FP 400e-3dc PDF
FP 400e-3dc PDF
400 Series
Electric
Pressure Control,
On-Off Deluge Valve
Model: FP 400E-3DC
Typical Applications
Optional Features
Petrochemical facilities
Marine environments
Remote monitor
Model: FP 400E-3DC
Operation
The BERMAD Model FP 400E-3DC is suitable for systems that include electric fire detection and a piping system with
a wide variety of open nozzles. Combining a pressure control feature, the FP 400E-3DC is recommended for systems
with high pressure supply source and/or relatively low flow.
In the SET position, the line-pressure supplied to both the main valves control chamber [1] and a 2-way Hydraulic
Relay Valve (HRV-2) [2] via the priming line [3] and through a Check Valve [4], an Accelerator [5] with priming
restriction, and a Solenoid [6], is trapped by the Check Valve, by the closed HRV, and by a closed Manual Emergency
Release [7]. The trapped pressure holds the main valves diaphragm and plug against the valve seat [8], sealing it drip
tight and keeping the system piping dry. The HRV is held closed by the line-pressure, supplied through the Solenoid.
Under FIRE condition, an electric signal triggers the Solenoid to open the HRV. Pressure is then released from the main
valve control chamber to the downstream, through the open HRV and the Pressure Reducing (PR) Pilot valve [9],
allowing the main valve to open, and water to flow into the system piping and to the alarm device. Should system
pressure rise above PR pilot setting, the PR pilot throttles, thereby enabling pressure to accumulate in the valves
control chamber. This causes the FP 400E-3DC to throttle closed, decreasing system pressure to PR pilot setting. The
Manual Emergency Release [7], overrides the PR pilot, causing the valve to open fully.
[6]
[4]
[5]
[2]
[7]
[3]
[1]
[9]
[8]
Engineer Specifications
The On-Off deluge valve shall be a UL-Listed, solenoid remote controlled elastomeric type globe valve with a
rolling-diaphragm.
The valve shall have an unobstructed flow path, with no stem guide or supporting ribs.
Valve actuation shall be accomplished by a fully peripherally supported, one-piece balanced rolling-diaphragm,
vulcanized with a rugged radial seal disk. The diaphragm assembly shall be the only moving part.
The valve shall have a removable cover for quick in-line service enabling all necessary inspection and servicing.
The control trim materials shall consist of St.St. 316 tubing and fittings, and plated brass accessories, including
Accelerator, 3-way Solenoid, HRV hydraulic actuated pilot valve, 2-Way Pressure Reducing Pilot, Y strainer and
Manual Emergency Release.
The control trim shall be supplied as an assembly, pre-assembled and hydraulically tested at an ISO 9000 and 9001
certified factory.
The Pressure Control and Solenoid Remote Controlled, On-Off Deluge Valve shall open and close in response to
activation of the solenoid, reducing higher upstream pressure to preset lower downstream pressure.
Model: FP 400E-3DC
System Components
1 - Main Valve, BERMAD FP 400E Series
2B - Accelerator with Priming Restriction
2R - Pressure Reducing Pilot
4B - Priming Strainer
7B - Check Valve
15B - Manual Emergency Release
18B - Priming Ball Valve
19B - Drip Check
24B - 3-Way Solenoid
26B - Hydraulic Relay Valve (HRV)
Optional
S - Valve Position Limit Switch / Switches
24B
26B
7B
2B
2R
4B
15B
18B
Hydraulic
Electric
UL Listed
The BERMAD Model FP 400E-3DC is UL-Listed.
The installation shall include Indicating and Drain Components.
Atmosphere
Model: FP 400E-3DC
Th
Technical Data
L1
L4
Tb
Ts
L1 (1)
1, 2
mm inch
205 8 1/16
2
mm inch
205 8 1/16
mm
257
inch
10 1/8
mm
320
inch
12 5/8
mm
415
inch
16 5/16
mm
500
inch
19 11/16
10
mm inch
605 23 13/16
12
mm inch
725 28 9/16
L4 (2)
205
8 1/16
N/A
N/A
250
9 13/16
320
12 5/8
415
16 5/16
500
19 11/16
N/A
N/A
N/A
N/A
Tw
228
220
11
8 /16
243
9 /16
253
10
312
12 /16
326
12 /16
346
13 /8
391
15 3/8
Ts
228
220
8 11/16
243
9 9/16
253
10
318
12 1/2
326
12 13/16
326
12 13/16
391
15 3/8
Th
226
8 /8
242
262
10 /16
261
10 /16
356
14
407
16
407
16
546
21 1/2
Tb
278
10 1/16
289
11 3/8
300
11 13/16
337
13 1/4
378
14 7/8
405
15 15/16
413
16 1/4
473
18 5/8
00
12
0
90
0
80
0
70
0
50
30
20
15
70
m3/h
13
Set
Va lue
30
Set Va lue
-2.0
-0.0
-0.3
-4.0
-6.0
-0.4
-0.7
-10.0
-12.0
11/2, 2
21/2
10
bar
-8.0
12
-1.0
-14.0
-16.0
-1.2
-18.0
00
50
00
40
00
30
00
20
00
12
80
0
60
-1.4
30
gpm
-20.0
20
psi
Connection Standard
Flanged: ANSI B16.42 (Ductile Iron),
B16.5 (Steel & Stainless Steel),
B16.24 (Bronze) or ISO PN16
Grooved: ANSI/AWWA C606 for 2, 3, 4, 6 & 8
Water Temperature
0.5 50C (33 122F)
Available Sizes
1, 2, 2, 3, 4, 6, 8, 10 & 12"
UL-Listed for sizes 1, 2, 2, 3, 4, 6, 8 & 10
Pressure Rating*
Max. inlet: 250 psi (17 bar)
Set: 30-165 psi (4.5-11.5 bar)
20
Notes:
1. L1 is for flanged ANSI #150 and ISO PN16.
2. L4 is for grooved end connections (Ductile Iron Only).
3. Provide adequate space around valve for maintenance.
4. Data is for envelope dimensions, specific component
positioning may vary.
90
12
0
Dimensions
Size
Tw
Optional Materials
Standard
3-Way direct actuated type
Brass body
Main valve closed when de-energized
Enclosure: General purpose watertight,
NEMA 4 and 4X / IP65, Class F
Power: 24VDC, 8 watts
UL - Listed
Options (see also ordering guide)
Hazardous locations:
Class l Division 1, Gr. A, B, C, D, T4 (code 7)
Class l Division 2, Gr. A, B, C, D, T4
ATEX, EEx d llC T5 (code 9)
Voltage: see ordering guide (voltage option table)
Stainless steel 316 body material (code K)