Relay Protection Matrix

The document outlines the configuration of protection functions and outputs for a generator protection relay. It lists 24 protection functions that can trigger trip or alarm outputs. It also maps these protection functions to 8 user-programmable outputs through logic gates like AND and NOT to determine which protections control each output.

Uploaded by

elcy
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
140 views

Relay Protection Matrix

The document outlines the configuration of protection functions and outputs for a generator protection relay. It lists 24 protection functions that can trigger trip or alarm outputs. It also maps these protection functions to 8 user-programmable outputs through logic gates like AND and NOT to determine which protections control each output.

Uploaded by

elcy
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

X

Phase TOC (51 TOC) (Over


Current Trip)

Phase IOC (50 P)


(High Load Alarm)
X

Neutral TOC (51N)


(Earth Fault Trip)

Neutral IOC (50N)


(Trip Function Disable)

Generator Unbalance
Stage-1 (46G-1) (Trip)

Generator Unbalance
Stage -2 (46G-2) (alarm)
X

Phase Under Voltage1


(27-1) (Trip)

Phase Under Voltage2


(27-2) (Trip)

Phase Over Voltage1


(59-1) (Trip)

Phase Over Volatge2


(59-2) (Trip)
X

Loss of Excitation (40)


(Trip)

Sensitive Directional
Power1 (32R)
(Reverse Power Trip)

Sensitive Directional
Power2 (32L) (Low
Forward Power Alarm)
X

Under Frequency 1
(81U-1) (Alarm)
X

Under Frequency 2
(81U-2) (Trip)
Over Frequency 1 (81O-1)
(alarm, Function Disable)

Over Frequency 2 (81O-2)


(Trip, Function Disable)
X

NOT VT Fuse Failure

NOT CB OPEN

Relay Major Alarm

Protection Function

Stator Differential (87G)


(Trip)

AND

AND

AND

AND

AND

AND

AND

AND

AND

AND

x
X

x
X

x
X

Relay Output

Unbalance & High Load


Alarm
Generator Portection
OPTD (No Connection)
Generator Portection
OPTD (No Connection)
Under Frequency alarm
Spare
Spare
Low forward Power
VT Fuse Failure
(No Connection)
VT Fuse Failure
Relay Inoperative
Turbine & HV BKR Trip
(86L2)
HV BKR Trip (86L1)
Spare
Spare
Spare
Spare

U8

U7

AND

U6

U5

U4

U3

AND

U2

U1

P8

P7

P6

P5

P4

X
X

P3

AND

P2

AND

AND

AND

AND

AND

AND
P1