Best Power Ferrups User Manual PDF
Best Power Ferrups User Manual PDF
50/60 Hz
USER MANUAL
FSS-0342J
Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
001 If You Have a Problem or a Question . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
002 If You Need More Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3
3
3
6
11
11
12
15
15
17
20
22
22
24
25
27
29
32
32
33
34
34
34
34
35
35
Section700: Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Introduction
Welcome to the growing FERRUPS family. FERRUPS represents a breakthrough in the design of advanced, online uninterruptible power systems.
Please read this manual thoroughly before operating your FERRUPS. Keep this manual handy for future
reference.
Page 1
Page 2
Back View
1.8-3.1 kVA
1.15 and 1.4 kVA
500 VA-850 VA
1 = On/Off Switch
3 = RS232 Communication Port
Page 3
CAUTION
To avoid possible equipment damage or personal injury, assume that AC voltage is present at the
FERRUPS terminals or receptacles any time AC input voltage or DC battery voltage is supplied.
FERRUPS can provide output voltage from its batteries even when there is no AC input voltage.
Whenever AC input voltage is present, FERRUPS can provide output voltage even when its batteries are
disconnected. Always disconnect the AC input source to make sure there will be no UPS output voltage; if
you have a separate battery cabinet, you must also shut off the DC switch or disconnect the battery cabinet
from the UPS.
To reduce the risk of electric shock, install the UPS in a temperature-controlled indoor area free of
conductive contaminants.
1
2
FE Plug-in Models:
Plug in the UPS. Once you have done this, the AC LINE light
should light. If the plug does not match your outlet (receptacle),
ask your electrician to install the outlet you need.
QFE Plug-in Models:
Do not use the cord you received to plug in the UPS; this cord is
for plugging your equipment into the UPS. The computer (or
other equipment) that you want to protect should have a power
cord that you can disconnect or unplug. Disconnect this cord
from your equipment and use it to plug in the UPS. If you
need to order a UPS power cord, please call the nearest
Best Power office. Once you have plugged in the UPS, the
AC LINE light should light.
Hardwired Models (models that are not plug-in):
Your electrician should have followed the instructions in the Installation Manual to install your UPS
and connect your protected equipment. Turn the AC Disconnect Switch on. The UPS AC LINE light
should light.
The AC LINE light will not light for models FE 1.8, FE 2.1, and FE 3.1 with serial numbers 25000 and up.
NOTE: If you have a separate battery cabinet with a DC switch on the front, turn the switch on now.
Turn the On/Off (I/O) switch to the On (I) position. (The On/Off switch is shown in step 2.) After a short
startup test, the green READY light should light (on earlier models the light will blink for a few seconds
before remaining lit).
The CHARGING light may be on at this point; this means FERRUPS batteries are not fully charged, and
FERRUPS is charging them now. FERRUPS automatically charges the batteries whenever the AC LINE
light is on and the BATTERY POWER light is off. The CHARGING light will turn off when the batteries
have been fully charged; this may take 24 hours. FERRUPS runtime (battery backup time) will be shorter
until the batteries have been charged.
Page 4
Thats it! Your FERRUPS is now providing conditioned, computer-grade power to your equipment, and
FERRUPS is ready to provide power from its batteries if there is a power outage or if there are AC input power
problems.
When the FERRUPS operating mode changes, FERRUPS will bring it to your attention. For example, when
FERRUPS runs on battery power, the yellow BATTERY POWER light comes on and FERRUPS beeps a few
times each minute. When there is a FERRUPS alarm, the red ALARM light comes on and FERRUPS sounds the
Morse code for the alarm.
See the rest of this manual for information on operation, communication, and alarms.
Page 5
FERRUPS Features
Front Panel Lights (LEDs)
Control Panel
On/Off Switch
Page 6
CAUTION
To avoid possible equipment damage or personal injury, assume that FERRUPS terminals or receptacles
may have AC voltage present any time AC input voltage or DC battery voltage is supplied. FERRUPS can
provide output voltage from its batteries even when there is no AC input voltage. When AC input voltage
is present, FERRUPS can provide output voltage even when its batteries are disconnected. Always
disconnect the AC input source AND disconnect or turn off DC (see Section 308) to make sure there will
be no UPS output voltage. To reduce the risk of electric shock, install the UPS in a temperature-controlled
indoor area free of conductive contaminants.
Page 7
The CHARGING light may be on at this point; this means FERRUPS batteries are not fully charged, and
FERRUPS is charging them now. FERRUPS automatically charges the batteries whenever the AC LINE
light is on and the BATTERY POWER light is off. The CHARGING light will turn off when the batteries
have been fully charged. This may take 24 hours. FERRUPS runtime (battery backup time) will be shorter
until the batteries have been charged.
Page 8
Now, you can set the time and date using the control panel. FERRUPS needs the correct time and date for
its Alarm and Inverter Logs, so you should reset the time and date whenever FERRUPS has been shut
down. Time is parameter 0; see Section 305 for more information on parameters. To set the time, follow
these steps:
PRESS THIS KEY:
[DISPLAY]
[0]
[ENTER]
[PROGRAM]
DISPLAY SHOWS:
Display:
Display:
0
00 Time: 11:30:20
00 Pgm:
Enter the correct time using the 24-hour system. To do this, you enter times from 1:00 a.m. to 12:59 p.m.
just as you would read them from a clock. From 1:00 p.m. to 11:59, however, you add 12 hours to the
clock time. So 8:30 a.m. would be entered [8] [3] [0], but 8:30 p.m. would be entered [2] [0] [3] [0].
Midnight is [0] [0] [0] [0], 12:30 a.m. is [0] [0] [3] [0], and so on. For example, if the time is 9:30 a.m., you
would enter the following:
PRESS THIS KEY:
[9][3][0]
[ENTER]
DISPLAY SHOWS:
00 Pgm:
930
00 Time 09:30:00
Set the date next. The date is parameter 10. To display the date, follow these steps:
PRESS THIS KEY:
[DISPLAY]
[1][0]
[ENTER]
[PROGRAM]
DISPLAY SHOWS:
Display:
Display:
10
10 Date: 01/01/96
10 Pgm:
Now, press the number of the month, then the number of the day of the month, and then the year. For
example, to enter June 14, 1996:
PRESS THIS KEY:
[0] [6] [1] [4] [9] [6]
[ENTER]
DISPLAY SHOWS:
10 Pgm:
061496
10 Date 06/14/96
Page 9
Please fill out the Warranty Registration Card in this manual and return it to Best Power. This card
helps Best Powers Worldwide Service when your FERRUPS needs routine maintenance or if there is a
problem.
Your FERRUPS includes free CheckUPS II Suite power management software. The CheckUPS II Suite
monitors power conditions; during a long power outage, CheckUPS automatically shuts down your
computer system just before the FERRUPS runs out of battery power. To install CheckUPS, see the
instructions you received with the software.
Thats it! Your FERRUPS is now providing conditioned, computer-grade power to your equipment, and
FERRUPS is ready to provide power from its batteries if there is a power outage or if there are AC input power
problems.
When the operating mode changes, FERRUPS will bring it to your attention. When FERRUPS runs on battery
power, the yellow BATTERY POWER light comes on and FERRUPS beeps a few times each minute. When
there is a FERRUPS alarm, the red ALARM light comes on and FERRUPS sounds the Morse code for the alarm;
FERRUPS also displays an alarm message on the control panel.
See the rest of this manual for information on operation, communication, and alarms.
Page 10
Light (LED)
Color
AC LINE
Green
Not applicable.
READY
Green
CHARGING
Green
Not applicable.
BATTERY
POWER
Yellow
FERRUPS is providing
condi-tioned power from the
AC input power source, or
FERRUPS is off.
ALARM
Red
No alarm exists.
Not applicable.
Page 11
The control panel is attached to the front of your FERRUPS with a six-foot (1.8-meter) cable, which lets you pick
up the control panel and hold it in your hand. The panels READY, BATTERY POWER and ALARM lights
work like the READY, BATTERY POWER and ALARM lights on the front of the UPS. (See Section 301.)
You can use the control panel to change FERRUPS system modes and display and change parameters. You can
also lock the control panel and change some of its features. If you press the wrong key at any time, press
[CLEAR] and then the correct key. The control panel will click each time you press a key.
How to Select It
What It Means
Off
FERRUPS is not providing power to your equipment, but you can still use
the control panel. The READY light is off.
Auto
Line Condition
Inverter On
(Battery Power)
Page 12
DISPLAY SHOWS:
FERRUPS by BEST
Password:
Password:
377
Level:
User
When you want to clear the password, press the [CLEAR] key until you see Password Cleared on the control
panel display.
DISPLAY SHOWS:
Display:
Display:
0
00 Time 07:04:08
To change a parameter, display it first. Then, press [PROGRAM], enter the new value you want for the
parameter, and press [ENTER]. (You will need a password to change most parameters.) For example, to change
parameter 0 (time), follow these steps:
PRESS THIS KEY:
[DISPLAY] [0] [ENTER]
[PROGRAM]
[9] [3] [0]
[ENTER]
Page 13
DISPLAY SHOWS:
00 Time 07:04:08
00 Pgm:
00 Pgm:
930
00 Time 09:30:00
DISPLAY READS:
-Keypad Locked-
When you lock the control panel, it will beep and show the display above for about two seconds; the control
panel will beep and show this display whenever you try to use the keys. The front panel lights (LEDs) will
continue to show the UPS status, and the control panel will show UPS alarms. To enable the control panel again,
PRESS THESE KEYS:
[CLEAR] and [ENTER] together
[8] [2] [0] [4] [9]
[ENTER]
DISPLAY READS:
Unlock #:
Unlock #: 82049
Keypad Unlocked
After about two seconds, the control panel will show the same display it showed before you unlocked it. If you
enter the wrong Unlock number, the control panel will display -Keypad Locked- for two seconds, and the
control panel will remain locked.
Page 14
First, FERRUPS checks its memory. If it finds a problem, the UPS sounds alarm O, Memory
Check ( ). (See Section 304.)
Inverter Test: The inverter converts DC battery power into the AC power your equipment uses. During the
Inverter Test, FERRUPS pulses its inverter to see if it delivers the proper amount of current. If
not, the UPS sounds alarm N, Check Inverter ( ). (See Section 304.) Although it is testing
the inverter, the UPS is not in Inverter Mode; it continues to condition input power, and it is
ready to provide battery power if there is a power outage. The BATTERY POWER light will
blink during this part of the test.
Battery Test: FERRUPS also checks its batteries to make sure that they can support your equipment for the
minimum specified runtime. If not, FERRUPS sounds alarm M, Check Battery ( ). (See
Section 304.) The READY light will blink during this part of the test.
Later models FE 1.8, FE 2.1, and FE 3.1 do not perform inverter tests.
Page 15
Letter
Audio
Code
Alarm Message
What It Means
What To Do
Low Battery
The UPS will shut down. Before this alarm, you should
have received a Low Runtime alarm ( ) to warn
you to shut down your equipment. When AC power
returns, turn FERRUPS on again. The green
CHARGING LED should light as the batteries
recharge.
High Battery
Low Runtime
Low AC Output
High AC Output
Output Overload
Hi Ambient Temp
Hi Heatsink Temp
To start the user test alarm from the control panel, press
[CONTROL] [8] [ENTER] [ENTER]. Repeat the
procedure to turn the alarm off.
Hi Transfmr Temp
The UPS may have shut down; if so, call Best Powers
Worldwide Service. If the UPS has not shut down, shut
down your equipment or bypass the UPS; then, turn the
UPS off and call Best Powers Worldwide Service.
Check Charger
Page 16
Letter
Audio
Code
Alarm Message
What It Means
What To Do
Check Battery
Check Inverter
Memory Check
Emergency PwrOff
Probe Missing
High AC Input
Call Service
Fan Alarm
The UPS may have shut down; if so, call Best Powers
Worldwide Service. If the UPS has not shut down, shut
down your equipment or bypass the UPS; then, turn the
UPS off and call Best Powers Worldwide Service.
Phone Best Powers Worldwide Service.
If you plan to view or change parameters from a control panel, see Section 302 for instructions.
If you plan to view or change parameters from a terminal or computer that you have connected to the RS232
port, see the commands in Section 402. When you use commands to display or change parameters, you can
identify the parameter with either its number or name. (The table shows both.) If you use the name, you can
enter the whole parameter name or just the short form shown in the table; you can also abbreviate the
parameter name as long as your abbreviation includes the letters in the short form.
Although you do not need a password to view any of the first 26 parameters, all of them require a password to
change. (See the Password column in the Parameter Table.) See Section 302 or 402 for password information.
All changeable parameters except 0 (Time), 10 (Date) and 15 (Unit ID) are set at the factory. Only qualified
technicians using the proper metering equipment should change other parameters. Improper calibration may
cause the FERRUPS to malfunction. Call Best Powers Worldwide Service before you attempt to change any
parameters except 0, 10 and 15.
Page 17
Number
Sample Display
Password
Terminal
Name
(Short Form)
Explanation
00 Time 07:04:00
None1
time
(t)
System Time. FERRUPS uses this time to record alarms and inverter runs.
When the DC power has been off and you restart the unit, the time shown will
be the last recorded time before shutdown. Reset time when DC power has
been off.
01 V In 120.7
Service
acvoltsin
(vi)
The input voltage FERRUPS is receiving. When this value drops below the
brownout voltage, FERRUPS switches to inverter.
02 V Out 120.7
Service
acvoltsout
(vo)
03 --Reserved--
04 I Out 3.1
Service
acampsiout
(o)
05 VA Out 374
Change Not
Allowed
vaout
(va)
Volt-Amps Out. The total apparent power your equipment is drawing from
FERRUPS. This value is based on parameter 2 multiplied by parameter 4, and
should be less than or equal to the VA or kVA rating of your unit. See
VALimit, parameter 19.
06 I Batt 0.0
Service
ibatt
(ib)
Battery Current. When the UPS is running on AC input, this is the charging
current in amps. When the UPS runs on battery power (inverter), this is the
amount of current (in amps) the batteries are supplying to the unit.
07 V Batt 48.51
Service
vbatt
(vb)
Battery Volts. The present battery voltage. FERRUPS will alarm if this value
is too low.
08 Freq 60.43 Hz
Change Not
Allowed
frequency
(f)
09 RunTime 12m
Change Not
Allowed
runtime
(rt)
10
10 Date 06/01/93
None1
date
(d)
System Date. FERRUPS uses this date to record alarms and inverter runs. The
date must be reset when you restart the unit after DC power is turned off.
ambtemp
(at)
The temperature (in Celsius) inside the unit. FERRUPS will alarm and shut
down if this value is too high.
123
12 SinkTemp 26c
heatsinktemp (st) The temperature of the heatsink. FERRUPS will alarm if this value is too
high.
13
13 --Reserved--
. or 112
Reserved
Change Not
Allowed
Reserved
On a FERRUPS control panel, you can display the Ambient Temperature by pressing [DISPLAY] [ . ] or
[DISPLAY] [1] [1] [ENTER].
Page 18
Number
Sample Display
Password
Terminal
Name
(Short Form)
Explanation
14
14 XfmrTemp 28c
Change Not
Allowed
xfmrtemp
(xt)
The temperature of the transformer. FERRUPS will alarm and shut down if
this value is too high. This parameter is only active on some models; for
other models, the display always shows -63c.
15
15 Unit ID
Network #1 UPS
None
(See note 1
on page 18.)
unitident
(id)
Unit ID. An identification string that can be configured for use with your
network.
16
fullload
(l)
17
17 Watts 374
Change Not
Allowed
watts
(w)
18
18 PF 0.73 Dist
Change Not
Allowed
powerfact
(pf)
The power factor of your equipment; the difference in the way it draws
voltage and current. Power factor is equal to Watts Out (parameter 17)
divided by VA Out (parameter 5). This parameter also tells whether the power
factor is leading (Lead), lagging (Lag), or distortion (Dist).
19
19 VALimit 500
Change Not
Allowed
valimit
(val)
20
20 #PwrOut 1
Change Not
Allowed
powerout
(po)
The number of times there has been a loss of input power since you started
the unit.
21
21 #OvrLds 0
Change Not
Allowed
overloads
(ol)
The number of times FERRUPS has sensed an overload; that is, the number
of times VA Out has been greater than VA Limit.
22
22 SysHrs 00000
Change Not
Allowed
syshours
(sh)
The total number of hours FERRUPS has been operating, regardless of mode.
This number does not increase while the On/Off switch is turned off.
23
23 InvMin 0000.0
Change Not
Allowed
invmin
(im)
The total number of minutes the inverter has run since startup.
24
24 Inverter Log
L 0319 2127 1215
Change Not
Allowed
inverterlog
(il)
A record of the date, time, duration and reason for the last 20 inverter (battery
power) runs. (See Section 306.)
25
25 Alarm Log
Change Not
A 0319 2127 1215 Allowed
alarmlog
(al)
A record of the date, time, duration and reason for the last 20 alarms. (See
Section 306.)
26
26 Test Results
(See explanation.)
testresults
(tr)
This parameter records the results of the last system test. The parameter
display includes the time and date of the test and the results of each part of the
system test. (See Section 303.)
Change Not
Allowed
Additional Parameters: The microprocessor in your FERRUPS keeps track of more than 100 parameters.
Parameters 27 and above are alarm and operation set points, calibration factors and other settings. You usually do not
need access to these parameters for normal operation of the FERRUPS. If you need information about the full range
of FERRUPS parameters, call Best Powers Worldwide Service to ask for TIP 407 or TIP 503. TIP 407 describes
communication from a control panel. TIP 503 describes communication through the RS232 port.
Page 19
DISPLAY SHOWS:
Display:
Display:
25
25 Alarm Log
The display will then scroll through the 20 most recent entries in the Alarm Log. If you have not had 20 alarm
conditions, the display will scroll through the entries FERRUPS has recorded. You can use the number keys as
you view this scrolling display:
USE THIS KEY:
[0]
[1] through [9]
TO DO THIS:
Pause the scrolling and start it again.
Go to the next log entry.
Each log entry consists of four pieces of information: the alarm code, the date (month/day) of the alarm, the time
(in 24-hour time) and the duration (in hours and minutes).
For instance, one entry might look like this:
B 0205 1017 0005
In this example, B means the alarm was Near Low Battery (see Section 304 for more information on alarm
codes); if alarm B was active, there would be an asterisk (*) after B. 0205" means the alarm occurred on
February 5 (2/5). 1017 means the alarm occurred at 10:17 a.m. 0005 means the alarm condition lasted for 0
hours and 5 minutes.
Inverter Log: The Inverter Log is parameter 24. To display the Inverter Log, follow these steps:
PRESS THIS KEY:
[DISPLAY]
[2][4]
[ENTER]
DISPLAY SHOWS:
Display:
Display:
24
24 Inverter Log
The display will then scroll through the 20 most recent entries in the Inverter Log. If the inverter has not run 20
times, the display will scroll through the entries FERRUPS has recorded. You can use the number keys as you
view this scrolling display:
USE THIS KEY:
[0]
[1] through [9]
TO DO THIS:
Pause the scrolling and start it again.
Go to the next log entry.
Page 20
Each entry includes four pieces of information: the inverter code, the date (month/day) of the inverter run, the
time (in 24-hour time) and the duration (in hours and minutes). For instance, one entry might look like this:
L 0205 0951 0015
In this example, L means the FERRUPS went to inverter because it lost AC input power; if the inverter was
still running, there would be an asterisk (*) after the L. 0205 means the inverter ran on February 5 (2/5).
0951 means the inverter ran at 9:51 a.m. 0015 means the inverter ran for 0 hours and 15 minutes.
Heres how to interpret the inverter codes:
Inverter Code
Meaning
Explanation
System Test
Brownout
Line Loss
Manual
Frequency
Reset
EventDate
08/25/1993
08/24/1993
08/24/1993
EventTime
11:25:32
12:13:18
12:05:07
Duration
00:00:45
00:01:08
00:08:11
Code/Event
J-User Test Alarm
A-Low Battery
B-Near Low Battery
The table shows whether the alarm is active now (Active), the date and time of each alarm, how long it lasted
(Duration), and what caused the alarm (Code/Event).
You can also display parameter 25 to view the Alarm Log; this display is the same as the control panel display.
Inverter Log: To display the Inverter Log on a terminal or computer, you can use the inverterlog or logs
command. (See Section 402. The logs command displays both the Alarm and Inverter Logs.) These commands
will display up to 20 log entries in a table. For example, the log might look like this:
Active EventDate EventTime Duration
No
08/25/1993 11:25:32 00:00:45
No
08/24/1993 12:13:18 00:01:08
Code/Event
M-Manual turnon
L-Line fault
The table shows whether FERRUPS is running on inverter (battery power) now (Active), the date and time that
FERRUPS ran on battery power, the length of time FERRUPS ran on battery power (Duration), and the reason
(Code/Event).
You can also display parameter 24 to view the Inverter Log; this display will be the same as the control panel
display.
Page 21
Page 22
Units with a Break-Before-Make Bypass Switch (see the label on the side of the switch):
Shut down your protected equipment; then, turn the bypass switch to LINE. Turn your equipment
on again if you must use it while the UPS is off. Your equipment will receive direct AC line instead
of conditioned power from the UPS. Go to step 2.
Units with a Make-Before-Break Bypass Switch (see the label on the side of the switch):
Make sure the AC line light is on, the Battery Power light is off, and the UPS is providing
output. If all three of these conditions are present, turn the bypass switch to LINE. If not, follow
steps 2-4 below before you switch the bypass switch to LINE; there will be a break in power to
your equipment after you have shut down your UPS and before you turn the bypass switch. Your
equipment will receive direct AC line instead of conditioned power from the UPS. Go to step 2.
CAUTION
Equipment will be damaged if you change the switch position when line is applied and the
UPS is off or on inverter! See TIP 410.
2. Turn off FERRUPS On/Off switch.
3. If your FERRUPS is plugged in, unplug it. If the UPS is not a plug-in model, turn off the AC Disconnect
switch.
4. 500 VA-3.1 kVA: If you have a battery cabinet that has a DC switch on the front, turn the switch off. If
your battery cabinet does not have a DC switch on the front, unplug the connector
between the battery cabinet(s) and the UPS; make sure you reconnect this connector
before you start the UPS again.
4.3 kVA-18 kVA: Unlock the lock in the center of the front panel and remove the panel. If there is a DC
switch behind the panel, turn it off. Reattach the panel to the UPS. If your UPS has
separate battery cabinets, turn off the DC switch at each battery cabinet.
If FERRUPS will be off for an extended time, recharge the batteries every 90-120 days. If you do not do
this, the batteries may be damaged. To restart the UPS, see Section 200. Make sure you complete all of the
steps so the UPS will operate properly.
Page 23
Description
Request to Send.
Clear to Send.
Signal Ground.
11
12
13
14
+12V, 0.5 amp (500 VA-3.1 kVA) or 0.3 amp (4.3-18 kVA). Do not use for setting
logic levels.
18
20
AS/400 Option.
21
Remote Shutdown.
23
24
25
Note that pins 2-5 and 7 are for RS232 communication, pins 11-13 and 23-25 are for remote monitoring, and pin
21 (used with 6 or 18) is for remote shutdown. The sections below will tell you more about how to take
advantage of these features. Pin 20 is for option use only.
Page 24
CAUTION
Do not make connections to the RS232 communication port if FERRUPS is connected to a positive
ground battery system. The RS232 ground must be isolated or equipment damage will result. For
help, call Best Powers Worldwide Service at 1-800-356-5737 or 1-608-565-2100, or call the nearest
Best Power office.
If you are connecting a terminal to the RS232 port, the terminal must be capable of serial communications.
If you are connecting a computer, the computer must be running terminal emulation software. Many popular
modem software packages can emulate a terminal; if you do not have a terminal emulation program, please call
Best Powers Worldwide Service for more information.
1. To connect FERRUPS DB25S (female) RS232 port to your terminal or computer, you will need a cable
designed specifically for this purpose. (See Figures 401-402.) Best Power offers cables for computers or
terminals using 25-pin or 9-pin serial ports; call your local Best Power office to order one of these cables. If
you would like to build your own cable, follow these requirements:
For more information on pin connections and the function of the non-serial pins on the RS232 port, see the
beginning of Section 400 and Section 403.
Note: To connect a modem, see TIP 503.
Figure 401
Page 25
Figure 402
2. Connect the cable from the RS232 port on the back of the FERRUPS to the serial port on your terminal or
computer.
3. Your terminal or computer should have these settings:
1200 baud.
8 data bits and 1 stop bit.
No parity.
FULL DUPLEX.
The terminal or terminal emulation software should also be set to FULL DUPLEX. If you are using a
terminal, note that FERRUPS supports the Televideo 900 series, ADM3A and WYSE 50 emulation.
The table below shows the standard settings at the FERRUPS DB25S port and what you can adjust these
settings to. Call the nearest Best Power office if you need to adjust any of the settings.
Specification
Connector
Standard Setting
Adjustable to:
Format
Standard setting or
7/8 bits, stop
Baud Rate
1200
50-38400
Parity
None
Duplex
Full
Full or Half
4. Turn your terminal on or run your terminal emulation software. Then press the [ENTER] key on your
keyboard. You should receive a message from FERRUPS, then a prompt. The prompt will vary depending
on your current password level:
=>
Normal prompt
User=>
User Password has been entered
Press [ENTER] on your keyboard a few times to make sure FERRUPS responds.
5. To control or monitor FERRUPS, simply type the command you need and press [ENTER]. The table on the
next page shows what keystrokes you can use as you type commands or view displays. See Section 402 for
more information on UPS commands.
Page 26
To do this
[BACKSPACE] or [CTRL]-[H]
Delete line.
[CTRL]-[X]
[CTRL]-[S]
[CTRL]-[Q]
Short Form
Password
alarmshelp
ah
None
Shows a list of all possible alarm messages, the audio code and letter
for each alarm and whether the alarm is active.
alarmlog
al
None
alarmtest
at
None
Allows you to test the alarm function. Alarmtest sounds the User
Test alarm (J). See Section 304.
alarmtest cancel
at c
Function
chm
None
clearalarms
ca
None
clearhistory
ch
None
Clears the minimum and maximum parameter values shown when you
use the extendedhistory or history commands.
clearpassword
cp
None
commands
cm
None
contdisplay
cd
Depends on
parameter
password
contstatus
cs
None
date
da
None
Displays system time and date. To set the date, enter date
[month]/[day]/[year].
chargermode
If you change parameter 39 to Yes, this command requires the User password.
Page 27
Command
Short Form
Password
delay
dl
None
Delays next command when you enter a number after delay. Each unit
represents 2.5 milliseconds, so delay 1 would cause a 2.5 mS delay.
For a 1-second delay, enter delay 400.
display
Depends on
parameter
password
extendedhistory
xh
None
None
? or he
None
history
None
identify
None
Shows Best Powers address and telephone number and the software
version.
inverterlog
il
None
logs
None
Displays both the Alarm and Inverter Logs. See Section 306.
message
"[message]"
None
off [time]
o [time]
None4
off [time]
autostart
o [time] a
None4
off cancel
oc
None4
parameters
Depends on
parameter
password
Shows a list of system parameters. See Section 305. You can also
display a range of parameters by entering the starting and ending
parameter number or name after the command.
Example: Parameters 1 10 will display parameters 1 through 10.
paramkeywords
pk
Depends on
parameter
password
Displays all parameters and their keywords (the names you can use
with commands). You can also display a range of parameters by
entering the numbers or names of the starting and ending parameters.
password
pw
None
format
help
Function
If you change parameter 39 to Yes, this command requires the User password.
Page 28
Command
Short Form
Password
program
pr
Depends
on
parameter
password
remote
rm
None
Configures the RS232 port so the connected terminal will work like a
control panel.
shutdown
or
shutdown
autostart
sd
None4
Shuts down the UPS output in 60 seconds (if you enter shutdown
alone) or the number of seconds you specify after the command. The
READY LED will blink until the UPS shuts down. If you specify
autostart, the UPS will restart shortly after power returns.
sd c
None4
shutup
sh
None
status
None
Shows date, time, system status, present system mode, active alarms,
and the value of various system parameters.
sm
None4
systemmode
auto
sm a
None4
Enters the Auto Mode. This is the normal FERRUPS mode. In this
mode, FERRUPS is conditioning AC input power for your
equipment; if there is a power outage, FERRUPS is ready to switch to
battery power.
systemmode
off
sm f
None4
Enters the Off Mode. In this mode, FERRUPS is not providing power
to your equipment, but you can still use FERRUPS control panel.
systemmode
inverter
sm I
None4
systemmode
linecondition
sm l
None4
stst
None4
time
None
Shows the current UPS time. To set the time, enter [hour]:[minutes]
after the command.
unshutup
None
shutdown cancel
systemmode
systemtest
sd a
Function
Lets you set the value of any parameter. You must enter the
appropriate password before you reset the value. See the Password
command above.
Format: PR [parameter # or name] [newvalue]
Example: PR 0 815 resets the time (parameter 0) to 8:15 a.m.
Page 29
These are relay contacts (rated at 25V AC/DC and 250 mA) that change
status on any alarm condition or when the UPS is turned off. (See the
beginning of Section 400.) Contacts that close on an alarm are available
between pins 23 and 24. Contacts that open on an alarm are available
between pins 24 and 25.
These are relay contacts (rated at 25V AC/DC and 250 mA) that change
status when the inverter turns on. (See the beginning of Section 400.)
Contacts that close on inverter operation are available between pins 12 and
13. Contacts that open on inverter operation are available between pins 11
and 13.
Remote Shutdown
FERRUPS can be connected to a remote shutdown switch to shut off output from the UPS to your protected
equipment. The shutdown switch must have a set of contacts that can apply FERRUPS +12 VDC on pin 6 to
FERRUPS pin 21. (You can use pin 18 instead of pin 6; do not use pin 14.) Use a shielded, single twisted pair
cable to connect the switch to FERRUPS pins. A connection between pins 6 and 21 (or 18 and 21) will shut down
FERRUPS output power to the protected equipment. When FERRUPS Remote Shutdown feature has been
activated, FERRUPS will be in the Off Mode, and the Emergency Power Off Alarm will sound. A control panel or
a terminal connected to the FERRUPS will display Emergency PwrOff. To restart the UPS, break the connection
between pins 6 and 21 (or between pins 18 and 21) at FERRUPS RS232 port. Then, follow the steps in the Startup
section for your model (202 or 203). Note that the 12-volt level on pin 6 or pin 18 is only available when
FERRUPS is operating.
You can change the type of signal that FERRUPS responds to and how quickly FERRUPS responds. You can also
set up FERRUPS to restart automatically when the shutdown signal stops. See TIP 503 or call Best Powers
Worldwide Service for more information.
Page 30
1-608-565-2509
Page 31
500VA/
350W
700VA/
500W
850VA/
600W
1.15KVA/
800W
1.4KVA/
1kW
1.8KVA/
1.25kW
2.1KVA/
1.5kW
3.1KVA/
2.2kW
4.6 amps
2.4 amps
2.1 amps
4.7 amps
4.5 amps
4.4 amps
2.6 amps
2.5 amps
2.4 amps
5.6 amps
2.8 amps
2.5 amps
6.0 amps
5.9 amps
5.8 amps
3.9 amps
3.8 amps
3.5 amps
6.6 amps
3.7 amps
3.2 amps
7.5 amps
7.3 amps
7.0 amps
4.4 amps
4.2 amps
4.0 amps
8.9 amps
5.1 amps
5.0 amps
4.6 amps
4.2 amps
9.5 amps
8.9 amps
8.4 amps
4.9 amps
4.6 amps
4.4 amps
13 amps
11 amps
6.3 amps
6.0 amps
5.8 amps
5.3 amps
12 amps
12 amps
11 amps
5.7 amps
5.4 amps
5.2 amps
17 amps
16 amps
8.5 amps
9.2 amps
7.8 amps
8.2 amps
16 amps
15 amps
15 amps
7.9 amps
7.5 amps
7.2 amps
20 amps
19 amps
9.8 amps
11 amps
9.4 amps
9.2 amps
18 amps
17 amps
16 amps
8.2 amps
7.8 amps
7.4 amps
28 amps
25 amps
14 amps
14 amps
12 amps
12 amps
26 amps
25 amps
24 amps
13 amps
12 amps
12 amps
10 amp
10 amp
10 amp
15 amp
15 amp
20 amp
20 amp
30 amp
4.1 amps
2.3 amps
2.1 amps
4.4 amps
4.2 amps
4.1 amps
2.2 amps
2.2 amps
2.1 amps
5.9 amps
3.3 amps
2.8 amps
6.2 amps
6.0 amps
5.7 amps
3.2 amps
3.1 amps
2.9 amps
7.0 amps
4.0 amps
3.4 amps
7.7 amps
7.2 amps
7.1 amps
3.8 amps
3.6 amps
3.5 amps
9.3 amps
5.7 amps
5.3 amps
5.0 amps
4.7 amps
10 amps
9.8 amps
9.4 amps
5.0 amps
4.8 amps
4.6 amps
14 amps
12 amps
6.8 amps
6.5 amps
6.1 amps
5.6 amps
13 amps
13 amps
12 amps
6.4 amps
6.2 amps
5.9 amps
18 amps
15 amps
8.8 amps
8.4 amps
8.0 amps
7.3 amps
16 amps
15 amps
14 amps
7.9 amps
7.6 amps
7.2 amps
21 amps
17 amps
10 amps
9.9 amps
9.0 amps
8.6 amps
19 amps
18 amps
17 amps
9.3 amps
8.9 amps
8.5 amps
30 amps
26 amps
15 amps
15 amps
14 amps
13 amps
28 amps
26 amps
25 amps
14 amps
13 amps
13 amps
Efficiency on AC Line
85%
86%
85%
88%
88%
90%
90%
91%
On Line BTU/hour:
KW/hour:
210
.062
277
.081
361
.106
372
.109
465
.136
474
.139
568
.166
742
.217
41
41
47
49
49
51
51
51
Runtime
Load:
9 min.
25 min.
14 min.
35 min.
11 min.
28 min.
18 min.
48 min.
14 min.
37 min.
11 min.
30 min.
9 min.
25 min.
14 min.
35 min.
45 lbs.
22.2 kgs.
51 lbs.
25 kgs.
57 lbs.
27.7 kgs.
86 lbs.
41.7 kgs.
94 lbs.
45.4 kgs.
120 lbs.
58.1 kgs.
132 kgs.
63.5 kgs.
144 lbs.
69 kgs.
58 lbs.
28 kgs.
76 lbs.
36.3 kgs.
82 lbs.
39 kgs.
126 lbs.
59.9 kgs.
148 lbs.
69.9 kgs.
176 lbs.
83 kgs.
188 lbs.
89 kgs.
248 lbs.
116.1 kgs.
AC Input Voltage
and Current,
Standard Charger
FE: 100 VAC
120 VAC
200 VAC
208 VAC*
220 VAC
240 VAC*
QFE: 110 VAC
115 VAC
120 VAC
220 VAC
230 VAC
240 VAC
Recommended AC
Input Service: 60 Hz
with 120VAC*
Full
Half
Load:
Weight :
Without Battery:
60 Hz Units:
50 Hz Units:
With Battery:
60 Hz Units:
50 Hz Units:
Dimensions
12 x 10 x 21.25 inches
15.1 x 15.2 x 20.2 inches
21.2 x 15.25 x 22.9 inches
(H x W x D)
305 x 255 x 540 mm
385 x 390 x 515 mm
540 x 390 x 585 mm
*Size input protection according to all applicable local or national codes. Fuse and circuit breaker sizes vary. Sizes shown are for the U.S. and
Canada.
**At 0.7 leading power factor.
Page 32
4.3KVA/3kW
5.3KVA/3.7kW
7KVA/5kW
10KVA/7.5kW
12.5KVA/10kW
18KVA/15kW
100 = 38 amps
120 = 32 amps*
200 = 19 amps
208 = 18 amps
220 = 17 amps
240 = 16 amps
220 = 19 amps
230 = 18 amps
240 = 17 amps
380 = 11 amps
400 = 10 amps
415 = 9 amps
100 = 46 amps
120 = 38 amps*
200 = 23 amps
208 = 22 amps
220 = 21 amps
240 = 19 amps
220 = 21 amps
230 = 20 amps
240 = 19 amps
380 = 13 amps
400 = 12 amps
415 = 11 amps
100 = 58 amps
120 = 51 amps*
200 = 29 amps
208 = 30 amps
220 = 27 amps
240 = 26 amps
220 = 27 amps
230 = 26 amps
240 = 24 amps
380 = 16 amps
400 = 15 amps
415 = 14 amps
200 = 45 amps
208 = 45 amps
220 = 41 amps
240 = 39 amps
220 = 43 amps
230 = 41 amps
240 = 39 amps
380 = 25 amps
400 = 24 amps
415 = 23 amps
200 = 59 amps
208 = 58 amps
220 = 53 amps
240 = 50 amps
220 = 55 amps
230 = 53 amps
240 = 51 amps
380 = 33 amps
400 = 31 amps
415 = 30 amps
200 = 85 amps
208 = 86 amps
220 = 81 amps
240 = 76 amps
220 = 81 amps
230 = 78 amps
240 = 75 amps
380 = 48 amps
400 = 46 amps
415 = 44 amps
120 = 40 amp*
208 = 25 amp
240 = 20 amp
120 = 50 amp*
208 = 30 amp
240 = 25 amp
120 = 65 amp*
208 = 40 amp
240 = 35 amp
208 = 60 amp
240 = 50 amp
208 = 75 amp
240 = 65 amp
100 = 42 amps
120 = 34 amps
200 = 21 amps
208 = 20 amps
220 = 19 amps
240 = 17 amps
220 = 19 amps
230 = 18 amps
240 = 17 amps
100 = 52 amps
120 = 44 amps
200 = 26 amps
208 = 26 amps
220 = 24 amps
240 = 22 amps
220 = 23 amps
230 = 22 amps
240 = 21 amps
100 = 68 amps
120 = 58 amps
200 = 34 amps
208 = 34 amps
220 = 31 amps
240 = 29 amps
220 = 31 amps
230 = 30 amps
240 = 28 amps
100 = 98 amps
120 = 82 amps
200 = 49 amps
208 = 48 amps
220 = 46 amps
240 = 41 amps
220 = 45 amps
230 = 43 amps
240 = 41 amps
Efficiency On AC
Line
90%
90%
90%
90%
91%
92%
On Line BTU/hour:
KW/hour:
1138
.333
1403
.411
1896
.556
2844
.833
3375
.989
4452
1.3
50
51
52
55
56
57
Runtime (minutes)
Full Load:
Half Load:
10
24
20
50
12
33
11
26
18
48
10
26
243 lbs.
115.7 kgs.
268 lbs.
131.1 kgs.
362 lbs.
176.5 kgs.
442 lbs.
217.7 kgs.
505 lbs.
251.3 kgs.
625 lbs.
312.1 kgs.
348 lbs.
163.3 kgs.
484 lbs.
229.1 kgs.
578 lbs.
274.4 kgs.
N Cabinet with
Standard Batteries
395 lbs.
(179.2 kgs.)
535 lbs.
(242.7 kgs.)
675 lbs.
(306.2 kgs.)
Dimensions
(H x W x D)
AC Input Voltage
and Current,
Standard Charger
FE:
QFE:
Recommended Input
Service for 60 Hz
Models**
Output Voltage and
Maximum Output
Current in amps***
FE:
QFE:
Weights:
Without Battery
60 Hz Units
50 Hz Units
With Battery****
60 Hz Units
50 Hz Units
NOTE: If your model has an internal NOTE: If your model has an internal bypass switch, add 8 in. or 200 mm to
bypass switch, add 8 in. or
the depth.
200 mm to the depth.
* FE 4.3KVA, 5.3KVA and 7KVA models have optional 120 VAC input voltage.
** Size input protection according to all applicable local or national codes. Fuse and circuit breaker sizes vary. Sizes shown are for the U.S. and
Canada.
***At 0.7 to 0.83 leading power factor.
****FE and QFE 10KVA, 12.5KVA and 18KVA models do not have internal batteries. Batteries are in a separate battery cabinet or rack.
Page 33
603 AC Output with Nominal Input Power and Loads (Protected Equipment)
Voltage Regulation:
FERRUPS provides 3% load regulation. Total voltage regulation under any line, load,
or battery condition to within -8.3% and +5% of nominal. Exceeds CBEMA and ANSI
voltage regulation standard for computing equipment.
Overload Capability:
On line (nominal AC volts in) 150% surge and 125% for 10 minutes. On inverter
(nominal DC volts in) 150% surge and 110% for 10 minutes. Overload operation is
not thermally limited. FERRUPS microprocessor continuously monitors output VA and
sounds an alarm before loss of output voltage regulation occurs.
Sine-wave Power:
FERRUPS provides sine-wave, computer-grade power with five percent or less total
harmonic distortion at rated load. It meets or exceeds CSA C22.2 No. 107.1.
Output Frequency:
On line: 60 Hz (FE) or 50 Hz (QFE) with nominal power line grid stability of 0.005 Hz.
On inverter: 60 Hz (FE) or 50 Hz (QFE) 0.005 Hz. Output frequency tracks input line
frequency up to limit, which is adjustable from 0.01 Hz to 3.00 Hz. Inverter turns on if
line frequency exceeds the selected limit.
Noise Rejection:
606 Environment
Storage Temperature:
Relative Humidity:
Operating Ambient
Temperature:
Batteries: -20 to +40 Celsius (-4 to 104 F). See Section 201.
UPS: -20 to +60 Celsius (-4 to 140 F) if batteries are removed from the
UPS.
0 to 95% without condensation.
0 to 40 Celsius (32 to 104 F) and 95% relative humidity.
Page 34
Ventilation Requirement:
The maximum operating ambient temperature drops 1 C per 300 meters (2 F
per 1000 feet) above sea level, with the maximum elevation being 3000 meters
(10,000 feet).
607 Protection
DC Input:
Output Protection:
The ferroresonant transformer inherently limits current and provides overload protection.
FERRUPS has high AC and low AC output voltage alarms, as well as an overload alarm.
If the AC output voltage falls below the low AC output voltage alarm setpoint, the unit
will alarm after 5 seconds. If the AC output voltage falls below the low AC output
shutdown setpoint, the unit will alarm and shut down.
Some FERRUPS models have output receptacles protected by fuses or circuit breakers.
Nominal battery voltage is 48 VDC. The standard battery charger is rated at 4 amperes at
54.8 VDC.
4.3 kVA to 18 kVA: Nominal battery voltage is 48 VDC for 4.3KVA-7KVA models and 120 VDC for 10KVA18KVA models. The standard battery charger is rated at 5 amperes.
Optional battery chargers at higher current ratings are available. Call the nearest Best Power office for more
information.
Page 35
Page 36
LIMITED WARRANTY
Transient Voltage Surge Suppression Circuitry
(For U.S. and Canadian Purchasers Only)
BEST POWER, a division of General Signal Power Systems, Inc. (BEST POWER) hereby warrants the
transient voltage surge suppression circuitry in each FERRUPS, FORTRESS, PATRIOT, UNITY/I,
CITADEL, or SPIKEFREETM product (hereinafter called "Product") sold by it for installation in the United
States of America and Canada to be free from defects in material and workmanship under normal use and service
for the lifetime of the Product, beginning with the date of sale to the initial retail purchaser, subject to the
following conditions. This warranty is applicable only to the initial retail purchaser (hereinafter called
PURCHASER), is not transferable, and is limited to the following remedies:
1. The replacement or repair of the transient voltage surge suppression circuitry in each Product that is returned
intact to BEST POWER and which shall appear to BEST POWER upon inspection to have been defective in
material or workmanship or to have been damaged through normal use;
2. The reimbursement to the PURCHASER of up to $25,000 per occurrence of documented physical damage to
specified computer equipment connected to a Product where such damage could have been prevented by
transient voltage surge suppression circuitry as detailed in BEST POWERs specification for the Product sold.
This warranty is made in addition to BEST POWERs Limited Two Year Warranty.
This warranty does not include any taxes which may be due in connection with replacement or repair nor any
installation, transportation or postage costs. These expenses will be paid by PURCHASER. Replacement or
repair will be made at BEST POWERs Worldwide Service, Highway 80, Necedah, Wisconsin 54646, U.S.A.
This warranty does not cover repair or replacement because of damage from unreasonable use (damage from road
hazards, accident, fire or other casualty, misuse, negligence, incorrect wiring) and any use or installation not in
conformance with instructions furnished by BEST POWER, or repairs or replacements needed because of
modifications or parts not authorized or supplied by BEST POWER.
This warranty is operable only upon the written acceptance by BEST POWER of an application by the
PURCHASER on BEST POWERs standard form for the above warranty coverage for the Product sold. In such
application, the PURCHASER shall represent that the Product sold has been properly installed and grounded in
accordance with instructions received from BEST POWER, and the PURCHASER shall also specify the
computer equipment to which the Product sold has been connected and the location of the computer equipment.
This warranty will not apply to any equipment not specified in the application by the PURCHASER as protected
equipment.
EXCEPT AS EXPRESSLY SET FORTH IN THIS WARRANTY AND BEST POWERs LIMITED TWO
YEAR WARRANTY, BEST POWER MAKES NO OTHER WARRANTIES, AND TO THE EXTENT
ALLOWED BY LAW, BEST POWER DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED,
INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR
FITNESS FOR A PARTICULAR PURPOSE.
REMEDIES UNDER THIS WARRANTY ARE EXPRESSLY LIMITED TO THE REPAIR OR
REPLACEMENT OF PRODUCTS AND THE REIMBURSEMENT SPECIFIED ABOVE, AND TO THE
EXTENT ALLOWED BY LAW ANY CLAIMS FOR LOSS ARISING OUT OF THE FAILURE OF
PRODUCTS TO PERFORM FOR ANY PERIOD OF TIME, OR SPECIAL, INDIRECT, INCIDENTAL OR
CONSEQUENTIAL DAMAGES OR OTHER ECONOMIC LOSS ARE EXPRESSLY EXCLUDED.
Some states do not allow limitations on how long an implied warranty lasts, so that the above limitation on
duration of implied warranties may not apply to you. Some states do not allow the exclusion or limitation of
incidental or consequential damages, so the above limitation or exclusion may not apply to you. This warranty
gives you specific legal rights, and you may also have other rights which vary from state to state. You are advised
to consult applicable state laws.
Page 37
Control Panel:
Environmental
Monitoring:
Extended Runtimes:
Interface Kits:
Plugs:
If your UPS does not have a plug, a bypass switch lets you transfer your protected
equipment to direct AC input power conveniently when its time to service your
FERRUPS. Your Best Power office can tell you if a bypass switch is recommended for
your UPS and describe the different bypass switches.
Best Power offers Control Panels and extension cables that let you monitor and
operate FERRUPS from a remote location.
Best Powers EnviroCom monitors many office and UPS conditions and phones you
when there is a problem. EnviroCom II also lets you 1) phone your FERRUPS for an
update on its status and environment, and 2) control and communicate with your
FERRUPS through a modem.
If you want extended runtimes, call Best Power for information on adding additional
battery capacity or an optional battery charger.
For computers that include their own UPS monitoring and shutdown software, Best
Power offers interface cable kits for use between your UPS and the computer. Kits
are available for Novell NetWare, IBM AS/400, Windows NT/LAN Manager/LAN
Server, Lantastic, and Banyan VINES.
The following plugs are available when you order new 120 VAC, 208 VAC, and 240
VAC units with a standard battery charger.
FE4.3KVA
FE5.3KVA
FE7KVA
Unit
120 VAC
208 VAC
240 VAC
FE500VA
5-15P
6-15P
6-15P
FE700VA
5-15P
6-15P
6-15P
FE850VA
5-15P
6-15P
6-15P
FE1.15KVA
5-15P
6-15P
6-15P
FE1.4KVA
5-15P
6-15P
6-15P
FE1.8KVA
5-20P
6-15P
6-15P
FE2.1KVA
5-20P
6-15P
6-15P
FE3.1KVA
L5-30P
L6-20P
6-15P
5-50P
L6-30P
L6-30P
5-50P
L14-30P
L14-30P
5-50P
L6-30P
L6-30P
N.A.
14-50P
L14-30P
N.A.
6-50P
6-50P
N.A.
14-50P
14-50P
Page 38
Receptacles:
The following output receptacles are available for new units. NOTE: 5-15R receptacles are
standard for the FE500, 700, and 850VA and 1.15 and 1.4KVA. 5-20R receptacles are
standard in FE1.8, 2.1, and 3.1KVA models. IEC 320 receptacles are only available for
QFE500VA-QFE3.1KVA models.
IEC 320
10A 250V
QA
EUROPEAN
SHUKO
10A/16A 250V
QB
UNITED KINGDOM
10A 250V
QF
AUSTRALIAN
10A 250V
QG
FRENCH
SHUKO
10/16A
250V
Warranties:
Besides our standard two-year warranty, Best Power offers several Warranty Enhancement Plans
to meet your service and maintenance needs. Contact the nearest Best Power office for more
information.
We hereby certify that the uninterruptible power system (QFE 500VA, 700VA, 850VA, 1.15KVA,
1.4KVA, 1.8KVA, 2.1KVA, 3.1KVA, 4.3KVA, 5.3KVA, 7KVA, 10KVA, 12.5KVA, and 18KVA)
complies with the RFI suppression requirements of Vfg. 243/1991 and Vfg. 46/1992. The German Postal
Service was notified that the equipment is being marketed. The German Postal Service has the right to
retest the equipment and verify compliance.
Hiermit wird bescheinigt, da die unterbrechungsfreie Stromversorgung (QFE 500VA, 700VA, 850VA,
1.15KVA, 1.4KVA, 1.8KVA, 2.1KVA, 3.1KVA, 4.3KVA, 5.3KVA, 7KVA, 10KVA, 12.5KVA, und
18KVA) in bereinstimmung mit den Bestimmungen der Vfg. 243/1991 und Vfg. 46/1992 funkentstrt
ist.
Der Deutschen Bundespost wurde das Inverkehrbringen dieses Gertes angezeigt und die Berechtigung
zur berprfung der Serie auf Einhaltung der Bestimmung eingerumt.
Best Power reserves the right to change specifications without prior notice.
Low Battery
Near Low Battery
High Battery
Low Runtime
Low AC Output
High AC Output
Output Overload
High Ambient Temp
High Heatsink Temp
User Test Alarm
W
K
L
M
N
O
P
Q
R
S
T
Best Power
FSS-0342J