Tech - Specification For Numrical Protection Relay
Tech - Specification For Numrical Protection Relay
NAME
CUSTOMER
JOB NO.
TECHNICAL SPECIFICATION
FOR
NUMERICAL RELAYS
REV.
NO.
DESCRIPTION
CONCEPT ENGINEERING
PROJECTS PVT. LTD.
DOCUMENT NO. :
CEPL/10162/EL/DOC09
TOTAL SHEETS : 10
CEPL/10162/EL/DOC09
Page 1 of 16
REV. 0
PROJECT NAME
CUSTOMER
JOB NO.
CONTENTS
1.0
SCOPE
2.0
CODESANDSTANDARDS
3.0
SITECONDITIONS
4.0
GENERALREQUIREMENTS
5.0
TECHNICALREQUIREMENTS
6.0
INSPECTION,TESTINGANDACCEPTANCE
7.0
PACKINGANDDESPATCH
CEPL/10162/EL/DOC09
Page 2 of 16
PROJECT NAME
CUSTOMER
JOB NO.
1.0
SCOPE
Theintentofthisspecificationistodefinetheminimumrequirementofdesign,manufacture,
testingpackinganddispatchofnumericalrelays.Thespecificationalsodefinesthe
requirementofcommunicationandintegrationwithdataconcentrator,substationMan
MachineInterfaceandupperlevelcontrolsystem.
2.0
CODESANDSTANDARDS
2.1
TheequipmentshallcomplywiththerequirementsoftherevisionofthefollowingIEC
standards/equivalentIndianStandardsunlessotherwisespecified.
IEC60068
:EnvironmentalTesting
IEC60073
:Basicsafetyprinciplesformanmachineinterface,marking&Identification
IEC60529
:Degreeofprotectionprovidedbyenclosure(IPCode)
IEC60255
:Electricalrelays
IEC61000
:Electromagneticcompatibility(EMC)
IEC61850
:Communicationnetworks&systemsinsubstation
2.2
Incaseofimportedequipment,standardsofthecountryoforiginshallbeapplicableifthese
standardsareequivalentormorestringentthantheapplicableIEC/Indianstandards.
2.3
TheequipmentshallalsoconfirmtothepreviousofIndianElectricityRulesandother
statutoryregulationscurrentlyinforceinthecountry.
2.4
IncaseIndianstandardsarenotavailableforanyequipment,standardissuedbyIEC/BS/VDE/
IEEE/NEMAorequivalentagencyshallbeapplicable.
2.5
Incaseofanycontradictionbetweenvariousreferredstandards/specifications/datasheetsand
statutoryregulations,thefollowingorderofpriorityshallgovern:
Statutoryregulations
DataSheets
JobSpecification
ThisSpecification
CodesandStandards
3.0
SITECONDITIONS
CEPL/10162/EL/DOC09
Page 3 of 16
PROJECT NAME
CUSTOMER
JOB NO.
Therelaysshallbesuitableforsatisfactoryoperationwheninstalledinapanellocatedina
pressurizedsubstationwithrestrictednaturalairventilatorintropicalhumidandcorrosive
atmosphere.Relayshallbedesignedtoperformallitsfunctionsandoperateundersite
conditionsspecifiedinswitchboarddatasheet.Ifnotspecificallymentionedtherein,adesign
ambienttemperatureof400Candanaltitudenotexceeding1000Mabovethemeansealevel
shallbeconsidered.
4.0
GENERALREQUIREMENTS
4.1
Theofferedequipmentshallbebrandnewwithstateofthearttechnologyandprovenfield
trackrecord.Noprototypeequipmentshallbeoffered.
4.2
4.3
4.4
Vendorshallensureavailabilityofsparepartsandmaintenancesupportservicesfortheoffered
equipmentforatleast15yearsfromthedateofsupply.
VendorshallgiveanoticeofatleastoneyeartotheenduserofequipmentandEILbefore
phasingouttheproduct/sparestoenabletheendusertoplaceorderforsparesandservices.
IncaseofrelaysmanufacturedoutsideIndia,therelaymanufacturerthroughhisIndian
establishmentorassociateinIndiashallprovideapplication,testing,commissioning,aftersales
serviceandothernecessarysupportforminimumof1.5yearstocustomer.TheirIndian
establishmentorassociatecompanyinIndiashallalsomaintainadequateinventoryofeachtype
ofrelayorsparestomeettherequirementarisingduringprojectexecutionandplantoperation.
RelaymanufacturershallpossesasignedMemorandumofunderstandingwiththeirIndian
associateforprovidingcustomersupport.
5.0
TECHNICALREQUIREMENTS
5.1
AuxiliaryPowerSupply
Unlessotherwisespecified,relayshallbesuitabletoacceptbothAC/DCsupplieswithrange
110Vto240Vwithtoleranceof15%.Theauxiliarypowersupplyshallpreferablybesite
selectablerequiringnoadditionalhardware.
5.2
BasicRequirementandConstructionDetails
5.2.1
Relayshallbesuitableforflushmounting.Therelayenclosureshallbedusttighthavingdegree
ofprotectionminimumasIP5X
5.2.2
RelayTerminalsshallbesuitableforterminationof2.5/4sqmmwires,forallhardwired
connections.
CEPL/10162/EL/DOC09
Page 4 of 16
PROJECT NAME
CUSTOMER
JOB NO.
5.2.3
RelayshallhavedrawoutfeaturewithplugintypePCBforeasyreplacement.Incaseoffixed
typerelay,therelayterminalsshallbeeasilyaccessiblefortestingandcommissioning.
5.2.4
Currentoperatedrelayshallhaveprovisionfor4wireCTinputand2wiresCBCTinput.However
thevoltageoperatedrelayshallhaveprovisionfor4wirePTinput.Incaseofcomprehensive
singlenumericalrelay,therelayshallhaveprovisionofbothcurrentandvoltageinputs.
5.2.5
CTshortinglinkshallbeprovidedatterminalblockasrequired.
5.2.6
Allnumericalrelaysshallhavekeypad/keystoallowrelaysettingfromrelayfront.Allhand
resetrelaysshallalsohaveresetbuttononrelayfront.Selfresetorhandresetfeatureofthe
relayshallbesoftwareselectableandpasswordprotected.
5.2.7
Relayshallbesuitableforboth1Aor5ACTsecondary.CTsecondary1Aor5Ashalleitherbe
softwareselectableorbyprovidingsuitablelink.Selectionbetween1Aor5Ashouldbepossible
atsite.
5.2.8
Relaysshallhaveselfdiagnosticfeaturewithindicationofrelayfailureonrelayfront.Relay
faults(Selfdiagnostic)shallbecommunicatedandannunciatedtodataconcentrator/
substationMMI.
5.2.9
Allnumericalrelaysshallbecommunicabletype.
5.2.10 Relaysshall,asaminimum,haveprotectionfunctionsasperfeederequipmentdatasheets.
Otherfunctionssuchasmeteringandcontrolshallbeprovided,ifspecifiedindatasheets/job
specifications.
5.3
SoftwareSecurity
Therelayshallbeprovidedwithsuitablesecurity(passwordprotection)againstunauthorized
WRITEACCESSforchangeinrelaysetting.Howeveritshouldbepossibletoviewmetering,
protectionsettings,statusandeventdataasREADONLYwithoutpasswordprotection.
5.4
DisplayandIndication
5.4.1
AllrelaysshallhavealphanumericLCDdisplayalongwithLEDindicationsfordisplayofsettings,
status,faultsandevents.Ifgraphicaldisplayisspecifiedindatasheet/jobspecification,relay
shallhavegraphicdisplayformimic/motorstartingcharacteristic,setting,status,faultsand
eventsinplaceofLED/LCDdisplay.
5.4.2
5.4.3
LCDdisplayshallbebacklitandtemperaturecompensatedupto650Cforcontrastandlegibility.
Asaminimum,therelayshallhaveLEDindicatinglampsforFaulttrip,Relayhealthy,Relay
unhealthy,ControlsupplyON.
CEPL/10162/EL/DOC09
Page 5 of 16
PROJECT NAME
CUSTOMER
JOB NO.
5.5
ProtectionFunctions
5.5.1 OverCurrent/EarthFaultProtection
i) Thissectiondescribesovercurrent&earthfaultprotectionfunction,whichmainlyinclude
differentsettingstagessuchaslowset,highsetandhighsetinstantaneous(51,50,51N,
50N).OvercurrentprotectionfunctionprovidedshouldhaveIDMTLcharacteristicforlow
setandhighsetstagesanddefinitetimedelayforhighsetinstantaneousstage.
ii) Overcurrentrelayshallbethreephasetypewith4elements;3elementsforinverseand
definitetimedelayovercurrentandoneelementforinversedefinitetimedelayearthfault
current.Selectionofinverseordefinitetimefeatureshallbeuserselectable.
iii) TheIDMTLcharacteristic(for51and51N)shallbeasperIEC.Theinversecharacteristicshall
includenormalinverse,veryinverse,extremelyinverse,longinverseandshallbesoftware
selectable.Inverseelementshallhavetwoormorestages(lowandhighset)forselectionof
requiredinversecharacteristictoachievecloseprotectionasrequired.
iv) RelayshallalsohaveseparatecurrentinputfromCBCTforearthfaultcurrentelement.It
shallbepossibletoconnectearthfaultelementeitherthroughCBCTortobeconnected
residually.Minimumsettingcurrentforsensitiveearthfaultelementshallbe1%.
v) Directionalovercurrent&earthfaultelementshallbeprovided,whereverrequired.
vi) Voltagebiasedovercurrent/earthfaultelementshallbeprovidedwhereverrequired.
5.5.2 MotorProtection
i)
Motorprotectionrelayshallhaveallprotectionfunctionsuchasovercurrent,thermal(over
load),lockedrotorcurrent,zerosequence,maximumnumberofstart,motoroverloadpre
alarm,motorreacceleration,lockout,inhibitofovercurrentprotectionduringmotor
startingthroughcontactorfeeders,hourruncount,inhibitstartafterelapseofmaximum
numberofstartsetc.
ii) Therelayshallbeprovidedwith6Nos.RTDand2Nos.BTDanaloginputs,ifspecifiedinthe
datasheet/jobspecification.ThenumericalrelaywithRTD/BTDinputsshallbesuitable
forcablelength1000mbetweenmotorandswitchboard,usingshieldedtriadcableof
conductorsize1.5sqmmcopper,unlessotherwisespecified.
CEPL/10162/EL/DOC09
Page 6 of 16
PROJECT NAME
CUSTOMER
JOB NO.
iii) Inrelayswherecontrolfunctionareprovidedaspartoftherelay,contactsofpushbuttons
fromfieldandinterlocksfromDCSshallbewiredtotherelayasdigitalinputusing2.5sqmm,
multicore,copperconductorcables.Thedistancebetweenpushbuttons/interlockto
switchboardmaybeconsideredas1000m,unlessotherwisespecified.Theadditional
componentsasrequiredtoovercomethecablecapacitanceeffectshallbeconsideredasa
partofsupplyofrelay.Thedigitalinputtorelayfromfieldcontactsandinterlocksshallbe
momentarytype.Logictolatchthemomentarycontact,asrequiredshallbebuiltasapart
ofcomprehensivemotorprotectionrelay.
iv) Motordifferentialprotectorshallbeprovided,ifrequiredasperdatasheet/job
specification.
5.5.3 TransformerProtection
i)
Inadditiontoovercurrent&earthfaultfunction,whereverrequired,thenumericalrelay
shallalsoincludestandbyearthfaultprotectionfunction(51G)forthetransformer.The
standbyearthfaultshalloperatefromaseparateneutralCTinputandshallhavedefinite
time/IDMTLcharacteristicasperIEC.
ii) Whereverthetransformerrequiresrestrictedearthfaultprotection(64R),separate
numericalrelayshallbeprovided.64Rfunctioncanbeincludedasapartofmaindifferential
protectionrelay(87T),unlessotherwisespecified.
iii) Separateauxiliaryrelaysshallbeprovidedfortransformerauxiliaryprotection
(OTI/WTI/Buchholz/MOGetc.).Thesamecanalsobeincludedasapartofnumericalrelay,if
availableinVendorsstandardrelay.
iv) Transformerdifferentialprotectionshallbeprovided,ifrequiredasperdatasheet/job
specification.
5.5.4 GeneratorProtection
i)
ThegeneratorprotectionsprovidedforDieselEnginedrivenGeneratorsshallinclude
followingminimumprotectionfunctions,unlessotherwisespecified:
Voltagerestrainedovercurrent(51V)
StandbyEarthfault(51G)
Negativesequence(46)
ReversePower(32)
Undervoltage(27)
CEPL/10162/EL/DOC09
Page 7 of 16
PROJECT NAME
CUSTOMER
JOB NO.
Overvoltage(59)
Thermaloverload(49)
PTfusefailuremonitoringfunction(60)
GeneratorDifferential(87G)
ii) InadditiontotheabovethefollowingprotectionfunctionsshallbeprovidedforHV
generators(turbine/dieselenginedriven)<unlessotherwisespecified:
Rotorbackupearthfault(64R)1stand2ndstage
Lowpowerflow(37)
Lossofexcitation(40)
Underfrequency(81U)
Rateofchangeoffrequency(df/dt)
iii) Followingadditionalprotectionfunctionscanbeconsideredasapartofgenerator
protectionnumericalrelay,ifspecifiedinthedatasheet:
Fieldovercurrent
Overfrequency(81O)
BackupImpedance(21)
Overfluxing(99)
Outofstep
5.5.5
Thegeneratorprotectionfunctionscanbeincludedasapartofonenumericalrelayora
separatenumericalrelayscanbeprovided.
5.5.6 VoltageOperatedProtectionFunctions
i)
Thesefunctionsincludeundervoltage(27),overvoltage(59),ONdelayandOFFdelay
timers,phasesequencevoltage,neutraldisplacementandSynchrocheckfunctionsetc.
ii) Theundervoltageandovervoltageprotectivefunctionsshallhavedifferentstageswith
IDMTLanddefinitetimecharacteristics.
iii) Ifspecifiedindatasheet,therelayshallhaveunderandoverfrequencyprotection
functions.Rateofchangeoffrequencyfunctionshallalsobeprovidedwherespecified.
5.5.7 Differentialprotection
Suitabledifferentialprotectionshallbeprovidedasrequiredasperdatasheet/jobspecification
forthespecificapplicationsuchasforgenerator,transformer,overallgenerator&transformer,
CEPL/10162/EL/DOC09
Page 8 of 16
PROJECT NAME
CUSTOMER
JOB NO.
motor,feeder,bussectionetc.Thefollowingrequirements,asapplicable,shallbecompiled:
i) Differentialprotectionshallbeeitherhighimpedanceorlowimpedancetype.Incaseof
highimpedancetype,suitablenonlinearresistorshallbeprovidedtolimitthepeak
overvoltage.
ii) Transformerdifferentialprotectionshallhavesuitableharmonicrestraintfeaturetoavoid
maltrippingduringswitching.
iii) Fortransformerdifferentialprotection,necessarycorrectionforratioerrorandfor
transformerprimaryandsecondaryvectorgroupingshallbetakencareintherelayitself
withoutadditionalICTs.Therequiredrelaysettingforthisshallbeprogrammable.
iv) DifferentialrelayandREFrelayshallhavefeatureforCTcircuitsupervision.Busdifferential
relayshallbeprovidedwithfeaturehavingcheckdifferential.
v) Incaseseparatehardwiredrelayisusedforcheckdifferential,thestatus/eventofsameto
becommunicatedthroughthenumericalrelayprovidedformaindifferentialapplication.
vi) Unlessotherwisespecified,thedifferentialrelayssuchasgeneratordifferential,
transformerdifferential,overallgeneratortransformerdifferential,motordifferential,
feederdifferential,etc.shallbesuitableforcableconnectionbetweenCTsandrelayof
length1000musing2.5sq.mm.,Cuconductor,PVCinsulated,armouredcable.Howeverfor
pilotwiretypedifferentialprotectionsprovidedforfeedershavinglonglengths,shielded
twistedpaircableofconductorsize1.5sqmmcoppermaybeconsidered.Incaseswhere
specialcable(suchasfibreoptic)isrequired,sameshallbespecificallymentionedbythe
bidderintheofferforEIL/Ownersacceptanceoncasetocasebasis.
5.5.8 SpecialProtectionFunctions
Numericalrelaysforspecialprotectionfunctionssuchasdistanceprotection,check
synchronizing,autosynchronizingetc.shallbesuitablyselectedtomeetthespecificjob
requirements.
5.6
MeteringFunctions
Themeteringfunctionshallbeprovidedasrequiredandsameshallbebuiltinsidethenumerical
relaysifspecifiedinthedatasheet.
5.7
ControlFunctions
5.7.1
Thecontrolfunctionshallbebuiltinsidethenumericalrelays.Ifspecifiedinthedatasheet.For
thispurposerelayshallhaveallPLC/Booleanlogicfunctionssuchthatcompletecontrollogicof
thefeederalongwithallnecessaryinterlocksasrequiredcanbedevelopedinsidetherelay.
CEPL/10162/EL/DOC09
Page 9 of 16
PROJECT NAME
CUSTOMER
JOB NO.
5.7.2
Relaysformotorfeedershallbeequippedwithallcontrolfunctionsandinterlocksrelatedto
motorfeeder.Ifreaccelerationisapartofmotorfeeder,thecontrolfunctionshallalsocover
reaccelerationlogic.
5.7.3
RelayswithintegralcontrolfunctionshallhavesufficientI/Ostotakecareofcompletefeeder
logic.
5.8
LockOut(86),TripCircuitSupervision(95),AuxiliaryRelaysandTimerFunctions
5.8.1
Unlessotherwisespecifiedthenumericalrelaysshallhavebuiltinlockoutfunction.Formotor
feedersadditionalbuiltinlockoutrelayshallbeprovidedtoreceiveprocesstripsignals,if
specifiedinthedatasheet.Lockoutelementsshallbeselfresetorhandresetandshallbe
softwareselectable.
5.8.2
Thenumericalrelaysshallhavebuiltintripcircuitsupervisionfunction,unlessotherwise
specified
5.8.3
Auxiliaryrelays/Timersfunctionetcasrequiredforcontrolschematicsshallbeprogrammable
asapartofnumericalrelay.Thenumberofsuchelementsasrequiredforschematicshallbe
considered.
5.8.4
TimerfunctionshallbeprogrammableforbothON/OFFdelays.
5.9
Disturbance/EventRecordingandDataStorage
5.9.1
Breakertrip/closestatus,relayfaults,tripvalues,eventdataanddisturbancerecorddatashall
bestoredintherelayinnonerasablememoryormemorybackedupbylithiumbattery.Under
nocircumstancessuchaswithdrawalofpowertotherelayshallthestatus,dataandeventsin
thememorygeterased.Unlessotherwisespecified,itshouldbepossibletosaveminimum3
recordsofeacheventandthelastdisturbancerecord.Subsequenteventshallbeoverwritten
followingprincipleofFIFO.
5.9.2
Alldisturbances/eventsshallbetimestampedwithintherelay.
5.10
Input/OutputInterface,FiltersandGalvanicIsolation
5.10.1 RelayshallhavecurrentinputfromCTsecondaryratedeither1Aor5A.Itshallhaveflexibilityto
settherelayoperatingparameteras1Ampor5Ampthroughprogrammingorthroughhard
wiredselectionatsite.
5.10.2 Voltage(throughPT)inputtorelay,shallbe110V+/10%unlessotherwisespecified.
5.10.3 Outputrelayshallhaveatleast4NOcontacts;eachshallseparatelybeprogrammableforeither
handresetorselfreset.Thecontactratingshallbeminimum5Aat250VAC/DC.
5.10.4 Relayshallbemadeimmunetocapacitanceeffectduetolonglengthofcables.Anyexternal
CEPL/10162/EL/DOC09
Page 10 of 16
PROJECT NAME
CUSTOMER
JOB NO.
hardware,ifrequiredforavoidingmaloperationofrelayduetocablecapacitanceshallbe
includedasastandardfeature.
5.10.5 AllI/Osshallhavegalvanicisolation.Analoginputsshallbeprotectedagainstswitchingsurges,
harmonicsetc.
5.11
RelayCommunication
5.11.1 AllnumericalrelayshallhavesuitableRS232portonthefrontforhookinglaptop.
5.11.2 Attherearnumericalrelaysshallhavesuitablecommunicationportforcommunicationwith
dataconcentrator/MMI/Stationbus.Thetypeofportshallbeselectedbasedonmethodof
communication(SerialorEthernet)andtypeofphysicaltransmissionmedium(twistedpair
copperorfiberoptic).Forserialcommunication,therelayportshallbeRS485orFO(fiberoptic)
andforEthernet(IEC61850based)communicationsameshallbeRJ45orFO.
5.11.3 SerialCommunication
Communicationbetweenrelayanddataconcentrator/MMIshallbeprovidedeithertoachieve
nonredundantcommunicationarchitectureasspecifiedindatasheet:
i)
NonRedundantSerialCommunication
InNonRedundantserialcommunicationarchitecture,dataconcentratorshallhaveoneport
foreachrelayLANwithrelaysmultidroppedonLAN.Underthisconfiguration,relay
suppliershallensurethatdelinking/disconnectingofonerelayfromLANshallnotaffect
thecommunicationwithotherrelays.
AlternativelyrelaysshallhaveFOpartandshallcommunicateinstartopologyandshallbe
connectedtostarcouplerusingFOcables.
ii) DualRedundantSerialCommunication
InDualredundantserialcommunicationarchitecture,dataconcentratorshallhavetwo
serialports(1no.ineachCPUmodule)forsimultaneousremotecommunicationonrelay
LAN.TherelaysshallbemultidroppedonRS485throughsingledropfromLANtoeach
relay.IntheeventofeitherfailureofanyrelayorbreakinLANcableorfailureofportat
dataconcentrator,theredundanthardwareshallensurehealthycommunicationbetween
relayanddataconcentrator.
Alternativelyrelays,ifspecified,shallcommunicateinstartopologyusingstarcoupler.
Communicationfromrelaytostarcouplershallbethroughsinglecommunicationport.
Communicationfromstarcouplertodataconcentratorshallbethroughdualredundant
communicationlink(eachlinkpartofseparatestarcou0plerunit).RS485toFOconvertors
whereverrequiredshallbepartofofferedrelay,otherhardware.Starcouplershallbe
providedwithdualpowersupplymodule.
CEPL/10162/EL/DOC09
Page 11 of 16
PROJECT NAME
CUSTOMER
JOB NO.
5.11.4 IEC61850basedcommunication
i)
InIEC61850basedcommunicationnetwork,Ethernetswitchesshallprovideerrorfree
communicationinharshsubstationenvironmentandshallbeimmunetoEMI.The
EthernetswitchesshallcomplytoIEC618503andshallbeKEMAapproved.
ii) Forrealtimedeterministicperformance,managedEthernetswitchshallbeconsidered
intheEthernetnetwork.Theswitchshallsupportfollowingfeatures:
Fullduplexoperation
PriorityQueuing
VirtualLAN(VLAN)
RapidSpanningtree
Multicastfiltering
iii) Unlessotherwiseagreed,maximumfournos.numericalrelaysshallbehookedupto
Ethernetswitchand20%portsshallbekeptasspare.
iv) Communicationbetweenrelayanddataconcentrator/MMIshallbeprovidedeitherto
achievenonredundantcommunicationarchitectureasspecifiedindatasheet.
a) NonRedundantEthernetCommunication
InNonRedundantEthernetbasedcommunicationarchitecture,numericalrelays
shallbehookeduptoEthernetswitchinstartopology.FromEthernetswitchsingle
communicationlinkshallbeextendedforhookingdataconcentratorandMMI.
b) DualRedundantEthernetCommunication
InDualRedundantEthernetcommunicationarchitecture,thecommunication
networkshallhaveeitherfaulttolerantringorhybrid(star/ring)topology.In
Ethernetnetwork,Ethernetswitchshallhavedualpowersupplyfacility.
1. FaultTolerantRingTopology
Incaseofringtopology,numericalrelaysshallbehookeduptoEthernetswitch
instartopology.Theswitchesshallbefurtherconnectedinringanddual
redundantcommunicationlinkfromanytwoswitchesshallbefurtherextended
todataconcentratorandMMI.
2. FaultTolerantHybrid(Star/Ring)Topology
IncaseofhybridtopologynumericalrelaysshallbehookeduptoEthernet
switchinstartopologyandtheswitches(withintheswitchboard)shallbe
furtherconnectedinring.
Alternatively,fromeachswitch(withintheswitchboards)dualredundant
CEPL/10162/EL/DOC09
Page 12 of 16
PROJECT NAME
CUSTOMER
JOB NO.
communicationlinkshallbeextendedtotwonumberbackboneswitchestobe
locatedwithintheswitchboard.
Forhookinguptodataconcentrator/MMI,dualredundantcommunicationlink
eitherfromanytwoswitcheswithintheringorfrombackboneswitchesshall
befurtherextendedandhookeduptotwonos.masterEthernetswitches
dedicatedforhookingdataconcentrator/MMI.Fromdataconcentrator/MMI
dualredundantcommunicationlinkshallbeextendedtothemasterEthernet
switches.
5.11.5 Thecommunicationprotocolshallbeselectedtotransferallinformationincludingtimestamp
datafromrelaytodataconcentrator/substationMMI.Therelaysshallpreferablycommunicate
onindustryopenprotocolsuchasIEC608705103/IEC61850/ModbusRTU/TCPIPoranyother
openprotocol.ProprietaryprotocolshallrequirespecificapprovalofOwner/EIL.
5.11.6 ThemaximumnumberofrelaysinoneLANshallbedecidedsoastoachievemaximumscan
timeas500msforstatusinputand3to6secforanalogandhistoricaldataconsideringtotal
numberofserialloopandstarcouplerasatotalintegration.Theabovescantimedoesnot
includescreenrefreshrateatMMI.
5.11.7 Forsequenceofeventrecording,timediscriminationbetweentwoeventsshallbemaintained
to1msecorbetter.
5.12 DataConcentrator/DataCommunicator
5.12.1 Dataconcentrator,ifspecified,shallbesuppliedtofacilitatecommunicationwithrelaysonopen
protocol.ProprietaryprotocolshallrequirespecificapprovalofOwner/EIL.
5.12.2 Incaseofproprietaryprotocol,theprotocolconvertorshallbesuppliedasapartofdata
concentrator.Protocolconvertor,ifprovided,shouldnotaffectthespeedofcommunication.
5.12.3 Asaminimumdataconcentratorshallhaveseparatepowersupplymodule,CPUmoduleandI/O
module.Fordualredundantarchitecture,eitherseparatedataconcentratorshallbeconsidered
ordataconcentratorshallhavedualredundantpowersupplymoduleanddualredundantCPU
module.TheCPUmoduleshallhavesufficientcommunicationportsdependingonrelayLAN
requirement.
5.12.4 DataconcentratorshallprovidegatewaytoupperlevelcontrolsystemonEthernet/IEC61850
protocol/ModbusRTUprotocolorprotocolasspecifiedinthedatasheet.Thecommunication
toupperlevelcontrolsystemshallbedualredundantasperdatasheet/systemarchitecture.
5.12.5 Dataconcentratorshallhavedigitalandanalog(4to20mA)I/Ocardssuitableforinterface
requirementspecifiedindatasheet.Unlessotherwisespecified,20%I/Osshallbeconsideredas
spare.Alternatively,aseparateDataAcquisitionUnitmaybesuppliedfordigitalandanalog
CEPL/10162/EL/DOC09
Page 13 of 16
PROJECT NAME
CUSTOMER
JOB NO.
interface.
5.12.6 DataconcentratorshallhaverequirednumberofportsforrelayLAN/starcouplers.Numberof
relayLAN/starcouplersshallbeasperprojectrequirement.20%orminimum2Nos.spare
portswhicheverismaximumshallbeprovidedforfutureextensions.
5.12.7 DataconcentratorshallhaverequirednumberofRS232/RS422portsforconnectiontoLaptop
PCandsubstationMMIhavingoperatorsworkstationandengineeringstationPC.
5.12.8 DataconcentratorshallhavedualredundantRS485/FO/Ethernetportforcommunicationto
substationMMIandupperlevelECSRTU.Hookuptoupperlevelsystemshallbecarriedout
extendingserialconnectivityfromeachcommunicationportsintwoCPUmodules.
5.12.9 ThepowersupplytoDataconcentratorshallbesameasspecifiedfornumericalrelayandshall
besiteselectable.
ManMachineInterface(MMI)
5.13.1 FollowingfunctionsasaminimumshallbeapartofMMI:
DisplayofsinglelineDiagram
Feedersstatusmonitoring
Datalogging
Relayparameterization
Eventrecording
HistoricalData&trending
Annunciation
5.13.2 Manmachineinterfaceshallbeindustrialgradesuitableforcontinuousoperationatdesign
ambienttemperaturewithrestrictednaturalventilation.
5.13.4 MMIshallbeoflatestversionofindustrialgradePCandthesameshallbeprovidedwith21
colormonitor(TFTflatscreen)withnonglareglassfilterstominimizeglarefromexternal
lighting.
5.13.5 Operatorworkstationshallhaveuserfriendlysoftwareforinteractivedisplayofsubstationdata
inmultiwindowfeature.Softwareshallhavecapabilitytodisplaysubstationsingleline
diagrams,displayofelectricalsystemparameters,reports,alarmannunciation,dailyand
monthlydatalogging,continuouspolling,relaymonitoring,relaysupervision,faultdisturbance
recordofeachrelay,graphicrepresentationandtrendingofdataetc.theofferedsystemshall
complywithrequirementsofIECforbasicandsafetyrequirementsforHumanmachine
interface.
CEPL/10162/EL/DOC09
Page 14 of 16
PROJECT NAME
CUSTOMER
JOB NO.
5.13.6 Engineeringworkstationshallhavesoftwareforengineering,detailedselfdiagnosticfor
maintenance,troubleshootingandchangingparameters.Further,itshallalsohavefacilityto
programandconfigurenumericalrelays,dataconcentratorandotherintelligentdevices.In
additionengineeringworkstationshallhaveallthefacilitiesasprovidedforoperator
workstation.
5.13.7 Theoperatorworkstationandengineeringworkstationfunctionsmaybecombinedasrequire
asperrequirementasspecifiedintherequisition.Jobspecifications.
5.13.8 TheMMIsystemshallbeprovidedwithcolorlaserjetprinterforgeneratinghardcopyofalarm,
eventandloggingreport.Theprintingshallbeondemand,unlessotherwiseagreed.Incase
onlineprintingofalarmandeventsarespecified,separatedotmatrixprintershallbeprovided.
5.13.9 Ifspecified,separatelaptopshallbeprovided.Thelaptopshallincludeallfunctionalitiesas
specifiedforMMIsystemandthesameshallbeprovidedwithrequiredlicensedsoftware,
hardware,accessoriesandmaterial.Systemconfigurationshallbelatestprovenmodeland
upgradable.
5.13.10Oneno.singlephaseUPSofrequiredcapacityshallbeprovidedtofeedpowersupplytoMMI
andprinter.TheUPSshallbeequippedwithbypassfeatureandthesameshallincludesealed
maintenancefreebatterytodeliverbackuptimeofminimum30minutes
5.13.11MMIsystemshallbeprovidedwithallassociatedfurnitureforPC,printer,UPSetc.
5.14 TimeSynchronization
5.14.1 Allinternalclocksofnumericalrelay,dataconcentrator,SOEmodules,MMIetc.shallalways
workinsynchronismsuchthatthereisoneandonlyonesystemwidetime.GPSshallbe
consideredtosynchronizewithanexternalsatelliteclock.Thetimesynchronizationaccuracy
shallbe1.0msecorbetter.
5.14.2 TheGPSsystemshallconsistofGPSantenna,lightingarrestor,GPSreceiver/serverand
associatedcables.
5.14.3 Thetimesynchronizationshallbecarriedouteitherthroughcommunicationoversubstation
relayLANorbyconsideringdedicatedtimesynchronizationchannel.Incaseofsynchronization
throughrelayLAN,thecommunicationprotocolshallsupporttocarrytimesynchronization
messagetotherelays/dataconcentrator/MMIandmaintainthedesiredaccuracy.Incaseof
timesynchronizationthroughdedicatedtimesynchronizationchannel,relaysanddata
concentratorshallbeprovidedwithIRIGBportandthesameshallbedirectlyhookeduptoGPS
receiver.
5.14.4 InEthernetbasedcommunicationnetwork,GPSreceiver,shallbedirectlyhookedupto
EthernetLANandallinternalclocksofthedataconcentrator,MMIandnumericalrelaysshallbe
updatedusingSNTPprotocol.
CEPL/10162/EL/DOC09
Page 15 of 16
PROJECT NAME
CUSTOMER
JOB NO.
6.0
INSPECTIONTESTINGANDACCEPTANCE
6.1
RelaysshallhavebeentypetestedasperrelevantIndian/internationalstandards.Typetests
shallincludeasminimumbutnotlimitedtothefollowing:
6.1.1
Temperaturewithstand
6.1.2
Disturbanceimmunity
6.1.3
Electromagneticcompatibility
6.1.4
HVwithstandstestforinsulation
6.1.5
Impulsevoltagetest
6.1.6
FunctionaltestsandCommunicationintegrity
6.1.7
Relaycharacteristicsverification
6.1.8
Degreeofprotection
6.2
Mechanicalstress/vibrationtest.Duringassembly,ownerorhisauthorizedrepresentativeshall
bepermittedtoassesstheprogramofworkaswellasascertainthatqualityofrawmaterialare
usedforthesame.Allassistanceasrequiredduringinspectionshallbegiventoinspector.
6.3
Finalacceptancetestsshallbecarriedoutatmanufacturer/assemblersworksunderhiscarand
expense.Manufacturershallalsoarrangeinstrumentsandequipmentsasrequiredfortesting.
Ownersrepresentativeshallbegivenminimum2weekspriornoticeforwitnessingthetests.
Manufacturershallfurnishtestcertificateindicatingtestresults.Acceptancetestsshallinclude
visualchecks,insulationchecks,heatruntestsandfunctionaltestsasaminimumorasper
manufacturersqualityplan.
6.4
Incaseoffullyassembledandtestedrelayssourcedfromabroad,manufacturershallfurnish
type,routineandacceptancetestcertificatesalongwiththesupplyofnumericalrelaysfor
Ownersperusal.
7.0
PACKING&DISPATCH
Therelaysalongwithsixsetofdetailedcatalog,typetestcertificate,acceptancetestcertificate
shallbeshippedtoswitchboard/panelmanufacturerinworldclasspackingasper
manufacturersstandard.Therelayshallbedulyprotectedwithpolythenesheetsandpackedin
boxdulyfilledwithfilterstopreventdamage.NecessarywarningHANDLEWITHCAREshallbe
inscribedonthebox.
CEPL/10162/EL/DOC09
Page 16 of 16