ISCOUT-IfLEX2 Service Manual
ISCOUT-IfLEX2 Service Manual
expert compact
LMI system for
Grove RT / TM
Contents
General Information
Warnings
System Description
What's wrong?
Angle sensing
Length sensing
Pressure sensing
Service Manual
Issue 8/2007 Rev. A
This document is listed under Order No.
50 650 69 0101e (Grove RT-TM)
MAIN MENU
General Information
TABLE OF CONTENTS
1
General Information.............................................................................................................................5
Warnings...............................................................................................................................................5
3
3.1
3.2
3.3
4
4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8
4.9
4.10
5
5.1
6
6.1
Length Sensing..................................................................................................................................12
Length sensing error - flow chart .........................................................................................................13
7
7.1
8
8.1
9
9.1
Load sensing......................................................................................................................................18
Load sensing error - flow chart ............................................................................................................18
10
11
12
12.1
12.1.1
12.2
12.3
12.4
12.4.1
12.5
13
Service Manual
14
14.1
14.2
14.3
14.3.1
14.3.2
14.3.3
14.3.4
14.3.5
14.3.6
14.3.7
14.3.8
14.4
14.4.1
14.4.2
14.4.3
Drawings ............................................................................................................................................ 28
Components of the LMI system PAT iFLEX2 with iSCOUT expert compact ..................................... 28
Block Diagram..................................................................................................................................... 29
Electrical System Diagram Standard System ..................................................................................... 30
Central Unit, Overview ........................................................................................................................ 30
Central Unit, Detail A........................................................................................................................... 31
Central Unit, Detail B........................................................................................................................... 32
Sensors Wiring (page 2) ..................................................................................................................... 33
Console Wiring (page 3) ..................................................................................................................... 34
Crane Interface RT530-2 / RT540E (page 4) ..................................................................................... 35
Crane Interface RT600E / RT700E / RT875E (page 4)...................................................................... 36
Crane Interface TM500E-2 (page 4)................................................................................................... 37
Main Central Unit Connector............................................................................................................... 38
Cable Reel (LG152/0056) Wiring Diagram ......................................................................................... 39
Cable Reel (LWG520/0002) Wiring Diagram ..................................................................................... 40
Luffer Extension Wiring Diagram ........................................................................................................ 41
15
15.1
15.2
15.3
15.4
15.4.1
15.5
16
17
17.1
17.2
Troubleshooting Moisture................................................................................................................ 58
Water Ingress...................................................................................................................................... 58
Condensation ...................................................................................................................................... 59
The manufacturer reserves the right to modify the contents of this manual without notice. Hirschmann will not be
liable for errors contained in this manual or for incidental or consequential damages in connection with the
furnishing, performance, or use of this manual. This document contains proprietary information, which is
protected by copyright, and all rights are reserved.
No part of this document may be photocopied, reproduced, or translated to another language without the prior
written consent of Hirschmann.
Hirschmann reserves proprietary rights to all drawings, photos and the data contained therein. The drawings,
photos and data are confidential and cannot be used or reproduced without the written consent of Hirschmann.
The drawings and/or photos are subject to technical modification without prior notice.
All information in this document is subject to change without notice.
General Information
GENERAL INFORMATION
This service manual is designed to assist a service or maintenance person in identifying system
problem areas or malfunctions. A digital voltmeter with the capability to measure current will be
required, along with standard maintenance and service tools.
NOTE: Knowledge of how to use a voltmeter to measure both voltage and current is assumed.
REFERENCE: For system operation, refer to the consoles operators manual 50 650 19 0101e.
WARNINGS
The LMI is an operational aid that warns a crane operator of approaching overload conditions and
over hoist conditions that could cause damage to equipment and personnel.
The device is not, and shall not be, a substitute for good operator judgment, experience and use of
accepted safe crane operating procedures.
The responsibility for the safe crane operation shall remain with the crane operator who shall ensure
that all warnings and instructions supplied are fully understood and observed.
Prior to operating the crane, the operator must carefully and thoroughly read and understand the
information in this manual to ensure that he knows the operation and limitations of indicator and
crane.
Proper functioning depends upon proper daily inspection and observance of the operating instructions
set forth in this manual. Refer to Section 6. Pre-Operation Inspection and Calibration Verification of
the operators manual.
The LMI can only work correctly, if all adjustments have been properly set. For correct
adjustment, the operator has to answer thoroughly and correctly all questions asked during
the setup procedure in accordance with the real rigging state of the crane. To prevent
material damage and serious or even fatal accidents, the correct adjustment of the LMI has
to be ensured before starting the crane operation.
Service Manual
3
3.1
The iFLEX2 system is a CAN bus system made up of a central microprocessor unit, operating
console, length/angle sensor, pressure transducers, and anti-two block switches. All components and
sensors are equipped with CAN bus controllers.
The PAT Load Moment Indicator system operates on the principle of reference/real comparison. The
real value, resulting from the pressure measurement is compared with the reference data, stored in
the central processor memory and evaluated in the microprocessor. When limits are reached, an
overload warning signal is generated at the operators console. At the same time, the aggravating
crane movements, such as hoist up, telescope out and boom down, will be stopped.
The fixed data regarding the crane, such as capacity charts, boom weights, centers of gravity and
dimensions are stored in memory chips in the central processor unit. This data is the reference
information used to calculate the operating conditions.
Boom length and boom angle are registered by the length/angle sensor, mounted inside the cable
reel, which is mounted on the boom. The boom length is measured by the cable reel cable, which also
serves as an electrical conductor for the anti two-block switches.
The crane load is measured by pressure transducer block attached to the piston and rod side of the
hoist cylinders.
The interactive user guidance considerably simplifies the input of operating modes as well as the
setting of geometry limit values.
3.2
CAN stands for Controller Area Network. Its intended use is as a serial bus system for a network of
controllers. Each controller connected through a CAN chip is called a "node" and is mostly used to
acquire data from a sensor. All nodes are connected to a common bus and all nodes are able to
simultaneously read the data on that bus. Also, all nodes are able to transmit data on that bus
however only one node at a given time has write access to the bus. If the message is relevant, it will
be processed; otherwise it is ignored. The unique identifier also determines the priority of the
message. The lower the numerical value of the identifier, the higher the priority.
The cable bus is a twisted pair of shielded wire. Data can be transmitted in blocks from 0-8 bytes at a
maximum transfer rate of 1 Mbit/s for networks up to 40 meters. For longer network distances the
maximum transfer rate must be reduced to 50 Kbit/s for a 1 km network distance. CAN will operate in
extremely harsh environments and the extensive error checking mechanisms ensure that any
transmission errors are detected.
3.3
Service Manual
WHATS WRONG?
So, whats wrong? Assuming you are reading these pages because of some kind of problem with the
PAT system, let us try to guide you quickly to solving the problem. In most cases, your problem will
fall under the following categories:
4.1
4.2
THE DISPLAYED ANGLE DOES NOT MATCH THE ACTUAL BOOM ANGLE
4.3
THE DISPLAYED LENGTH DOES NOT MATCH THE ACTUAL BOOM LENGTH
4.4
THE DISPLAYED SLEWING DOES NOT MATCH THE ACTUAL SLEWING ANGLE
4.5
Please note that the indicated load is calculated by the system from the geometry information in the
computer, the operators selections, and all the sensor inputs. If the load display is off, it can therefore
be due to an error in any or several of these inputs! Refer to section Load sensing to narrow down the
source of your problem.
4.6
If the console does not show any sign at all (no lights, no buzzer, no display), the problem is either in
the wiring between console and central unit, or the console itself. Refer to section No console display
for further troubleshooting.
4.7
4.8
4.9
4.10
Angle Sensing
ANGLE SENSING
The System measures the angle of the main boom of the machine with an angle sensor. The angle
sensor is contained within the cable reel, located on the left side of the main boom.
Block Diagram
Angle
Sensor
CAN-Bus
Converter
Cable Reel
iFLEX2
CU
Pressure Transducer
The signal runs from the angle sensor to the Can-Bus converter board, both located in the cable reel.
From there, it travels as digital information on the CAN-Bus to the pressure transducer, which acts as
a T-connector to the main CAN-Bus running to the central unit.
So, what do you do when you are having a problem with your angle read-out?
Start by verifying the angle display. Refer to the section Troubleshooting A Sensor Problem Using
The Display to call up the sensor signal on your console display. The CAN-Bus is digital and as such
will either transmit the signal correctly or not at all. If your readings are off, you have to determine
what is causing the problem (reference the following flow charts).
X1
X14 (A2B)
X20
X21 (angle)
LED
CAN-Bus electronics in cable reel
The angle sensor has a potentiometer built in that is driven by a pendulum. As the angle changes, so
will the pendulum and with it the potentiometers axle. The converter board supplies a constant
voltage of 5V to the angle sensor and in return monitors the voltage of the potentiometer.
The terminal used is X21. The angle sensor is connected as follows:
Terminal X21
1
+ 5V
3
Signal
5
GND
Service Manual
5.1
compare
YES
2ND
Angle
sensor is
functioning
correctl
1ST
Angle sensor
range values:
4500mV at 0
2500mV at 45
500mV at 90
Recalibrate angle
sensor.
(Reference Angle
sensor calibration
procedure).
YES, 1st
NO
Is the voltage
between the
range of 4.75
to 5.25V ?
MEASURE AGAIN
2ND
Is the voltage
between the
range of 4.75
to 5.25V ?
NO
Replace converter
board
YES
If unplugging the angle sensor made the voltage return to
the acceptable range, replace the angle sensor. Follow
procedure for angle sensor installation and calibration.
10
Angle Sensing
YES
NO
Replace converter
board.
Note: If you need to determine the angle for voltages other than
shown above, do so by using the following formula:
Angle (degrees) = 90 degrees ((Voltage-1.875) * 72)
11
Service Manual
LENGTH SENSING
The system measures the length of the main boom of the machine with a length sensor. The length
sensor is contained within the cable reel, located on the left side of the main boom.
Block Diagram
Length
Sensor
CAN-Bus
Converter
Cable Reel
iFLEX2
CU
Pressure Transducer
The signal runs from the length sensor to the CAN-Bus converter board, both
located in the cable reel. From there, it travels as digital information on the
CAN-Bus to the pressure transducer, which acts as a T-connector to the main
CAN-Bus running to the central unit.
So, what do you do when you are having a problem with your length read-out?
Start by verifying the length display. Refer to the section Troubleshooting A Sensor Problem Using
The Display to call up the sensor signal on your console display. The CAN-Bus is digital and as such
will either transmit the signal correctly or not at all. If your readings are off, you have to determine
what is causing the problem (reference the following flow charts).
X1 (CAN)
X14 (A2B)
X20
X21 (angle)
LED
CAN-Bus electronics in cable reel.
The length sensor has a potentiometer built in that is driven by a gear drive from the cable drum. As
the length changes, the cable drum will turn and with it the potentiometers axle. The converter board
supplies a voltage of about 4.7V to the length potentiometer and in return monitors the output voltage
of the potentiometer. The terminal used is X20. The length sensor is connected as follows:
Terminal X20
1
+ (~ 4.8V)
3
Signal
5
- (~ 0.2V)
12
Length Sensing
6.1
Ensure the
cable reel has
5-8 turns of
preloading on
the reel.
Length sensor is
functioning correctly.
YES
NO
Replace length
sensor.
Does the indicated
length vary
significantly from the
actual length (more
than 0.3 feet)?
YES
NO
13
Service Manual
YES
Is the voltage
between the
range of 4.7V
to 5.0V ?
1ST
NO
2ND
Is the voltage
between the
range of 4.7V
to 5.0V ?
YES
NO
Replace
converter
board.
The length sensor returns a voltage between 0.16V at 0 turns of the length pot (= fully retracted) and
4.84V at 10 turns. How many turns you get at full extension depends on the gear ratio, the boom
length, the length cable used and the spooling pattern, so we cannot provide a standard table for it.
What we can give you for trouble-shooting, however is the following table that shows the expected
output voltage (measured between X20-5 and X20-3 Signal) for each complete turn of the length
potentiometer. Note that this does not sync to the number of turns of the cable reel, though:
Length Sensor Signal on Pin 3
Turns
Voltage X20-5 to
X20-3
0
0.00
1
0.46
2
0.93
3
1.40
4
1.87
5
2.34
6
2.81
7
3.28
8
3.75
9
4.22
10
4.68
For the boom control system, the length sensors are the same as described above with the exception
of cable reel internals (location of hardware, wiring, and gear wheels). Refer to the LWG520 and
LG152 spare part list for these differences.
14
Pressure Sensing
PRESSURE SENSING
The System measures the pressure of the boom lift cylinder for both rod- and piston-side.
Both sensors are contained within one box that also contains the electronics needed for amplification
and creation of the CAN-Bus signal.
Block Diagram:
(2)
PressureMeasuring
Cells
CAN-Bus
Converter
Pressure Transducer
7.1
iFLEX2
CU
NO
YES
Ensure that the pressure lines
are drained and disconnected.
Note: After exchanging the pressure transducer block, both transducer channels need to be zeroed,
see procedure Zero-Setting The Transducer Inputs.
15
Service Manual
SLEWING SENSING
The system measures the slewing (rotational position) of the cranes upper with a slewing sensor. The
slewing sensor is contained within the slip ring assembly.
Block Diagram
Slew
Potentiomet
er with (2)
outputs
Current
Converter
iFLEX2
CU
The slew potentiometer has two potentiometers built in that are driven by the slip ring axle. As the
slewing angle changes, so will the axle and with it the potentiometers outputs. Use the display screen
by pressing i (info) twice to show all sensor inputs.
ANGLE
(deg)
0.0
30.3
60.0
89.9
120.1
150.1
180.0
-150.1
-120.1
-90.0
-60.1
-30.0
0.0
SL ANG 1
(mv)
717
1174
1680
2158
2641
3144
3595
3144
2642
2160
1681
1172
718
SL ANG 2
(mv)
2161
2645
3150
3595
3141
2639
2161
1681
1180
718
1168
1680
2161
3000
2500
2000
1500
Potentiometer 1
1000
Potentiometer 2
500
0
0
45 sensor
90inputs135
Display screen
for
0
16
45
90
135
180
225
180
-135
SLEW ANGLE
270
-90
315
-45
360
0
Slewing Sensing
8.1
NO
YES
You can also leave the wires connected as use your meter in
Voltage-mode to measure the output signals. In this case, you
will see the 420mA range as a 1.1 to 5.5 Volt range.
If the voltage or currents do not fall in line with the
charts and tables shown below, and no system
errors are present, the problem may be mechanical.
Open the slip ring unit and determine if the slew potentiometer is set
mA 2
mA 3
24
20
mA
16
12
8
4
0
0
90
180
270
360
De gr e e s
17
Service Manual
LOAD SENSING
Please note that the load displayed by the LMI is not a direct measurement, but a calculated value
that is based on a lot of factors. Outside of the measured values (sensors), those include:
9.1
NO
YES
If the voltage or currents do not fall in line with the charts and tables
shown below, and no system errors are present, the problem may be
Open the slip ring unit and determine if the slew potentiometer is set
18
No console display
10 NO CONSOLE DISPLAY
If the console is not showing any lights, such as warning lights, backlighting, etc. it is most likely
missing power. Start with the following:
No console display
Are fuses
in line?
YES
NO
YES
Open console
Is power
being
supplied?
NO
NO
If no power was
supplied on the
connection board
but was supplied on
the external
connector, the
interface board must
be replaced.
YES
Replace fuse.
Connecting
cable is
loose or
defective.
is power
being
supplied?
NO
YES
NO
Console main
board need
replaced.
H2: 3,3 V
YES
Software
Error
H1: 5V
19
Service Manual
11 A2B PROBLEM
A2B problem
YES
NO
Check for
damaged length
cable and wiring.
If broken length
cable, refer to
system wiring.
If wiring is correct,
replace A2B
switch.
NO
Replace the
slip ring.
20
YES
Is the anti-two
block warning
light on?
NO
NO
YES
Ensure the
bypass
plug is
installed.
Are the
ohmmeter
readings correct?
YES
CAN-bus communication
12 CAN-BUS COMMUNICATION
The System measures the length of the main boom, the angle of the main boom, the pressures of the
lift cylinder, and the A2B state of the machine via a CAN-Bus connection. Since this is a digital bus
connection, it is not possible to measure the signals on the bus with a multimeter. Instead, the LMI
provides you with error codes that give you an indication of the bus state.
The error codes are one of the following:
E61
E62
E63
E64
E65
Error in the CAN bus data transfer for all CAN units
Error in the can bus data transfer of the pressure transducer sensor unit
Error in the can bus pressure transducer sensor unit
Error in the can bus data transfer of the length/angle sensor unit
Error in the can bus length/angle sensor unit
Block Diagram
E65
E61
E64
CAN-Bus
Converter
iFLEX2
CU
E62
Pressure Transducer
Cable Reel
E63
The block diagram tries to clarify that: If the CU does not see any CAN-Bus component, it will report
an E61. If it sees only the cable reel, it will report an E62 (pressure transducer missing). If it sees only
the pressure transducer, it will report an E64 (cable reel missing). E63 means that the pressure
transducer is available, but is reporting an internal error. E65 means that the cable reel unit is
available, but is reporting an internal error.
So, what do you do when you are having a problem with one of those codes?
12.1
E61
In case of an E61, start by connecting the two cables on the transducer block together. If an E62
appears, the transducer block must be replaced. If an E61 appears, reconnect the cable from the from
the central unit to the transducer block. At this point, if an E61 still appears check your cabling. You can
verify that power is being supplied to the sensor by testing the CAN connectors per this layout:
Connector
M12, 5 contacts
Pin Layout (CiA DR-303-1 7.2)
Pin 1
Pin 2
Pin 3
Pin 4
Pin 5
Shield
+ Ub
Ground
CAN High
CAN Low
Measure between pins 3 and 2 for crane voltage. If you see voltage, check all pins for continuity.
The iFLEX2 must be replaced if this cable is functioning correctly. If the E61 error code has become an
E64, connect the cable reel can bus cable to the transducer block and remove the can bus connector at
the cable reel. If this causes an E61 to appear, the can bus cable between the cable reel and transducer
block must be replaced. If an E64 remains, use the Ohm-meter to check the connector in the cable reel.
Either the connector has failed or the can bus converter boards must be replaced.
21
Service Manual
12.1.1
E61
Yes
E62
E64
No
E61
E61
Yes
Yes
No
E64
22
CAN-bus communication
12.2
E62
In case of an E62 the CU is reporting no signal from the pressure transducer. Start by checking your
cabling between CU and pressure transducer, even though it is not very likely that there is a problem
with it since the same cable carries also the signals from the cable reel and those appear to be fine.
You can verify that power is being supplied to the sensor by testing the CAN connectors per the
above pin layout. If you are sure that the sensor is being supplied, you have to replace the pressure
transducer.
12.3
E63
In case of an E63, the pressure transducer is reporting an internal problem. You cannot troubleshoot
any further, but need to replace the pressure transducer.
12.4
E64
In case of an E64, the CU is reporting no signal from the cable reel unit. Start by connecting the two
cables on the transducer block together. If an E62 occurs, the transducer block must be replaced.
If an E61 occurs, measure the cable from the transducer block to the cable reel with an Ohm-meter.
Check all pins of the CAN bus cable for continuity and cross-check for short circuits.
If the continuity check fails, the cable must be replaced. If the cable appears to be fine, next check
the connector at the cable reel. You can verify that power is being supplied to the sensor by testing
the CAN connectors per the pin layout (see E61). Replace the connector if this check fails.
If the connector checks properly, the board in the cable reel might be defective.
X1
X14 (A2B)
X20
X21
LED
CAN-Bus electronics in cable reel.
X1 Pin
CAN
CAN_SHLD
CAN +UB
CAN GND
CAN_H
CAN_L
23
Service Manual
12.4.1
E64
E62
Replace transducer
block
E61
Yes
Cable
checks good
Yes
No
Replace
cable
Check connector
at cable reel
Connector
checks good
No
Yes
Replace
connector
12.5
E65
In case of an E65, the cable reel is reporting an internal problem. In most cases, this will be an angle
sensor, length potentiometer or A2B wiring. Go to those chapters (Angle Sensing, Length Sensing,
A2B PROBLEM) to continue trouble shooting.
24
to review software
version information,
select the INFO and
then the "INFOHaeder" button once
The screen will show all sensor inputs as in the example below. For each sensor, an equivalent
voltage is shown in millivolts, along with the physical sensor value that that voltage refers to.
Pressure sensors are shown with physical values of [bar], angle sensors and slew sensors in degrees
and length sensors in feet (or meter for metric charts).
The values shown in the screen here are just examples of actual values. Refer to the table listed
below for actual value ranges.
If you suspect a sensor error or problem with a sensor, compare the indicated physical value of the
sensor on the display screen with the real value, i.e. length, angle, etc.
The voltages given are internal calculation values only; you will not be able to actually measure them
anywhere on the electronics! Typical values to be expected are:
Pressure transducers (piston and rod), 500mV @ 0 PSI; 4500mV @ maximum PSI
Length sensor, 500mV @ retracted boom length; voltage extended depends on the various
boom lengths.
Angle sensor, 4500mV at 0; 2500mV at 45; or 500mV at 90
25
Service Manual
Voltage Values
Value displayed Value
displayed [mV] +/- 10mV
Pressure Transducers
300 bar, type 314
500
1500
2500
3500
4500
Angle Sensor
500
1500
2500
3500
4500
Length Sensor
500
1500
2500
3500
4500
PSI
0
1088
2176
3263
4351
Bar
0
75
150
225
300
degrees
90
67.5
45
22.5
0
boom horizontal
feet
0
fully retracted
boom vertical
If the displayed value does differ from the actual value, please refer to the following sections to find
the cause of the problem:
If the displayed angle is incorrect, please go to section Angle Sensing.
If the displayed length is incorrect, please go to section Length Sensing
If the displayed pressures are incorrect, please go to section Pressure Sensing
26
Sig 2 (mA)
0.03mA
12.00
16.00
20.00
16.00
12.00
8.00
4.00
8.00
27
Service Manual
14 DRAWINGS
14.1
28
Components of the LMI system PAT iFLEX2 with iSCOUT expert compact
Drawings
14.2
BLOCK DIAGRAM
70 pin
Connector
Crane Power
Graphic
Console
CANBUS
Current
4..20mA
CAN-connector
CAN-connector
Slew Sensor
CAN-connector
Dual Pressure
Length/Angle Sensor
A2B
29
Service Manual
14.3
14.3.1
to sensors
> page 2
to console
> page 3
to crane
interface
> page 4
Hirschmann Automation and Control GmbH reserves proprietary rights to this drawing and to the data shown there on. The drawing and data are confidential
and are not to be used or reproduced without the written consent of Hirschmann. This drawing is subject to technical modification without prior notice.
30
Drawings
14.3.2
to sensors
> page 2
to console
> page 3
Hirschmann Automation and Control GmbH reserves proprietary rights to this drawing and to the data shown there on. The drawing and data are confidential
and are not to be used or reproduced without the written consent of Hirschmann. This drawing is subject to technical modification without prior notice.
31
Service Manual
14.3.3
to crane
interface
> page 4
Hirschmann Automation and Control GmbH reserves proprietary rights to this drawing and to the data shown there on. The drawing and data are confidential
and are not to be used or reproduced without the written consent of Hirschmann. This drawing is subject to technical modification without prior notice.
32
Drawings
14.3.4
Hirschmann Automation and Control GmbH reserves proprietary rights to this drawing and to the data shown there on. The drawing and data are confidential
and are not to be used or reproduced without the written consent of Hirschmann. This drawing is subject to technical modification without prior notice.
33
Service Manual
14.3.5
Hirschmann Automation and Control GmbH reserves proprietary rights to this drawing and to the data shown there on. The drawing and data are confidential
and are not to be used or reproduced without the written consent of Hirschmann. This drawing is subject to technical modification without prior notice.
34
Drawings
14.3.6
Hirschmann Automation and Control GmbH reserves proprietary rights to this drawing and to the data shown there on. The drawing and data are confidential
and are not to be used or reproduced without the written consent of Hirschmann. This drawing is subject to technical modification without prior notice.
35
Service Manual
14.3.7
Hirschmann Automation and Control GmbH reserves proprietary rights to this drawing and to the data shown there on. The drawing and data are confidential
and are not to be used or reproduced without the written consent of Hirschmann. This drawing is subject to technical modification without prior notice.
36
Drawings
14.3.8
Hirschmann Automation and Control GmbH reserves proprietary rights to this drawing and to the data shown there on. The drawing and data are confidential
and are not to be used or reproduced without the written consent of Hirschmann. This drawing is subject to technical modification without prior notice.
37
Service Manual
14.4
38
Drawings
14.4.1
Hirschmann Automation and Control GmbH reserves proprietary rights to this drawing and to the data shown there on. The drawing and data are confidential
and are not to be used or reproduced without the written consent of Hirschmann. This drawing is subject to technical modification without prior notice.
39
Service Manual
14.4.2
TO LG152/0056
REFER TO CABLE REEL
(LG152/0056) WIRING DIAGRAM
Hirschmann Automation and Control GmbH reserves proprietary rights to this drawing and to the data shown there on. The drawing and data are confidential
and are not to be used or reproduced without the written consent of Hirschmann. This drawing is subject to technical modification without prior notice.
40
Drawings
14.4.3
Hirschmann Automation and Control GmbH reserves proprietary rights to this drawing and to the data shown there on. The drawing and data are confidential
and are not to be used or reproduced without the written consent of Hirschmann. This drawing is subject to technical modification without prior notice.
41
Service Manual
42
Sensor Calibration
15 SENSOR CALIBRATION
15.1
Now you can follow the calibration procedure step by step or can select the type of calibration by
. Press "ESC" to finish calibration procedure.
scrolling with function key
pressure signal
piston side
pressure signal
rod side
slewing angle
signal
43
Service Manual
15.2
NOTE: The only thing adjustable for the pressure transducers is the zero point, which is the signal the
transducer outputs when there is no (zero) pressure sensed.
44
Sensor Calibration
15.3
NOTE: The only thing adjustable for the slew potentiometer is the zero point, which is complete when
the boom is at the 0 position over the front of the crane.
NOTE: The range for auto-calibrating this value is from -10 to +10. By pressing the AUTO key, the
zero setting occurs automatically and the indicator line will move to zero on the dial.
Calibration screen (slewing angle)
45
Service Manual
15.4
NOTE: The length sensor can be calibrated for its zero point and its full range.
With retracted boom, the potentiometer of the length sensor has to be at its 0 position, which is all the
way counter-clockwise. For extended boom, the adjustment is done by software as described below.
The length should be calibrated to be about 0.1 feet (or 0.05m for metric) accurate for retracted and
extended lengths. Perform the following steps:
Calibration screen (boom length)
Fully retract the main boom and check if indicated length is within 0.1 feet (or 0.05m for metric) of
actual retracted boom length.
If it is not, adjust length potentiometer mechanically as described below:
46
Sensor Calibration
With boom fully retracted turn the center screw of the length pot unit counter clockwise to a soft
stop.
During adjustment an additional button "OK" appears. Check value and set actual length as fully
retracted length by pressing OK. Afterward next calibration screen appears.
Calibration screen minimum length
47
Service Manual
Now extend main boom all the way out. Make sure you are within the allowed operating range
(especially maximum radius).
During telescoping out the boom an additional button "OK" appears.
Start calibration maximum length
Check whether boom is fully extended, then press "OK". Afterward next calibration step (angle)
appears.
Calibration screen maximum length
48
Sensor Calibration
15.4.1
13.
14.
15.
16.
49
Service Manual
15.5
The angle sensor can be calibrated for its zero point and with steep boom
Material required: calibrated inclinometer
Select Angle sensor calibration menu and start procedure by pressing "OK"
Calibration screen (boom angle)
50
Sensor Calibration
Boom down.
Release adjustment screws of the
angle sensor.
Mechanically adjust top of angle
sensor housing exact parallel with
boom by help of inclinometer.
Fix adjustment screws of the angle
sensor.
Having adjusted the angle sensor mechanically check value and press "OK" for the next step.
Start calibration for "zero degree" angle
51
Service Manual
When the boom angle is within the calibration range, the screen will add the
CHANGE,
SET and
OK text as shown below:
calibrate angle
Measure the boom angle with the inclinometer and when the boom is positioned in the calibration
range, compare the measured angle to the displayed angle.
If the indicated angle is within +/- 0.1 degrees of the measured angle, confirm with OK.
Otherwise, select SET to adjust the angle.
adjust angle
Once you push SET , the screen is going to change to the angle adjustment screen. Use the +
and - buttons to adjust the indicated angle to match the measured angle.
When the display shows the correct angle, press OK.
Press ESC to leave sensor adjustments and return to normal LMI screen.
52
Error Codes
16 ERROR CODES
The following Error Code Table gives a brief description of Error Codes elimination. Refer to the noted
sections for detailed Troubleshooting information.
LMI System Error Code Table (LSQG V 1.xx):
Error code
Error
Cause
E01
E02
E03
E04
E05
E06
E12
E11
Elimination
53
Service Manual
Error code
Error
Cause
Electronic component in the
measuring channel is
defective.
refer to E12
refer to E12
refer to E1A
E13
E14
E15
E16
E17
E18
E1A
E1B
E1C
E21
E22
E23
E24
E25
E26
54
Elimination
refer to E11
refer to E11
refer to E12
refer to E12
refer to E12
refer to E12
refer to E14
refer to E14
refer to E15
refer to E15
refer to E16
refer to E16
Error Codes
Error code
E27
E2A
E2B
E2C
E31
E32
E37
Error
E52
refer to E17
refer to E1A
refer to E1A
refer to E1A
Flash-EPROM defective
E39
E51
refer to E17
E38
E47
Elimination
E43
Cause
Flash-EPROM defective
The system program in the
LMI does not match to the
programming in the crane
data file
The system program in the
LMI and the programming in
the load chart file do not
match.
Write/read memory (RAM) or
central unit defective.
Flash-EPROM defective
Flash-EPROM defective
55
Service Manual
Error code
E53
E56
E57
E61
Error
Wrong setup of min. analog
inputs length1, angle1,
pressure1
Cause
Flash-EPROM defective
Buffered data file does not
contain valid data.
Flash-EPROM defective
CAN Bus cable between the
central unit and the sensor
unit defective or not
connected.
Can bus port in the central
unit defective
Short circuit in a CAN Bus
cable
Cable between the central
unit and the sensor unit
defective.
Can bus port in the central
unit defective
Can bus port in the sensor
unit is defective
Sensor unit is defective
The analog values of the
sensor unit are invalid
E62
E63
E64
E65
E66
E67
E84
E85
E89
E98
EAB
See E62
See E62
See E63
See E63
Reset system
Connect PC terminal and watch
error messages
Replace A2B switch
56
Elimination
Error Codes
Error code
Error
Cause
Disconnected cable in the
A2B switch
Setup ID in DGA12.9
EAC
EAD
EDB
EDC
EDD
Battery empty
EDE
Record lost
EDF
EFD
LMI Watchdog
extra time
Elimination
Reset system
Connect PC terminal and watch
error messages
change batterie, after this setup
of RTC
Message disappears after a few
seconds
Message disappears after a few
seconds
Message disappears after a few
seconds
Note:
If a fault message is displayed that is not included in the present list, then please contact your local Hirschmann
Customer Service. > www.hirschmann-ac.de <
57
Service Manual
17 TROUBLESHOOTING MOISTURE
The PAT iFLEX LMI contains electronic components in various locations, such as central unit, sensors,
junction boxes etc. These internal components cannot be designed to withstand exposure to moisture
over a longer period of time. For this reason, the housings of the components are water protected
according to IP 65. If you find water or moisture inside any of the housings, the source for the water
ingress has to be detected and corrected to ensure proper operation.
There are two major possibilities for the occurrence of excessive moisture inside an enclosure:
Water ingress
Condensation
This outline gives instructions for detecting the cause for excessive moisture by using simple
troubleshooting methods and how to prevent the moisture ingress from happening again.
17.1
WATER INGRESS
There are different possibilities for water ingress. It is possible to find out the source of water ingress by
going through the following steps and ruling out one possibility after the other until the cause is identified:
1) Spray Cleaning
The enclosures used for the PAT LMI system are water protected to IP 65. This means protection against the
environment, such as rain. However, through the use of spray cleaner at short distances, it is possible to
force water through the gasket or strain relieves. For this reason, avoid spraying any components from short
distances with spray cleaners. Convey this fact to any member of a maintenance crew.
2) Missing / Loose Screws
All screws have to be present and to be equally tight to ensure water protection of the enclosure. If there are
screws missing, replace them. If no screw is missing, check the tightness. If any were loose, then open all
screws and then re-tighten them equally.
3) Bent Lid
An enclosure will only seal correctly if the lid is not bent. To check this, loosen all screws of the lid, take the
lid off the box and visually inspect it for deflection. If the lid is bent or damaged, it needs to be replaced. Try
to determine what has caused the lid to be bent and eliminate the reason for that. Order a new lid through
your PAT representative.
4) Defective Gasket
The gasket underneath the lid seals the unit. The gasket needs to be in good condition in order to seal
correctly. If the gasket is torn, brittle or severely bent, it needs to be replaced. Order a new gasket through
your PAT representative.
5) Loose Strain Relieves
The strain relieves allow cabling to enter the box without allowing water to enter it. The strain relieves have to
be correctly tightened in order to do this. Check the tightness by taking the external cable into one hand and
carefully trying to turn it. If the internal wires turn with the outer cable, the strain relief is loose. Get a new
grommet (insert) through your PAT representative and replace the existing one with the new one. Tighten the
strain relief correctly. Note: Whenever a strain relief is opened, i.e. to replace a cable, a new grommet needs
to be used. Never re-use any grommet or the strain relief will not seal properly!
6) Water Entry Through External Cabling
Even with a tight strain relief, water may still enter the box through the inside of the cable. In this case, you
have to find out why and where water enters the cable. Look for damages to the cable itself and inspect the
opposite side of the cable. In example, if the cable comes from a connector that is full of water, the water will
run through the inside of the cable and fill up the central unit, too.
58
Troubleshooting Moisture
17.2
CONDENSATION
In a climate with high humidity and rapidly changing temperatures, condensation can happen inside
any enclosure, usually the larger the volume of the box, the more likely. In this case, water drops build
up on the inner components when humid air is trapped inside the box. With condensation, water
tightness is not a problem the box is sealed just fine, which is what prevents the trapped air from
exiting the box. There are two ways to deal with condensation:
If the volume is very small, a desiccant bag might be able to soak up the airs humidity.
If the effect is more severe, the only way to get rid of this effect is then to give the box the ability to breath
without sacrificing its water tightness. Contact your PAT representative for breathing elements to than can be
added to the box and will help to reduce the effects of humid climates.
59
Service Manual
NOTES:
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
60
Revision History
18 REVISION HISTORY
Version
Rev. A
Date
Modifications
2007-08-17 First Issue for Grove RT and TM cranes
iFLEX2 with iSCOUT expert compact
Name
Konopka
61