Literature Review: Forced Draft and Induced Draft Fans
Literature Review: Forced Draft and Induced Draft Fans
specific fuel it is designed to use [3]. Forced draft fans not only supply the
air for the total airflow, but they also provide air to make up for heater
leakage and some sealing air requirements. The forced draft fan is kept in
the cleanest environment possible, meaning it is kept in room air and is not
around the high temperature, acidic environment of exhaust gasses.
Because FD fans are kept in such a clean environment, it is much less
susceptible to failures, unlike an induced draft fan. Also because of the FD
fans well-kept location, it makes access much easier for things like
maintenance and replacements. Compared to the ID fans, a lower initial
cost, are much cheaper to maintain, have fewer vibration problems, have a
shorter fan shaft, and require less space because of its lesser plot width. [4]
Variable Frequency Drives and Controls
Optimizing control systems for the Variable Frequency Drives (VFDs) in
coal plants may increase efficiency of the coal plant. Variable speed fans
need to be adjusted to give the desired airflow. There are many different
kinds of VFDs and they can have different features as well depending on the
fan they will be used on. Variable drive fans utilize hydraulic or magnetic
couplings. These couplings make the fan wheel speed independent of the
motor speed. Fan speed controls are usually integrated into automated
systems to maintain the correct speed of the fan. The speed of the FD and ID
fans can also be controlled by electronic variable-speed drive, which controls
the speed of the motor. This method means more energy efficiency of at
reduced speeds, than the hydraulic or magnetic couplings. [5] Fan dampers
can be used to control gas flow in and out of the fan. They can be installed
on the inlet or outlet side. These dampers can slow the flow of gasses or
change how the gas enters the fan wheel. [6] Fan hubs can be arranged in
three ways: Forward, Backward, and Radial. These different configurations
can results in different outcomes. Forward use blades curved toward the
direction of rotation of the fan wheel. Backward are used to design to handle
gas steams with relatively low particulate loadings. The backward are more
energy efficient than radial fans. Radial fans have blades that extend straight
from the hub. [7]
A study conducted at Alabama Power to create more efficient control
devices for 2 units that have more than 25 years of service has resulted in
better efficiency. This resulted in 0.15 percent heat rate improvement and
$120,000 per year in savings. Two damper drives control heated and
tempering primary air to a common duct. A third damper feeds hot hair to
the pulverizer. A distributed control system (DCS) positions 21 dampers to
maintain a target temperature within the pulverizer and to develop air flow
to the correct amount, so that ground coal can be transferred to furnace
burners. Secondary air from the two FD fans turns to wind boxes. A pulverizer
then feeds the coal to a row of burners. This controls ID fan inlet dampers
while fans speeds are between 17-25 percent maximum. High speed fans
mean the dampers are open and the draft is controlled only by fan speed.
These drives come with field-mounted contract electronic units and HART
protocol communication capability. The unit is processor controlled and
receives 20mA set point signals from the digital control system. It feeds
back 20 mA signals representing the signals precise actuator positions. This
unit controls the need for torque or limit switches. When voltage is cutoff, the
motor is cutoff from its power source. This device utilizes digital positioning,
known as a smart drive. These digital drives can use advanced frequency
converter technology to vary torque or travel speed of the intelligent
actuators. This unit eliminates the need for torque or limit switches. [8]
1.
RPM=
120 x Frequency
number of poles
VFD is a device that will make fans more efficient by utilizing the properties
of AC motors concerning frequency and speed. A fan with a VFD can run
more efficiently, and will also be easier to control and monitor. Theoretically,
VFDs would be an excellent option to consider for ensuring fans to run more
efficiently.
Integration of VFDs
The VFD can be very easily integrated into the existing system of a
plant by putting in line between the power source and the motor itself.
Switches will be put in place to operate the VFD and have an override in
which the fan would run at full speed, in case of VFD failure. VFD integration
used on an ID fan of a 300MW coal fired power plant located in north-east of
Yunnan province is estimated to have a power saving rate of 43.8%. [11] The
VFD will enable the motor to run at lower frequencies causing the fan to run
at lower speeds, which will result in lower power consumption.
Possible Vendors
VFDs may be obtained from many different vendors including Kirby
Risk, Springfield Electric, Siemens, and Flanders Electric. Flanders Electric
has a local office in Marion, IL.
Codes and Standards
As stated in the National Electrical Code; when dealing with AC motors
with adjustable voltage or variable torque drive systems the ampacity of
conductors and the ampere rating of all safety switches including, branchcircuits, short-circuits, and ground-faults shall be based on the maximum
operating current that is stated on the motor nameplate [12]. In addition, the
over current protection should be set to 125% of the phase converter
nameplate single-phase input full-load amps [13].
Summary
Coal power plants operate on a few basic principles; however, many of
them are aging, and are in need of more efficient operating methods. The
forced draft and induced draft fans are some of the highest consumers of
energy in the entire power plant. One of the possible solutions to cut down
on energy use and be more efficient would be to look at placing variable
frequency drives on FD and ID fans throughout the plant. Overall, the focus
of this project is to increase efficiency of the auxiliary loads at coal power
plants, and in turn help lower consumer prices.
References
[1]
Electric Power Plant Design, Headquarters, Department of the Army,
Washington, DC,
1984. pp. 1-1
[2]
Binstock, Morton. "Coordinated control for power plant forced and
induced draft fans during startup and fan speed changes." Patent Storm.
N.p., 1980. Web. 7 Oct 2010.
http://www.patentstorm.us/patents/4181099/description
[3]
ProcessRegister. "Forced Draft Fans." Process, Energy and Greater
Manufacturing
Industries Manufacturer Directory - Buy, Sell, Trade with Industrial Suppliers,
Exporters and Importers. 07 Oct. 2010. Web. 07 Oct. 2010.
http://www.processregister.com/Forced_Draft_Fans/Suppliers/pid2983.htm
[4]
Hudson Products Corporation. "FinFin Technical Info." Welcome to
Hudson Products. 2009. Web. 07 Oct. 2010.
http://www.hudsonproducts.com/products/finfan/tech.html
[5]
(2010, October 6) Centrifugal_fan. [Online]. Available:
http://en.citizendium.org/wiki/Centrifugal_fan
[6]
(2010, October 7) The Steam Generator. [Online]. Available:
http://en.citizendium.org/wiki/Conventional_coalfired_power_plant#The_steam_generator
[7]
(2010, October 7) Digitial Positioners. [Online]. Available:
http://www.controlglobal.com/articles/2010/DigitalPositioners1003.html
[8]
(2010, October 6) Convential Coal Power Plant. [Online]. Available:
http://en.citizendium.org/wiki/Conventional_coalfired_power_plant#The_steam_generator
[9]
ABB Inc. - Drives and Power Electronics. (2010, October 4) VariableFrequency Drives
Upgrade Reactor Circulating Pumps. [Online]. Available:
http://www.joliettech.com/what_is_a_variable_frequency_drive.htm
[10] M. Harshman. (2010, September 26) Variable-Frequency Drives
Upgrade Reactor
Circulating Pumps. [Online]. Available:
http://www.powermag.com/o_and_m/2710.html
[11] mediumvoltagedrive.de/1-power-generation/6.doc