RSP-PROJ - ELEC - CABLE - 03 - Hipot Test Report of Cable

This document is a hipot test report for an HT cable used in the augmentation of existing MSDSs and installation of new MSDSs at Substation. It provides details of the project, panel and cable, and reports the results of IR value and hipot tests conducted on the cable. IR values were measured before and after a 60kV DC hipot test was performed on the cable for 5 minutes with no phase shorting and a leakage current of 2mA. The cable passed the tests with IR values of 20GΩ both before and after the hipot test.

Uploaded by

Katik Xalxo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
100% found this document useful (2 votes)
4K views

RSP-PROJ - ELEC - CABLE - 03 - Hipot Test Report of Cable

This document is a hipot test report for an HT cable used in the augmentation of existing MSDSs and installation of new MSDSs at Substation. It provides details of the project, panel and cable, and reports the results of IR value and hipot tests conducted on the cable. IR values were measured before and after a 60kV DC hipot test was performed on the cable for 5 minutes with no phase shorting and a leakage current of 2mA. The cable passed the tests with IR values of 20GΩ both before and after the hipot test.

Uploaded by

Katik Xalxo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 1

FORM: RSP-PROJ/ELEC/CABLE/03

HIPOT TEST REPORT FOR HT CABLE


PROJECT/ PKG.

SUBSTATION
PANEL DETAILS
FEEDER DETAILS
CABLE DETAILS
CABLE MAKE
DATE OF TESTING

:
:
:
:

AUGMENTATION OF EXISTING MSDSs AND INSTALLATION OF


NEW MSDS IV, V & VI/ PKG. 087 (M/s SIEMENS)
MSDS-V
RM-1 GIS
33kV SWBD (PANEL NO. 08)
33kV GIS SWBD (PANEL NO. 04)
33kV RM-1 INCOMER-1
33KV, 3Cx400Sq.mm., AL, XLPE/ Cable length: 1250 Mtrs
UNIVERSAL
28.03.2015

1. IR VALUE MEASUREMENT (BEFORE HIPOT):


PHASE
VOLTAGE
DURATION
IR VALUE
APPLIED
R-E
5 KV DC
1 MINS.
20 G
Y-E
5 KV DC
B-E
5 KV DC
R-Y
5 KV DC
Y-B
5 KV DC
B-R
5 KV DC
2. HIPOT TEST:
PHASE SHORTING
R-Ph
Y-Ph
B-Ph

Y-B-E
B-R-E
R-Y-E

VOLTAGE
APPLIED
60 KV DC
60 KV DC
60 KV DC

DURATION
5 MINS.

3. IR VALUE MEASUREMENT(AFTER HIPOT):


PHASE
VOLTAGE
DURATION
APPLIED
R-E
5 KV DC
1 MINS.
Y-E
5 KV DC
B-E
5 KV DC
R-Y
5 KV DC
Y-B
5 KV DC
B-R
5 KV DC

REMARKS

REMARKS

20 G

RSP- Projects

NAME
DEGINATION

LEAKAGE
CURRENT (In mA)
2

IR VALUE

TESTING DONE BY
SIGN

REMARKS

WITNESS BY
RSP- PD

RSP- ETS