Load Combination

The document outlines load combinations on different types of transmission line tower structures under normal and broken-wire conditions. It provides vertical, longitudinal, and transverse load values for intact and broken weight spans of A-type, B-type, B section, C-type, C section, D600, and dead-end tower configurations under varying temperature and wind scenarios. Load combinations include vertical loads, longitudinal wind loads, transverse wind loads on the structure, and tension loads on the conductors and insulators.

Uploaded by

ram
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
34 views1 page

Load Combination

The document outlines load combinations on different types of transmission line tower structures under normal and broken-wire conditions. It provides vertical, longitudinal, and transverse load values for intact and broken weight spans of A-type, B-type, B section, C-type, C section, D600, and dead-end tower configurations under varying temperature and wind scenarios. Load combinations include vertical loads, longitudinal wind loads, transverse wind loads on the structure, and tension loads on the conductors and insulators.

Uploaded by

ram
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 1

LOAD COMBINATION ON TRANSMISSION LINE TOWER STRUCTURE AT RELIABILITY, SECURITY AND SAFETY CONDITIONS

VLI = Vertical Load in Intact Weight Span


VLB = Vertical Load in Broken Weight Span

= Line Deviation
TOWER
TYPE

TWS = Transverse Wind on Structure


LWS = Longitudinal Wind on Structure

T1 = Tension at 320C + 100% Wind


T2 = Tension at 320C + Nil Wind

T3 = Tension at 40C + Nil Wind


T4= Tension at 40C + 36% Wind

WIND - LONGITUDINAL DIRECTION

CONDITION

NORMAL CONDITION

WC = Wind on Conductor
WI = Wind on Insulator String

WIND - TRANSVERSE DIRECTION

BROKEN-WIRE CONDITION

NORMAL CONDITION

BROKEN-WIRE CONDITION

LOADS

VERT

LONG

TRANS

VERT

LONG

TRANS

VERT

LONG

TRANS

VERT

LONG

TRANS

A-TYPE

VLI

LWS + 0.0

0.0

VLB

LWS+0.5*T2*
Cos/2

0.5*T2*
Sin/2

VLI

2.0*T1 or T4*
Cos/2

TWS+WC+WI+0.0

VLB

0.5*T1 or
T4*Cos/2

TWS+0.6*WC+WI+0.5
*T1 or T4*Sin(/2)

B-TYPE

VLI

LWS + 0.0

T3*Sin/2

VLB

LWS+1.0*T3*
Cos/2

1.0*T3*
Sin/2

VLI

2.0*T1 or T4*
Cos/2

TWS+WC+WI+2*(T
1 or T4)*Sin(/2)

VLB

0.5*T1 or
T4*Cos/2

TWS+0.6*WC+WI+1.0
*(T1 or T4)*Sin(/2)

B SECTION
TOWER

VLI

LWS + 0.0

T3*Sin/2

VLB

LWS+1.0*T3

0.0

VLI

0.0

TWS+WC+WI+0.0

VLB

T1 or T4

TWS+0.6*WC+ WI
+0.0

VLI

LWS + 0.0

T3*Sin/2

VLB

LWS+1.0*T3*
Cos/2

1.0*T3*
Sin/2

VLI

2.0*T1 or T4*
Cos/2

TWS+WC+WI+2*(T
1 or T4)*Sin(/2)

VLB

T1 or
T4*Cos/2

TWS+0.6*WC+WI+1.0
*(T1 or T4)*Sin(/2)

C SECTION
TOWER

VLI

LWS + 0.0

T3*Sin/2

VLB

LWS+1.0*T3

0.0

VLI

0.0

TWS+WC+WI+0.0

VLB

T1 or T4

TWS + 0.6 * WC +
WI+0.0

D 600

VLI

LWS + 0.0

T3*Sin/2

VLB

LWS+1.0*T3*
Cos/2

1.0*T3*
Sin/2

VLI

2.0*T1 or T4*
Cos/2

TWS+WC+WI+2*(T
1 or T4)*Sin(/2)

VLB

T1 or
T4*Cos/2

TWS+0.6*WC+WI+1.0
*(T1 or T4)*Sin(/2)

Dead-End

VLI

LWS+T3

0.0

VLB

LWS+0.0

0.0

VLI

T1 or T4

TWS+0.5*WC+WI+
1.0*T1 or T4

VLB

0.0

TWS + 0.1 * WC +
WI+0.0