52
Register
Number
Variable
NONE
1&2
THC
3&4
AVG THC
5&6
HI THC
7&8
LO THC
9&10
DET TEMP
Used Exclusively In
Register
Number
Variable
Used Exclusively In
11&12
FILTER TEMP
13&14
PUMP TEMP
15&16
FLAME TEMP
17&18
INT TEMP
19&20
AIR PRESSURE
21&22
SAMPLE PRESSURE
23&24
FUEL PRESSURE
25&26
27&28
ANALOG IN 1
29&30
ANALOG IN 2
31&32
ANALOG IN 3
33&34
ANALOG IN 4
35&36
ANALOG IN 5
37&38
ANALOG IN 6
39&40
ANALOG IN 7
41&42
ANALOG IN 8
43&44
EXT ALARMS
Coil
Number
Status
Used Exclusively In
NONE
LOCAL/REMOTE
SERVICE
ZERO MODE
Zero/Span Option
SPAN MODE
Zero/Span Option
SAMPLE MODE
PURGE MODE
IDLE MODE
GEN ALARM
CONC ALARM
10
CONC MAX
11
CONC MIN
Zero/Span Option
53
Coil
Number
Status
Used Exclusively In
12
INT TEMP
ALARM
13
DET TEMP
ALARM
14
FILT TEMP
ALARM
15
PUMP TEMP
ALARM
16
AIR PRESSURE
ALARM
17
SAMP
PRESSURE
ALARM
18
FUEL PRESSURE
ALARM
19
FLAME OUT
20
SIGNAL STR
21
OVER RANGE
22
HEATER FAIL
23
SENSOR FAIL
24
ZERO NOISE
ALARM
25
ZERO CHK/CAL
Zero/Span Option
26
SPAN CHK/CAL
Zero/Span Option
27
BIAS VOLTAGE
28
MB STATUS
29
MIB STATUS
30
I/O BD STATUS
31
EXT ALARM 1
32
EXT ALARM 2
33
EXT ALARM 3
54
Coil
Number
Action Triggered
100
NONE
Coil Group
Used Exclusively In
Coil
Number
Action Triggered
Coil Group
Used Exclusively In
101
ZERO MODE
Zero/Span Mode
Zero/Span Option
102
SPAN MODE
Zero/Span Mode
Zero/Span Option
103
SET BACKGROUND
104
105
CAL TO SPAN
106
AOUTS TO ZERO
107
AOUTS TO FS
108
EXT ALARM 1
109
EXT ALARM 2
110
EXT ALARM 3
55i
Read Registers for 55i
Register
Number
Variable
NONE
1&2
LOCAL/REMOTE
3&4
SERVICE
5&6
CAL MODE
7&8
9&10
RUN MODE
11&12
IDLE MODE
13&14
INJECT
15&16
ZERO MODE
17&18
SPAN MODE
19&20
GEN ALARM
21&22
23&24
25&26
NM CONC MAX
27&28
NM CONC MIN
29&30
INT TEMP
Used Exclusively In
55
Register
Number
Variable
31&32
DET TEMP
33&34
FILT TEMP
35&36
COLUMN TEMP
37&38
AIR PRESSURE
39&40
CARRIER
PRESSURE
41&42
FUEL PRESSURE
43&44
FLAME OUT
45&46
CH4 OVERRANGE
47&48
NM OVERRANGE
49&50
CAL FAILURE
51&52
HEATER FAIL
53&54
SENSOR FAIL
55&56
BIAS VOLTAGE
57&58
DATA INTEG
59&60
61&62
NM SPAN CHK
63&64
WINDOWS SANE
65&66
MB STATUS
67&68
MIB STATUS
69&70
I/O BD STATUS
71&72
EXT ALARM 1
73&74
EXT ALARM 2
75&76
EXT ALARM 3
Used Exclusively In
56
Coil
Number
Status
NONE
LOCAL/REMOTE
SERVICE
CAL MODE
Used Exclusively In
Coil
Number
Status
RUN MODE
IDLE MODE
INJECT
ZERO MODE
SPAN MODE
10
GEN ALARM
11
12
13
NM CONC MAX
14
NM CONC MIN
15
INT TEMP
ALARM
16
DET TEMP
ALARM
17
FILT TEMP
ALARM
18
COLUMN TEMP
19
AIR PRESSURE
20
CARRIER
PRESSURE
21
FUEL PRESSURE
22
FLAME OUT
23
CH4
OVERRANGE
24
NM
OVERRANGE
25
CAL FAILURE
26
HEATER FAIL
27
SENSOR FAIL
28
BIAS VOLTAGE
29
DATA INTEG
30
31
NM SPAN CHK
32
WINDOWS
SANE
Used Exclusively In
57
Coil
Number
Status
33
MB STATUS
34
MIB STATUS
35
I/O BD STATUS
36
EXT ALARM 1
37
EXT ALARM 2
38
EXT ALARM 3
Used Exclusively In
Action Triggered
Coil Group
Used Exclusively In
100
NONE
101
START RUN
102
START CAL
103
104
STOP
105
INJECT
106
BACKFLUSH
107
108
AOUTS TO ZERO
109
AOUTS TO FS
110
EXT ALARM 1
111
EXT ALARM 2
112
EXT ALARM 3
80i
Read Registers for 80i
58
Register
Number
Variable
NONE
1&2
Hg0
3&4
Hg2+
5&6
Hgt
Used Exclusively In
Register
Number
Variable
Used Exclusively In
7&8
Hg0 RANGE
9&10
Hg2+ RANGE
11&12
Hgt RANGE
13&14
INTENSITY
15&16
INTERNAL TEMPERATURE
17&18
CHAMBER TEMPERATURE
19&20
PROBE TEMPERATURE
21&22
CONVERTER TEMPERATURE
23&24
UMBILICAL TEMPERATURE
25&26
VENTURI PRESSURE
27&28
ORIFICE PRESSURE
29&30
31&32
BLOWBACK PRESSURE
33&34
EDUCTOR PRESSURE
35&36
VACUUM PRESSURE
37&38
FLOW
39&40
PMT VOLTS
41&42
CHAMBER PRESSURE
43&44
PROBE SPAN
45&46
Hg0 SPAN
47&48
Hgt SPAN
49&50
Hg0 BACKGROUND
51&52
Hgt BACKGROUND
53&54
Hg0 COEFFICIENT
55&56
Hgt COEFFICIENT
57&58
PROBE FAILSAFE
TEMPERATURE
59&60
DILUTION FACTOR
61&62
ANALOG IN 1
63&64
ANALOG IN 2
65&66
ANALOG IN 3
67&68
ANALOG IN 4
69&70
ANALOG IN 5
59
Register
Number
Variable
Used Exclusively In
71&72
ANALOG IN 6
73&74
ANALOG IN 7
75&76
ANALOG IN 8
77&78
PROBE NUMBER
79&80
81&82
83&84
85&86
87&88
89&90
91&92
93&94
95&96
CALIBRATOR ACTUAL
CONCENTRATION
97&98
LAMP TEMPERATURE
99&100
OXIDIZER TEMPERATURE
101&102
OXIDATION
103&104
INTEGRITY
105&106
UMB TEMP 2
107&108
EXT ALARMS
60
Coil
Number
Status
NONE
SERVICE
Hg0 MODE
Hgt MODE
Hg0/Hgt MODE
Used Exclusively In
Coil
Number
Status
SAMPLE MODE
10
11
12
BLOWBACK MODE
13
GENERAL ALARM
14
INTERNAL TEMPERATURE
ALARM
15
CHAMBER TEMPERATURE
ALARM
16
CHAMBER PRESSURE
ALARM
17
18
INTENSITY ALARM
19
Hg0 CONCENTRATION,
MAXIMUM ALARM
20
Hg0 CONCENTRATION,
MINIMUM ALARM
21
Hg2+ CONCENTRATION,
MAXIMUM ALARM
22
Hg2+ CONCENTRATION,
MINIMUM ALARM
23
Hgt CONCENTRATION,
MAXIMUM ALARM
24
Hgt CONCENTRATION,
MINIMUM ALARM
25
MOTHERBOARD STATUS
ALARM
26
MEASUREMENT
INTERFACE BOARD STATUS
ALARM
27
28
CALIBRATOR STATUS
29
Used Exclusively In
61
Coil
Number
Status
30
31
32
33
34
35
36
PROBE 1 SELECTED
37
PROBE 2 SELECTED
38
PROBE 3 SELECTED
39
PROBE 4 SELECTED
40
LOCAL/REMOTE
41
42
HYDRATOR
43
PROBE 1 STATUS
44
PROBE 2 STATUS
45
PROBE 3 STATUS
46
PROBE 4 STATUS
47
EXT ALARM
48
SPIKING MODE
Used Exclusively In
62
Coil
Number
Action Triggered
Coil Group
100
NONE
101
Hg0 MODE
Measure Mode
102
Hgt MODE
Measure Mode
103
Hg0/Hgt MODE
Measure Mode
104
Zero/Span Mode
105
Zero/Span Mode
106
Zero/Span Mode
107
Zero/Span Mode
Used Exclusively In
Coil
Number
Action Triggered
Coil Group
Used Exclusively In
108
Zero/Span Mode
109
Zero/Span Mode
110
Zero/Span Mode
111
Zero/Span Mode
112
SET BACKGROUND
113
114
PROBE SELECT 1
Probe Select
Hydra Model
115
PROBE SELECT 2
Probe Select
Hydra Model
116
PROBE SELECT 3
Probe Select
Hydra Model
117
PROBE SELECT 4
Probe Select
Hydra Model
118
SYSTEM SPAN 1
System Span
119
SYSTEM SPAN 2
System Span
120
SYSTEM SPAN 3
System Span
121
SYSTEM SPAN 4
System Span
122
SYSTEM SPAN 5
System Span
123
SYSTEM SPAN 6
System Span
124
Zero/Span Mode
125
SPIKING
126
INSTRUMENT SPAN 1
Instrument Span
127
INSTRUMENT SPAN 2
Instrument Span
128
INSTRUMENT SPAN 3
Instrument Span
129
HYDRATOR ALARM
130
EXT ALARM
81i
Read Registers for 81i
Register
Number
Variable
1&2
Hg CONCENTRATION
3&4
Hg SPAN
5&6
Hg FLOW
7&8
DILUTION FLOW
Used Exclusively In
63
Register
Number
Variable
Used Exclusively In
9&10
COOLER TEMPERATURE
11&12
AMBIENT TEMPERATURE
13&14
PRESSURE
15&16
17&18
ANALOG IN 1
19&20
ANALOG IN 2
21&22
ANALOG IN 3
23&24
ANALOG IN 4
25&26
ANALOG IN 5
27&28
ANALOG IN 6
29&30
ANALOG IN 7
31&32
ANALOG IN 8
33&34
EXT ALARMS
35&36
Hg RANGE
64
Coil
Number
Status
SERVICE
HG SPAN BIT 1
HG SPAN BIT 2
HG SPAN BIT 3
GENERAL ALARM
STANDBY MODE
10
11
12
13
COOLER TEMPERATURE
ALARM
14
AMBIENT TEMPERATURE
Used Exclusively In
Coil
Number
Status
Used Exclusively In
ALARM
15
PRESSURE ALARM
16
Hg FLOW ALARM
17
18
CONCENTRATION ALARM
19
MOTHERBOARD STATUS
ALARM
20
MEASUREMENT
INTERFACE BOARD STATUS
ALARM
21
22
LOCAL/REMOTE
23
EXT ALARM 1
24
EXT ALARM 2
25
EXT ALARM 3
Coil
Number
Action Triggered
Coil Group
100
NONE
101
INSTRUMENT ZERO
MODE
Zero/Span Mode
102
Zero/Span Mode
103
Zero/Span Mode
104
Zero/Span Mode
105
Zero/Span Mode
106
Zero/Span Mode
107
STANDBY
108
AOUTS TO ZERO
109
HG SPAN BIT 1
Span Level
110
HG SPAN BIT 2
Span Level
111
HG SPAN BIT 3
Span Level
112
AOUTS TO FS
Used Exclusively In
65
Coil
Number
Action Triggered
113
EXT ALARM 1
114
EXT ALARM 2
115
EXT ALARM 3
Coil Group
Used Exclusively In
146i
Read Registers for 146i
66
Register
Number
Variable
Used Exclusively In
NONE
1&2
GAS CONC
3&4
TARGET GFLOW
5&6
ACTUAL GFLOW
7&8
TARGET ZFLOW
9&10
ACTUAL ZFLOW
11&12
TARGET TFLOW
13&14
ACTUAL TFLOW
15&16
O3 CONC
Photometer Option
17&18
PERM CONC
19&20
PRESSURE
Photometer Option
21&22
BENCH TEMP
Photometer Option
23&24
LAMP TEMP
Photometer Option
25&26
O3 LAMP TEMP
Ozonator Option
27&28
INTENSITY
Photometer Option
29&30
NOISE
Photometer Option
31&32
ANALOG 1
33&34
ANALOG 2
35&36
ANALOG 3
37&38
ANALOG 4
39&40
ANALOG 5
41&42
ANALOG 6
43&44
ANALOG 7
45&46
ANALOG 8
Register
Number
Variable
Used Exclusively In
47&48
49&50
EXT ALARMS
Coil
Number
Status
Used Exclusively In
NONE
GAS BIT 1
GAS BIT 2
GAS BIT 3
SPAN BIT 1
SPAN BIT 2
SPAN BIT 3
O3/PERM BIT 1
O3/PERM BIT 2
O3/PERM BIT 3
10
O3/PERM BIT 4
11
PHOTO BIT 1
Photometer Option
12
PHOTO BIT 2
Photometer Option
13
GAS A
14
GAS B
15
GAS C
16
GAS D
17
GAS E
18
GAS F
19
OZONATOR
Ozonator Option
20
PERM OVEN
21
USER 1
22
USER 2
23
USER 3
24
USER 4
25
USER 5
26
USER 6
67
Coil
Number
Status
Used Exclusively In
27
USER 7
28
USER 8
29
GEN ALARM
30
AMBIENT TEMP
31
O3 LAMP TEMP
Ozonator Option
32
PERM GAS
TEMP
33
PRESSURE
Photometer Option
34
PHOT BENCH
TEMP
Photometer Option
35
PHOT LAMP
TEMP
Photometer Option
36
PHOT
INTENSITY
Photometer Option
37
O3 LEVEL
Photometer Option
38
MB STATUS
39
MIB STATUS
40
I/O BD STATUS
41
LOCAL/REMOTE
42
SERVICE
43
EXT ALARM 1
44
EXT ALARM 1
45
EXT ALARM 1
46
STANDBY
68
Coil
Number
Action
Coil Group
100
NONE
101
GAS BIT 1
Gas Bit
102
GAS BIT 2
Gas Bit
103
GAS BIT 3
Gas Bit
104
SPAN BIT 1
Span Bit
105
SPAN BIT 2
Span Bit
Used Exclusively In
Coil
Number
Action
Coil Group
Used Exclusively In
106
SPAN BIT 3
Span Bit
107
O3/PERM BIT 1
O3 Perm Bit
108
O3/PERM BIT 2
O3 Perm Bit
109
O3/PERM BIT 3
O3 Perm Bit
110
O3/PERM BIT 4
O3 Perm Bit
111
PHOTO BIT 1
Photo Bit
Photometer Option
112
PHOTO BIT 2
Photo Bit
Photometer Option
113
AOUTS TO ZERO
114
AOUTS TO FS
115
EXT ALARM 1
116
EXT ALARM 2
117
EXT ALARM 3
5020i
Read Registers for 5020i
Register
Number
Variable
NONE
1&2
CONTINUOUS SO2
3&4
CONTINUOUS SO4
5&6
BATCH SO4
7&8
F0 AVERAGE
9&10
F0 STD DEV
11&12
F0 POINTS
13&14
F1 AVERAGE
15&16
F1 STD DEV
17&18
F1 POINTS
19&20
SMP AVERAGE
21&22
23&24
SMP POINTS
Used Exclusively In
69
Register
Number
Variable
Used Exclusively In
25&26
FILTER BKG
27&28
INT TEMP
29&30
CHAMBER TEMP
31&32
33&34
35&36
37&38
39&40
CHAMBER
PRESSURE
41&42
SAMPLE FLOW
43&44
PMT VOLTS
45&46
FLASH VOLTS
47&48
FLASH REF
49&50
ANALOG IN 1
51&52
ANALOG IN 2
53&54
ANALOG IN 3
55&56
ANALOG IN 4
57&58
ANALOG IN 5
59&60
ANALOG IN 6
61&62
ANALOG IN 7
63&64
ANALOG IN 8
65&66
CONV FLOW
67&68
AMBIENT TEMP
69&70
AMBIENT PRES
71&72
73&74
75&76
EXT ALARMS
77&78
STP/AMBIENT
70
Coil
Number
Status
NONE
Used Exclusively In
Coil
Number
Status
SERVICE
ZERO MODE
SPAN MODE
SAMPLE MODE
FILTER MODE
PURGE MODE
GEN ALARM
10
11
12
13
14
PERMEATION SPAN
SOURCE TEMP ALARM
15
16
17
CHAMB PRESSURE
ALARM
20
21
CONVERTER FLOW
ALARM
22
23
24
25
26
27
28
MB STATUS ALARM
29
30
31
32
LOCAL/REMOTE
Used Exclusively In
71
Coil
Number
Status
33
EXT ALARM 1
34
EXT ALARM 2
35
EXT ALARM 3
Used Exclusively In
72
Coil
Number
Action Triggered
Coil Group
Used
Exclusively In
100
NONE
101
ZERO MODE
Zero/Span Mode
102
SPAN MODE
Zero/Span Mode
103
SAMPLE MODE
Sample/Filter Mode
104
FILTER MODE
Sample/Filter Mode
105
SET BACKGROUND
106
CAL TO SPAN
107
AOUTS TO ZERO
I/O Expansion
Board Option
108
AOUTS TO FS
I/O Expansion
Board Option
109
EXT ALARM 1
110
EXT ALARM 2
111
EXT ALARM 3
This section describes the updates and corrections that apply to the
Geysitech (Bayern-Hessen) Protocol appendix.
Update Serial
Communication Parameters
: 7 or 8
: 1 or 2
Parity
Data rate
<STX>DA<CR>
Reply String:
Address+1
+5681+00<SP>03<SP>04<SP>000 0000000<SP>003<SP>+1175+01<SP>03<SP>04<SP
Address+2
Third Concentration=11.75
0000000000<SP><CR>
73
<STX>DA<CR>
Reply String:
Address+1
+5681+00<SP>03<SP>04<SP>123 0000000<SP>003<SP>+1175+01<SP>03<SP>04<SP
Address+2
Third Concentration=11.75
1230000000<SP><CR>
42i
Change Default Chamber Temp
Control/Alarm Limits
Ozonator Safety Update
In the Operation chapter at Main Menu > Alarms > Chamber Temp,
change the default chamber temperature control/alarm limit references in
associated text and screens from 47 C to 48 C and 51 C to 52 C.
In the Operation chapter at Main Menu > Service > Ozonator Safety,
add the following highlighted text to the first paragraph as indicated in the
following example:
The Ozonator Safety screen is used to turn the ozonator safety feature on
or off. If the ozonator safety is turned off, the ozonator will always be on,
even if the converter is not up to temperature. The ozonator shuts off if
there is a converter temperature alarm or an ozone flow alarm. If the safety
override is on, the instrument generates an ozone flow alarm.
74
42i TL
Monitoring Signals Update
Measurement Calculations
Update
In the Introduction chapter, add 500 and 1000 ppb, and 500 and 1000
g/m3 to the Specifications table as shown in the highlighted example that
follows:
Table 14. Model 42i Trace Level Specifications
Preset ranges
75
42i, 42i HL, 42i LS, 42i TL, 42i Y, and 17i
Add Note to Streaming
Data Configuration
In the Operation chapter, add the following note at Main Menu >
Instrument Controls > I/O Configuration > Analog Output Config; and
also at Main Menu > Instrument Controls > I/O Configuration > Analog
Output Config > Select Channel > Choose Signal To Output:
Note The settings are different depending on the AUTO/MANUAL
MODE and RANGE MODE settings. Changing either of these settings
will produce a different set of analog output data items. If either of these
modes is going to be changed on a regular basis, then the user must
configure each set of data separately after changing the modes to each
setting.
76
A new version pump has been added to the 42i, 42i LS, 42i NOx, and 43i
HL. This pump is interchangeable with the old pump. It retains the same
part number, but requires a different repair kit. The new version pump
includes the repair kit part number of the on the pump label, the old pump
does not.
This section provides the repair procedure for the new version pump and
includes a pump rebuild kit part number to be added to the Replacement
Parts List in the Servicing chapter.
77
Disassembly
1. Turn instrument OFF, unplug the power cord, and remove the cover.
2. The compressor housing cover must be removed to gain access to the
inside of the compressor housing. Remove the four compressor housing
cover screws and then remove the cover. Re-use any gasketing. Remove
any debris that may have accumulated in the bottom of the compressor
housing.
3. Remove the four top plate screws and remove the top plate. Note the
positioning of the flapper plate relative to the valve ports on the top
plate and bottom plate. Lift off the flapper plate.
4. Remove the bottom plate.
5. Check that all parts are free from dirt and clean as necessary. DO NOT
scratch the parts.
6. Removal of the old diaphragm: Rotate the fan so that the diaphragm
is positioned at the top dead center. This will help unseat the edge of
the diaphragm. If required, push up from underneath the diaphragm or
use a non-metallic tool to pry up the diaphragm from the housing
groove. Unscrew the old diaphragm by turning it counterclockwise
using both hands. DO NOT use tools!
Note Take care not to lose the shim rings positioned between the
diaphragm and connecting rod, as the same shim rings must be used during
re-assembly.
Assembly with New 1. Place the shim rings removed in the previous step onto the threaded
Diaphragm and Valve
stud of the new diaphragm. Carefully screw the new diaphragm into
the connecting rod. Turn the diaphragm until is snug, then lift and
grip the edges of the diaphragm at 7 and 2 oclock and tighten firmly
using both hands. DO NOT use tools!
2. Turn the fan until the diaphragm is flat across (mid-point of the
stroke). With the diaphragm centered over the compressor housing,
firmly seat the diaphragm edge into the compressor housing groove.
78
3. Place the clean bottom plate onto the compressor housing using the
reference mark made earlier to ensure the correct orientation. Then
place the new flapper on top of the intermediate plate.
79
5. Replace the compressor housing cover and gasket. Install the four cover
screws. Do not over-tighten.
Add Part Number of New Version
Pump to Replacement Parts List
107751-00
43i, 43i TLE, 48i, 48i TLE, 48i HL, 410i, 450i,
and 5020i
Add Rebuild Procedure
for New Version Pump
A new version pump has been added to the 43i, 43i TLE, 48i, 48i HL,
410i, 450i, and 5020i. This pump is interchangeable with the old pump. It
retains the same part number, but requires a different repair kit. The new
version pump includes the repair kit part number on the pump label, the
old pump does not.
This section provides the repair procedure for the new version pump and
includes a pump rebuild kit part number to be added to the Replacement
Parts List in the Servicing chapter.
80
1. Turn instrument OFF, unplug the power cord, and remove the cover.
Make a sketch of the position of any tubes and fittings for ease of reassembly later.
2. Mark the position of the pump top plate, bottom plate and compressor
housing relative to each other by drawing a line on the edges with a
pencil or marker to ensure proper re-assembly.
3. The aluminum compressor housing cover must be removed to gain
access to the inside compressor housing. Remove the four screws and
then remove the cover. Re-use any gasketing. Remove any debris that
may have accumulated in the bottom of the compressor housing.
4. Remove the four top plate screws and remove the top plate. Note the
positioning of the flapper valve relative to the valve ports on the top
plate and bottom plate. Lift off the flapper valve.
5. Remove the bottom plate.
6. Check that all parts are clean from dirt and clean as necessary. DO
NOT scratch the parts.
7. Removal of the old diaphragm: Rotate the fan so that the diaphragm
is positioned at the top dead center. This will help unseat the edge of
the diaphragm. If required, push up from underneath the diaphragm or
use a non-metallic tool to pry up the diaphragm from the housing
groove. Unscrew the old diaphragm by turning it counterclockwise
using both hands. DO NOT use tools!
Note Take care not to lose the shim rings positioned between the
diaphragm support cup and connecting rod, as the same shim rings must
be used during re-assembly.
While unscrewing the diaphragm with one hand, use your other hand
to secure the support cup and shim ring(s) onto the diaphragm stud.
Lift the diaphragm, support cup and shim ring(s) from the pump.
81
Assembly with New 1. Place the parts removed in the previous step onto the threaded stud of
the new diaphragm. Carefully screw the new diaphragm into the
Diaphragm and Valve
connecting rod. Secure the support cup and small parts onto the
diaphragm stud using a technique similar to that used during removal.
It is helpful to hold the connecting rod at a slight angle until the
threads are started. Spin the diaphragm on until it is snug, then lift and
82
grip the edges of the diaphragm at 7 and 2 oclock and tighten firmly
using both hands. DO NOT use tools!
Tip: If the pump is loose and not mounted, position and hold the pump
with the motor shaft vertical when starting the threaded diaphragm stud
into the connecting rod. This helps to prevent the small parts from falling
off the stud.
2. Turn the fan until the diaphragm is flat across (mid-point of the
stroke). With the diaphragm centered over the compressor housing,
firmly seat the diaphragm edge into the compressor housing groove.
3. Place the clean bottom plate onto the compressor housing using the
reference mark made earlier to ensure the correct orientation. Then
place the new flapper on top of the intermediate plate.
4. Place the clean top plate on top of the bottom plate using the reference
mark made earlier to ensure the correct orientation. Tighten the four
top plate screws snugly in a diagonal pattern and then tighten to a
maximum torque of 6-7 inch-lbs. Turn the fan by hand to confirm that
the pump turns freely.
5. Replace the compressor housing cover and gasket. Install the four cover
screws. Do not over-tighten.
Add Part Number of New Version
Pump to Replacement Parts List
108002-00
43i, 43i TL, 48i, 48i HL, 48i TLE, 49i, 49i PS,
146i, 410i, 450i, 5020i and 42i NOy
Add Rebuild Procedure for
New Shimless Version Pump
A new version pump has been added to the 43i, 43i TL, 48i, 48i HL, 48i
TLE, 49i, 49i PS, 146i, 410i, 450i, 5020i, and 42i NOy. This pump is
interchangeable with the old pump. It has a new part number 111553-00
and uses the same rebuild kit as the new version pump. The new shimless
version pump includes the repair kit part number on the pump label.
This section provides the repair procedure for the new shimless version
pump and includes a pump rebuild kit part number to be added to the
Replacement Parts List in the Servicing chapter.
83
New Shimless
Version Pump
1. Turn instrument OFF, unplug the power cord, and remove the cover.
Make a sketch of the position of any tubes and fittings for ease of reassembly later.
2. Mark the position of the pump head plate, intermediate plate and
compressor housing relative to each other by drawing a line on the
edges with a pencil or marker to ensure proper re-assembly.
3. The aluminum compressor housing cover must be removed to gain
access to the inside of the compressor housing. Remove the four screws
and then remove the cover. Re-use any gasketing. Remove any debris
that may have accumulated in the bottom of the compressor housing.
84
4. Remove the four socket cap screws and remove the head plate. Note
the positioning of the valve plate relative to the valve ports on the head
plate and intermediate plate. Lift off the valve plate.
5. Remove the intermediate plate.
6. Check that all parts are clean from dirt and clean as necessary. DO
NOT scratch the parts.
7. Removal of the old diaphragm: Rotate the fan so that the diaphragm
is positioned at the top dead center. This will help unseat the edge of
the diaphragm. If required, push up from underneath the diaphragm or
use a non-metallic tool to pry up the diaphragm from the housing
groove. Unscrew the old diaphragm by turning it counterclockwise
using both hands. DO NOT use tools!
Lift the diaphragm from the pump. Parts removed must be replaced
exactly as found. If repairing multiple pumps, take care not to mix
parts.
85
Assembly with New 1. Carefully screw the new diaphragm (no shims are needed) into the
connection rod. Secure the support cup and small parts onto the
Diaphragm and Valve
diaphragm stud using a technique similar to that used during removal.
It is helpful to hold the connecting rod at a slight angle until the
threads are started. Spin the diaphragm on until it is snug, then lift and
grip the edges of the diaphragm at 7 and 2 oclock and tighten firmly
using both hands. DO NOT use tools!
2. Turn the fan until the diaphragm is flat across (mid-point of the
stroke). With the diaphragm centered over the compressor housing,
firmly seat the diaphragm edge into the compressor housing groove.
3. Place the clean intermediate plate onto the compressor housing using
the reference mark made earlier to ensure the correct orientation. Then
place the new valve plate on top of the intermediate plate.
4. Place the clean head plate on top of the intermediate plate using the
reference mark made earlier to ensure the correct orientation. Tighten
the four socket cap screws snugly in a diagonal pattern and then tighten
to a maximum torque of 6-7 inch-lbs. Turn the fan by hand to confirm
that the pump turns freely.
5. Replace the compressor housing cover and gasket. Install the four cover
screws. Do not over-tighten.
Add Part Number of New In the Servicing chapter at Replacement Parts List, add the following
Shimless Version Pump to part number and description of the new version pump repair kit below the
Replacement Parts List existing pump repair kit part number as follows:
108002-00
86
The Setup Run Screens menu is used to define and edit up to five custom
Run screens. The Setup Run Screens menu is visible only when the
instrument is in the Service mode.
Custom Run Screen
Title Bar
INTT
DIAGNOSTICS
31.4C
mm
Pres
Instrument Readings
750.0Hg
l/
Flow
SAMPLE
RANGE
0.0min
11:27
AVG
DIAGS ALARM
AVG
DIAGS ALARM
87
The Select Run Screen menu is used to display the Run screen editor.
In the Main Menu, choose Service > Setup Run Screens > Select a Run
Screen.
The Edit Run Screen menu is used to edit the contents of the custom run
screen. This menu allows the user to edit the run screen title, toggle the run
screen ON and OFF, and specify the number of items to be displayed on
the Run screen (1-10).
Edit Run Screen
EDIT RUN SCREEN:
>EDIT TITLE
ENABLED
NUMBER OF ITEMS
ITEM 1
ITEM 2
RANGE
AVG
DIAGS ALARM
ITEM 8
Edit Title
OFF
8
TEMP
PRES
FLOW
The Edit Title screen is used to edit the contents of the title bar on the
selected Custom Run screen.
In the Main Menu, choose Service > Setup Run Screens > Select a Run
Screen > Edit Title.
EDIT RUN SCREEN TITLE:
DIAGNOSTICS
ABCDEFGHIJKLMN
OPQRSTUVWXYZ
0123456789 ./RANGE
AVG
BKSP
PAGE
SAVE
DIAGS ALARM
Use
,
,
, and
to position the cursor on the title,
the characters, and the BKSP, PAGE, and SAVE selections. Use
to
select a character or the BKSP, PAGE, and SAVE selections.
The BKSP selection is used to backspace the cursor in the title. The PAGE
selection toggles the characters between upper case and lower case. The
SAVE selection is used to save changes made to the title.
Enabled
88
The Enabled screen is used to toggle the selected custom Run screen ON
and OFF. When a Run screen is ON, it will be displayed on Run screen
when using
to scroll through the available Run screen
displays. When a Run screen is OFF, it will be skipped when scrolling
through the Run screen displays. For example, if Run screens 2 and 3 are
set to OFF, and Run screens 1, 4, and 5 are ON, scrolling down through
the available Run screen displays will display only Run screens 1, 4, and 5.
In the Main Menu, choose Service > Setup Run Screens > Select a Run
Screen > Enabled.
ENABLE/DISABLE RUN SCREEN:
CURRENTLY:
OFF
SET TO:
ON ?
TOGGLE VALUE
RANGE
Number of Items
AVG
DIAGS ALARM
In the Main Menu, choose Service > Setup Run Screens > Select a Run
Screen > Number of Items.
SET NUMBER OF ITEMS:
CURRENTLY:
5
SET TO:
4
CHANGE VALUE
RANGE
Item Number
AVG
SAVE
DIAGS ALARM
In the Main Menu, choose Service > Setup Run Screens > Select a Run
Screen > Item number.
89
RANGE
Concentrations
AVG
DIAGS ALARM
In the Main Menu, choose Service > Setup Run Screens > Select a Run
Screen > Item number > Concentrations.
42i Screen
CONCENTRATIONS:
>NONE
NO
NO2
NOx
LO NO
LO NO2
LO NOx
RANGE
AVG
<--
DIAGS ALARM
HI NO
HI NO2
HI NOx
RANGE (NOX)
43i Screen
CONCENTRATIONS:
>NONE
SO2
LO SO2
HI SO2
RANGE (SO2)
RANGE
90
AVG
<--
DIAGS ALARM
48i Screen
CONCENTRATIONS:
>NONE
CO
RANGE STATUS
RANGE
Other Measurements
AVG
<--
DIAGS ALARM
The Other Measurements screen is used to display a list of nonconcentration parameters that can be specified for the selected item
number.
In the Main Menu, choose Service > Setup Run Screens > Select a Run
Screen > Item number > Other Measurements.
42i Screen
OTHER MEASUREMENTS:
>NONE
INT TEMP
CHAMBER TEMP
COOLER TEMP
NO2 CNV TEMP
PERM VON GAS
PERM OVN HTR
RANGE
AVG
DIAGS ALARM
CHAMBER PRES
FLOW
PMT VOLTS
OZONATOR FLOW
43i Screen
OTHER MEASUREMENTS:
>NONE
INT TEMP
<-CHAMBER TEMP
PERM OVN GAS
PERM OVN HTR
CHAMBER PRES
SAMPLE FLOW
RANGE
AVG
DIAGS ALARM
91
48i Screen
OTHER MEASUREMENTS:
>NONE
S/R
INTERNAL TEMP
CHAMBER TEMP
CHAMBER PRES
SAMPLE FLOW
INTENSITY
RANGE AVG
MOTOR SPEED
Analog Inputs
<--
DIAGS ALARM
The Analog Inputs screen is used to display a list of analog inputs that can
be specified for the selected item number.
In the Main Menu, choose Service > Setup Run Screens > Select a Run
Screen > Item number > Analog Inputs.
ANALOG INPUTS:
>NONE
ANALOG IN 1
ANALOG IN 2
ANALOG IN 3
ANALOG IN 4
RANGE
AVG
DIAGS ALARM
ANALOG IN 8
92
-XXX.X V
2254
INC/DEC
SAVE VALUE
RANGE
AVG
DIAGS ALARM
DIAGS ALARM
In the Replacement Parts List of the Servicing chapter, add the Teflon
particulate filter option, if it is not already included:
102701-00
AVG
43i HL
Heated Kicker Option
Add information for the heated kicker option to the 43i HL instruction
manual as follows:
Add the following heated kicker description and part number to the
Replacement Parts List in the Servicing chapter:
104123-00
93
Heated Kicker
Replacement
Use the following procedure to replace the optional heated kicker assembly.
Equipment Required:
Heated kicker assembly (optional)
Allen wrench, 5/32-inch
Equipment Damage Some internal components can be damaged by small
amounts of static electricity. A properly ground antistatic wrist strap must
be worn while handling any internal component.
1. Turn instrument OFF, unplug the power cord, and remove the cover.
2. Using a 5/32-inch Allen wrench, remove the four optical bench
retaining screws.
3. Disconnect the plumbing connections as appropriate to gain enough
clearance to lift the optical bench off the heated kicker. Carefully note
the plumbing connections to facilitate reconnection.
4. Remove the heated kicker from the optical bench.
5. Install the new heated kicker assembly.
6. Reposition the optical bench on top of the heated kicker, insert and
tighten the four optical bench retaining screws, and reconnect any
plumbing connections by following the previous steps in reverse order.
7. Calibrate the instrument. Refer to the Calibration chapter in this
manual.
94
Heated Kicker
Heated Hydrocarbon
Kicker (Optional)
The hydrocarbon kicker removes hydrocarbons from the gas stream while
leaving the SO2 concentration unaffected. It operates on a selective
permeation principle using differential pressure to force hydrocarbon
molecules to pass through the tube wall. The differential pressure is created
across the tube wall as sample gas passes through a capillary tube which
reduces its pressure. The sample gas is then fed to the shell side of the
hydrocarbon kicker.
The optional heated hydrocarbon kicker is used in applications requiring
more efficiency than the standard kicker. The heated kicker operates at the
same temperature as the optical bench and requires no additional power.
Heated Hydrocarbon
Kicker
95
For 49i PS, in Chapter 3 at Digital Input Settings > Select Relay >
Instrument Action, add Pump Off to the end of the Choose Action list.
For 49i PS, in Chapter 8 at the Digital Inputs section, add Pump Off
to the digital input list.
Remove References to
Ozonator Solenoid
146i
Add Photometer Timer Note
If a particular subsystem is turned off, then its associated alarms will always
be evaluated as OK. For example, if the ozonator lamp is not up to
temperature, but the ozonator is turned off, then the ozonator lamp
temperature alarm will read as OK until the ozonator is turned on.
Add the following note to the Zero Flow Calibration description and the
Gas Flow Calibration description, in Chapter 3, under the Service section,
and to the Mass Flow Controllers procedure in Chapter 4:
Note Turn off the ozonator, permeation oven, and photometer functions
before performing a flow controller calibration, as these functions may
affect the measured flow at the manifold.
96
Modify the Flags map, Figure B-1, to include Password Lock fourth bit
from the left, and Service - third bit from the left.
At the Gas Flow Controller topic in the Service Menu section of the
Operation chapter, add the following highlighted text to the end of the
second sentence:
Allowable selections are: 25, 50, 100, 200, and 500 sccm; and 5, 10, 15,
and 20 slm.
97
5020i
Add STP/Ambient
98