ABB Power Generation Guide
ABB Power Generation Guide
ABB, Inc.
in collaboration with Rocky Mountain Institute, USA
Table of contents
Introduction
Scope
11
12
Technologies Scope
12
13
14
14
14
15
15
15
16
16
16
17
17
18
18
18
Acknowledgements
19
Notice
19
20
20
Industry-Specific Terminology
21
Keywords
21
23
Module Summary
23
23
25
25
25
26
26
27
28
29
29
31
31
31
31
32
34
35
36
36
Facility Operators
37
38
39
40
40
41
41
41
46
Efficiency Calculations
46
46
Savings Calculations
47
48
52
53
Module Summary
53
53
54
54
56
56
Pump Characteristics
57
59
Table of Contents | 3
Table of Contents
60
63
72
73
76
Pump Automation
77
78
79
81
83
Fan Systems
84
85
Fan Characteristics
85
86
87
89
93
97
Fan Automation
98
98
99
101
102
103
103
HVAC Systems
104
104
105
106
111
Motor Characteristics
116
119
125
128
131
133
135
135
135
136
136
136
143
VFD Topologies
146
148
154
VFD Harmonics
156
157
157
VFD Maintenance
171
172
175
Module Summary
175
176
176
177
177
Electrical Power
177
179
Power Factor
Reactive Power Compensation Concepts
180
181
Motor Soft-Starting
182
VAR Compensators
183
186
187
Harmonics Concepts
187
Harmonics Mitigation
189
Table of Contents | 5
Table of Contents
193
193
194
195
195
196
196
198
201
201
Load Analysis
201
202
202
Harmonic Analysis
203
204
205
Power Transformers
205
Transformer Concepts
205
207
208
214
Transformer Retrofits
217
218
219
219
222
223
223
223
225
225
226
227
Module Summary
227
Automation Concepts
227
228
229
Process Instruments
229
Analytical Instruments
231
Process Actuators
231
Control Valves
232
233
Sequential Control
Feedback Control
Process Characteristics
Advanced Control and Optimization
Model-Based Control
234
235
236
238
239
Inferential Control
240
240
240
242
243
Supervisory Control
Performance Monitoring Systems
Condition Monitoring Systems
243
243
245
Rotating Machinery
245
246
Control Systems
246
246
248
250
251
253
253
253
254
255
258
259
Table of Contents | 7
Table of Contents
Boiler-Turbine Control
258
258
259
263
Combustion Control
265
268
270
Turbine-Generator Control
271
274
277
282
Burner Controls
282
282
Emissions Controls
285
Condenser Systems
289
Condensate System
292
295
Sootblowing Systems
297
298
299
Module Summary
299
299
301
302
304
304
304
304
306
Implementation Issues
306
307
308
311
311
312
313
315
315
316
317
318
319
Summary of Benefits
321
323
Module Summary
323
323
324
325
326
327
327
328
328
331
Module Summary
331
331
331
331
332
332
333
333
334
335
336
336
338
Table of Contents | 9
Table of Contents
339
341
Thermodynamic Cycle
341
342
Cycle Operation
342
Boiler Operation
343
345
References
349
On-Line Resources
353
Revision History
356
Introduction
Energy Efficient Design of Fossil-Fuel-Fired
Steam Power Plant Auxiliary Systems
It is the greatest of all mistakes to do nothing because
you can only do a little Sydney Smith (17711845)
Energy efficiency is the least expensive way for power and process industries to
meet a growing demand for cleaner energy, and this applies to the power generating
industry as well.
This auxiliary equipment has a critical role in the safe operation of the plant and can
be found in all plant systems. Perhaps the diversity of applications is one reason
why a comprehensive approach to auxiliaries is needed to reduce their proportion of
gross power and to decrease plant heat rate.
This handbook takes a comprehensive view of auxiliary systems and describes some
common approaches to energy efficient design which can be applied in retrofit and
new plant projects. This handbook reviews drive-power concepts, and provides
useful design and engineering guidelines that can help to improve energy efficiency.
The extent of these energy savings are shown in fully worked-out numerical
examples and in actual plant case histories throughout the text.
This handbook may be used as part of a training course for managers and
technical staff in operating and engineering service companies, and may also be
used in mechanical or electrical engineering university programs. This handbook
complements existing best practices for power plant engineering and is not a
substitute for detailed plant design and safety guidelines published by standards
bodies and industry associations. The relevant sources for detailed guidelines are
listed in the References section.
Introduction | 11
Scope
Technologies Scope
This handbook defines plant auxiliaries to include all motor-driven loads, all electrical
power conversion and distribution equipment, and all instruments and controls.
Process chemical and thermodynamic efficiency is not directly within the scope of this
handbook. The controllable losses which are within the reach of automation systems
are of interest, as are methods of recovering waste heat or energy from the cycle
using drivepower technologies.
Some industry sources may use the overly-narrow term auxiliary to refer only
to certain fan and pump systems. An overly-broad term that includes all auxiliary
systems (and much more) is balance of plant: (BoP). Starting from this level, we can
define three categories of auxiliary systems:
A subset of BoP that encompasses drive power components such as pumps, fans,
motors and their power electronics such as variable-frequency drives. These provide
drive power for fuel handling, furnace draft, and feedwater pumping. These systems and
components will be referred to as Drivepower.
A subset of BoP that encompasses only the electrical power systems conversion,
protection, and distribution equipment, excluding motors and variable-frequency drives.
This subset includes power transformers and LV and MV equipment. These systems
and components will be referred to as Eelectrical BoP (EeBoP) or Electric Power
Systems.
A subset of BoP that encompasses only the instruments, control, and optimization
systems. These provide boiler-turbine and other control functions. These systems and
components will be referred to as I&C or simply Automation
Some examples of auxiliary equipment from these categories are shown on the cutaway
view of a plant on the following page. A common aspect of auxiliary technologies is that
they handle all the electrical power and control signals throughout the entire plant.
All the technologies discussed are commercially available and the engineering practices
described in this handbook are non-proprietary. Some newer technologies and their
energy efficiency potential are reviewed in the final module of the handbook.
Figure I.1 - Plant cutaway showing location and type of auxiliary equipment (ABB Inc. USA Products
for Power Generation Industry)
Introduction | 13
The share of auxiliary drivepower of total plant power has been increasing for other
reasons too, mainly from the installation of mandatory anti-pollution equipment,
increased fuel variability, and general performance degradation due to the
accumulated effects of aging on plant equipment.
Introduction | 15
relative new plant contract prices. The following data is for power plants, but applies
to most other large process plants as well:
Fans and motors :
In large capital engineering projects, the early design phase accounts for just 1
percent of a projects up-front costs, but at that point up to 70 percent of its lifecycle costs may already have been committed (Lovins, 1999). Energy-inefficient
designs are then frozen-in, often for several decades in the case of large
process or power plants. Therefore, it is important for designers and engineers
to learn how to quickly review their energy design options and perform relative
cost analyses before the final design concept is firmly established; the focus is on
quickly, because that 1 percent time window is not very long at all. For example, in
a three year project, that window will be less than two weeks.
High
Investment
Design
review
Design
Audit
Modest
Investment
Energy
Audit
Low
Investment
Conceptual
Design
Detail
Engineering
Operation
Retrofit
& Upgrade
Figure I.2 - Investment return vs. project phase for energy design assessments
Introduction | 17
The market for learning about industrial plant energy efficiency is large and growing.
According to a recent survey of corporate energy managers (Johnson Controls,
2008), 70 percent have invested in educating staff and other facility users to increase
support for improving internal energy efficiency.
Commodity Product versus Custom Engineering
Many of the technologies that comprise plant auxiliaries are becoming less customengineered items and taking on more of a commodity status. This commercialization
of technology advances brings benefits to customers such as lower price,
shorter delivery times, and increased reliability. On the other hand, more complex
technologies, such as variable speed drives, may not be plug-and-play ready for
all applications. Operating and engineering staff need to learn to recognize these
situations so that commodity solutions can be still be applied successfully without
the deep involvement of supplier engineers. The guidelines and information in this
handbook provide a bridge between off-the-shelf auxiliary equipment, such as VFDs,
motors, and some DCS packages, and the plant applications they are supposed to
serve.
Industry versus Academia
Academic training of engineers is important, but there is also a history of technical
education for power generation and process industries within the engineering and
supplier industries. For example, ABBs Automation University, as well as GEs
Power Systems Engineering Course and its accompanying Design Guides, which
have been taught to practicing engineers for 60 years. and AspenTechs University
are all examples of the industry educating their own.
The fossil fuel plant version of this handbook assumes that the reader is familiar
with the basic design and operation of a fossil-fuel steam boiler. The Appendix
has a brief overview of sub-critical boilers main components and their function.
Acknowledgements
This handbook is the result of collaboration between ABB Inc., Power Systems
Division, and the Rocky Mountain Institute. Rocky Mountain Institute (RMI) is an
independent, entrepreneurial, nonprofit organization. Special thanks to Dr. Amory
Lovins, Chief Scientist of RMI for his valuable comments and inspiring work on
energy efficiency for industry, and for the opportunity to complete this work at RMI
offices in Snowmass, Colorado, USA. The RMI-Competitek DrivePower and Cooling
Manuals are an often-cited, valuable source of reference material for this handbook.
Thanks also to all the ABB engineers and scientists without whose contribution of
time and material this handbook would not have been possible; for automation:
Daniel J. Lee, Pekka Immonen, and Robert Herdman. For motors and VFDs:
Moledina M. Varvani, Dennis Kron, and Jiuping Pan. For electrical power systems:
Hamid SaharKhiz, Majid Rahimi, Brian D.Scott.
Special thanks to Richard W. Vesel of ABB Power Systems USA for his generous
support, technical guidance and encouragement, and to Arash Babaee of ABB
Power Systems Canada for his review and comments. The ABB Application
Guides were a valuable reference for this handbook, and have been frequently
cited, although no special permissions have been yet been sought for internally
copyrighted graphics and case examples from this ABB-owned material.
This handbook was written and edited by Robert P. Martinez at RMI, Snowmass,
USA while on sabbatical leave generously provided by the ABB Norway, Strategic
R&D department, led by John Pretlove. Thanks to Cameron Burns of RMI for copyediting the first draft and for being a friend during my familys stay at RMI. Final
editing, review and publication was carried out by Richard Vesel, with support from
program manager Milovan Grbic and marketing director Andy Gavrilos.
Notice
The information in this document is subject to change without notice and should
not be construed as a commitment by ABB. ABB assumes no responsibility for any
errors that may appear in this document.
In no event shall ABB be liable for direct, indirect, special, incidental or consequential
damages of any nature or kind arising from the use of this document, nor shall ABB
Introduction | 19
be liable for incidental or consequential damages arising from use of any software or
hardware described in this document. This document and parts thereof cannot be
reproduced or copied without written permission from ABB, and the contents thereof
must not be imparted to a third party nor used for any unauthorized purpose.
Copyright and Confidentiality
This handbook is published in two versions: one version will be made broadly
available to educators and other public consumers as part of Rocky Mountain
Institutes public service efforts to increase awareness of energy efficient design
though their 10xE program. Another version will be published internally by ABB and
may contain confidential portions not intended for wide circulation.
MPC
Model Predictive Control
MV
Medium Voltage (typically 2400V,4160V,4800V,13,800V)
NEMA
National Electrical Manufacturers Association
NPHR
Net Plant Heat Rate
POF
Planned Outage Factor
SST
Station Service / Startup Transformer
UAT
Unit Auxiliary Transformer
UCF
Unit Capability Factor
USC
Ultra Supercritical
VFD
Variable Frequency Drive
VSD/ASD Variable Speed Drive, Adjustable Speed Drive
UT
Unit (Step-up) Transformer
Industry-Specific Terminology
Backpressure power
Banked
Condensing power
Day/night loading
Dispatchable/mid-range
Frequency response
Heat rate
Shift loading
Spinning reserve
Unit
Keywords
Energy Assessment, Energy Efficiency, Energy Management, Generating Station,
Power Plant, Variable Frequency Drives, Transformers, Power Factor
Introduction | 21
Module 1A
The Need for Efficient Power Generation
Module Summary
This module makes the business case for energy efficient plant auxiliary systems and
discusses some trends in electricity markets and power generation technologies.
Agency, 2006). Integrated gasification combined cycle (IGCC) plants are not yet
competitive as of 2008 (which is why government is subsidizing many such projects).
Their low relative costs make coal-fired plants competitive in the U.S. with other
large central generating plants.
Figure 1A.1 Trends in energy consumption, (2007 BP Statistical Review of World Energy)
Many new coal plants were being planned or constructed as of 2008, but with
some uncertainty regarding the future trend due to carbon footprint and other
environmental concerns over current coal-fired plant technology. Regulations
imposing carbon dioxide emissions charges will eventually change the economics
in favor of CCGT and other more efficient fossil plant types. Even without emissions
taxes, the licensing of new plants is threatened by growing grass-roots opposition
at local and state levels. According to the US Department. of Energy (DoE), 59 of
151 planned new coal plants were either refused licenses or abandoned in 2007,
and 50 plants are being challenged in court. Environmental groups have successfully
challenged these new plants by arguing that the additional capacity could be gained
through energy efficiency and renewable sources of power. With the industry facing
a possible moratorium on new plants, it is more important than ever to make existing
plants as energy efficient as possible.
Whether limited by emissions or supplies, the fossil-fuel power generation industry
must sooner or later reduce the carbon per unit energy produced. The prominence
of coal means that it will play an important role in the transition to a low-carbon
future. Dr. Amory Lovins, a leading US energy analyst, anticipated the need for such
a transition many years ago when he said; It is above all the sophisticated use
of coal, chiefly at modest scale, that needs development. Technical measures to
permit the highly efficient use of this widely available fuel would be the most valuable
transitional technologies. (A. Lovins, Energy Strategy: The Road Not Taken 1976)
large supercritical boilers led to the conclusion that pulverized coal-fired electricity
generation was a mature technology, with an efficiency limited by practical and
economic considerations to around 40 percent. However, improvements in
construction materials and in computerized control systems led to new designs for
supercritical boilers that have overcome the problems of the earlier plants (IEA Coal
Online - 2, 2007). Although most new coal-fired plants are expected to use drum
steam boilers, the share of supercritical technology is rising gradually (International
Energy Agency, 2006).
Combined-Cycle Gas Turbine (CCGT)
A combined-cycle gas turbine (CCGT) power plant uses a gas turbine in conjunction
with a heat recovery steam generator (HRSG). It is referred to as a combined-cycle
power plant because it combines the Brayton cycle of the gas turbine with the
Rankine cycle of the HRSG. The thermal efficiency of these plants has reached a
record heat rate of 5690 Btu/kWh, or just under 60 percent.
Some Steam Plants are Lagging
At the beginning of the 21st century, it was believed that a single-cycle coal-fired
power station with an efficiency of more than 50 percent would be possible by 2015
(Kjr and Boisen, 1996 in IEA Coal Online - 2, 2007). The efficiency of some new
design plants may be high, but almost 75 percent of the existing coal-based fleet of
plants in the U.S. is over 35 years old, with an average net plant efficiency of only
slightly above 30 percent (Ferrer, Green Strategies for Aging Coal Plants, 2008).
In addition to the less efficient design of core equipment, these older plants suffer
an additional efficiency handicap due to plant aging; they become less reliable and
generally less efficient due to leakage, fouling, and other mechanical factors. Another
trend which lowers efficiency is the change in fuel supply systems toward off-design
coals for which the boiler has not been optimized (IEA Coal Online - 2, 2007). Fuel
supplies may be subject to further tweaking as generating companies seek to reduce
their carbon footprint by substituting a portion of the coal they use with biomass.
Another important reason that older plants are lagging in efficiency is that many of
them are operating at 3050 percent below their rated capacities, where efficiencies
of all sub-systems are lower. The realities of a more deregulated and competitive
marketplace, with renewable and distributed energy sources and new system
operating reserve requirements, have led to previously baseloaded plants being
operated as dispatchable plants; an unforeseen operating regime (ABB Power
Systems, 2008). One view of this latter issue is the global distribution of load factor
of nominally baseloaded steam turbine plants less than 500MW for the period 2001
2005. The following figure shows that the median load factor is only 64 percent.
Figure 1A.2 - Distribution of load factor of base-loaded plants, (World Energy Council, 2007)
greater than in drum boiler designs. Increased demand for auxiliary power increases
a plants net heat rate and reduces the amount of salable power.
Module 1B
The Potential for Energy Efficiency
Technical Efficiency Improvement Potential
A recent study by the International Energy Agency (IEA) suggests a technical
efficiency improvement potential of 1826 percent for the manufacturing industry
worldwide if the best available (proven) technologies were applied. Most of the
underlying energy-saving measures would be cost-effective in the long term. Another
study, by the U.S. Dept. of Energy, focused on the energy efficiency opportunity
provided by automation and electric power systems in process industries. An
improvement potential of 1025 percent was suggested by industry experts, who
were asked to consider improvements within the context of operational or retrofit
situations. The results of that study are shown in the figure below, and in more detail
in the Automation module sections of this handbook.
Figure 1B.1 - Process industry survey results on potential of energy efficiency, (US DoE, 2004)
Module 1B | 29
The World Energy Council (WEC), through its Performance of Generating Plant
(PGP) Committee, is now gathering and normalizing such data so that valid
comparisons can be made across countries and markets.
Similar performance benchmarking efforts are done in the U.S., but through
industry-funded organizations like EPRI. Standardization efforts are best
represented by IEEE Std 762-2006 IEEE Standard for Definitions for Use in
Reporting Electric Generating Unit Reliability, Availability, and Productivity.
Interestingly, the WEC found that new drivers geared toward profitability,
cost control, environmental stewardship, and market economics are shifting
the focus away from traditional measures of technical excellence such as
availability, reliability, forced outage rate, and heat rate (World Energy Council,
2007). Their PGP database has added individual unit design and performance
indices that can be used to compare efficiency and reliability across designs.
The published performance data will help industry improve practices, and will
put a spotlight on under-performing plants and companies.
Efficiency Potential Revealed by Country Comparisons
The potential for energy efficiency, at least from a U.S. perspective, is also
indicated in a recent (2007) comparison of fossil-fuel-based power generation
efficiencies between nations that together generate 65 percent of worldwide
fossil-fuel-based power. The Nordic countries, Japan, the United Kingdom,
and Ireland were found to perform best in terms of fossil-fuel-based generating
efficiency and were, respectively, 8 percent, 8 percent and 7 percent above
average in 2003. The United States is 2 percent below average. Australia,
China, and India perform 7 percent, 9 percent and 13 percent, respectively,
below average. The energy savings potential and carbon dioxide emissions
reduction potential if all countries produce electricity at the highest efficiencies
observed (42 percent for coal, 52 percent for natural gas and 45 percent for
oil-fired power generation), corresponds to potential reductions of 10 exajoules
of consumed thermal energy and 860 million metric tons of carbon dioxide,
respectively (Graus, 2007).
The IEA analysis mentions that more than half of the estimated energy and
carbon dioxide savings potential is in whole-system approaches that often
extend beyond the process level (Gielen, 2008). Integrative Design is this
handbooks approach to the most challenging energy efficiency issues in plant
auxiliary design.
Module 1B | 31
China and India account for four-fifths of the incremental demand for coal, mainly
for power generation. For the first time, Chinas carbon dioxide power emissions in
2008 exceeded the United States emissions; the lower quality coal used in India and
other rapidly expanding economies, decreases plant efficiency and leads to increased
carbon dioxide emissions per unit electricity (International Energy Agency, 2006).
Figure 1B.2 Relative share of CO2 mitigation efforts, all consumption, (International Energy Agency,
2006)
When the model is applied to process industries alone, the impact of energy
efficiency is proportionately larger. The figure below shows the blue scenario,
which uses the same ACT scenario describe above, but with a higher carbon
dioxide charge of $50 per (metric) tonne, instead of $25/tonne (Taylor, 2008).
Figure 1B.3 - Relative share of CO2 mitigation efforts in process industries, (Taylor, 2008)
Applying this model to the power generation sector in particular suggests that
its carbon dioxide emissions are cut by 36 percent using all of the approaches
shown. Half of those savings (18% of total) can be attributed to relatively lowtechnology energy efficiency measures alone.
Energy efficiency measures are the most important of all the carbon dioxide
mitigation approaches for process industries, contributing to almost half of
the impact on emissions (Martin, 2004). Although these predictions apply to
process industries, the relative potentials are likely to be valid for the steam
power generation sub-sector as well.
Module 1B | 33
Power plants which operate partially or wholly at full load will have more salable
power. At less than capacity, the fuel savings are significant. In coal-fired steam
power plants, fuel costs are 60-70% of operating costs.
Tax creditstake advantage of newer policies such as EPACT 2005, which may
provide tax credits for efficiency efforts. Similar policies are in effect in the EU and
China.
Mainstream industry authority Engineering NewsRecords influential Top Lists
rankings now include Top Green Design Firms and Top Green Contractors:
The market for sustainable design has passed the tipping point and is rapidly
becoming mainstream (http://enr.construction.com/).
Increasingly, shareholders and capital markets are rewarding companies who treat
their environmental mitigation costs as investments (Russel, 2005).
Retrofitting may save some older plants from early retirement due to noncompliance with regulations such as the EUs Large Combustion Plant
Directive on pollution (nitrous oxides, sulfur dioxide, mercury, and particulates)
(International Energy Agency, 2006). In the US, increased compliance may
smooth permitting of new units or plants.
All of the dirty dozen in Carbon Monitoring For Actions (CARMA) list of
top carbon dioxide emitting sources in the U.S. are coal-fired power plants,
emitting an average of about 20 million tonnes of carbon dioxide per year
per plant. Blacklists like these, which include rankings by company as well,
are increasingly being consulted by large institutional investors and sovereign
wealth funds. With tightened credit markets, there is therefore an even
greater incentive for top management to watch carbon dioxide emissions.
See the section on Benchmarking for other global efforts toward increased
transparency.
start. The recent Functional Safety standards IEC-61508 and 61511 point the way
forward for energy design and management standards evolution.
Many of the barriers listed below are managerial or procedural rather than technical
in nature. These important non-technical aspects are discussed in the final module of
this handbook. The discussion is generic for most large power and process facilities,
but a specific industry will have additional competitive and regulatory pressures.
Local, State, National and International Regulatory Authorities
Authorities provide the regulatory framework for the activities of all the other
stakeholders. The efforts of authorities are closely linked with those of the standards
organizations. These factors, however, may contribute to inefficient plant designs:
Regulations often permit pass-thru of all fuel-related costs directly to the rate
base. This financially discourages any economization efforts related to fuel
consumption, i.e. efficiency.
Lack of clarity, unity and commitment to emissions charging makes investors wary
of long-term investments in energy efficiency and/or carbon dioxide emissions
reduction.
Deregulation and the ensuing volatility in fuel and energy prices may also
discourage the long-term thinking necessary to make some efficiency and carbon
dioxide emissions reduction schemes justifiable.
Shareholders & Investors
The observations in this paragraph regarding shareholders and investors apply
mainly to new construction or large-scale redevelopment projects. See the following
paragraphs for barriers more applicable to facility owner/operators of older plants
and retrofit project contexts. Shareholders and investors often influence project
schedules, contract clauses, functional specs for new construction and major
retrofits of plants. These factors, however, may contribute to plants that are
ultimately energy inefficient:
Project schedules are compressed; front-end design and concept studies are
underfunded or curtailed.
Scope of redevelopment projects is narrow because investors generally want
to avoid changes to the long remaining lifespan of the standing capital stock
(International Energy Agency, 2006).
Designs are frozen early by a pre-established milestone date, even if important
data may be missing.
Cost analysis methods are too crude, or not coupled tightly enough to the
conceptual process design, or have wrong initial assumptions regarding risk,
return, and lifetime; calculations may ignore significant indirect costs and savings
such as substitution costs, maintenance savings, and peak energy prices.
36 | ABB Energy Efficiency Handbook
Operational energy costs may be treated as a fixed cost and therefore receive
much less attention than a variable cost.
Low-bid, fixed-price contracting without strong, well-defined and enforceable
energy performance guarantees, at the plant, unit and equipment levels.
Purchasing managers seek multiple suppliers to reduce cost; this strategy leads
to increased design and data fragmentation. Purchasing managers may still prefer
individual vendors versus full-service/system integrators.
Energy-expert consulting companies are usually the last to be hired, and therefore
have much less influence over the conceptual design.
Drawings are issued for construction before even the first vendor drawing is
seen, much less approved (Mansfield, 1993), leading to hasty, often energyinefficient re-design at the interfaces.
Capital scarcity might favor smaller plants with lower efficiency (Gielen, 2008).
Facility Operators
Facility Operators craft the original specifications, validate the design during
commissioning and acceptance trials, determine operational loading and
maintenance of facility, and usually initiate and manage retrofit projects. These
factors, however, may contribute to plants that are ultimately energy inefficient:
Retrofit projects to improve energy efficiency are funded from operating budgets,
not from larger capital expenditure budgets; payback expectations and discount
rates are all generally much higher than in green-field projects.
Managers focus on optimizing process productivity, in which energy is only one
of several other cost functions and may not receive the consideration it deserves;
many modern plant-wide optimization systems optimize for productivity, which
only indirectly improves energy efficiency.
There is a war for money between process improvement and energy efficiency
camps in a typical plant; process improvement teams and their measures seem to
get more respect.
An increasing number of plants are centralizing purchasing, which means less
engineer involvement in purchasing decisions. Since purchasing centralization
weve seen companies shift away from using a lifecycle cost model, which seems
very short-sighted to us. Some of the decisions customers have been making are
committing them to a stream of ongoing expenses that could have been reduced.
(Control Engineering article 8/15/2005).
Facility operators receiving a new/retrofitted plant/unit are under-pressure to begin
operations as soon as possible so they are therefore less critical with respect to
energy targets during acceptance tests.
Facility operators do not or cannot operate plant at design capacities due to
changes in market or other factors.
Module 1B | 37
Plant engineering and maintenance teams are losing experienced older staff;
facility operators do not provide adequate training for staff on energy efficiency.
Power plant/power house energy managers (superintendents or maintenance
directors) lack the necessary communication and salesmanship skills to push through
good energy efficiency proposals. (a post on J. Cahills blog, 2007).
Reluctance to admit non-optimal, energy inefficient, operation to upper
management the perception is that this reflects badly on plant management and
their plant operations team.
Fear of production disruptions from new equipment or new procedures to improve
efficiency (International Energy Agency, 2006); doubts about safety, controllability
or maintainability
Expansion projects will simply duplicate an existing unit on the same site,
repeating many of the same design mistakes, to reduce the up-front engineering
hours; low-labor copy-and-paste projects may also overlook opportunities for
rationalization & integration with the existing unit(s).
Design and Engineering Companies
Design and engineering companies determine design specs of facility, select
components and execute the design. These factors, however, may contribute to
energy inefficient plants:
A tendency to oversize pumps, fans, and motors by one rating, and oversize them
again after handoff to another discipline, and then again by project leaders:
Bottom limits in standards already have a safety margin, but these limits
are interpreted as a bare minimum (from fear of litigation) and an additional
safety margin is added.
Overload maximums received from process engineer are interpreted by
mechanical and electrical teams as continuous minimums; fat margins are
added in lieu of detailed loading study.
Additional margins are then added for future, but unplanned, capacity
increases.
Engineers on auxiliary systems are inordinately fearful of undersizing and risk
being singled out as the bottleneck that prevents operation at full design
capacity of other, more expensive, hardware
Large, commodity motors and fans are commercially available only in discrete
sizes. After all the margins, an engineer will choose the next size up if the
design point falls between two sizes.
A tendency to aggressively reduce engineering hours to increase margins on
fixed-priced contracts and to avoid selecting premium components for such
contracts.
Trade-offs between floor space and pipe/ductwork efficiency are not life-cycle
cost-estimated; civil and architectural concerns are the default winners due to
their early head start in most projects.
Trade-offs between reliability and energy efficiency are not life-cycle costestimated. Higher energy costs are seen as insurance against large, but virtual
opportunity costs.
Lack of energy design criteria and efficiency assessment steps in the standard
engineering workflow. There is typically a design optimization step for cost, safety,
reliability, and other concerns, but not for energy efficiency.
Shortage of engineers in key industries; junior and outsourced engineers are
making higher-impact decisions.
A reluctant to deviate from their standard design templates, especially on
expansion projects where the design has been delivered on previous units. This
leads to short cuts and uncritical copying-and-pasting of older, non-optimal
designs.
Engineers work mainly within the confines of their discipline and do not see
opportunities for inter-disciplinary optimization of the total design. For example:
Mechanical engineers miss out on optimizations from chemical engineering
to use waste heat and to optimize plant thermodynamics or create useful
by-products.
Process engineers do not leverage the full potential of automation, selecting
instead familiar equipment like valves to perform control tasks better suited to a
variable frequency drive.
Electrical engineers do not fully understand the process needs for power, such
as duty cycles, and therefore do not fully optimize their designs.
None of the engineers mentioned above are typically very quick to leverage
advances in materials science, which enable higher operating parameters.
Equipment Vendors and Design Tool Providers
Equipment Vendors and Design Tool Providers determine component energy
efficiencies. The vendors tools directly affect the engineers workflow, models, and
documentation. These factors, however, may contribute to energy inefficient plants:
Vendors provide black-box components with closed/proprietary/rigid interfaces,
which are not easily optimized for the whole system; this is the result of a trend
toward commoditization.
Proliferation of design tools and data formats which are non-integrated and their
design model is non-navigable between vendor tools; this hinders integrative
design.
Lack of full-scope energy-optimization functionality in the leading design and
modeling tools
Module 1B | 39
Module 1B | 41
Other sources of objective standards are the professional societies and industry
associations, although the latter may show more bias toward their industry in certain
situations:
Many standards for steam-water cycle design of cycle equipment can be found
in the various ASME and NFPA codes, but these are not within the scope of this
handbook. The ASME test codes for determining efficiency, however, are of interest.
Energy is a political as well as a technical subject; some associations (not those
mentioned above) promoting best practice are actually lobby groups with strong,
but not obvious, links to commercial or political entities with various agendas. These
sources can be useful if their advice is taken together with the objective sources
listed above. Some of these unofficial sources of design guidance are listed in the
Reference section of this handbook. The following list is not a comprehensive list
of all relevant standards; appearing here are only those that have some relevance to
plant auxiliaries energy performance and design.
Best Practices
DoE EERE Best Practice guides for Steam, Pumping Systems, Fans www1.
eere.energy.gov/industry/bestpractices
EPRI studies and reports there is a large population of useful reports
ABB Electrical Transmission and Distribution Reference Book (the T&D
manual)
Module 1B | 43
Module 1B | 45
Hours
% of Full Load
5%
400
100
10%
800
90
15%
1200
80
20%
1600
70
20%
1600
60
15%
1200
50
10%
800
40
5%
400
30
0%
20
1 00%
8,000 hrs
Weighted Avg 65
A more accurate view of annual energy consumption for the above components
profile is the sum of the energies at each load level:
Annual Energy (kWhr) = (hrs) at load level(i) x (%) full load at load level(i) x full
load (kW)
Duty cycle is similar to load profile, but is used to refer to shorter time periods (days
or hours) and for cycling (on-off) loads, rather than more continuously variable loads.
Energy and Power Units
Energy has many forms and can be described using many units. The most common
units and their conversion factors are given in the Appendix.
1 horsepower (hp) = 0.7457 kW = 2546 Btu/hr
Savings Calculations
Savings calculations are used to determine the difference in energy and cost
between two components or systems.
By combining the formulas above, one can compare the annual savings of energy for
two components or systems of varying efficiency E1(%) and E2(%). The result is an
energy saving (Se) in kW per year (assume 8,000 hrs in absence of data):
Annual Energy Savings (kWhr) = 0.746(kW/hp) x P(hp) x 8,000 x 100(%) x (1/E2
1/E1)
Module 1B | 47
One can then multiply by the cost of energy (in $/Kwh) to determine the financial (or
capitalized) cost of the annual energy savings calculated above, in $:
Annual Dollar Savings ($) = Se (kWh) x Q ($/kWh), where Q is the price per kWh of
electricity
In these calculations the price (Q) of energy is assumed to be constant. In fact,
energy prices may change as often as every 15 minutes in a de-regulated market,
with much higher prices during peak periods. The average annual price of electricity
shows a rising trend. See the section on present value for methods to account for
this change.
Lifecycle Costing Methods
Life-cycle costing (LCC) is a method of calculating the cost of a system over its
entire lifespan. LCC is calculated in the same way as total cost of ownership
(TCO). A technical accounting of systems costs includes initial costs, installation and
commissioning costs, energy, operation, maintenance and repair costs as well as
down time, environmental, decommissioning and disposal costs. These technical
costs, for an example transformer, are listed below.
n
For systems that directly emit carbon dioxide or other pollutants, the cost of
operation should include remediation costs, and the taxes which authorities charge
(or may charge) per unit of emissions. For electrical loads powered from a fossil-fuelbased source, the carbon dioxide amounts (in tons) are still relevant, but the carbon
dioxide tax (in $) should not be added to that components operational costs if the
tax has already been factored into the price of the consumed electricity.
Present value (PV) of a future amount (FV) at period n in the future at i interest
rate is:
PV = FVn x 1/(1 + i)n
Present value of a uniform series of payments, each of size US (for Uniform Series):
PVus = US x ((1 + i)n - 1 )/i(1 + i)n
Where i is the interest rate from 0-1 (for a 6% rate, i = 0.06)
The formula for PV of a uniform series can be used to determine the value of annual
energy savings, where the annual cost is calculated as shown at the start of this
section.
If the average annual price of electricity rises at p% per year, then the flat rate Q
must be multiplied by the following rising price factor f:
f = (qn 1) / (q 1)
Where: q = 1 + p/100
And p is the price increase in %
Using the formula for a 1 kW loss after 20 years shows an accumulated cost which
is 41 times the cost of the first year if the average annual increase in the energy price
is 7 percent (ABB Ltd,Transformers, 2007).
Payback Calculations
If the PV of the energy savings over n periods (years) exceeds that of the
investment cost (X), then the investment should be made. The number of periods
required for PV to equal X is the payback period. For a given value of X, therefore,
the payback period n can be calculated.
The monetary value of energy losses, called the capitalized loss value, is defined as the
maximum amount of money the user is willing to invest to invest to reduce losses by 1 kW.
Levelized Cost Calculations
For non-uniform payments, use the levelized cost (LC) method to determine the
levelized amount. This method simply uses the PV formula on each amount to
determine the total PV of the stream, then applies the inverse of the PVus formula
to determine a levelized amount for each period. To evaluate projects, one can use
either the total PV or the LC method. Both will reach the same conclusion, except
that the LC shows a comparison by period. In evaluating energy efficiency project
alternatives, it may be useful to calculate the capital equivalent cost (CEC). The
CEC is found by adding the capital cost to the PV of all the operating costs over the
units lifetime. This calculation provides a sound basis for comparing bids.
Limitations of PV Methods
Present value methods make assumptions regarding lifetime (number of periods n)
and discount (interest) rate i which have a large impact on the calculated value. In
evaluating energy efficiency projects or components, the conventional assumptions
tend to undervalue the savings. High-quality, high efficiency motors, for example,
may have a longer lifespan (n) than standard motors. Also, the lower risk of energy
efficiency projects should be reflected in a lower discount rate, especially in common
comparisons with new capacity. This comparison is between negawatts (energy
efficiency) and Megawatts (new capacity).
Module 1B | 51
Module 2
Drive Power Systems
To the optimist, the glass is half full.
To the pessimist, the glass is half empty.
To the efficiency engineer, the glass is twice as big as it needs to be.
Module Summary
This module describes the impact of design and engineering on the energy-efficiency
performance of auxiliary drive power systems; motors, fans & pump systems, and
variable speed drives.
This section examines drive power systems from an energy efficiency perspective only
and does not provide guidance on critical aspects of drive power engineering such as
safety interlocking or fault-tolerant design. See the References and Standards sections
for more complete guidance on all other aspects of drive power design & engineering.
Module 2 | 53
This handbook module offers design and engineering guidelines that may help prevent
some of this energy waste in new and retrofitted power plants and industrial process
applications.
Pump Systems
An entire pumping system is a network of fluid handling components such as pumps,
valves, pipes and tanks. The purpose of the pumping system is to provide a certain flow
and pressure to the fluid needed by the process unit.
Pump Types and Concepts
There are many different pump types, but two basic categories are 1) kinetic and 2)
positive displacement. Positive displacement pumps are more suitable for constant flow
applications. Where there is flow variation, then kinetic pumps like the centrifugal (also
known as rotodynamic) and axial flow (also known as turbine type) pumps discussed in
this section, are more suitable. See the References section for sources of information
on other pump types, applications and standards.
Figure 2.2 - Centrifugal pump system and internal design, ABB Drives, 2005
In a centrifugal pump, the fluid enters the pump at the impeller eye, the center of the
pump. This is the suction part of the pump. The rotating impeller imparts velocity
(kinetic energy) to the fluid as it is accelerated along the impeller blades and squeezed
through the narrow volute, at right angle to its line of entry. As the volute cross-section
area increases, the fluid velocity decreases and a higher pressure (head) develops
towards the discharge end of the pump.
In an axial pump, the fluid is accelerated by the action of a propeller and moves parallel
to the axis or shaft of the pump. In mixed flow pumps, the impeller uses both radial and
axial motion to accelerate the fluid along a path that exits the pump at an angle with the
pump axis or shaft.
Pump Characteristics
The performance of the pump is given by pump curves, which show how much pressure
(Head) can be developed at various flow rates (capacities) at a given speed. Note that
Head (H) has units of length (ft.) but is actually a measure of a fluids energy per unit
weight. The distance refers to the height that a column of the fluid could support under
gravity. A useful approximate conversion formula between Head and psi is:
H (ft) = ( H (psi) x 2.31 ) / Sp
H (m) = (H (kp) x 9.8) / Sp
Module 2 | 57
Axial-flow pump performance curves are steep, meaning that they can deliver
nearly constant flow over a wide range of pressure. Centrifugal pump curves are
much flatter, meaning that they can provide a range of flows over a relatively narrow
pressure range.
They normally make the biggest contribution to the plants in-house energy
consumption. Another estimate for boiler-feedwater pump consumption is
around 15 MWe on a 600 MWe plant, or around 2.5% of gross power (Goodall,
1981).
In power plants, the typical margins over this published NPSHR values may run
from 50% to100% for a complex boiler feedwater (BFW) system with transient
suction condition operations. Particular attention to NPSH margin should be
given to boiler feedwater system where load rejection and system transients
are expected, (Black & Veatch, 1996)
The suction requirements of BFW pumps are sometimes met by specifying a
lower-head booster pump upstream of the main BFW pump.
head have curves starting at the zero point. Systems with high friction have steeper
curves. Systems with low friction but high flow requirement will have flatter curves.
The figure below shows the pump curve for a typical centrifugal pump as well as the
system load curve for the head and flow it must deliver. The pump will operate at
the values of head and flow where the two curves intersect, known as the operating
point, where supply meets demand.
If two pumps operate in parallel, their pump curves are added horizontally, giving
a single equivalent pump curve with higher capacity, but with heads the same as
one of the pumps operating singly.
If two pumps operate in series, then their characteristic curves are summed
vertically, to give a single equivalent pump curve with higher heads, but capacities
the same as one of the pumps operating singly.
H (Head)
Pump curve
Operating point
Friction
losses
System curve
Static
& pressure head
Q (flow)
Figure 2.3 Pump head vs. flow performance and system curves
kW = (Q x H x Sp) / 6128
Where:
Q = capacity: in GPM (Gallons Per Minute)
H = total developed head (ft)
60 | ABB Energy Efficiency Handbook
(l/min)
(m)
(water = 1)
Pump input power required (also known as Brake Horsepower: (BHP) is the water
horsepower divided by the pump efficiency: Eff
BHP = WHP / Eff
For estimation of efficiency (using SI units) in centrifugal pumps with developed head
(H) between 15 to 100m water and flowrate (Q) between 20 and 300 cu.m/hr one
can use the following pump model (Rajan 2003) which has a standard error of about
1%:
Eff (%) = 65.08 x H -0.12446 x Q0.094734
Affinity Laws
Pumps of similar design but different impeller sizes can be compared by using
the pump affinity laws. These affinity laws (see below) below describe the relation
between the rotational speeds of the pump (n), flow rate (Q), head generated (H) and
power absorbed (P) by the fluid:
For a given speed, a pump curve has an operating point where efficiency is
maximum, referred to as the Best Efficiency Point (BEP). The region of high efficiency
close to the BEP is called the bullseye. Designers strive to make this the actual
operating range for the system, as this will reduce both energy and maintenance
costs. When the operating point moves away from the BEP , then relatively more
brake horsepower (input power) is required per unit water horsepower output.
Module 2 | 61
1480 r/min
60
h=71%
h=85%
h=83%
1184 r/min
40
30
150
Operating points
Power kW
Total Head m
System curve
h=83%
1350 r/min
50
1480 r/min
1350 r/min
1184 r/min
100
50
0
200
400
600
800
Rate of Flow m3/h
m: meter
kW: kilowatt
1000
1200
Figure 2.5 Variable speed pump performance curves, (US DoE Sourcebook, 2006)
Due to the similarity of the efficiency and system curves, there is little loss of
efficiency when a pump operates at lower rotational speed. The new operating
point is still in the pump efficiency bullseye, its ideal operating region for that speed.
Pump efficiency curves at the BEP do not change significantly with pump speed
62 | ABB Energy Efficiency Handbook
within the family of pump performance curves. When speed is reduced by half of
the rated speed, pump efficiency at the new speeds BEP may only be reduced by
3%, for example. Pump efficiency is relatively unchanged, but the decrease in power
consumption at the lower pump speed is substantial.
H (Head)
Pump curve
BEP
Efficiency
BHP
Q (flow)
Recall that pumps and fans are cube-law applications because their power
consumption varies with the cube of the speed of the pump or fan.
This relationship yields large power savings even from modest speed reductions,
and favors designs that seek to reduce speed, such as using Variable Speed
Drives (VSDs). See section on Pump Flow Control Methods.
The cube law also strongly favors selecting the right size of pump for the
operating conditions. See section on Pump System Design & Engineering for
guidelines on correct pump sizing.
Designers can also benefit from selecting high efficiency pumps, which are generally
4% to 7% more efficient and may cost little or no more than standard efficiency
pumps. Using a lifecycle approach, super-efficient pumps are even more cost
effective. Efficiency varies widely with pump type and flow range; according to the
Hydraulic Institute, the pump efficiency of large single-stage end-suction pumps
operating at their BEP and at flow rates in the 100 cu.m/h range is 81%.
Pump Flow Control Methods
Some of this section is adapted from the application guide: Using Variable Speed
Drives in Pump Applications (ABB Oy. Drives, 2006)
The process system will usually require variable flow rates from the pump. There
are four common methods to control the output of a pumping system: Throttling,
Module 2 | 63
Bypassing, On-Off, and Variable speed control, as shown in the figure below.
Variable speed control may be achieved by motor frequency modulation using a
Variable Frequency Drive, or by using gears and hydraulic couplings.
Figure 2.7 - Common flow control methods, (ABB Oy) Drives, 2006)
The relative power consumption of the different control methods can be estimated
from the area between the x and y-axes and the operating point on a pressure-flow
curve as shown in the figure below. This comparison is based on the formula for
pump power (P): flow x head (P=Q x H). In the example shown, the relative power
consumption for an average flow rate of 70% (of full flow) is calculated using typical
values for the different flow control methods.
Throttling
Flow control can be achieved by modulating a valve immediately downstream from
the pump. Throttling effectively changes the process system curve seen by the
pump: the valve introduces friction into the system; this makes the system curve
steeper so that it intersects the pump curve at the lower, desired flow rate, as shown
in the top left chart in the figure below. In this example, the operating point is moved
from (Q = 10, H = 10) to (Q = 7, H = 12.7). The relative power consumption can be
calculated by P = 7 x 12.7 = 89.
This method has low capital costs, but throttled systems waste energy in two main
ways: pressure drop across the valve, and because at reduced capacity the pump
performs below its optimum efficiency point.
Figure 2.8 - Energy efficiency impact of various flow control methods, (ABB Oy. Drives, 2006)
In power plants, excess pump and throttling energy is not entirely wasted in
applications that call for heating of the fluid anyway; as is the case in boiler
feedwater regenerative heating. There are three reasons to avoid using such
indirect heating to justify continued use of throttling control:
Higher maintenance costs of the pump operating far from its BEP
A highly-oversized valve will operate in a nearly closed state, which is not
stable. This situation arises in constant speed pumping systems where each
layer of engineering bureaucracy adds its own safety margin in calculating
pressure drops through pipes, heat exchangers etc. and then, finally,
in selecting the pumps. The control valve ends up with all these safety
margins, as added pressure drops. (Liptak, 2005)
Module 2 | 65
Most importantly, for high pressure systems such as power plant boiler
feedwater, is the severe wear on valve components from throttling at 2,400
psig (16.5 MPa) (Black & Veatch, 1996)
Bypassing
Although not commonly used for flow control, bypassing (also known as
recirculation) is applied mainly to circulation duty pumps. The flow output to the
system is reduced by bypassing part of the pump discharge flow to the pump
suction. Flow through the bypass system is controlled by valves. This means that the
total flow increases (from 10 to 12.4), but the head decreases (from 10 to 6.6). The
relative power consumption is P = 12.4 x 6.6 = 82.
A minimum flow recirculation system is sometimes necessary if the pump operates for
extended periods at low flow rates, when the pressure is too low to induce adequate
flow into the system. Recirculating flow wastes energy and should therefore be kept
to a minimum. Automatic modulating control of the recirculating flow system will
ensure that that the recirculation flow control valve only opens when measured pump
flow drops below a certain minimum threshold. Recirculating systems are sometimes
required on systems equipped with variable speed flow control to guard against low
flow conditions. The drive logic of a VFD speed controller may also be programmed to
warn operators and to shut off the pump in these cases.
In power plants, this type of pump control may be used in boiler feed
and condensate pumping systems to provide flow control and to prevent
overheating of the pump at low flow rates. (Black & Veatch, 1996)
Another reason why designers may add a recirculating flow loop is to keep the
pump at a higher state of readiness for increased demand. An improved design
may make use of any existing, smaller and more responsive startup pump
instead of a recirculation loop.
On-Off Control
On-off control is often used where stepless control is not necessary, such as
keeping the pressure in a tank between preset limits; in these applications, the pump
is either running or stopped. The average flow is the relationship between the on
time and the total time, on plus off. The relative power consumption can then be
easily calculated by P = 0.7 x 100 = 70.
Figure 2.9 - Energy efficiency impact of various flow control methods, (ABB Oy. Drives, 2006)
In power plants, boiler feedwater (BFW) pumps are driven by one or more, or
combinations of: squirrel cage induction motor, synchronous motor, mechanical
drive steam turbines, or gear drive from main shaft of turbine. Traditionally,
pump drivers have been selected focusing on reliability at the expense of
efficiency due to their critical role in the steam cycle. Ref ABB Drives. There
Module 2 | 67
have been several studies (Black & Veatch 1996, EPRI 1995, ABB 2008) to
compare the different options for pump drivers (prime movers) on base-loaded
pulverized coal steam power plans, and the effect on net plant heat rate.
In all studies the option with a constant speed motor-driven BFW pump using
throttle valve control is the least efficient, wasting significant energy at loads
<100% throttle flows. The two basic options involving speed control are sliptype adjustable speed drives and non-slip VFD drives.
In all options except the VFD there is likely a need for mechanical reducing gear
if the pump has a design speed greater than the motor rated speed. Reducing
gears are efficient, but still lose up to 1.5% of the input shaft power. For an
8MW pump, this loss represents almost 1GWh lost per year.
In all studies, the VFD option to vary motor output speed achieved better net
turbine heat rate and better turbine output at all throttle flows when compared
with speed control via slip-type hydraulic coupling. (Black & Veatch, 1996)
A third option is the steam turbine-driven feed pump. This pump is driven
by a condensing turbine that takes steam extracted from the IP/LP turbine
and exhausts to the main condenser. The disadvantages of this type of drive
arrangement are the extra valving and piping, plus added complexity in startup,
requiring an additional startup electrical motor. The VFD alternatives output
does not directly depend on the available steam flows, which vary with loading
and season.
In the comparison between the different drivers, a slightly better heat rate is
achieved with the turbine driven alternative. At the cost of more valve and
piping complexity, the turbine exhaust may be used in feedwater regenerative
heating, further enhancing the viability of this alternative.
Still another design option, found in some older plants, is a main turbine shaft
drive. These require variable speed coupling for speed control and gears,
plus an additional startup electrical motor. (Homer M. Rustebakke, GE Utility
Division, 1983). The added complexity and lower reliability has made this
design less common on newer plants.
A comparison of the above four BFWP drive alternatives was done for a
500MW unit with 2 x 50% capacity BFPs in parallel (Black & Veatch 1996).
The comparison was done at 3 different load rates: 100, 75 and 50% throttle
flow and considers net turbine heat rate (NTHR) and electrical output (NTO).
In that comparison, the VFD alternative offers better NTHR and NTO than the
68 | ABB Energy Efficiency Handbook
hydraulic coupling alternative, at all throttle flows. At 50% load, the throttle
alternative has bhp=14,459 (10.8 MW) whereas the VFD alternative has bhp=
9,185 (6.9 MW).
This difference is a substantial 36% improvement, representing a net
reduction of 3.9 MW continuous power consumption.
Case Example
Helsinki Energy, Finland
Helsinki Energy is one of the leading experts in the world in the field of
Combined Heat and Power (CHP) technology and one of the biggest energy
companies producing and distributing electricity and district heat in Finland.
Helsinki Energys Hanasaari B power plant is located by the seaside in the
city of Helsinki and has a capacity of 220 MW for electricity and 445 MW for
Module 2 | 69
district heating. The power plants efficiency is 85%. In 1990 Helsinki Energy
was granted the UN International Environmental Award for its pioneering
and determined work in developing CHP technology and the consequent
improvement of the citys air quality.
Originally, the Hanasaari power plants equipment was selected among the
best available technologies at the time of construction to fulfill the requirements
of high availability and efficiency. However, since the time of construction,
variable speed drive technology had taken a big leap forward. Even though
the old ASEA and Strmberg wound-rotor motors with slip recovery control
systems operated very well, Helsinki Energy decided to upgrade them in order
to reduce maintenance work and to further improve the plants efficiency. Given
the efficiency problem of boiler feedwater pumps driven by fixed speed motors
at partial loads, the most economic control is achieved with a variable speed
drive system. The boiler feed-water pump is rated at 4500 kW (6050 hp).
In the spring of 1999, Helsinki Energy ordered from ABB four water-cooled
ACS 1000 drive systems with AMB 560 motors and oil-immersed 3-winding
supply transformers. The Hanasaari B power plants automation upgrade
project was executed together with Helsinki Energys Helen Engineering that
specializes in the design of energy production and distribution equipment
as well as in the related project management. The aim of these design and
construction services is to support the profitability of business operations
throughout the life cycle of the equipment.
Boiler feed-water pumps are one of the biggest energy consumers in a power plant.
Operating feedwater pumps with variable speed drives can significantly increase the
efficiency of a power plant. Outside the boiler feed-water pumps nominal range, the
capacity needs to be sufficient to handle rare but possible abnormal situations in a boiler
that operates under very high pressure. Depending on the local authorities requirements,
the pump, and the supplying drive, must be capable of delivering 10-25 % over pressure
70 | ABB Energy Efficiency Handbook
or overflow. As a consequence, the drive operates practically all the time under partial
load, a situation where a variable speed drive offers the best available efficiency.
Using ACS1000 variable speed drives as level control devices for feedwater drums
can reduce maintenance of the feedwater throttling valves. These havent necessarily
been designed for the full pressure differential resulting from throttling the flow with
fixed speed motors. Further savings can be achieved by designing a new generating
units electricity distribution network for feedwater pumps operated by Variable
Frequency Drives. As main loads, their across-the-line starting behavior typically
impacts on - depending on impedance of the plant transformer- capital cost, either
through a more expensive transformer, through higher fault currents, or a more
expensive switchboard. Variable speed drives as such act as soft starters and cause
no starting current peaks. The ACS1000 can be connected via the most common
fieldbuses to become an integral part of the plants control system. Original case text
from ABB Switzerland , MV Drives, 2008.
Case Example
Power Losses in KW
300
Fluid Coupling
250
Energy
Savings
200
150
Speed Range
100
50
VFD
0
3567
3645
3724
3850
3976
4150
4322
A European power plant was comparing fluid coupling with AC drive for its feed
pump (1,450 kW) control. The comparison shows that within the speed range
needed, the AC drive consumed about 150 kW less than the fluid drive.
Energy saving: about 1,200,000 kWh/year
Reduction in CO2 emissions: 600,000 kg/year (660 tons)
Reduced reactive power
Reduced stress to the supply
Reduced need for maintenance
Case text provided by: (ABB Oy. Drives, 2006)
Module 2 | 71
Taken together, all the above effects make the efficiency of an average length
industrial, rough-walled, average diameter pipe typically about 69% (deAlmeida,
2006). Using low friction piping techniques can increase the efficiency of piping to
90%.
Engineers may also tend to oversize pumps so that the ratio between minimum
and maximum energy loss is not large. This means that the gain will not change
much with load (Liptak, 2005), making their control task easier, but at the expense
of wasted energy. Pumping system authorities provide these additional sizing
guidelines for selecting a centrifugal pump in combination with a VFD:
For a system with some static head, a pump should be chosen such that the
maximum flow rate is slightly to the right-hand side of the best efficiency point
(BEP). The exception is for a constant flow regulated system, in which case the
recommendation is to select a pump that operates to the left of BEP at maximum
pressure. This approach optimizes pump operating efficiency (US DoE, 2008).
Recall that the combined performance characteristic of a multiple pump system can
be determined as follows:
Pumps operating in series have a combined performance curve which is calculated
by adding the individual curves vertically, providing increased total head.
Pumps operating in parallel have a combined performance curve which is calculated
by adding the individual curves horizontally, providing increased total flow.
The advantages (right-sizing, reliability) of using multiple pumps must be weighed
against some additional costs; the extra equipment requires additional cabling,
piping and space. Isolation or check valves between multiple pumps in parallel may
be necessary to avoid fluid flow through inactive pumps. The LCC analysis of this
configuration should also consider the generally lower efficiency of smaller motors
compared to larger ones. The direct on-line (DOL) motors will also incur a power
factor penalty, compared to using a VFD for speed control on a single larger motor.
The reliability advantage of parallel pumps, each controlled with a VSD, is that if one
pump fails, the remaining pumps can continue uninterrupted.
Pump Automation
Proper control of multiple pump arrangements is essential to realizing their full
energy saving potential. Pump priority control balances the operating time of all
the pumps in the system over the long term. This can boost energy efficiency by
Module 2 | 77
operating pumps closer to their best efficiency point according to the required flow
(duration curve or actual signal) and pump capacities.
Pump automation is important to take advantage of the speed control provided by
VFD-equipped pumps. The applications are varied, but one common design uses
signals from flow or pressure transmitters as input to a feedback loop, which then
modulates the output to the VFD. The desired flow or head setpoint is provided
by a unit-level control system. In head-controlled systems, differential pressure
transmitters (PDTs) are commonly used to provide the pressure drop across unit
loads. For proper head control, the placement of PDTs must span the target load
plus the additional loads incurred by piping and valves. If the unit has a common
supply header to supply multiple loads, then the ISA recommends that pressure
transmitters for this header should not be located near any major load junctions.
In some multiple pump systems, a VFD-driven pump is combined with a constantspeed pump. In these cases, automation can be used to provide additional flow
control on either (or both) sides of the constant speed pumps BEP. For low-flow
control when the VFD pump approaches its maximum speed, then a switch or signal
will auto-start the constant speed pump. According to the ISA guidelines (ISA 2005),
extra increments of pumping capacity are started by pressure (when demand is
increasing), but stopped by flow (when demand is decreasing).
See the section in Automation module on Feedwater Control systems for a
description of typical pump automation applications in power plants.
Pump System Design Guidelines - Summary
Sources for this section are RMI (Lovins A. 2007), the US DoE EERE (US DoE Best
Practices, 2008) Pumping Tip Sheet, Hydraulic Institute and Europump.
Reduce Static & Pressure Head and Flow Requirements
Gather data to understand the actual loading requirements, especially the duty cycle
and load profile of the pump.
Consider process design or operational control alternatives that reduce the
maximum and average flows and static or pressure head required.
instead of flow throttling; see the section on sliding pressure control in the
Automation module of this handbook.
slip is generally lower if high-efficiency motors are used; the extra rotational speed
from a motor efficiency retrofit must be accounted for in the new application design.
Startup Conditions
The inertia of centrifugal pumps is normally small enough to be ignored where the
prime mover is an induction motor. However, this inertia should be considered
together with motor pull-in torque requirements if a synchronous motor is used.
Torque developed by an induction motor varies roughly with the square of the
applied voltage. Voltage drops during startup of large motors may lead to insufficient
startup torque. On most true centrifugal pumps, closing the discharge valve will
reduce the power requirement during early startup. On axial pumps the opposite is
true, so the discharge valve should remain open during startup. On mixed design
pumps, the discharge valve is opened at some point during startup, when axial
behavior begins to dominate (IEEE, 2007).
The reduced torque demand will make it less likely for the electrical engineer to trade
away optimum running efficiency for a design with high starting torque capability.
Pump startup against very high static head or system pressures will increase the
starting torque requirements of the prime mover, which is most often an electric
motor. If the process allows it, then any method should be used to reduce a high
startup torque requirement.
In power plants, the check valve on the boiler feedwater pump discharge line
isolates the pump from boiler drum pressure during startup to at least 70%
full speed. When the check valve opens, torque and speed demand increases
rapidly, the 10% margin of motor over load torque may disappear and startup
may not succeed (IEEE, 2007). The concern over long startups and overheating
may prompt the electrical engineer to trade away optimum running efficiency
for a design with high starting torque capability. The inrush of power late in the
startup may lead the engineer to oversize other power system components,
such as a unit auxiliary transformer, at the expense of lower continuous
operating efficiency.
In some plant designs a motor-driven startup boiler feedwater pump is specified.
This is a requirement for steam-turbine driven main BFW pumps, but has
advantages even when the prime mover is an electric motor. Depending on its
design, this pump may also be used outside of its startup role to provide additional
capacity and response. (Black & Veatch 1996). Turbine driven pumps have lower
See the Power Systems, Transformer section for details on transformer sizing
for startup and the Motor Startup section for details on motor sizing for reduced
voltage startup.
Power Factor
The chosen speed control method also has a significant impact on power factor
(PF). Lower PF leads to oversized power supply equipment and reduced efficiency.
The following figure shows how PF suffers when a motor operates much below its
rated speed, as is the case in throttling flow with a control valve.
Figure 2.11 - Effect on PF of different flow control methods, (ABB Motors & Drives, 2004 S. Weingarth)
The ABBs PumpSave calculation tool estimates the energy and cost savings when
using variable speed AC drives compared to other flow control methods (throttling,
ON/OFF, and adjustable speed using hydraulic or other slipping type drives).
Many pump manufacturers support their products with power and efficiency
calculation tools.
Fan Systems
Industrial fan systems in the US annually consume 78.7 billion kWh of electricity,
representing 15 percent of the electricity used by motors (US DoE Sourcebook,
2006). An entire fan system is a network of fans, dampers and/or inlet guide vanes,
and ductwork. The purpose of the fan system may be to provide a certain flowrate
of air, or to maintain a partial vacuum. Fans can supply large volumes of air, up to 1
million cubic feet per minute, but typically only at low pressures.
In power plant combustion processes, the largest demands for auxiliary drive
power come from the ID and FD fans. Typically, FD and ID fan motors consume
enormous amounts of energy in a plant, with motor sizes approaching 14 MW
to 18 MW in many larger plants. When a boiler is operating at non-peak loads
and the traditional fan-motor-damper system is in use, a good deal of energy is
wasted in the fan/motor combination. If a 15 MW motor is wasting 20 percent
of its energy due to inefficient flow control, that waste amounts to 3 MWh during
each hour of operation. At current prices, that equates to roughly $100 an hour.
At 5,000 hours a year of operation, it represents a half-million dollar loss.
In power plants, fans used to supply combustion air are termed forced
draft (FD) fans, and fans used to exhaust combustion flue gases are termed
induced draft (ID) fans. Primary air (PA) fans supply air to carry an air+fuel
Module 2 | 85
mixture through ducts to the burner nozzle (or fuel bed) and on into the steam
generator. Together, all the fans electric drive power may add up to 2-3% of the
plants rated output.
Single stage (one rotor/blade set) axial fans are typically used in FD service
on balanced draft steam generators. FD fans are sometimes referred to as
blowers. If a centrifugal fan is used, then it is likely to have backward curved
blades for improved efficiency.
Axial fans in ID service have higher pressure needs that require a 2-stage fan.
Axial fans with variable pitch blades are expected to be used more often in
ID service, due to more stringent emission control requirements. A lowered
particulate count can reduce some concerns associated with axial fan blade
fouling (Black & Veatch, 1996). If a centrifugal fan is used instead of an axial
fan, then it is likely to have forward-curved blades. The higher stack pressure
drop due to emissions control equipment has led to increased horsepower
requirements of ID fans and booster fans. The ID hp is typically doubled by the
addition of a wet limestone scrubber, with some units requiring up to 4 times
more horsepower (GE Utility Division, 1983).
On larger plants, all these fans are typically configured in pairs working in parallel,
mainly for reasons of redundancy. See section on Multiple Fan Systems for more
details.
Fan curve
Pressure
BEP
Efficiency
BHP
Flow
Figure 2.14 -Typical fan performance curve, showing efficiency and power relationships
(kW = kPF/EFFm)
mechanical efficiency, %
airflow, cubic feet per minute
total pressure rise across the fan, inches of water
compressibility factor, dimensionless
brake horsepower
(m3/sec)
(millibar)
(kW)
Values for k depend on the absolute inlet and outlet pressures. Using a range
of typical k factors, the mechanical efficiency of different fan types and designs
can be calculated:
Centrifugal fan; forward-curved blade
45-60%
Centrifugal fan; radial-tipped blade
60-70%
Centrifugal fan; backward-curved blade 75-85%
Centrifugal fan; airfoil blade
80-90%
Axial flow fan
85-90%
Ref : (Babcock & Wilcox, 2005)
Static pressure (SP) is often used instead of total pressure in discussing fan
performance. Fans are rated by either their total efficiency or their static efficiency.
For large fans at design speed, most of the fan total pressure is in the form of static
pressure, so the difference between the two efficiency measures is small.
The Affinity Laws for fans are the same as for pumps, but with an additional factor to
account for change in air or gas density. Fans, like pumps, are cube-law applications
whose power consumption increases with the cube of fan rotational speed.
Fan System Load Curves
The system of ducts, elbows, dampers etc. create a resistance load that is
proportional to the square of the volumetric flow. When plotted as Pressure vs. Flow,
the system load curve has a parabolic (quadratic) shape. In reality, the pressure
drops are slightly greater, and the curve slightly steeper, due to losses in flow
irregularities such as vortices and swirls (US DoE Sourcebook, 2006).
Module 2 | 87
Pressure
Fan curve
Operating point
Efficiency
System curve
Flow
Figure 2.15- Typical system load curve, showing efficiency and power
Supply fans generally work against a system back pressure, while return fans
exhaust to low-pressure i.e.: the atmosphere. The system curve for supply fans is
therefore typically shifted higher up the vertical axis than that of return fans. In high
constant pressure systems, the system curve is shifted vertically up the pressure
axis and is flatter at operating flows.
In power plants terminology, the supply fans are the Primary Air (PA), Forced
Draft (FD) and the Gas Recirculation (GR) fans which supply air to the furnace
chamber. The return fans are the Induced Draft (ID) and FGD booster fans.
Designs with both FD and ID fans are termed balanced draft plants, and the
balance point of zero gauge pressure is the furnace.
FD fans must develop pressure to overcome system resistance in ductwork,
air heater, burner or fuel bed and the furnace itself. FD fans must supply
enough flow to serve needs of fuel combustion plus flow lost due to air leaks
in the heater and other areas. FD fans draw fresh air and therefore are more
vulnerable to density changes due to outside air temperature change than ID
fans. Colder, denser air increases the mass flow and power requirements.
Fan Stability
At low flow, there may be no clear intersection of the fan and system curves, and
thus no clear stable operating point,. This causes unstable operation in which the
fan pulsates as it hunts back and forth for an operating point, reducing the energy
efficiency and increasing the wear on fan components. On most fans, this unstable
region occurs to the left of the maximum pressure point, so fans should always
88 | ABB Energy Efficiency Handbook
operate to the right of that point. Pulsation is more likely in fans whose pressure rise
exceeds 10 in. of water. (ISA, 2005)
These unstable modes are more likely to occur in variable speed operation at
very low speeds, or when outlet dampers are throttling the flow to create high
backpressure conditions, or in multiple parallel fan systems operating at low flow
rates. If a VFD is used for flow control, then it can be easily programmed to avoid
these areas of operation.
Pipes, Ducts and Elbows
Resistance pressure drops vary generally with the square of the flow rate. Some
additional useful rules of thumb for energy-conscious designers of ductwork:
Pressure drops along ducts vary roughly with the fourth power of the duct
diameter and are responsible for much of the total system resistance. Even small
increases in diameter will have a large impact on energy efficiency of the system.
Energy is wasted in irregular flows such as swirls and vortices. Elbows, especially
near fan inlet or outlet, cause especially high losses, decreasing the flow by up to
30% (US DoE Sourcebook, 2006). These resistances are also known as system
effects.
Round ducts have less surface area per unit of cross-section, and smoother flow
compared to ducts with square cross-sections.
Fan Flow Control Methods
When centrifugal fans are required to operate at variable loads, the pressure and
flow may be controlled by one of the following methods:
Inlet dampers
Inlet guide vanes
Outlet dampers
Two-speed motor control
Variable speed control by VFD or hydraulic coupling methods
When inlet dampers and guide vanes are partially closed they create a pre-swirl in
the direction of rotation of the fan. This motion reduces the relative velocity of the air
with respect to the fan blades and therefore reduces the fan capacity and pressure.
(Black & Veatch, 1996)
Inlet guide vane control is more efficient than inlet dampers due to reduced friction in
creating the pre-swirl movement.
Module 2 | 89
Outlet dampers are least efficient of all methods; they throttle the airflow to remove
power supplied by the fan. As outlet dampers close, the system curve becomes
steeper, intersecting the fan curve at the required lower flow rate, and at a point
below the fans BEP.
Vane or damper control is highly non-linear, and little control is possible near the fullopen position
Inlet guide vanes are more effective on forward-curved than backward-curved fans;
an important consideration in some retrofit situations (Competitek, 1995). The struts
and actuators needed for inlet guide vanes obstruct flow and will slightly reduce
efficiency.
In power plants, VFDs are an increasingly popular solution for variable speed
control, but ID fan speed control in may also be achieved by other means, such as
single-speed motors with variable speed fluid couplings. The relative performance
and merits of these alternatives in are explored in the Pump Flow Control section,
but the conclusions apply generally to most fan applications as well.
Axial fan control is provided by variable pitch fan blades whose angle can be
changed in real-time to adjust the load on the fan. The effect of variable pitch fan
blade has a similar effect as inlet guide vanes on the flow. In large applications, the
blade pitch is changed using hydraulic actuators. If speed changes are infrequent,
then manually adjustable pitch blades or belt-drive systems with different diameters
may be used, but these methods require the fan to be at standstill for some time.
The efficiency of variable pitch fan control is similar to that of VFD speed control,
but the increased number of moving parts and decreased motor efficiency at offcapacity loading make a VSD an attractive alternative, even on axial fans. In large
two-speed induction motors, typically, the low speed is selected for the most
common operating point and the higher speed for all the higher loads. Switching
between speeds in large motors, however, is neither trivial nor smooth and may lead
to process transients and upsets.
Some power generating plants that have experienced problems with speed
changes simply keep the fan at high constant speed with consequently higher
energy loss. (Black & Veatch, 1996), due to the sensitivity of furnace conditions
to fan pressure fluctuations. Also, if the 2-speed fan has been oversized, a
very common engineering practice, then it is likely that the top speed will
never be used.
Figure 2.16 - Input power for different centrifugal fan control methods, (ABB Drives, 2005)
In power plants, ID fans are ideal candidates for VFD control, as the following
short case histories illustrate. Axial ID fans in particular, with their inherently low
turndown capability and steep pressure vs. flow curves compared to centrifugal
fans, are also well suited for VSD control. Good control can be achieved either
by VFD motor speed control or by variable pitch blades, which have a good,
nearly linear response.
In PC plants, the relatively high and constant system pressures (mostly due
to the windbox and burner pressures) to be overcome by PA fans over a large
range of flow, may make them less attractive for VSD speed control. PA fans
are typically matched and packaged together with the burner assembly and
may therefore not lend themselves to retrofit engineering.
Module 2 | 91
Case Example #1
Power Plant, UK
The ID fans at a UK power plant (200 kW + 150 kW) were running at full speed
with flow control by dampers, but as the boiler ran at low loads for long periods,
management believed that energy could be saved with variable speed control. When
variable speed AC drives were installed for flow control, and dampers locked in open
position, these benefits were noted:
Energy saving: 1,000,000 kWh/year
Reduction in CO2 emissions: 500,000 kg/year
Faster response to load changes (Immonen, 2003)
Noise level reduced from 89 dBA to 77 dBA
Payback period of just 16 months
Case Example #2
Industrial Power Plant
Inlet Vanes
AC Drive
Fan shaft power
120
100
80
60
40
20
0
0 30
60 90
Case Example #3
Industrial Power Plant
Inlet Vanes
AC Drive
Fan shaft power
120
100
80
60
40
20
0
0 30
60 90
An industrial power plant compared inlet guide vanes to AC drives (110 kW each) for
its FD (Forced Draft) fan. The power plant is running continuously and the fresh air
flow varies from 50% to 90% of the maximum capacity. With AC drives: Power plant
FD fan - AC drive instead of inlet guide vanes, Power plant booster fan - AC drive
instead of inlet guide vanes
Energy saving: 482,000 kWh/year
Reduction in CO2 emissions: 241,000 kg/year
Better pressure control with varying loads
Less maintenance by soft starting
Efficient combustion
Case Example #4
Abbott Power Plant, UI, USA
In a drive to reduce the plants operational costs, Abbott Power Plant engineers
selected ABBs ACS1000 standard medium-voltage (MV) drive to control a 1000 hp
fixed speed scrubber booster fan that was previously regulated by inlet vanes, and
thereby improved the overall efficiency with reduced maintenance effort.
Energy savings of USD $63,000 per year, an improvement by 25% on inlet vanes
Reduced maintenance and hardware savings : USD $10,000 per year
Payback on investment period was 24 months
Additional benefits of the variable speed drives include:
no motor start-up problems
total process controllability
Fan System Design and Engineering
Fan selection and sizing is based on many factors. The most important criteria are
the systems pressure and flow requirements and how these vary under operating
conditions.
Module 2 | 93
days. Energy efficiency efforts, including radial leakage reduction in air heaters,
could be sufficient to remove such a capacity restriction in these plants
ID fan capacity may, however, be a real bottleneck for some plants potential
to burn waste fuels. VFD overspeed may provide the additional short-duration
capacity needed to burn a small inventory of waste fuel. For longer term firing
with waste fuel, a fan retrofit or booster fan may be required. Generally, use
of VFDs is the only way to get additional capacity from a fan system if
the overall combustion process is fan limited when running full out at
nominal frequency. Running a VFD at 5-10% overfrequency is possible, as
long as the overall design of the fan/motor/drive system is appropriate for
overspeed operation.
Module 2 | 95
The load factor determination of existing fan systems should also include the
position of any mechanical flow control devices (inlet vanes, dampers etc.), as this
may reveal an energy-saving retrofit opportunity for variable frequency control.
In power plants, the basic flow requirement for FD fans is the stoichiometric
amount of air given by the chemical oxidation reaction equation, plus a certain
amount of excess air to compensate for imperfect mixing during combustion,
less the flows to the PA fans. The stoichiometric amount varies with the coal or
fuel type. Values for these are available from ASME standards and test codes.
For ID fans, the basic flow requirement is given by the stoichiometric (chemical
equation) products of combustion, plus leakage flows.
On balanced draft boilers, where the furnace is under slight negative pressure,
air tends to leak in, especially as boilers age. Leakage in air heaters is a source
of 1) reduced cycle efficiency and 2) increased auxiliary power. Air heaters are
used to recycle heat from the flue gas back into the boiler, by pre-heating the
fresh air for prior to combustion. Air heaters increase the boiler efficiency by
10% to 15% (Babcock & Wilcox 2005) and are typically located immediately
downstream of the economizer. Air heater leakage reduction will improve heat
transfer in the air heater and therefore will also improve overall cycle efficiency.
Regenerative air heaters transfer heat from hot to cold sides by warming up
metal tubing set into a slowly rotating rotor. The efficiency of the air heater itself
is typically 85% to 90% (Rajan 2003). Typical leakage values for regenerative
air heaters range from 6-15%, and values increase with age and consequent
wear of seals, and air leakage rates of 20% are not uncommon (Guffre 2007).
Tubular and heat-pipe (recuperative) air heaters have no mechanical seals and
therefore have low leakage rates, typically under 3%.
Process design attention to reducing air leakages will reduce the loading on
the ID fans. At typical rates, air seal leakage accounts for up to 25% of fan
horsepower (Guffre 2007), which represents between 0.5MW to 2.0MW of
fan auxiliary power, depending on plant design. Radial leakage in regenerative
air heaters is unwanted flow from cold to hot sides of the heater. Radial
leakage adds to the fan load and, because it is not pre-heated, does not
aid combustion either. Leakage also disturbs the balance between primary
and secondary flow and has been observed to cause poor flame stability
and increased desuperheating (attemperation) spray flows (McIlvaine, 2008).
The leakage of fresh air into the flue gas stream decreases the efficiency of
downstream emissions control equipment such as the electrostatic precipitator.
The fan pressure requirements at unit MCR conditions can be estimated using
component pressure drop equations, but the industry sources named above
have typical, empirically determined values. For FD fans, the largest pressure
drops are across the burner/windboxes and across the air heater. For ID fans,
the largest pressure drops are across the scrubber, air heater, and economizer
outlet. Special attention to the design of these components, especially the
regenerative air heater, will have a beneficial effect on auxiliary system and
thermal energy efficiency. The rotary design of regenerative air heaters still
used in new plants dates back to 1923. Reducing gaps and installing modern
seals can lead to a 50% reduction in radial leakage on existing regenerative air
heaters (McIlvaine, 2008).
See power generation industry texts (Black & Veatch, 1996) and (Babcock &
Wilcox, 2005) for details on the individual leakage flows and pressure drops for
FD, ID and PA fans.
Module 2 | 97
Fan Automation
Proper control of multiple fan arrangements is essential to realizing their full energy
saving potential and to avoid unstable or stall operation due to interactions between
multiple fans at low flows, especially for fans in parallel. Isolation dampers between
multiple fans in parallel may also be necessary to avoid air flow through inactive
fans. In fans with damper control, a flow cascade loop is typical, with the master
comparing actual to demanded airflow. The setpoint is sent to the cascade slave
loop for comparison with a sum of the damper position signals. The ISA Control &
Optimization handbook contains details on this loop and additional control loops
for optimizing cycling fans with dampers (ISA, 2005). Good fan flow control is
very important if the downstream process is combustion, in which air supply will
determine the intensity and the safety of the process.
In power plants, stable FD fan pressure is essential to the stability and efficiency of
the combustion process downstream in the furnace. Smooth variation of pressure
with flow is necessary, and this can be achieved through either adjustable pitch
blades on axial fans or with VFD speed control. Multiple fans pose a special
challenge for smooth control; to ensure smooth performance design requires the
combined effort of both the controls and mechanical engineering disciplines.
Fan flow control is important to several critical boiler & turbine control systems:
Combustion control (firing rate, fuel/air) control , involving FD fans, - Excess air (O2)
control involving ID fans, Furnace draft (pressure) control, involving ID fans, Gas flow
distribution (recirculation) control, involving GR fans.
Correct instrumentation and actuation is also important to the overall controllability
of these loops. Flow transmitters are typically not calibrated or not capable at low
flow rates (<25%). Louver-damper fan systems pose a particular control challenge,
due to the non-linearity, hysteresis and leakage (up to 10%) of dampers (ISA, 2005).
Dampers with smart positioners will increase the controllability of these actuators.
Automation also plays an important energy efficiency role in reducing power
requirements during large fan startup; see the Fan Drive Train section for details.
Fan System Design Guidelines - Summary
Sources for this summary section are: (Lovins A. 2007) and the DoE EERE (US DoE
Best Practices, 2008) Fan SourceBook.
Reduce Static & Pressure Head and Flow Requirements
Consider process design or operational control alternatives that reduce the
maximum and average static or pressure head required. Consider these aspects
also under startup conditions.
98 | ABB Energy Efficiency Handbook
In power plants, Gas Recirculation (GR) fans operate in high temperature and
particulate airflows, making them unsuitable for axial fans with directly exposed motors.
Module 2 | 99
Fans with non-overloading blade design, common in power plant draft service,
have absolutely no benefit from an oversized motor, because horsepower
drops with increasing flow beyond the BEP.
In older designs, piggyback or pony motors were used to allow engineers to specify a
right-sized, highefficiency main motor. If the application allows some method to keep
the fan rotating at low speed, then a VFD with flying start capability can then use that
rotational energy in the startup sequence, thus reducing the heat load on the motor.
The Motor Startup section has some guidelines for reduced voltage startup.
In power plants, a 1500-hp ID fan motor may use its full rated starting torque
with a safety margin of only 10%, but then drop to 30 to 50% of full load once
it has settled to run at normal speed. This motor will typically lose, at 50% load,
about 1.8% points in efficiency and over 2% points in power factor. At 30%
load the motor does much worse, perhaps a 4% efficiency loss (Competitek,
1996).
ID fans have a high duty factor, and each % point of efficiency loss in such large
motors is worth tens of thousands of dollars per year. The savings will justify
many efforts to provide some form of starting assistance to these motors.
Module 2 | 101
The Fan System Assessment Tool (FSAT) from US DoE. The FSAT calculates
power consumption and efficiency of upgraded fan systems.
ABBs FanSave calculation tool compares AC VFD drive control against
traditional flow control methods for fans (outlet damper, inlet vane or pitch control
methods). The tool provides financial and environmental estimates for each
control method retrofit project and recommends a suitable VFD drive type.
Note that some fan calculation tools assume a parabolic fan curve and a system
curve with zero constant pressure. This latter assumption may invalidate some of the
results for high constant-pressure applications.
Figure 2.17 Conveyor systems and VSD energy savings diagrams (De Almeida, 2006 )
Module 2 | 103
In many conveyor systems, the conveyors are running at maximum speed and the
feeder controls the flow of material. Energy can be saved by using some form of
variable speed control via a VFD on the motor; the speed of the conveyor can then
be varied with the amount of material flow. When there is no flow, the conveyor runs
at minimum speed; material sensors can be used to detect if the conveyor is empty
or not.
HVAC Systems
The large fans at the heart of HVAC systems are cube-law applications whose power
requirement increases as the cube of the motor speed. Commercial and residential
buildings offer the highest energy saving potential, but even industrial facilities
HVAC systems can yield energy efficiency gains through careful redesign of their
air handling components. Most of the design guidelines from the section on Fan
Systems also apply to HVAC air handling systems, but are re-stated here only in
summary form.
The most efficient HVAC fans (70-85 % total efficiency) are axial design or backwardcurved centrifugal fans. Large, round ducts with a minimum of sharp elbows will
reduce pressure requirements. A right-sized and energy-efficient electric motor will
save from 5-15% over a standard, oversized one. VFD speed control can save a
further 20-40% for fans operating at lower loads and dramatically reduce noise. Even
when compared to axial fans with variable pitch blades, VFDs are still a slightly more
efficient method of air flow control.
Compressed Air Systems
Reciprocating pumps and rotary screw pumps which are used in compressed air
systems are a linear law load, whose power requirements vary linearly with motor
speed, as shown in the figure below. Air compressors account for 10% of industrial
consumption of electricity, yet they have poor energy efficiency. Estimates of the
potential energy savings are in the range from 5% to 50% (De Almeida, 2006),
and average savings are estimated to be 25%. These estimated are based on the
following assumptions: Power-110 kW, Equipment life span-15 years, Operating
hours-4000 h/year, Electricity price- 5 c/kWh.
In linear-law systems, it is the running time of the motor at various speeds which
will determine the energy demand and the potential for savings. (Competitek 1996).
Some systems have their compressors running continuously just to maintain the
minimum required pressure; a smaller helper motor could be used to handle such
situations more efficiently. An even better option is to use a variable frequency
drive (VFD) to control the speed of the compressor. The figure below shows energy
saved by using a VFD for speed control on a rotary screw air compressor:
Figure 2.18 Compressed air power required by control method, (De Almeida, 2006)
Module 2 | 105
Figure 2.19 - Small LV (left) and large (right) MV induction motors, (ABB Drives, 2008)
For example, a 60Hz , 4-pole motor with 1.5 % slip has a synchronous speed ns = (2
x 60 x 60 ) / 4 = 1,800 RPM, and a nominal speed nn = (100 1.5)/100 x 1800 = of
1,773 RPM.
The motors maximum torque (also called breakdown torque and pull-out torque)
occurs at about 80% of nominal speed. A standard induction motors maximum
torque is typically 2 to 3 times the nominal torque. The maximum torque Tmax occurs
at slip smax, which is greater than nominal slip.
The slip at which maximum torque occurs is proportional to rotor resistance. In
order to use an induction motor efficiently the motor slip should be in the range 0 to
smax. This can be achieved through right-sizing of the motor to its application, or by
controlling voltage and frequency by using a variable frequency drive (VFD).
In a squirrel cage type of induction motor, shown in the figure below, the rotor
conductors are placed longitudinally. The cross-section of these bars determines
the torque and speed characteristics of the motor. Their simple operation and
construction make squirrel cage induction motors the workhorses of industry. These
motors exhibit versatility, reliability, and are available in all sizes up to 18MW. Other
basic types of induction motors are wound rotor motors and some variations on
these two designs, such as multispeed motors.
Figure 2.20 - Induction motor cutaway view, ABB Motors & Drives, 2007
synchronous motor requires temporary use of the induction principle; a small number
of conducting bars in the rotor are used to develop startup torque until the rotor
has sufficient speed to pull-in to the stator speed, at about 85% full speed, and
thereafter operate fully synchronously. The standard horsepower, speed, and voltage
ratings of synchronous motors are listed in Sections 21.10 and 21.12 of NEMA
standard MG1
Synchronous Motor vs. Gas Turbine
The following section is based on information from ABB and IEEE Std.666-2005,
paragraph 11.3.1.1:
For very high-power applications, four-pole synchronous motors are a cost-effective
alternative to powerful mechanical drives such as turbines; this may be the reason
behind a trend toward ever larger synchronous motors. Compared to steam or
gas turbine drive, synchronous motors are more energy efficient and require less
maintenance. A gas turbine averages only 25 to 38% efficiency and less than 25%
at off-peak loads. The efficiency of a large synchronous motor is between 97 and
99%. Gas turbines require frequent costly attention and have other drawbacks
compared to electric drive, as shown in the table below. One facility (Statoil Snhvit
plant) reported an additional 10 normalized on-stream days per year for their LNG
liquefaction compression application after converting to a motorized drive system.
Characteristic
Gas Turbine
Synchronous Motor
heavy auxiliaries
Efficiency
Average operational efficiency
20,000 hrs
100,000 hrs
25,000 hours
6-10 days
1-2 days
4,000 hours
Control Response
Slow
Medium to quick
3-4 years
1-2 years
reliability in the drive means that larger trains are possible; and large compressors
are more efficient, too. The cumulative effect of these benefits yields an average
of between 3.5% to 5.0% efficiency improvement in large (e.g. LNG) compressor
applications (ABB Inc, Oil & Gas Norway, 2008). The payback compared to a
conventional gas turbine drive is less than half a year.
Synchronous motors are generally more efficient than induction motors at higher
power ratings, as shown in the following figure (data up to1600 hp). At even higher
power ratings (above 9000 hp) this improved efficiency favors synchronous motors
in lifecycle costs when compared to induction motors. Synchronous motors are
typically used at lower speeds relative to induction motor applications, but are more
expensive, more complicated, and have higher maintenance costs compared to
squirrel-cage induction motors.
In the past, synchronous motors were favored due to their speed control capability
by simple frequency variation, and also for their ability be used for plant-wide power
factor correction . Variable Frequency Drives (VFDs), however, can now provide
the precise speed control of induction motors that was previously only possible
through frequency control on synchronous motors. Some drive types equipped with
active front-end power electronics may also be used in plant-wide PF correction as
well. One area where synchronism has the advantage; the inherent slip of induction
motors, which increases with load, may lead to slower speed response to load
changes. Fast response is necessary to reduce the risk of pressure fluctuations in
some dynamic pumping applications, for example.
1000 hp = 746 kW
Figure 2.21 - Typical Full Load Efficiencies for synchronous vs. induction motors, (IEEE, 2007)
Module 2 | 109
Locked-rotor code letter: A code letter that defines an inrush current a motor
requires when starting it.
Manufacturers name and address
In addition to this required information, motor nameplates may also include data
such as frame size, NEMA design letter, service factor, full-load efficiency, and power
factor.
Motor System Loads
A motor application is fundamentally defined by the loads torque-speed
requirement, the duty cycle, and the load profile.
Load Torque vs. Speed Requirement
According to these definitions from ABBs Technical Guide (ABB Drives 2002) and
the Competitek Drive Power manual (Competitek 1996), the applications can be
categorized by how the power varies with motor speed.
Linear-law loads require constant torque across the entire speed range, and
power consumption varies linearly with speed. Examples of this type of load are:
reciprocating compressors , positive displacement pumps, drilling machines,
conveyors and grinding systems (curve (a) on page 112).
Cube law loads require a torque which varies with the square of speed, and
power consumption varies with the cube of that speed. Examples of this
type of load are: pumps and fans and winders. The prevalence and high
power consumption of these loads is why they deserve special attention in
designs for improved energy efficiency (curve (b)).
Constant power loads; A constant power load is normal in steelmaking when
material is being rolled and the diameter changes during rolling. The power is
constant and the torque is inversely proportional to the speed (curve (c)).
Constant torque, then constant power loads. This load type is common in the
paper industry. It is a combination of constant power and constant torque
load types. This load type is often a consequence of dimensioning the system
according to the need for certain power at high speed (curve (d)).
Square law loads require a torque which is directly proportional to speed, and
power consumption varies with the square of that speed. Examples of this type of
load are hoists and winches.
Constant speed loads are applications which require constant speed but varying
torque. Examples of such applications are grinding and milling machines, sawmill
blade cutters and escalators (Competitek 1996), and extruders, all of which must
run at the same speed regardless of loading.
Module 2 | 111
Figure 2.22 Load types by torque vs. speed performance, (ABB Drives 2002)
Figure 2.23 Load profile showing %-load versus %-total time (annual)
Figure 2.24 Load type curve where high starting torque is needed, (ABB Drives 2002)
Module 2 | 113
Figure 2.25 Fan torque vs. speed, with relative values at five equidistant speed points, (ABB Drives
2002)
t
t
t
t
t
=
=
=
=
=
1211
1211
1211
1211
1211
x
x
x
x
x
198.2
198.2
198.2
198.2
198.2
/(
/(
/(
/(
/(
0.99
0.92
0.78
0.57
0.29
x
x
x
x
x
1927)
1927)
1927)
1927)
1927)
x
x
x
x
x
2/60
2/60
2/60
2/60
2/60
=
=
=
=
=
13.2
14.3
16.7
22.9
45.0
s
s
s
s
s
The total starting time from 0 to 991 rpm is approximately 112 seconds.
Module 2 | 115
Note that when the machine operates with negative slip, it is in generator mode
(region G on the figure) and the torque versus speed performance is inverted.
Figure 2.26 - Torque vs. speed for squirrel cage induction motor, (ABB Drives 2002)
Module 2 | 117
High torque, high starting torque, but with lower starting current. Car puller,
crusher with flywheel, pulverizers, and high inertia drives that do not require high
efficiency. Design D has higher starting torque than C, but motor efficiency is
lower.
Motor Service Factor
Motors will have a service factor (SF), typically 1.0, or 1.1, or 1.15. As an example;
a 1000hp motor with an SF of 1.15 means that the motor could be run at 1150 hp
indefinitely without risk of overheating, but only at the rated voltage and frequency
conditions. The standards specify that the motor can operate at a nameplate
temperature rise of 90C at service factor horsepower. SF offers a means to avoid
oversizing a motor to handle temporary modest increases in load and uncertainty
about loading.
Designers must be aware that higher temperatures will reduce a motors ability to
withstand some of the other effects, such as increased harmonics, which stress the
insulation. The IEEE offers some further warning; the efficiency and power factor at
service factor load can be different from the respective values at rated nameplate
levels. It may not be energy-efficient to run for long periods at SF horsepower.
Another consideration for designers wishing to actually use the SF margin is that the
motors starting and breakdown torque capability is based on rated horsepower only.
If the starting torque requirement was high to begin with, and was then significantly
increased under the new SF operating conditions, then there is no guarantee that
the motor will be able to start within an acceptable time limit.
With careful design of the power system, as described in the Power Systems
section, a well understood loading condition, and with robust real-time monitoring of
the motor, it is worthwhile and defensible to exploit allowable SF margins of a highquality motor. The motor will be more correctly sized to its application and will offer
improved efficiency at normal operating conditions.
In some applications, extra drive power is required for short durations; for
example to maintain condenser performance during peak supply on a hot
summer day. In these cases, a VFD will be able to increase speed to within
the SF limits, while the VFD drive diagnostics continually monitors motor
temperature.
A NEMA committee warned a long time ago (in the 1960s) against use of SF on
large motors as an alternative to a higher standard horsepower rating. Their advice
on this issue is reproduced below:
118 | ABB Energy Efficiency Handbook
Standard horsepower increments in the larger ratings are usually within a 1.15
range, so that the next larger standard horsepower can be reasonably selected in
lieu of the service factor.
Use of a larger horsepower when overload is required avoids exceeding the
nominal temperature rating for the class of insulation system used and avoids any
encroachments upon the thermal life of these larger, vital motors.
Use of a larger horsepower when overload is required eliminates any reduction in
torque margin.
Advances in motor technology over the last half-century, however, may eventually
lead NEMA to a revision of their old guidelines and allow designers the room to
improve energy efficiency without any fear of compromising reliability.
Motor Power and Efficiency
The power and speed requirements are set by the applications load profile. For
example, in pump and fan applications, the load torque decreases with the square of
the speed; this is a direct result of the Affinity Laws discussed in the Pump and Fan
systems sections. The power rating of a motor indicates its output mechanical power,
often stated in horsepower or kW. Motor electrical (input) power is usually stated in kVA.
Motor Mechanical Power
The motors mechanical output power is simply the output torque multiplied by
motor speed. In SI units:
Pm = T x N
Where:
T = torque, (Nm)
Pm = mechanical power at the shaft (watts)
N = speed, (rad/s)
The same formula with power in kW and speed N in rpm (where 1 rpm = 2 x / 60) is:
Pm = T x N / 9550
Where:
T = torque, (Nm)
Pm = mechanical power at the shaft (kW)
N = speed, (rpm)
Module 2 | 119
The active power (kW) at the motor terminals can also be calculated from electrical
parameters Pin = 3 x VL-L x IL x PFP
Where:
Pin = power (kW)
V L-L = three phase line-to-line voltage (kV)
PF P = per-unit power factor (cos(n))
For example: What is the nominal efficiency of a 400 kW ( V= 4.16kV, 71A and PFP =
0.85) motor?
The above formulas can be used to calculate the nominal efficiency of the motor as
follows
n = Pm / Pin = 400 / (3 x 4.16 x 71 x 0.85 ) = 0.92 (approx)
To calculate the input electrical energy cost for R running hours, given input voltage
and current and a Price:
Cost= 31/2 x VL-L x IL x PFP x R x Price$/kWh /1000
The VFD section contains additional formulas for estimating motor current, and
additional electric power formulas are in the Electric Power System part of this
handbook.
Motor Efficiency
Motor efficiency refers to the amount of input electrical power required to achieve
a particular output from the motor. Using the power formula from above, a 100 hp
rated motor with 93% efficiency at rated load will draw 89.1 kVA from the supply
when running at full load and 0.9 power factor. The motor current at this operating
point is shown as the FLA (full load amp) rating on the motor nameplate.
Most motors will the show nominal full load efficiency value on their nameplate as
determined by a highly-accurate dynamometer and a procedure described by IEEE
Standard 112, Method B. These measurements provide average values from a large
test sample of motors. The motor efficiency of an individual motor in the field can
only be determined by field testing methods, such as measurements with a wattmeter. Statistics on the manufacturers test sample provide a minimum efficiency
value which also appears as the guaranteed minimum efficiency on the nameplate;
this value assumes that the worst motor in the sample could have losses as much
as 20% higher than the average. These minimum values are in Table 12-8 in NEMA
MG-1 (Cowern, Baldor Electric, 2004).
Standard motors tend to operate most efficiently at between 75110% of full load
speed. Smaller motors are less efficient than larger motors. Standard motors below
Module 2 | 121
200 hp have efficiency between 80 to 90%, while the efficiency for motors in the
range of 250 to 5000 hp varies between 90 to 96%. Larger motors with higher peak
efficiencies tend to have flatter efficiency curves above 50% load, as shown by
curves (1) and (2) in the figure below. For these larger motors, maximum efficiency is
still at about 95%, but with only a small (0.3 to 1.0%) decrease to full load.
Figure 2.27- Efficiency vs. Load for squirrel cage induction motors, (IEEE, 2007)
As the curve shows, efficiency drops sharply below 50% load for all motors. An
average 100 hp standard- efficiency motor loses 15% in efficiency as load decreases
from 50% to 25% of full load (Competitek 1996). As a general rule, smaller motors
lose more efficiency than larger motors at lower loads.
Motor Losses and Efficiency
The greatest losses in a motor are the iron losses that occur in the rotor and
stator, accounting for 50 percent of the total loss. This can be improved by using
low loss steel and thinner laminations. Copper losses account for 20 percent.
Using an optimum slot fill design and larger conductors can reduce these losses.
Bearing friction and windage losses total 23 percent and can be reduced by using
a smaller cooling fan. Stray losses, which account for 7 percent of the total, can
be reduced by improving the slot geometry. The main sources of motor losses and
corresponding design improvements are shown in the figure below from the ABB
Review Special Report on Motors & Drives, 2005. By virtue of these design changes,
motors have improved in efficiency by an average of 3 percent in the last decade
(from 1995 to 2005).
There are important design trade-offs between losses and torque performance; low
rotor resistance results in high full load speed (low slip), high efficiency (low rotor
losses), and slightly higher starting current. High rotor resistance results in high
starting torque for line current drawn and slightly lower current during starting, but
results in lower full load speed and lower efficiency (high rotor losses).
122 | ABB Energy Efficiency Handbook
Figure 2.28 Cutaway view showing sources of motor losses, (ABB Drives, 2006)
Rotor ohmic (I2R) losses are proportional to slip and are in the rotor winding of
a squirrel cage motor. Higher-efficiency motors tend to have lower slip and will
therefore rotate faster under the same loading conditions: one percent increase in
efficiency is equal to about a 1/3 of a percentage point decrease in induction motor
slip. Voltage at the motor terminals also has an effect on efficiency, as discussed in
the section on Power Quality - Voltage and Frequency Variation
Power Factor
Power factor (PF) is a measure of the amount of reactive power which the motor
draws from the power source. A PF less than 1.0 means that some reactive power,
which is induced by the motor coils, must be generated and carried by the power
supply system. Industrial end-users pay a demand charge based on maximum
reactive power usage within a certain time period. This charge is in addition to the
regular cost of energy, charged per kWh, and covers the providers cost for the
increased size of their power delivery equipment. An oversized electric motor will
typically decrease (i.e. worsen) the PF by 10% compared to a right-sized motor.
PF in induction motors generally follows the same shape as the efficiency curves
with respect to % loading.
PF is a minimum at no load and reaches a maximum near full-load condition. This
relationship between PF and motor speed is shown in the figure below, from IEEE
Module 2 | 123
Std 666. The average 100 hp standard-efficiency motor loses about 10% points in
PF from full load to 50% load, and almost 20 more points moving down to 25% load.
The PF as listed on the nameplate applies to the full load operating condition.
Figure 2.29 - PF vs. Load for squirrel cage induction motors, (IEEE, 2007)
The capacity of the power system to deliver real power (the only kind which can do
real work) can be increased by applying various reactive power compensation
methods, either at the motor, or centrally in the electrical power supply system.
High-Efficiency Motors
With the Energy Policy Act (the EPAct) of 1992, the USA and Canada imposed
new, minimum efficiency standards, effective from October 1997, for generalpurpose induction motors of NEMA designs A and B. These motors are typically 38
percentage points higher in efficiency than standard motors. The EPAct specifically
targets motors from 1 to 110 hp (0.75 to 150 kW) as prime candidates for
improvement, with a published list of high-efficiency motors and reduced electricity
tariffs for users of these motors..
A similar program by the Danish Energy Authority published a list of high efficiency
motors and offers subsidies for motors purchased from this list: US$ 10 per kilowatt
for both new plant and for replacements. In the EU there are three class levels of
efficiency, known as Eff1, Eff2 and Eff3, applying to low voltage two- and four-pole
motors with ratings between 1.1 and 90 kW. Both the US DoE and the EU require
that a motors efficiency rating be prominently displayed on the motors nameplate.
A higher-efficiency, premium NEMA class of motors is also available, known as
class E. The price of these premium, higher efficiency motors ranges from 10 to
20 percent higher than standard motors in continuous duty applications (US DoE
124 | ABB Energy Efficiency Handbook
Sourcebook, 2006). A high efficiency motor has lower energy losses (described
in the figure below), hence lower running temperature and improved reliability; all
desirable characteristics in critical and high-duty applications. These NEMA premium
efficiency 3-phase motors have efficiencies ranging from 86.5% at 1 hp (750 W) to
95.8% at 300 hp (220 kW).
The recent legislation in the Energy Independence and Security Act of 2007 (EISA)
calls for increased efficiency of motors manufactured after December 19, 2010.
EISA regulation re-classifies EPACT minimum efficiency motors as Subtype I, so
these motors will be required to have nominal full-load efficiencies that meet the
levels defined as premium by NEMA MG-1 (2006). The EISA law also creates a
completely new category (Subtype 2) of motors which regulates efficiency for motor
designs that were not covered under previous legislation, such as polyphase motors
rated at less than 600 volts.
Motor Slip and Energy Efficiency
High efficiency motors tend to have less slip at a given load compared to standard
efficiency motors. The reduced slip may provide improved torque vs. speed
characteristics, but the increased speed at operating point may incur power losses
greater than the gains of increased motor efficiency. The increased speed is an
important factor to consider when facing a motor retrofit situation. A general
rule of thumb is that every 1% increase in efficiency is equivalent to about a 1/3%
decrease in slip (Competitek, 1996). The losses due to increased speed occur only
in constant speed applications, and are largest in cube-law applications such as fan
and pump systems. The gains from using high-efficiency motors can be preserved
by 1) specifying a variable speed drive to reduce speed, 2) specifying a smaller rated
motor (if peak loads allow) or 3) compensate by trimming the pump impeller or fan
blades (Competitek, 1996) 4) specifying a high-slip, but still relatively more efficient
replacement motor.
Motor Couplings, Speed Control & Variable Frequency Drives
Motor Shaft Couplings
A motors shaft can be either directly coupled to the drive shaft of a pump or fan,
or indirectly coupled by using chains, belts or gears. Indirect coupling is necessary
when physical space or layout restrictions prevent the motor from being in-line with
the drive shaft, or to allow for mechanical speed adjustment.
Speed adjustment is not the same as speed control, in which speed can be varied
continuously by a signal from an operator or an automatic controller. The pros and
cons of the various coupling methods are discussed below, but direct shaft-to-shaft
coupling is the only method with zero drive-train losses.
Module 2 | 125
Chain Drives
Chain drives have no slip and are suitable for low speed, high torque applications.
They are high-maintenance couplings, but can achieve efficiency up to 98%. The
desired speed adjustment is achieved by changing the diameters of teeth of the
chain wheels.
Belt Drives
Belts have the lowest efficiency of all the common coupling methods, V-belts are
the least efficient belt type due to inherent slip, followed by cogged V-belts flat
belts, and synchronous belts. Synchronous belts are the most efficient belt type
(up to 97%), but are intolerant of abrupt changes in loading (Competitek, 1996).
The desired speed adjustment is achieved by changing the diameters of the belt
pulleys. In standard belts, wear leads to increased slippage and reduced efficiency.
Synchronous belt pulleys are available only in discrete sizes; and adjusting belt
drives to achieve the optimum speed may be impossible.
Gear Drives
Gear reducer efficiencies depend on the type of gear and reach 98% for helical and
conic gears. Screw and worm type gear drives have efficiencies from 66 to 96%.
(Competitek, 1996) Due to higher cost, however, gear drives are less common than
other coupling methods. Gear drives are more suitable for low speed, high torque
loads. The desired speed adjustment is achieved by changing the number of teeth of
the gear wheels.
Coupling Alignment
Torque is reduced by about 1% per degree of misalignment up to 5 degrees, after
which failure is likely. (Competitek, 1996) Flexible couplings compensate for minor
alignment errors and reduce the risk of bearing failure, but at the cost of reduced
efficiency. Rigid couplings with laser-aided alignment are recommended practice on
high-performance machinery.
Multiple Speed Motors
A form of speed control is possible with multiple speed motors, constructed to
be able to operate at one of several discrete speed settings. There are two basic
designs: motors with multiple poles or motors with multiple windings. Selective
energizing allows these motors to achieve different multiples of speed. The former
design (also known as a consequent pole motor) has only two speeds, but the
motor with multiple windings and poles can have 2, 3 or 4 speeds. For example, a
2-speed, 2-winding motor can provide ratios of 2:1, 3:2, or 4:3 (Competitek 1996).
In two-speed induction motors, the low speed is typically selected for the most
common operating point and the higher speed for all the higher loads, including test
block load (Black & Veatch 1996).
126 | ABB Energy Efficiency Handbook
Multiple speed motor systems have some inherent disadvantages; 1) for large
motors, switching between speeds is neither trivial nor smooth and may lead to
process transients and upsets. The sequence of power breaker and pole switching
must be closely coordinated with motor speed 2) Multiple speed motors tend to
be slightly less efficient than single speed motors, due to compromises in their
design to allow for multiple sets of windings. Although they deliver savings in cubelaw applications, they are still less efficient than the VFD plus single-speed motor
combination.
Wound Rotor Motors
Wound rotor motors are induction motors with a slip-ring and brush assembly which
connects the rotor to an external variable resistor. Varying this resistance will change
the rotor resistance and slip, hence speed of the motor. The disadvantage of this
motor type is that significant slip energy is dissipated in the resistor (Competitek
1996). Slip-recovery variations (Kramer and Scherbius drives) on wound rotor
designs increase the efficiency to VFD plus motor levels (Competitek 1996). The
brush assembly is similar to that found on DC motors and is a source for the same
maintenance and reliability issues associated with DC motors.
Variable Speed Control Technologies
There are a number of different coupling technologies specifically for continuous
speed control which are commercially available and feasible for large industrial
machinery: hydrodynamic, hydro-viscous, magnetic, and DC or AC variable speed
drives (known as a Variable Frequency Drive (VFD) for AC systems). All of these
technologies provide the necessary speed control and achieve energy savings over
the less efficient flow control methods such as control valve or damper throttling.
In hydrodynamic type couplings, the shaft drives an impeller which imparts energy
to oil which then transfers it to blades of a runner fixed to another shaft. Control
is achieved by varying the amount of oil via a scoop tube. The hydrodynamic
coupling will always have slip losses, even at rated speed, typically 2%-3%. The
hydraulic coupling offers a form of soft-start capability, but this comes at the
expense of controllability at low speeds (Competitek 1996). This type of variable
speed arrangement is still common in many existing plants (Black & Veatch,
1996).
In the hydro-viscous type of variable speed control, a thin film of oil between a
series of discs transfers energy from the driving shaft to the output shaft through
shear forces. Speed control is achieved by varying the pressure on the discs. The
hydro-viscous coupling can be locked at rated speed, incurring no losses, which
make this type of drive useful as a clutch for starting.
Module 2 | 127
Calculate maximum running torque and input power, using average or peak-load
sizing methods
For VFD speed control, follow the design guidelines in that section to determine
motor loadability.
Determine starting conditions based on process requirements & power supply;
inertia, starting time requirements, load torques during startup, voltage drop on
bus due to high starting current, resonance vibration frequencies during startup.
Use the minimum voltage if starting with reduced voltage as basis for calculating
motor speed vs. Torque, and ensure at least 10% margin over the pump torque
vs. speed during startup
Step 3: Select motor type and rating based on the above work; the minimum motor
specifications needed are listed below.
Design type: Induction vs. Synchronous
Power rating
Efficiency Rating and efficiency vs. speed
Speed, Frequency and Slip (vs. speed)
Voltage Level : LV or MV
Service Factor
Frame size : NEMA frames or IEC frames
Required IP class enclosure, mounting type (vertical vs. horizontal)
Synchronous speed and number of poles
Problem of Motor Oversizing
Oversizing of motors is a very common, but hidden cause of energy inefficiency.
Oversizing does not lead to any highly visible failure events, but it is a continuous,
low-level problem as energy costs and total emissions accumulate. Oversized
motors, those operating an average of less than 60% of rated load, will incur three
operational penalties:
Reduced motor efficiency
Reduced slip (hence higher speed); important for cube-law load applications
Reduced (worsened) Power Factor (PF)
Data from the US electric power utility PG&E showed that one-half of industrial
motors are operating at less than 60% of their rated load, and one-third are
operating at less than half their rated load (cited in Competitek, 1996, Ch.9).
According to the same source, motors operating below 60% load incur an efficiency
penalty of 0.5 to 1.5 percentage points. Motors operating at half their rated load are
2.0 to 4.0% less efficient than at rated load.
Module 2 | 129
Starting a Direct-On-Line (DOL) over-sized motor means the motor starter and
other power system components will need to be oversized, as the majority of
starting current is reactive and dependent on the motor size; larger motors take
more starting current. For this reason, VFDs and Soft Starters should be evaluated
for suitability during the motor specification process. As the section on Variable
Frequency Drives explains, these devices can correct for all accumulated design
margins and also provide the required soft-start capability.
Engineers may wish to believe that the widespread problem of oversizing is actually
due to under-loading; in other words, that the plant is operating at much less than
its target rated capacity due to prevailing market conditions beyond their control.
An analysis of the large motors in a US pulp and paper mill, however, revealed an
average load times capacity factor of 43% at a time when the mills where operating
at nearly full rated capacity (cited in Drive Power manual Competitek, 1996). Data
such as these suggest that the problem of oversizing is real, and that it must be
solved by engineers and technical managers.
Causes of Motor Oversizing
The causes of technical oversizing are investigated in detail throughout this
handbook, but the story of how margins creep in a typical project is told below, in
the case of a large industrial motor:
The process designer, following the guidelines in the Pump and Fan Systems
sections of this handbook, will provide the electrical engineer with the maximum
required pump or fan torque at the required operating speed. This process
specification is often misinterpreted, by the electrical engineer, to mean the minimum
acceptable continuous torque for the motor even if the requirement is actually a
peak load which must be sustained only for a small fraction of the motors duty
(Competitek, 1996).
The electrical engineer may further oversize the motor in the face of uncertain,
high-starting torque requirements and other power system uncertainties, just as
the process designer may have overstated the torque and speed requirements
to account for later changes in piping design or capacity demands. Customer or
company guidelines may force the electrical engineer to specify a high service factor
(1.15) machine and class F insulation, all of which add even more unnecessary
margin.
The project lead engineer may add further layers of margin fat by applying an acrossthe board-design margin of error or safety, as well as a generous future capacity
increase margin. Finally, if the resulting specification is only slightly higher than a
standard commercial rating, then the next and higher rating is usually selected. The
130 | ABB Energy Efficiency Handbook
gap between standard ratings is larger as motor power increases, which makes this
common practice costly in the long run. Most of the above margins are compounded
(margin as a percentage of the margin below), the end-result is a motor which is
often twice as large as it needs to be.
Motor Sizing and Selection
The motor design and engineering procedure described previously will help to
establish whether the maximum torque specification is a normal maximum or a
short-duration peak maximum. If the value represents a transient peak torque, then
other methods, such as a motor service factor margin should be investigated
before this value is used as the baseline for sizing. The design procedure then
calculates, from the maximum required torque at the required operating speed, the
motors power rating according to the motor power formulas and will establish
the system (bus) voltages. (See ANSI C50.41-1982 for list of preferred motor rated
voltages.) The nominal system voltages are slightly higher than the rated motor
voltage due to anticipated steady state voltage regulation in the power supply
system. Special attention to motor starting conditions is important for energy
efficient design. As with peak running loads, transient conditions should be carefully
vetted before they are allowed to form a minimum requirement. Other transient
conditions such as high ambient temperature should receive the same critical
profiling analysis as duty cycle. Worst-case estimation of ambient temperature may
lead to extra thermal margins and larger than necessary machines.
Average Load Sizing
Maximum load sizing is the default method for sizing, but the alternative Andreas
method uses average-load power. This average load sizing is only for applications
that do not require high inertia load starting or frequent starting, and which
operate at varying loads. Since motor heating is a limiting factor in sizing a motor,
this method uses the RMS (root-mean-square) losses, approximated by RMS
horsepower over the load cycle, to determine the thermal suitability of a motor. The
RMS horsepower is defined as that equivalent steady-state hp which would result
in the same motor temperature rise as that of a defined load cycle (See reference
Competitek, 1996, for an example calculation.) The calculated RMS hp will indicate
the required motor rating from thermal considerations, but the maximum peak load
must still be within the range of that motors service factor.
Motor Starting Conditions - Acceleration
The NEMA MG1 and ANSI C50.41 standards provide sizing rules based on the
torque required for accelerating the inertia of a rotating mass. Induction motors built
according to these standards develop at least 70% of their full load torque during
startup, which should be sufficient for most load applications.
Module 2 | 131
Motors serving high inertia loads such as fans, however, exceed the NEMA normal
inertia limits. These special motors required for those applications tend to be
oversized with additional thermal capacity to account for load torque and possible
low voltage conditions, factors which slow the acceleration time period and thus
allow the motor to accumulate more heat. See the example for determining
acceleration time of an industrial fan in the Fan Systems section.
Motor Starting Conditions - Voltage
Low voltage conditions during startup are a particular challenge for large motor
applications. The effect of low voltage starting conditions on developed torque is
magnified, because torque drops with the square of the applied voltage. Very long
acceleration times and increased heating or even the inability to reach full operating
speed are some of the consequences of inadequate design for startup.
For motors running in island mode networks, such as oil platforms, even smaller
motors might require starting methods other than DOL due to the lower short circuit
capacity of such networks (ABB Review, Ahlinder, 2001).
The three most common designs for motor startup are: 1) Direct-On-Line (DOL), 2)
Star-Delta 3) Soft-starters, which also include VFDs. Direct-on-line simply connects
the motor terminals directly to the supply network. DOL is the lowest capital cost
and most used system to start small squirrel-cage asynchronous motors. As shown
on the figure (left) below, starting is carried out at full voltage, high current and
with constant frequency; this develops a high starting torque with much reduced
acceleration times. This method is useful for full-load starting applications. High
inrush currents, first of 10-12 times rated current, then holding at up to 6-8 times
well into startup, will stress both the power system and motor.
Star-delta and soft-starters or VFDs are collectively referred to as reduced voltage
methods, with star-delta being the most common. In star-delta, inrush currents are
reduced by using first a star circuit, then switching over to a delta circuit during later
startup.
Figure 2.30 - Relative startup characteristics for different starting methods Ref (ABB Motors & Drives,
2007)
Carefully designed special lubrication and cooling systems will provide some extra
thermal support margin needed by the motor for high transient load conditions.
Existing motors can avoid being de-rated if extra cooling is available for such
situations. Learning more about the process load and duty cycle, then careful
calculation and proper mitigation efforts will help in right-sizing a motor under all
conditions.
A high-starting torque design motor has lower operating efficiency at full load. For
some applications with many starts & stops and short running times, however, a
high-starting torque motor may be the overall most energy efficient selection.
Motors in Retrofit Situations
Downsize an Underloaded Motor
An underloaded motor has poorer efficiency and power factor. These motors can be
identified in an energy assessment process. The replacement motor can be sized
based on the actual load factor; a 100 hp (75 kW) motor at 50% loading can be
replaced by a 50 hp (37 kW) motor. This replacement motor should be chosen to
have higher efficiency, but careful attention to slip is important.
In an economic analysis of motor downsizing performed by RMI in their Competitek
Drivepower Manual, an average 100 hp (75 kW) standard motor at less than 50%
loading can be downsized (to a much smaller, but slightly more efficient model)
for a payback in under 3 years, in a cube-law application. Additional benefits
of a downsized replacement motor are a smaller motor starter and smaller, less
expensive conductors (Competitek 1996).
Module 2 | 133
Many more tips for energy efficient motor systems can be found in the DoE EERE
(US DoE Best Practices, 2008) Motor Tip Sheet.
Motor System Maintenance
The large number of motors in a plant requires a comprehensive motor management
program to ensure they are managed cost-effectively. Such a policy helps bring
together capital, maintenance and revenue budgets, showing the effect they have
on each other when different types of motors are selected. Industrial users benefit
from such a policy through reduced energy costs, by upgrading to high-efficiency
motors at the most cost-effective time. The forward planning inherent in the practice
helps reduce downtime. Inventory can also be reduced through a fast track delivery
agreement. (ABB Review, Special report, Motors & Drives, 2005). Many technical
tips for motor systems maintenance can be found in the DoE EERE (US DoE Best
Practices, 2008) Motor Tip Sheet.
Module 2 | 135
Figure 2.31 - Torque-speed curves for idealized VFD, (ABB Drives 2002)
Module 2 | 137
using a VFD has major benefits in reducing pump wear, particularly in impellers,
bearings and seals.
There are some additional side-benefits for VFD-flow control in pumping systems.
With a VFD receiving a signal from a pressure transmitter, it is possible to monitor
the pressure of the incoming pipeline and configure the converter to take steps if
the risk of cavitation is high; i.e. if pressure falls below NPSHR plus a margin. Water
hammer is caused by rapid changes in flow. These flow changes are followed by
rapid pressure transients that cause pipes, pipe supports and valves to be damaged
causing leakage. VFDs allow the user to gradually ramp pump acceleration at a safe
rate to avoid hammering.
Despite the potential for 60% savings in many cube-law applications, only 5%
of all industrial motors are controlled by VFDs, and it is estimated that 30% of
existing motors can be cost-effectively retrofitted with VFDs (ABB Drives, 2006).
The potential is larger in smaller applications (under 2.2 kW) where 97 percent of all
motors have no form of speed control at all, equating to some 37 million industrial
motors sold annually worldwide (ABB Review, Special Report Motors & Drives,
2003). 40 percent of the value (and 90 percent in units) of all drives shipped are
rated at less than 40 kW.
Improved Motor Efficiency
Another benefit of VFDs is the improved energy performance of the motor itself. The
VFD control allows the motor to operate closer to its best efficiency point. The drive
can generate a family of characteristic curves for the motor, in the same way that a
speed-controlled motor generates a family of characteristic pump curves. In both
cases, the intersection with the load characteristic curve gives an operating point
which is near to the area of optimum efficiency for the equipment.
VFDs can correct for oversized motors by running them at reduced speed. The
operational benefits of such correction can justify a VFD even in applications which
do not call for speed control.
Compared to most other speed control methods described in the Motors and
DriveTrains section, with a VFD there is no loss due to mechanical slip between
motor and load.
Two and Four Quadrant Operation
Quadrant operation is the term used to describe a drives ability to provide braking,
reversing (2-quadrant) and regenerative (4-quadrant) power. The quadrant refers to
the space these modes occupy on a torque-speed axis shown in the figure below.
For loads which generate power for only a short time, then it is typical to offer only a
braking resistor where the power generated is dissipated as heat losses.
4
Decelerating
Accelerating
Accelerating
Decelerating
Active rectifiers will allow these losses to be regenerated into electrical power for the
network. The type of rectifier will determine if power can flow in both directions. A
conventional passive diode rectifier only supports motor loads where the power flow
is only in one direction.
Motor Soft-Starting
VFDs provide the same functionality as a dedicated soft-starter - a power-electronics
device installed in-line with the motor that slowly ramps up the voltage for a smoother
startup. Soft starting is mainly used to limit large motor starting currents and to better
manage power factor during startup so that the electric power system is not unduly
stressed. Soft-starting therefore improves voltage bus stability, reduces currents
and allows reduction in transformer size, and other power system hardware. There
is also reduced risk of process disturbance due to voltage drops; and fewer trips of
other electrical devices connected to the same bus. Most motors experience startup
in-rush currents that are 5 to 6 times higher than normal operating currents, which is
reduced to 1.5 with VFDs, thus reducing wear on the motor. Soft starting reduces heat
load and allows a greater number of starts within a given time period, increasing the
flexibility of the control system to optimize the process. (Motors not equipped with a
VFD or other form of soft startup power electronics are referred to as Direct-On-Line
(DOL) motors. ) Note that the load itself may also benefit from a smooth ramping up
of torque and speed. The sections on Motor Starting Conditions and VFD Starting
Torque Conditions discuss design criteria for startup conditions.
Module 2 | 139
Figure 2.33 Slip compensation of a VFD shown on motor torque vs. speed curve, (ABB Oy. Drives,
2002)
motor speed or torque setpoint. Having the PID controller onboard the drive reduces
loop latency to a minimum and allows faster response to process changes when
compared to central speed control. The extra responsiveness is useful in a few
applications with highly varying load torques, where precise speed control is a
requirement. VFD control can hold the process at a steady set point, instead of
exhibiting cycling that may occur with other means of speed control.
VFD programming tools are equipped with libraries of application-specific control
functions for pumps, fans, cranes etc. The control blocks in these libraries have predefined Input-Output characteristics and are optimized for these applications
Regenerative Braking
Some VFDs are able to harvest wasted energy through motors acting as
generators. This is also known as 4-quadrant operation. The LCI and VSI drive
types (described below) can be ordered with inverter-equipped front-ends that are
capable of such 4-quadrant operation. In conveyor systems with uphill and downhill
conveying, some VFD drives can manage energy sources and sinks using a common
bus principle, with optimum efficiency and energy flow between motors of motoring
and generating mode (ABB Switzerland, MV Drives, 2002 p.16, Fact Pack #2).
Inherent Motor Monitoring and Protection
VFDs have built-in power functionality needed to protect a motor from abnormal
conditions in the power supply or within the motor itself. Most critically, VFDs have
acceleration and deceleration ramp limiting functions and motor current limiters
to prevent driving torques which cannot be sustained by the motor. VFDs isolate
motors from the electrical supply line, which can reduce motor stress and inefficiency
caused by varying line voltages, phase imbalance and poor input waveform.
Many of these vital protective functions would otherwise require the installation
of separate devices. The most common protective functions are: short-circuit,
over current, unbalanced phase, ground fault, motor temperature, and motor
stall. VFDs also monitor for underloaded situations, as in the activation of safety
release mechanisms in the driven equipment, and will also detectphase loss on the
incoming side. If a problem is detected, the VFD will send a warning or an alarm to
operators, and initiate a drive trip.
Built-in monitoring of motor current and temperature, plus many other parameters
allows the VFD to detect, warn and even take action to mitigate the effects of certain
drive system problems. For example, if the motor current is oscillating, this may
indicate a problem at the couplings. No extra current transducer is required for this
monitoring. VFDs may also be programmed to take action when a faulty gearbox
or bearing sends a high-temperature signal when operating at full load, but no
Module 2 | 141
such warning at lower loads. In this situation, the VFD can decrease the load until
an appropriate time for maintenance on the faulty equipment. These monitoring
functions can improve the uptime of a plant, with benefits as described in the section
on Lifecycle Costing Calculations - Energy cost of a trip
Overspeed Capability
By controlling the frequency and voltage, VFDs can achieve higher motor speeds
than otherwise possible from only a fixed electric power supply. This overspeed
capability may be sufficient to handle modest production capacity increases without
the investment needed to replace the motor or actuator. Speed increases of 5-20
percent are not a problem for VFDs on most motors. This extra capacity is within the
ratings of most installed motors, which are specified with generous margins plus a
service factor. Margins and more details on over-speeding can be found in the NEMA
MG-1 standard.
Variable torque applications, such as pumps and fans, require increasing torque
with speed. If the intention is to run above the motors nominal speed, then it may
be necessary to oversize the motor due to the reduced torque in the field weakening
region.
Voltage Fluctuation Ride-Through
This feature is especially useful on weaker networks (for example, in industrial boiler
applications) with transient voltage dips; VFDs allow the motor to ride through
such dips thus avoiding a trip. Dips may last from a few cycles to a few hundred
milliseconds. See the section on Lifecycle Costing Calculations - Energy cost of
a trip
Voltage Boost and IR Compensation
At low speeds during startup (<20 Hz), a VFD can provide a temporary increase in
voltage to help motors achieve a higher breakaway torque, without the high currents
associated with DOL starting. One pitfall with voltage boost is the risk of overheating
of very lightly loaded motors at speeds under 10 Hz (Bezesky 2001). Voltage
boost applies a fixed extra voltage, but with IR compensation the extra voltage is
proportional to the motor current, as shown in the figure below. IR compensation
will therefore only provide extra voltage for motors under load and drawing current,
reducing the risk of saturation and overheating.
Both of these features apply only to voltage/frequency (scalar) drives, or vector
drives operating in scalar mode. Vector drives by design can generate higher
starting torques and do not need a voltage boost feature; these drives can provide
several hundred percent higher than nominal torque for motor starting. The ability of
drives to boost starting torque allows engineers in some cases to avoid oversizing or
selecting less-efficient high-torque motor designs.
Figure 2.34 Voltage boost at low speed, ABB VFD Programmable Features
Figure 2.35 - Small (LV) and large (MV) VFD hardware (ABB Drives, 2008)
Motor
Converter
3
Rectifier
Intermediate
DC Link
Load
Inverter
Figure 2.36 Diagram showing VFD nomenclature, (ABB Switzerland, MV Drives, 2002)
The most common converter topology is composed of three main equipment stages:
A front-end rectifier unit on the 3-phase supply side to convert AC to DC power
and to ensure that harmonics drawn from the network are kept within tolerance.
A DC link composed of one or more capacitors and inductors which filter and
smooth the DC voltage
An inverter unit, using one of the power electronics technologies described in the
sections below, performs the inversion and modulation of the voltage which is
applied to the motor windings.
The effect of these stages on the sinusoidal input AC supply is shown in the figure
below:
Figure 2.37 - VFD waveform at different stages, using PWM-type drive as an example (ABB Inc. 1998)
VFD Topologies
The main drive topologies which are in wide usage today are listed below, based on
descriptions from the ABB Drives Fact Pack #1, 2005.
Voltage Source Inverter (VSI)
This section is based on information in (Competitek 1996), (IEEE, 2007), and (ABB
MV Drives, 2002)
The VSI drive is sometimes referred to as a Variable Voltage Inverter (VVI) because
it achieves speed control by varying the voltage fed to the motor. In its simplest and
earliest form, the VSI inverters switching elements produced a 6 (or 12 or higher)
step voltage waveform output for the motor. The design of the VSI topology is shown
in the figure below. A common topology and control combination for low to medium
horsepower AC machines today is VSI hardware using PWM inverter control. The
high-speed PWM switching converter provides fast response, precise speed control
and maintains high PF over the entire speed range.
Un
Um
Rectifier
L1
Supply
L2
L3
Monitoring
Control
Um
DC
L
Inverter
Motor
+
c
V1
V3
V5
V4
V6
V2
U1
V1
w
M3-
Control electronics
control, manufacturing, communications
Figure 2.38 - VSI design schematic ABB (ABB Switzerland, MV Drives, 2002)
The main characteristics of a VSI drive with PWM are summarized below.
power range
: up to 8,000 kW (for 3-level inverters)
motor voltage levels : 2.3 to 6.9 kV
speed range
: 0 100%
has low starting current
does not contribute short-circuit current
not capable of regenerative operation,
high ac input power factor, near unity for entire speed range
converter efficiency >= 98%
PF is high and constant over entire speed range
low network harmonics, voltage reflections & voltage stress
Module 2 | 147
In the LCI design the DC current is switched directly to the synchronous machines
windings, which behave like a DC machine. LCI drives have a simple and robust
design because no special switching circuit is needed; the thyristors are switched
by the action of the current waveform of the load itself (Competitek 1996). A control
function using a feedback sensor in the motor prevents the rotor from falling out of
step. The LCI drive system can be furnished with regenerative braking capability,
which is discussed in the section on VFD Regenerative Braking. The main
characteristics of this drive type are:
Unmodified, it is suitable only for synchronous motors, with brushless or slip ring
excitation
Wide speed and power range 1- 80 MW
Speed control range (0)-10-100%
More expensive than other drives
Poor power factor at low speed
Suitable for continuous operation
Fans & pumps, compressors
Converter efficiency > 99%
A modified LCI drive with a large DC-link capacitor can use CSI technology to drive
either synchronous or induction motors. The capacitor also servers to shape the
waveform so that harmonic heating in the motor is reduced (Competitek 1996).
Cycloconverter
The Cycloconverter design does not use any intermediate DC circuit, which limits the
load frequency to a maximum of 83% of the line frequency (for cross-current type
of drive). Cycloconverters are used for high power, low speed synchronous motor
drives such as rolling mill drives, and ship propulsion. The main characteristics of
this drive type are:
Voltage
Module 2 | 149
Efficiency/%
90
80
70
50
0
10
20
30
40
70
100
Frequency/Hz
Figure 2.40 Efficiency improvement with DTC flux optimization, (ABB DTC Presentation, 2008)
Multi-Drive
In the multi-drive architecture, multiple inverters are fed from a common DC-link bus
and central rectifier unit. The individual inverters do not all have to have the same
power rating: a multi-drive package can consist of drives of very different sizes. A
higher overall VFD efficiency is achieved by eliminating the separate rectifier and
DC-link for each drive. In a plant with many drives, the total lifecycle savings can be
significant.
A multi-drive architecture also allows a cost-effective way to reduce energy-wasting
harmonics by installing a single active front-end supply unit or at least a 12-pulse
line supply. Another advantage of this technology is to be able to supply energy from
VFD Regenerative Braking from one motor to another motor in the group, without
the need for any additional power inter-connection equipment.
Module 2 | 151
Figure 2.41 - Multi-drive system1) rectifier section 2) common DC-link 3) drive sections 4) power supply (ABB Drives 2002)
Multi-drive systems are cost-effective in applications where there are several motors
installed close together, such as sets of conveyors, fan banks, pump banks or
in master-slave applications which require motor synchronization, such as paper
machines. Compared to set of single drives, these systems save cabling on the
power input side and allow faster replacement of faulty units. The cost of multi-drives
are decreasing, but these systems still require some engineering when compared
to single drive applications; this may explain why multi-drives are generally underutilized in industry. A lifecycle cost (LCC) analysis, however, may reveal energy
savings large enough to overcome a preference for standard, non-engineered single
drive products.
AC Motor Control Terminology
Discussions on motor speed or torque control require clarification of a few basic terms
in common usage. The Variable Speed Drive (VSD) term, as used in the Pump and
Fan sections of this handbook, refers to any means of modulating the output shaft
speed given a constant input shaft speed from the source of drive power. Another
common and equivalent term to VSD is ASD: Adjustable Speed Drive. A variety of
methods to vary shaft speed are discussed in the Motors and Drive Trains section.
In some industry texts the broader term VSD is used even when VFD control is meant.
Sometimes, only the word drive or converter is used to refer to a VFD, and some
technical sources may incorrectly refer to the entire VFD as only the inverter. The
naming situation is further complicated when AC torque control drives, also known as
vector drives, are included. The preferred, and least ambiguous, term for all these AC
drive technologies is Variable Frequency Drive, abbreviated as VFD.
152 | ABB Energy Efficiency Handbook
The discussion in this section is limited to the application of VFDs within an industrial
process, and the drives interaction with the motor and the load. For a discussion on
how VFDs may impact power quality of the electric power system, see the section
on Electric Power Systems.
Speed and Torque Performance
If a motor is driven without a VFD, then its performance characteristics cannot be
modified; the motor will produce only the torque at a certain speed given by its
torque vs. speed curve and specified values for starting, breakdown and full-load
torque as shown in the figure below (left side). When started direct-on-line (DOL),
the motor accelerates continuously, passing through these points until it reaches its
nominal operating torque and speed.
Figure 2.42 Torque-speed curve for a motor (left) and a VFD-equipped motor (right), (ABB Drives
2002)
With a VFD, however, the input voltage and frequency can be continuously
modulated so that a family of characteristic torque-speed curves is available over the
nominal speed range, as shown on the figures right side. The actual operating point
of the drive system is the intersection between the active torque-speed curve of the
drive-motor combination with the torque-speed characteristic curve of the load.
A VFD is commonly used in speed-control mode, in which the torque is determined
by the load. Some VFD designs allow a torque control mode, in which the speed is
then determined by the load.
A VFD can drive and hold the motor at any point along any of these characteristic
motor curves, limited only by the thermal capability of the motor and the load on the
motor. The VFD can hold the motor at Tmax for short-term overloads. In practice,
VFDs typically will limit the maximum available torque to 70% of Tmax.
Newer VFD designs, however, can achieve high breakaway torques, typically 2 times
nominal torque.
Module 2 | 153
be calculated by multiplying the total current by the power factor, also shown as
cos(n).
In the constant flux region (below field weakening point):
In the constant flux region the motor currents do not depend on speed. The active
current can be approximated as follows:
I a = In x (Tload/Tn) x cos(n)
Where:
In = nominal (nameplate) current
At higher torque values motor current becomes nearly proportional to the torque. A
good approximation for total motor current at a given load is as follows:
Im = In x (Tload/Tn) when Tload is between 0.8 x Tn and 0.7 x Tmax
For example: a 150 kW motors nominal current is 320 A at power factor 0.85.
What are the approximate active and total currents at 120% torque, below the field
weakening point? Using the approximation formulas from above:
Ia = 320 x 1.2 x 0.85 = 326 A
Im = 320 x 1.2 = 384 A
In the decreasing flux region (above field weakening point), the motor currents
depend on speed. The active current can be approximated as follows:
Ia = In x (Tload/Tn) x ( n/nn ) x cos(n) = In x (Pload/Pn) x cos(n)
Where:
P n = nominal (nameplate) power
Within a certain operating region the total motor current becomes proportional to the
relative power.
I m = In x (Tload/Tn) x ( n/nn ) = = In x (Pload/Pn) when Tload is between 0.8 x (nn/n) and
0.7 x (nn/n)2 x Tmax
Module 2 | 155
For example: a 150 kW motors nominal current is 320 A. How much current is
needed to maintain the 100% torque level at 1.3 times nominal speed (assume Tmax
=3 x Tn)? Using the approximation formula above:
Im = 320 x 1.3 = 416 A
For additional motor power and torque formulas see the Motor and Drive Train
section.
Drive Efficiency
Efficiency levels of MV AC drives vary from 95 to 99%, including the supply
transformer, power factor correction equipment and any harmonic filters. A typical
VFD efficiency curve stays relatively high (above 90%) and constant until about 20%
of full load. At loads below 20% full load, the VFD efficiency drops to between 75%
and 90%. This drop is partly because the losses in the drive electronics account
for an increasing proportion of the input power. The extra protective circuits which
are often built-into modern VFDs, such as suppressors and line reactors, improve
reliability but they come at a slight cost in drive efficiency (Liptak, 2005). Vendors of
VFDs may promote small drive efficiency margins over other vendors, but these are
tiny compared to the efficiency gains of the entire drive power system, VFD, drive
train and pump or fan. Engineering support, programmability and other factors will
likely play a more important role in total drivepower system efficiency, which is the
only valid basis for comparisons and design decisions.
VFD Harmonics
A harmonic is a sinusoidal component of a periodic wave or quantity having a
frequency that is an integral multiple of the fundamental frequency. Harmonics are
caused by the non-linear switching action of VFD inverter electronics. The rapid step
changes in voltage levels found in most drive outputs, and especially in PWM drives,
create flux harmonics and heating within the motor. Rotor heating from PWM drives
can range from 30% to over 300% more than with only 60Hz input power, depending
on the type of modulation control used (Competitek 1996).
High harmonic content coming from early frequency converters led to heating
of motor windings and the practice of de-rating the motor 5-10% for use with
VFDs. Modern VFD drives now output low levels of harmonic content and
perform according to the detailed standards in IEEE 519 and NEMA MG1 Part 31
specifications (or G5/3 n the UK); it is usually no longer necessary to de-rate a motor
for use with a VFD (US DoE, 2008).
Harmonics tend to be drawn from the supply network and may affect other electrical
equipment. For a discussion of the energy impact of these supply-side harmonics,
156 | ABB Energy Efficiency Handbook
and of ways to mitigate their effects, see the Electric Power Systems section
Harmonics Mitigation.
VFD Application Design and Engineering
After two decades on industrial service, VFDs have evolved to high levels of reliability
and functionality. Early VFD pitfalls have been eliminated in modern VFD designs.
On the motor side, early pitfalls encountered with VFD applications were related to
harmonics and voltage spikes, which induced heating and led to motor damage.
On the power side, early pitfalls with VFDs were line interference, power system
harmonics and poor power factor at low speeds.
VFD Trends
Advancements in power electronics and usability are moving drives toward the
status of a commodity item. In the past, all drives were considered engineered
items which suppliers (such as ABB) would configure based on detailed application
specifications that the customer would put out to tender. Engineered drives with
custom capabilities may still be required for applications with special loading
profiles, special environmental conditions, or where plant power supply issues
such as harmonics and phase unbalance pose a particular challenge. Most drives
have features that handle these issues out of the box for approximately 85% of all
applications (ABB Drives, 2006). All drives are available as separate devices, but
often component drives are embedded in small-scale OEM equipment solutions
requiring speed control.
Although VFDs are becoming more of a commodity item, careful engineering
following the guidelines below will help to address most of the problem areas and to
achieve the expected efficiency improvements.
VFD Selection and Sizing
The following sections provide an overview of the steps involved in dimensioning a
drive system. This overview focuses on energy efficiency aspects; for more complete
guidelines see the full ABB Technical Guide No.7 for Dimensioning a Drive (ABB
Drives 2002) upon which this section is based, or the NEMA Application Guide for
AC Adjustable Speed Drive Systems 2001, IEEE Paper No. PCIC-2001-7.
Select Drive Size & Rating
Standard drives can be selected from the catalog and with some vendor assistance,
based on inputs from the process, mechanical and electrical application engineers.
The requirements for each of the four main elements in the drivetrain system are
shown in the figure below.
Module 2 | 157
The typical dimensioning steps for a drive and motor system are listed below.
These steps apply mainly for variable torque applications, such as a pump or fan
application. Details and example calculations for each step are given in the ABB
Technical Guide for Dimensioning of a Drive System, 2002.
Step 1: Check initial requirements and conditions of network and the load
1.1 Required
1.2 Required
1.3 Required
1.4 Required
speed
Figure 2.44 Motor loadability curves comparing 1) 2-pole and 2) 4-pole motors
2.1 Determine the required maximum load torque at full speed - narrow
selection of motors
2.2 Check motor loadability. using torque profile curve, at the nominal speed
and then over the required speed (rpm) operating range
2.3 Check for high application load torque starting conditions
2.4 Determine motor nominal torque and power, based on number of motor
poles
2.5 Select a new (or approve an existing) motor; add a margin (from 10 to 30%,
depending on loading information certainty) so that power is available at
maximum speed.
Step 3: Choose a VFD and associated equipment
3.1 Determine type of load (cube law, constant power, constant torque,
quadrant operation)
3.2 Determine total motor continuous current (Amps) at full speed
3.3 Specify any special operating conditions and required IP (enclosure) class
Module 2 | 159
In practice, the manual selection & sizing process outlined above is complemented
by engineering software tools as discussed in the section on VFD Sizing and
Selection Tools. Vendors normally have certain selection tables where typical motor
powers for each converter size are given; these tables are also incorporated into the
software tools.
For example: a pump has a 300 hp (224 kW) load at a speed of 2000 rpm; there is
no special starting torque requirement.
Step 1: First find the necessary load torque:
T = 300 x 5252 / 2000 = 788 lb.ft (SI: T = 9550 x 224/2000 = 1070 Nm)
Step 2: Check the loadability for a few candidate motors:
For a 2-pole motor at 2000 rpm, loadability is 95%, which means that the nominal
torque must be at least:
T n = 788 / 0.95 = 830 lb.ft (1125 Nm)
For which the nominal power must be at least:
P n = 830 * 2000 / 5252 = 316 hp, so a 350 hp motor ( 1975 rpm , 460V, 500 A, PF
0.87) is chosen.
The nominal torque of that motor is:
T n = 350 x 5252 / 1975 = 913 lb.ft (262 Nm)
The motor current at 2000 rpm (in the constant flux range) is approximately:
I M = Pload x In / Pn = Tload x In / Tn = 788 x 500 / 830 = 474 A
The continuous current used to select a VFD is then 474 A.
For a 4-pole motor, loadability at 2000 rpm is 75%
The same series of calculations reveal that the motor current is less than that for
the 2-pole motor at the operating speed, so the 4-pole motor is chosen as the most
energy efficient.
Module 2 | 161
damage motor insulation, and are a particular concern in MV retrofit situations (ABB
Switzerland, MV Drives, 2002). Some preventive design tips for inverter-fed motors
are 1) use input and output reactive filters and 2) ensure that the grounding system
is well designed. According to one source, (Competitek 1996), PWM drives cannot
tolerate long cable lengths (longer than 500 m due to standing wave effects. It is
important to consult with drive vendors and their expertise before specifying VFDs
with long cabling to motors.
Radiated EMI
Output Filter
3-Phases, Earth
VSD
Conducted EMI
Input Filter
Radiated EMI
Conducted EMI
MOTOR
Figure 2.44 EMI disturbance from VFD (shown as VSD above) cabling, (DeAlmeida, 2006)
Circulating currents can also be induced in the walls of metal conduits, even when
it contains balanced phases. A preventive design tip is to use non-metallic conduit
material, such as PVC (Competitek 1996).
Motor Capability - Resonance Issues
The following issues may arise due to complex, dynamic interactions between the
VFD drive-electric motor and pump (or fan) system. These unwanted dynamics
are usually eliminated for maintenance or reliability reasons, but they also degrade
system energy efficiency if allowed to continue at a level judged tolerable for the
equipment. This phenomenon is also called torque pulsation in some technical
sources.
Structural Resonance. Resonance is a mechanical vibration phenomenon
that occurs when the VFD output frequency matches the one of the natural
frequencies of the entire pump, piping, and mounting system. The strong
vibrations at these particular frequencies are harmful to the motor and pump
equipment couplings, bearings and support structure.
These resonances are usually designed-out of pumps and motor combinations
operating at known constant speeds. In variable speed applications however, the
wide variation in motor frequency may uncover new resonances, especially those
resulting from fluid pressure pulsations. Pumping system authorities (US Doe,
Hydraulic Institute, Europump) recommend the following techniques to predict
and avoid resonance situations (US DoE, 2008):
Simple hydraulic resonance calculations
164 | ABB Energy Efficiency Handbook
Figure 2.45 - Motor torque performance curves possible with VFD control, (ABB Oy. Drives, 2002)
A heavier-duty VFD may be required for applications with high starting torque
requirements, or where there are high torque pulsations (Competitek 1996). The
NEMA Application Guide for AC Drives (2001) cautions that applications with
static torques above 140% of full load torque may require an oversized drive and a
motor with higher torque capacity. Vector drives are an alternative solution to this
application requirement.
Variable torque loads such as most pumps (and some fans) have low torques at
low starting speeds. Constant torque applications typically have higher starting
torque requirements than variable torque loads. High-inertia rotating machinery,
Module 2 | 165
such as very large fan, however, may require special attention to achieve startup,
as discussed in the Fan Drivetrain section. One possible solution is to bypass the
VFD during startup, allowing the motor to develop to its full breakaway torque to get
the load moving. See NEMA-MG1 and the NEMA Application Guide for AC Drives
(Bezesky 2001) for some special precautions regarding this approach.
Constant torque applications typically have higher starting torque requirements
than variable torque loads, and stricter requirements for acceleration and torque
repeatability. Although VFDs, properly sized, can satisfy these applications, they are
also good candidates for vector control drives. A vector control drive can provide
more precise torque control and much higher low-speed torque than scalar drives.
Soft Starting Torque
A common torque vs. speed curve for a VFD-equipped motor is a gentle ramp up
to maximum continuous torque at about 30% of rated speed, then a horizontal line
meaning constant torque all the way up to 100% of rated speed. Compared to a
simple soft-starter, VFDs have the advantage of being able to adjust the ramp time for
the voltages and frequencies at the motor terminals, as shown in the following figure.
Figure 2.46 - VFD adjustable startup- speed vs. startup time, (ABB Oy. Drives, 2002)
The figure below shows how VFD driving torque adjustment can be engineered to follow
the load torque for optimal energy and acceleration time performance during startup.
35
120
30
100
25
80
20
60
15
40
10
20
0
0
500
1000
Driving torque
1500
2000
Load torque
2500
3000
Acceleration time
3500
Time [s]
Torque [kNm]
0
4000
Speed [rpm]
Figure 2.47 - Load torque, run-up torque and time as function of speed, (ABB Switzerland, MV Drives,
Ormen Lange case, 2008)
In power plants, flying start capability can prevent a unit shut-down in the case
of a temporary trip of the ID or FD fan. These large fans normally take a long time
to decelerate, necessitating a boiler shut-down and a long re-start of the unit. A
flying start allows the drive to re-accelerate the rotating fan shaft and avoid a boiler
shutdown.
when equipped with a VFD. The effect of extra cooling is shown on the following
figure. The following figure shows how an actual VFD can provide near-constant
torque from zero to nominal speed, if sufficient cooling is available to maintain a
constant nominal operation temperature for the motor; values with subscript n are
nominal values. Note that torque is limited in the field weakening range of operation
regardless of cooling method.
Figure 2.48 Standard induction motor loadability 1) without and 2) with separate cooling, (ABB
Drives 2002)
With VFD speed and torque overdrive, a motor may be dimensioned according
to its normal use, not for transient peak conditions, thus reducing motor size and
investment cost. Where loading peaks are expected, however, it is important that the
load, the VFD and the motor are compatible, otherwise the motor or the converter
may overheat and increase the risk of damage.
Figure 2.49 - Torque-speed curves with VSI-PWM VFD and 2 types of load, (based on deAlmeida,
2006)
This figure shows torque and power for a totally-enclosed fan-cooled (TEFC)
induction motor fed by a VSI-PWM type VFD, assuming. Two typical load curves are
shown; constant and quadratic (i.e. cube-law power load) torque. These loads can
be served by a normally-sized VFD. Loads with high starting or breakdown torque
requirements require more careful sizing and selection of the VFD.
Drive Loadability and Cooling Issues
Energy losses in the VFD cubicle are a measure of the drive efficiency. For drives
averaging 98% efficiency, therefore, the heat energy is 2% of the input power. This
heat must be removed from the VFD, usually through forced cooling. It is important
to ensure sufficient drive module cooling and to include the drive fans and cooling
system in a regular maintenance program.
Generally speaking, a frequency converters short term loadability is often more
critical than the motors. The motor thermal rise times are typically from 15 minutes
(small motors) to several hours (big motors) depending on the motor size. The
frequency converters thermal rise times (typically a few minutes) are given in the
product manuals (ABB Drives 2002).
Proper application design and regular maintenance are the key to realizing drive
suppliers claims of mean-time-between-failure (MTBF) specification somewhere
between 20 and 100 years. Advances in technology however, are likely to prompt a
facility to upgrade a drive within a shorter time frame. The life expectancy of the VFD
converter is generally directly related to the temperature of the internal components,
especially the capacitors (US DoE, 2008).
Module 2 | 169
Figure 2.50 Photo of a large input isolation transformer, (ABB Drives, 2008)
Operating Environment
Due to the sensitivity of drive electronics, in retrofit situations the VFD hardware
cannot usually be placed in the same location as previous mechanical speed
reduction equipment (US DoE, 2008). VFDs electronics are housed in an enclosure
called a cubicle. Like most electronics, the VFD cannot normally tolerate corrosive,
very humid or very hot ambient conditions. For this and other reasons related to
cooling (see the section on Drive Cooling), the VFD cubicles are usually placed in
a separate electrical room, usually together with low-voltage switchgear & motor
control centers. Typical dimensions for a large VFD cubicle are 916 ft long, 3 ft
deep and 6 ft high. VFD drives and switchgear can be housed in modular prefabricated units for easy site installation and limited civil engineering costs.
Figure 2.51 Photo of a typical MV drive cubicle ABB Drives, 2008 (ACS-5000 Medium Voltage drive)
VFD Maintenance
Availability (the inverse of failure rate) of a modern VFD is typically in the high 99+%
range. VFDs provide online diagnostic information of the status of the drive and
Module 2 | 171
Figure 2.52 - Screenshots of DriveSize motor sizing and selection tool, showing loadability of motor in
a pump or fan application, with quadratic torque load, (ABB Motors & Drives, 2007)
Module 2 | 173
Module 3
Electric Power Systems for Auxilaries
Module Summary
This module provides general design & energy impact of the most common
components of in-plant electrical power system, also known as Electrical Balance
of Plant (EBoP). Most of the material in this section is applicable to all industrial
electrical power systems. The purpose of this section is to help identify areas of
controllable losses in medium and low-voltage (MV and LV) plant power systems and
to provide some guidelines to mitigate those losses.
The information in this module may be generally applied to all industrial facilities
industries with large internal power distribution networks; industry-specific text is
shown in alternate text, such as follows:
For power plants, the scope for this module begins at the generator busbars
connection to the auxiliary transformer(s), but also includes the power path
leading through the main step-up transformer. The relationships between electric
power system balance of plant (EBoP) items are shown in the figure below.
Figure 3.1 Electrical balance of plant equipment in a fossil-fuel power station, ABB Power
Systems, 2008
Module 3 | 175
This section examines power systems from an energy efficiency perspective and
does not provide guidance on other, critical aspects of power system engineering
such as protection & control, safety, or installation. For more complete guidance on
all other aspects of power system design, see both the standards and references
sections of this handbook.
In a power plant, most of the auxiliary power demand, up to 80% of total auxiliary
load, is used by large MV electric motors that are typically connected to the medium
voltage switchgears/switchyards supplied through unit auxiliary transformers.
Between 6 to 15% of gross electrical output can go to auxiliary power, depending
on the type of prime mover for large pumps and fans, the type of fossil fuel, and
the required environmental control systems.
Module 3 | 177
Reactive power is the power required to bring electrical components to the status of
operation when magnetization or induction is involved, as with generators, transformers,
and motors. Though necessary for operation, reactive power does no useful work and
simply circulates within the network.
Apparent power is the angular sum of Active and Reactive powers derived from the
following formula:
S= (P2 + Q2)1/2
Where:
S = Apparent power (volt-amps)
P = Active power (watts)
Q = Reactive power (volt-amps reactive)
Power factor is the angular relationship between the Apparent power and the Active
power; this phase angle is represented by the Greek letter , and the power factor is
defined as the ratio P/S or cos()
The following formulas describe power in 3-phase systems:
Apparent power
S=UxI
Active power
P = U x I x cos()
Reactive power
Q = U x I x sin()
Power factor (PF)
cos() = P/S
Apparent Power S
Measured in VA
Reactive Power Q
Measured in VAR
Phase angle
Active Power P
Measured in Watts
Figure 3.2 The power triangle diagram
For a symmetrical 3-phase system, these same formulas can also be expressed as
follows:
= 31/2 x U x I1
S = 3 x U1 x I1
P = 3 x U1 x I1 x cos()
= 31/2 x U x I1 cos()
= 31/2 x U x I1 sin()
Q = 3 x U1 x I1 x sin()
Where:
U = rms value of the phase to phase voltage
U1 = rms value of the phase to neutral voltage
I1 = rms value of the phase current
The unit for all forms of power is the watt (W). The unit watt is also called volt-ampere
(VA) when stating electric apparent power and volt-ampere-reactive or simply Var (VAR)
when stating reactive power.
Harmonic Power, not shown in the power triangle figure, is power which is dissipated at
higher harmonic frequencies.
A harmonic is a sinusoidal component of a periodic wave having a frequency that is an
integral multiple of the fundamental frequency (i.e. 50 or 60 Hz). Harmonic Distortion
factor (DF) is defined as the ratio of the root-mean-square (RMS) of the harmonic
content to the RMS value of the fundamental wave, expressed as a percent of the
fundamental.
The distortion factor (DF) is applicable to the definition of the total harmonic distortion
(THD) for voltage harmonics and the total demand distortion (TDD) for current
harmonics.
DF =
* 100%
Fixed losses, also referred to as iron or core losses, occur mainly in the
generators/motors/transformer cores and do not vary according to current load,
beyond the threshold required for energizing. (Leonardo Energy, 2008).
If harmonics are present, then iron losses in transformers will vary with the current, as
discussed in the Transformer losses section, Effect of Harmonics.
It has to be noted that, not only do copper losses in electrical devices increase direct
power consumption, but they also produce heat. To keep the device within the
tolerable heat range, equipment shall be cooled either individually (e.g. fan or pump in
transformers) or centrally by introducing HVAC (Heating, Ventilation and Air Conditioning)
to the electrical enclosure or room. These additional cooling systems will further
decrease the overall net produced energy. Generated heat will affect the aging of the
electric components as well.
Power Factor
Lagging PF is due mainly to the reactive power demands of large inductive loads
such as induction motors. Reactive power does no useful work, but all plant power
system elements must nevertheless be sized to accommodate it. A high PF system is
considered to have values between 0.9 to 1.0, and low PF systems have values less
than 0.8 for in-plant power supply. The disadvantages of low power factor are:
Increased losses: the current that carries reactive power leads to losses in
electrical devices such as transmissions, distributions and in transformers. These
I2R losses are real power and reduce the overall efficiency of the system.
Reduced capacity: generators, transformers and other power system equipment
carrying reactive power have a consequently reduced capacity for carrying real
power.
Increased maintenance: The heat, which accompanies these losses, often leads
to reliability and maintenance issues and decreased component lifetimes.
Reduced voltage regulation: low PF worsens systems voltage regulation of a
transformer (RMI-Competitek,1996)
Most industrial customers, with the possible exception of utilities themselves, are
penalized by the electric utility for low plant PF. Industrial process plant PF typically
ranges from 0.87 to 0.95, but best practice calls for a 0.95 total PF (including
harmonics) and a fundamental PF greater than 0.97. Another design goal is to maintain
high PF over the entire normal operating range of the equipment.
For coal-fired steam power plants the power factor of aggregated plant auxiliary
loads, at the auxiliary transformer, is typically around 0.80~0.85 (ABB EBoP
2008). Note that this PF is lower than the industry averages described above.
The power factor at the unit step-up transformer is a bit higher, typically at 0.85 to
0.90, but may vary considerably depending on the type of customer loads served.
Module 3 | 181
=
=
=
=
Recall that is the phase angle and that PF = cos , so therefore = arcos (PF).
More detailed formulas and sample calculations for sizing of passive central
compensation circuit elements are from www.leonardo-energy.org, under the
subject of Centralized Reactive Power Compensation
Motor Soft-Starting
The power system is stressed by direct on-line (DOL) motor starts; large induction
motor DOL startups draw 5 to 8 times the normal operating current for a sustained
period and at low power factor. Soft-starters typically reduce individual startup
currents to only 1.5 to 2 times the operating current, improving PF during startup,
but without speed control capability during normal operation. The reduced inrush
current reduces the heat load on the motor, allowing more frequent starts between
182 | ABB Energy Efficiency Handbook
cool-down periods. Soft-starting also allow the engineer more flexibility in right-sizing
the components of electrical power system by reducing the peak loading.
See the section Motor Starting Conditions for more requirements on motor
starting, and their connections to the power system.
The term soft starter usually refers to a class of power electronics devices capable
of ramping up voltage to achieve a smooth motor startup. It is important to note that
VFDs can also provide soft-starting capability, along with the added benefit of
high and constant PF across the operating speed range. When operational speed
control is not required, however, soft-starters may be the more economical choice.
Static Synchronous Compensators (STATCOMs, described in the previous section)
also provide soft-start capability. Unlike most VFDs, however, compensators can be
serviced while the motor is running.
Synchronous Motors for PF Compensation
The IEEE standard Std. 666-2007 suggests that synchronous motors used on
continuous loads can be run with a leading power factor and thus compensate for
lagging power factors from other, smaller motor loads that are running throughout
the day. Because of their separate source of excitation, the load of synchronous
motors can be increased without requiring any additional reactive power (the unity
power factor motor), or the load can be increased and the motors will supply reactive
power as well (0.8 power factor or overexcited motor). This recommendation applies
only to continuous, low-speed and high-power applications. Also, the corrective
benefits are at the major bus level in the plant; so losses due to poor PF on lowerlevel busses are not avoided (Competitek, 1996).
VAR Compensators
Network users on the demand side of the step-up transformer pay for both real
and reactive power. Real power is billed by actual megawatt-hours consumed,
but reactive power is billed as a demand charge based on the maximum required
within the period. Statistically aggregated maximum demand will help determine
the individual units generator capacity and PF excitation level. When more reactive
power is demanded, then the excitation may deliver it (within the generator capability
curve), but the capacity for productive real power (MW) from the generator will
be reduced. Freeing the generator to supply more real power would increase the
capacity of the unit and the transmission lines to their maximum, thermal limits.
The amount of reactive power that the network demands from the generator is
not constant; these mega-VARS (MVAR) can vary considerably, in both leading
and lagging modes, throughout the day. Activation of a large industrial load on the
Module 3 | 183
network will change the VAR demand on the network, for example. To manage
changing network power factor needs, utilities may install sets of capacitors and
reactors which can be mechanically switched in or out of service. These devices are
known as mechanically switched capacitance (MSC) and reactance (MSR), and can
be operated in under a second.
Some dynamic network events, such as lightning strikes, short circuits, or other
faults, require a much faster and more accurate compensation response by
the utility. Static VAR Compensators (SVCs) use the same power electronics
technologies found in VFDs to switch in (or out) VAR-compensating elements as fast
as 2 times per cycle. The term static refers to the solid-state electronics lack of
moving parts in this device when compared to mechanical (MSC or MSR) or rotating
devices. SVCs are more expensive than the mechanical compensators, but they
are continuously controllable, offer much faster and more precise response, without
regard for hysteresis in the load pattern. In practice, these two VAR compensation
methods are complementary; mechanical devices can switch in large steps, and the
SVC can be used for fast and fine tuning of the compensation.
Figure 3.3 SVC switches for reactance (left) and capacitance (right), (ABB Grid Systems,2009)
VAR compensators can be placed at any point in the electrical power system;
near the generator source, in the grid, or near the large consumer loads. VAR
compensators can increase the net real power output of the generator, but they are
not without small losses. These small losses can be further minimized by specifying
more, smaller increments of capacitive and reactive elements, based on an LCC
analysis.
The following case material was provided by Brian Scott of ABB Grid Systems.
A generator with rated output of 695MVA is currently producing 625.5 MW. The
utility operator wishes to increase the real power output to 693 MW, an increase
of 67.5 or almost 11%. The PF requirements are from 0.9 leading to 0.95 lagging.
184 | ABB Energy Efficiency Handbook
The generator capability (P-AQ) curves in the figure below show the amount of
reactive power required for each of these limits, without (left) and with (right) SVC
compensation. Before starting an SVC design, it is recommended that power
flow and voltage stability studies be performed. As with other compensation
technologies, a harmonics analysis of the entire system is also necessary. And, as
with all large equipment in the power system, a detailed understanding of the load
pattern is important for engineering an optimal solution and for determining the
desired operation points that minimize losses.
600
400
300
Reactive Power (Mvar)
400
200
-200
200
100
0
-100
-200
-400
-300
-400
-600
0
100
200
300
400
500
600
700
-500
685
690
695
700
Active Power (MW)
705
Figure 3.4 Generator capability curves before (left) and after (right) SVC Var compensation, (ABB
Grid Systems, 2009)
Module 3 | 185
In one case where PF was increased from 0.8 to 0.95, the efficiency of the
GSU transformer increased by 0.06% due to PF improvement alone. For stable
operation and other practical reasons, the PF at the generator cannot be
increased much past 0.95.
L
Cos
M
Induction
Motor
MV BUS
ARU
DC-Link
INU
Figure 3.5 Schematic of VFD with active rectifier unit circuit, (ABB USCRC, 2008)
Figure 3.6 P-Q diagram showing ARU capability, (ABB USCRC, 2008)
186 | ABB Energy Efficiency Handbook
The benefits of ARU compensation functions are twofold 1) Full balancing the
reactive power demand of all auxiliary loads and thus gives the possibility for
the generator to produce more active power, 2~3% of rated capacity while still
maintaining the required external reactive power capability 2) Reactive power
compensation from ARUs can improve the plant leading phase operation capability
and also plant auxiliary system operation performance under various disturbances
such as suppressing transient over-voltage or under-voltage caused by generator
load rejection.
Figure 3.7- Harmonics-induced damage, (ABB Kurt Schipman ,Active Filter Savings, 2008)
Module 3 | 187
Harmonic pollution may also cause kWh meters to give faulty readings; these
devices are important for monitoring energy consumption.
Harmonics are said to distort the pure 60Hz sinusoidal waveform that carries useful
power from the source. The summary effect of these waveforms yields the Total
Harmonic Distortion (THD) measure.
Figure 3.8 Graph of high harmonic content 50 Hz waveform, (ABB Kurt Schipman)
Figure 3.9 Graph of harmonic current magnitudes of the above waveform, (ABB Kurt Schipman)
Although limits vary in different areas, the IEEE 519-1992 (USA), G5/4 (UK) standards
limit THDV 5% and limit for each harmonic component. The worldwide standard IEC
61000-2-4 also limits THD. This limit is acceptable even for very sensitive loads. These
standards also provide detailed harmonics mitigation design guidelines.
VFD-Induced Harmonics Concepts
Under ideal operating conditions, the current harmonics generated by a p-pulse linecommutated converter can be characterized by Ih=I1 / h and h=pn 1 (characteristic
harmonics) where n = 1, 2, ... and p is an integral multiple of six. In cases of nonideal conditions (e.g. unbalanced converter input voltage, unequal commutation
reactance,..), other harmonics can emerge: even, triple, odd non-characteristic and
non-integral (inter-harmonics) harmonics belong to this group.
Harmonics Mitigation
It is considered best practice to reduce harmonics in the system at their point of
origin. Installing filters near the harmonic sources, such as with VFDs, can effectively
reduce harmonics. By using an individual passive filter for each VFD instead of a
large centralized filter, one can also avoid the potential problem of over-correction at
low loads. Also, the VFD with filter and motor with may then be moved elsewhere in
the plant, to different buses without any re-engineering of a central system. The next
best placement of filters is at the nearest switchboard or feeder switchgear.
Harmonics Mitigation Using Passive filters
The following section is adapted from material by ABB Kurt Schipman Active Filter
Savings, 2008, and Dr. Amory Lovins in Competitek,1997.
For large, easily identifiable sources of harmonics, conventional passive filters
designed to meet the demands of the actual application are the most cost efficient
means of eliminating harmonics. These filters consist of capacitor banks with
suitable tuning reactors and damping resistors. In addition to harmonics mitigation,
these filters also perform PF correction because they act as a capacitor at the
fundamental power frequency.
Some disadvantages of passive filters are listed below:
Offer a low impedance path to harmonics
Tuned below the first harmonic that exists in order to minimize resonance risk
Filtering efficiency depends on network parameters, hence filtering performance
cannot be guaranteed
Danger for overloading due to load increase or background distortion, difficult to
extend
Multiple branches required for filtering more than one harmonic
Multiple branches required for filtering multi-pulse arrangements
Large space requirement and weight
Always provide capacitive power: but AC drives do not require capacitive power
Generators may not cope well with leading power factor
Sizing rules not yet adapted to modern load types
In LV applications, passive filters are used less and less
Module 3 | 189
Figure 3.10 Passive filter performance vs. frequency, (ABB, Schipman Active Filter Savings, 2008)
Load
icompensation
Coupling
system
Active Filter
Figure 3.11 Active filter with load schematic, (ABB, Schipman, 2008)
The highest amplitude harmonics are usually the 5th and 7th harmonics; these can
be removed by using a 12-pulse uncontrolled diode bridge rectifier. A 24-pulse unit
can be used for weaker networks or where more stringent THD requirements apply.
VFD-Induced Harmonics Mitigation
There are several approaches to mitigating harmonics induced by VFDs in the power
supply system. The main methods are:
Module 3 | 191
Increasing the resolution of the drive inverter by selecting those with a higher
pulse count .
Adding properly tuned filters on the supply line to the VFD.
Newer technology active front-ends for the drive typically reduce harmonics
induced on the supply side.
A comparison of the harmonic content between 6 and 12 pulse rectifiers is shown in
the figure below:
Figure 3.13 Harmonic distortion for 6 and 12 pulse rectifiers, (ABB Industrie AG, 2006)
Higher power applications (large MV drives) typically will use harmonics-free or highpulse (18 pulse or higher) inverters to better distribute the load internally. An ideal
18-pulse drive will eliminate the 5/7/11/13th harmonics, but not the 17/19th (harmonics
created are pulse number +-1). A harmonics analysis will reveal if these harmonics are
problematic. For very large drive systems, 15MW or larger, a common solution might
be a 12 (or 24)-pulse diode supply and passive filters on the line side or alternative a
36-pulse drive without a filter. A third approach is to specify a drive with active front end
(Active Rectifier Unit: ARU) to control harmonics on the supply-side.
Case Example
Harmonics in a Pumping Cluster
The figure below shows line voltages & line currents at pumping cluster; the values
for harmonic distortion were THDV = 12%, THDI=27%
750
500
Volts
250
0
-250
-500
-750
3000
2000
Amps
1000
0
-1000
-2000
-3000
10:25:43.72
10:25:43.73
CHA Volts
10:25:43.74
CHB Volts
10:25:43.75
CHC Volts
10:25:43.76
CHA Amps
CHB Amps
10:25:43.77
10:25:43.78
CHC Amps
Figure 3.14 Line voltages and currents before filtering, (Schipman, 2008)
The following figure shows line voltage and currents with active filter, which improved
the values for harmonic distortion to THDV = 2%, THDI=3%:
750
500
Volts
250
0
-250
-500
-750
3000
2000
Amps
1000
0
-1000
-2000
-3000
10:41:55.72
10:41:55.73
CHA Volts
10:41:55.74
CHB Volts
10:41:55.75
CHC Volts
10:41:55.76
CHA Amps
CHB Amps
10:41:55.77
10:41:55.78
CHC Amps
Figure 3.15 Line voltages and currents after filtering, (Schipman, 2008)
Module 3 | 193
VFDs and other power electronics with built-in power factor controllers will therefore
act to reduce the applied voltage under these conditions to minimize losses in the
motor.
In contrast to voltage variations, small frequency variations have little effect on motor
energy efficiencies.
Protection systems safeguard the motors, power system equipment, and human
staff from damaging effects of short-circuits and ground faults. The equipment
typically in need of protection are: generators, busbars, lines, and transformers.
The brains of protection systems are so-called numerical relays which sense a
fault condition and then command a circuit breaker to interrupt one or all phases
of power; this is known as a trip. VFDs have many built-in protective functions to
protect the motor from abnormal power supply conditions.
Modern, microprocessor-based control and protection systems offer distinct energyefficiency advantages over older, purely electro-mechanical devices. The ability
to execute more complex control logic, in close communication with the process
controls running within the DCS, allows a higher degree of energy optimization than
possible with electromechanical switching only. Load management schemes can be
implemented which balance supply and demand across parallel plant units in a way
that that minimizes losses and enhances power quality. Power control systems
also enable complex unit-wide automatic startup and load shedding routines;
these can conserve existing capacity and avoid energy-wasting trips, and
long or wasteful re-starts. The self-supervision capabilities of modern control and
protection devices further reduces the chances for an energy-wasting trip event.
Figure 3.16 Automatic generator synchronizer device, (ABB Power Products 2006).
In power plants, the power control system can be programmed to ensure that
the GSU, the auxiliary and the distribution transformers are not energized when
not in use.
Modern power control also enables integrated allocation optimization when
there are multiple sources of power, as described in the section on Multi-Level
Real-Time Optimization.
Module 3 | 197
Much of the design reference information available under the category of substations
also applies to large industrial power supply systems.
Generator Control
In power generation, an automatic synchronization device is recommended for
parallel switching of generators with the power grid. The synchronizer brings the
rotation speed (frequency) and voltage of the generator to within the required
tolerance range, using higher and lower commands to the turbine-generator
controller and the voltage controller (ABB Power Products 2006). Voltage, phase
angle and frequency are all dynamic quantities; the synchronizer ensures that the
breaker contacts touch at the instant when the phases are matching.
In power plants, the auxiliary power supply system typically has a high-speed
transfer system to ensure a secure supply of power to boiler drivepower; i.e.
the BFW pump, circulating pump, and draft fans. In case of an interruption
in power, this switchover function provides power from an alternate, standby
network. This control function allows the unit to continue operating and avoid
the energy waste (and large opportunity cost) associated with a boiler trip.
Transformer Control
This section is adapted from the ABB Switchgear Manual, (ABB Power Products 2006):
Power control devices were once commonly used to operate the taps which change
the transformation ratio of a power transformer. This function serves to adapt the
voltage in case of load fluctuations, to distribute the load, to adjust active and
reactive currents in interconnected systems. Although most modern transformers are
equipped with automatic voltage regulation, transformers in parallel operation still
require tap change functionality to minimize the reactive current circulating between
transformers. Electric furnaces, rectifiers and other devices also rely on tap change
control for variation of their input voltage.
In a large power or process plant, electrical engineering (EE) is often the last
discipline to be engaged, after process, mechanical and controls. This leaves
the EE with little influence to practice efficient integrative design, since most
other aspects are now frozen. This of course, has a deleterious effect on the
energy efficiency of a plant, as virtually all of the internally consumed energy
passes through the electrical system.
The power system is also the first to be commissioned, which further restricts the
time that the EE can spend on conceptual studies described below.
The trend away from turnkey projects and toward multiple suppliers fragments the
design and communication, making integrative approaches more difficult.
The vital role of power systems to all other plant equipment is the reason why
customers often stipulate liquidated damages in contracts with their suppliers.
This threat of very large opportunity cost from downtime is a subtle deterrent
toward newer designs with potentially significantly lower lifecycle costs.
(opportunity costs are not as real as wasted energy costs, but often get the same
accounting treatment)
In a retrofit situation involving increased electrification or the introduction of VFDs, it
is good practice to re-examine the entire power system to ensure it is right-sized and
still capable of delivering high quality power at high reliability. For example, with a
change in loading previous schemes for Power Factor (PF) compensation may need
to be re-evaluated to avoid increased in-plant losses due to low PF or even for overcorrection in some cases.
Figure 3.17 Simplified single-line diagram for unit connected power system IEEE Std.666-2007,
Design Guide for Power Stations
Figure 3.18 Single-line diagram showing for a unit connected power system, (ABB EBoP/CRC)
Module 3 | 201
Current loads (kiloamps) can then be calculated from the loads in the load list.
The electric power formulas at the start of this chapter and may be used to
calculate current load in transformers and synchronous generators. For induction
motors direct-on-line, see the the handbooks Motors section on motor power
formulas. For VFD=equipped motors, see that sections formulas for motor current
estimation.
Power Flow and System Voltages
System voltage selection has an energy efficiency impact. Choosing a higher bus
voltage where possible (for example 6,900V vs. 4,160V for auxiliary busses) will
reduce ohmic losses due to the lower current levels relative to low voltage busses.
Selecting MV rather than LV drives and motors will reduce ohmic losses in drivepower equipment. Motors and transformers rated at the higher voltage levels
generally offer higher efficiencies as well. Commercially available circuit breakers
are limited to interrupting a maximum of 3000A of short-circuit current. This current
limitation may lead designers to split up busses and supply them from multiple,
smaller transformers. Smaller transformers have lower efficiency than larger units.
Thus, higher bus voltages will allow the designer to specify fewer, larger transformers
which will increase the overall efficiency of the system, and enjoy up front cost
savings during equipment purchase.
Power flow and short-circuit analyses are required to ensure that voltages are
correctly selected during various power flow (both active & reactive) scenarios.
Startup Analysis (Motor Starting)
Motors without soft starters draw many times their full load operating current during
their startup. High torque demands during startup will also increase the load on
the power system and may lead to over-sizing of components for these transient
conditions, at the expense of lower continuous running efficiency. The electrical
and mechanical/process engineers are encouraged to work together to find creative
solutions to make motor startup easier on the power system. For example, a
bypass valve could be opened during startup to temporarily relieve pressure, if this
is allowed by the process. Startup considerations are discussed in the Fan Startup
In power plants, very large motors such as BFW pumps or FGD booster fans
may be fed from a separate, higher voltage (13,800V) bus.
Voltage drops at motor terminals during startup may be down to as low as 80% of
the normal levels for large motors with long motor leads, far from the main auxiliary
bus. (Black & Veatch 1996). Motors which are designed for reduced voltage starting
may be specified, but these motors have lower operating energy efficiency. A better
strategy is to specify auxiliary power system with a higher capacity supply, at least
during plant start-up conditions. This will improve bus voltage regulation, but will
increase the short-circuit duty of the switchgear (Black & Veatch 1996).
For power generation stations, a startup analysis should also include a reacceleration study that investigates the consequences of a system trip
followed by a quick resumption of power. In such cases several large motors
must restart and re-accelerate at the same time.
A similar study is recommended to investigate the amount and consequences
of the in-rush power peak that occurs immediately after unit synchronization.
Another opportunity for energy saving is to alter the excitation method during
turbine startup. A static frequency converter may allow the elimination of much
energy-intensive compressed air during turbine startup.
Harmonic Analysis
A formal harmonic analysis helps to predict the harmonic content, based on the ratio
between non-linear loads (like VFDs) and linear loads (like DOL motors) revealed from
the Load List. The VFD vendor can help with a first order analysis, but some rules of
thumb are provided here, adapted from (CSELive, P.Lynch, 3/1/2008). An industry
rule of thumb is that when these loads represent more than 20% of the total loading,
then specific power solutions hardware should be considered. This assumes that the
drives to be installed have at least 3% ac line reactance or dc link reactance as a
part of their standard designs.
Module 3 | 203
If the drives dont include internal reactance, or if many of them are only 6-pulse
VFDs, then the system tolerance level drops to about 10%. If these thresholds are
exceeded, then a formal harmonic analysis is recommended. If the level of excess
harmonic content is high and many drives are involved, installation of an active filter
will likely be most appropriate; if only a small number of large drives are involved,
then installing drives with active front-ends probably is the best solution. See the
section on Harmonics Mitigation for more details on passive and active filters.
Equipment Sizing and Bus Design
Correct balancing of loads across buses will improve power quality and thus energy
efficiency. In plants with multiple power sources, a correct balancing will also lead
to optimal sizing of all power system components and reduced startup power
requirements per bus.
A proper analysis will yield the optimum breaker and cable sizing; poor sizing of
components here can have consequences for both energy efficiency and protective
functions. Undersized cables have higher losses, as discussed in the section on
Cable Selection & Sizing.
Contactors for Bypassing
Soft-starters are typically bypassed by a contactor (KB) as shown in the figure
below when the motor has completed its startup. VFDs, however, are not normally
installed with such a bypass contactor for the full load condition. For large motors,
specifying a contactor to bypass the VFD, which is not 100% efficient, may be cost
effective. The feasibility of this design depends on the motors duty factor and the
duration at continuous maximum load, and several other factors; see NEMA-MG1
and the NEMA Application Guide for AC Drives (2001) for some special precautions
regarding this approach.
Fuse
Contactor KL
Soft
starter
Contactor KB
M
3-
Figure 3.19 Schematic of motor soft-starter on power system, (ABB Motors & Drives, 2007)
204 | ABB Energy Efficiency Handbook
Power Transformers
There are many different types of transformers; the focus of this section is on power
transformers, whose main function is to change the voltage levels between a power source
and a power consumer, with a minimum of losses. The relevant international standard for
power transformers is IEC 60076-1 Power Transformers (VDE 0532 Part 101).
Transformer Concepts
The basic, century-old design of a 3-phase transformer consists of two sets of
copper coils wound around the same iron core. The windings form concentric
shells of copper around a central core of laminated iron alloy plates, which forms
a closed loop for the magnetic field. The primary (input) winding induces a voltage
in a secondary (output) winding through the process of electromagnetic induction,
transmitted through lines of magnetic flux in the shared core. In principle, however,
energy can be transmitted in either direction. The magnitude of the induced voltage
on the secondary side (when the terminals are open) is proportional to the ratio
of the number of turns of the windings. A transformer tap is a connection point
along a transformer winding that allows a certain number of turns to be selected.
Transformers that have a set of variable turn ratios enable a rough mechanical form
of voltage regulation of their output. The tap selection is made via a tap changer
Module 3 | 205
Short-circuit impedance
Secondary (high) voltage rating
Transformer MVA rating
Primary (low) voltage rating
are $1000 or more per kW of losses (usually iron losses only). This performance
guarantee is also sometimes known as a loss evaluation agreement.
Estimating Transformer Losses
Theoretically, a transformer has its highest efficiency at the load in which iron loss
and copper losses are equal. Therefore the load at which the efficiency is highest
can be found from the following formula:
% optimum load = ( iron loss / copper loss)1/2 x 100
This is about 57% of full load, and the curve is fairly flat for realistic core and load
loss values. Because transformer designs are conservative with respect to load, the
actual highest efficiency point is usually found closer to 80% of the rated load.
Knowing the losses, the efficiency of a transformer can be calculated from the basic
formula:
% efficiency = [ (input in Watts - total losses in watts) / (input in watts) ] x 100
In practice, the total losses are hard to measure for an existing transformer, so the
no-load efficiency of a transformer is usually calculated as shown below. This noload efficiency is useful for comparing different transformer types.
% efficiency = ( V x Aout ) / ( V x Ain )
Empirical data can be used to estimate the total percentage transformer losses (Pv),
using the graph below for typical oil-immersed two-winding distribution transformers
up to 40MVA rating, and the following formula:
P v = P o + A 2P k
Where:
A
Io
Po
Pk
=
=
=
=
Figure 3.20 Transformer load-loss estimation curve, (ABB Power Products 2006)
The graph for the load losses Pk has an upper limit for rated high voltage 123kV and
a lower limit for rated high voltage 36kV.
For a 2.5 MVA transformer for 20/0.4 kV operating at half load (a= 0.5) and PF=0.8,
the percentage no-load losses, as shown in the graph above are P0 = 0.6%, and the
percentage impedance losses Pk =1.0%. The percentage total transformer losses Pv
are:
Pv = 0.6% + (0.25)(1) = 0.85%
In terms of real power, the total losses are = Pv x S x PF:
Total losses = 0.85% x 2500 kVA x 0.8 = 1,700 kW
Combining the formula for total % losses with the definition of efficiency leads to the
following formula for Transformer Efficiency (Eff %) :
Eff = 100% - 100% x ( P o + a2Pk) / (a x Sr x PF + Po)
Transformer losses are stated in MW, MVAR and MVA. The IEEE Std. C57.12.00 and
IEEE Std. C57.12.01 [B8] provide the tolerances associated with the transformer
losses (IEEE 2007).
Module 3 | 209
According to one power engineering industry guideline (Black & Veatch 1996),
step-up transformer MVAR losses can be estimated by applying the following
multipliers to the generator MVA rating.
kV (HV)
Multiplier
69
0.09
115
0.10
138
0.11
161
0.12
230
0.13
345
0.14
500
0.17
Figure 3.21 Multipliers (of MVA) to determine transformer MVAR losses, (Black & Veatch 1996)
The same source cites empirical data behind the following multiplier for transformer
MW losses, which suggest that power transformers are on average 99.7% efficient:
MW losses = Generator MVA rating x 0.003
In a power plant, as an example of using these multipliers, one can start with a
generator rated at 500MW real power and 0.9 network PF, and a high-voltage
side of 138kV.
Calculate the generator MVA rating : 500/0.9
= 556.0 MVA
Calculate the transformer MW losses : 556 x 0.003
= 1.7 MW
Calculate the transformer MVAR losses
: 556 x 0.11
= 61.2
MVAR
Total Transformer Losses = iron losses + core losses + auxiliary (cooling) losses
Skin effect losses, which increase with frequency, are a final, but minor source of
losses.
By increasing or decreasing the cross-section of the winding conductors or the core,
a wide range of designs with lower losses can be achieved; the quantity of materials
will be higher and therefore also the cost of the transformer. See the section on
Transformer Lifecycle Costing for more details on the trade-offs between capital and
operating costs.
For unit step up transformers, rated in hundreds of MVA, there are design
optimizations that introduce beneficial second-order effects, moving the
optimum efficiency point upwards into the 70-80% load range, and flatten the
efficiency curve even more. Realistically, a modern large step-up transformer
can be expected to be at or near peak efficiency over a range of 50-100% of
rated load, with that peak efficiency being at or near 99.7%.
Effect of Harmonics
The increased number of non-linear loads such as VFDs and switched power
supplies can lead to greater harmonic content. Harmonic distortion losses in a
transformer, mainly in the windings, are due to deformation of leakage fields. Losses
mean higher temperatures and deterioration of transformer insulation and efficiency
performance. The magnitude of losses associated with the fundamental and the
higher order harmonics are shown in the table below, for MV and HV lines and stepdown transformers in a distribution network.
The standard IEC 61378-1 describes a method to calculate losses when the current
contains harmonics. The standard ANSI/IEEE C57.110-1991 also provides an
estimation method, based on a certain load current spectrum of harmonics, which
is used to calculate the transformers K factor; its ability to withstand increased
losses due to harmonic currents on the low-voltage side(Phillips 2009). The K-factor
is used mainly for 480V step-down units and provides guidance on derating of the
transformer when high levels of harmonics are present.
Module 3 | 211
Figure 3.22 Transformer losses due to harmonics , Leonardo Energy,Network Losses 2008
Harmonics losses can be reduced using the same methods described in the
Harmonics Mitigation section.
Transformer Cooling
There are 5 basic power transformer classes, based on how they dissipate internal
heat from losses;
A for dry-type transformers, in which core and windings are embedded in cast
resin. These transformers are used up to 20MVA and a maximum of 36kV.
O for mineral (or other flammable) oil-immersed transformers, which have a
maximum temperature below the oil flame point 300 oC.
K for synthetic-oil immersed transformers, which have a higher maximum
temperature.
G for gas cooling system with fire point > 300 oC
W for water cooled systems
Note that oil-immersion serves as both insulation and coolant, and is most common
on all large (>20MVA) transformers. There are several alternatives for removing the
heat generated by losses, and these may be combined at different stages in the
transformer. For example, in oil immersed transformers, the cooling circuit collects
hot oil at the top of the tank and returns cooled oil lower down on the side. The
cooling arrangement consists of two circuits, one inner and one outer. The inner
circuit transfers heat from the hot transformer surfaces to the oil, and the outer
circuit transfers the heat to a secondary cooling medium. IEC standards provide
definitions for the different types of oil immersed transformer cooling arrangements.
Code
Inner circuit
Outer circuit
ONAN
Oil Natural
Air Natural
ONAF
Oil Natural
Air Forced
OFNAN
Oil Forced
Air Natural
OFAF
Oil Forced
Air Forced
OFWF
Oil Forced
Water Forced
The transformer MVA power ratings are usually are stated to reflect different levels of
cooling. For example, the rating ONAN/ONAF1/ONAF2 may be 120/160/200. These
ratings show the maximum power rating depending on the level of cooling active.
At low loads, the ONAN circuits are sufficient; no forced cooling, hence no auxiliary
losses, are active.
Cooling has the effect of moving the operational power point lower down on the
saturation curve. The cooler the transformer, the more power and energy can be
passed through the transformer. On the other hand, power that is consumed by the
cooling devices serves to effectively increase the transformer total losses.
Oil-filled transformers with pump circulation cooling systems are common, but these
have higher losses and the higher parts count means reduced reliability compared to
fan-cooled type units. The only advantage of pump-cooled systems is the reduced
size of the unit.
Some dry-type transformers, for example, Resi-block transformers, have a design
that can withstand extremely cold temperatures. These transformer types do not
need startup heaters, as oil-filled units do in such conditions, to achieve operating
temperatures. From an energy perspective, transformers without need for startup
heating save energy, provided that full load efficiencies are not reduced.
The standards (IEC-3540) define the hottest-spot temperature in the winding as the
limiting factor for loading & overloading limits, and provide a method for calculating
Module 3 | 213
this temperature based on bottom or top oil temperature measurements and the
gradient.
Transformer Configuration
Some facilities specify separate power transformer units for each phase, usually
based on the assumption that separate units offer increased reliability over combined
3-phase units. Although this may have been true in the past, the reliability of 3-phase
transformers is now so high that it should no longer be the main reason to split
phases. Single phase transformers have lower energy efficiency than combined
phase units, are more expensive and require more auxiliary equipment which
combined units can share between the phases. Additional reliability can be achieved
through a bus design which includes a reserve transformer powered from another
source, for example.
In power plants, the generator step-up unit (GSU) is 5 to 6 times more prone
to failure than network transformers. This higher failure rate is due to the
much higher thermal and mechanical stresses experienced by these large
transformers. The average age of large power transformers in the US is now 39
years (as of 2008). To maintain a slight edge in efficiency, but mainly to avoid
the costs of random failures, this fleet of 130,000 aging transformers should
be carefully monitored and screened for potential problems and eventual
replacement or refurbishment. ABB, for example, offers transformer monitoring
systems (TEC), and has a formal program offering (TRES) for fleetwide
assessments of utility transformer condition, providing users with indications
where there is substiantially increased risk of failure for individual transformers.
Hartford Steam Boilers insurance division projects that the 2% annual
failure rate of the existing installed base will increase to 5% by the year
2013. Most (43%) of these failures will be due to problems with the
winding insulation.
Problem of Over-sizing
In contrast to the design guidelines for motors and drives, an oversized transformer
is actually somewhat more efficient than one operating at 100% capacity
Most improper selection and sizing are due to an incomplete load analysis. Even if
the load analysis is complete and correct, there may still be a tendency to add too
many margins for electrical equipment, especially for power transformers and large
motors.
These margins may surpass 100% when the actual duty cycle is examined more
closely, using historical data. Even if significant future load expansion is anticipated,
it is generally more economical to size the transformer with the necessary additional
hardware to allow higher capacity cooling to be added later, when it may be required
(IEEE 2007).
A certain overload for a limited period of time is permissible. However, overloading
which leads to increased winding temperature above 221 F (105 C) in oil immersed
transformers increases the probability of bubbling in the cooling oil, which may lead
to dielectric breakdown in the transformer. Aging of the oil will also be accelerated by
stress due to overheating.
Module 3 | 215
Case Example
In one power plant, the transient high startup power demand led to a grossly
oversized unit auxiliary transformer of 10MVA. This plant was also a pumped
storage facility in which the generator was used as a motor for the water pump.
The transient high load was due to a 12,000hp (9 MW) starting motor, which
operated for only 15 minutes each day, during startup rotation of the motorgenerator when in pump mode. The transformer was sized to accommodate
this very high, but short-lived load, even though the normal auxiliary load was
less than 2MVA.
An improved design was `to specify a separate dedicated startup pony
transformer which has a rating high enough for the temporary high load. After
startup was complete, this transformer could then be bypassed in favor of a
2 MVA unit auxiliary transformer. This pony transformer could safely serve the
high transient load with a rating much less than 10MVA, since the duration
period is so short.
Sizing a power plant unit auxiliary transformer is based on normal and
maximum expected auxiliary loads, but with an eye to load profile and duration.
According to IEEE Std.666-2007 Design Guide, these auxiliary loads vary for
different types of plants such as for combined-cycle and coal-fired plants. For a
combined-cycle plant, the starting load (particularly static type) to bring the gas
turbine to firing speed is considerable, when compared to normal operating
load. Since the start duration is typically less than 30 min and is infrequent for
a base load plant, temporary loading beyond nameplate per IEEE Std. C57.91
[B13] in lieu of oversizing the auxiliary transformer would be a consideration for
kilovolt ampere selection. It would be advisable to include this type of expected
loading duty in the transformers specification.
Transformer Retrofits
The benefits of new transformer design can be gained at lower capital cost by
selective replacement of certain elements, such as winding, core and cooling
system, while retaining the existing tank and mounts. These replacements can
increase energy efficiency on old transformers without the need for additional
civil and mechanical engineering needed to accommodate a new form factor. A
component retrofit may also have shorter lead times compared to a complete unit
especially for large power transformers. The decision to replace transformer internals
should be addressed in the course of a plant power systems assessment. The
greatest energy efficiency is gained by complete replacement of the old transformer,
especially if the original transformer is over 50 years old. Advances in transformer
core steel technology can substantially reduce core losses.
The following table shows the general benefits of reduced winding losses in new
transformers vs. old, and the range of capital costs involved for different transformer
capacities.
Module 3 | 217
% Losses(old)
% Losses(new)
$5k-$10k
0.2
0.1
Medium
$6k-$12k
0.5
0.2
Small
$10k-$15k
0.6
0.3
In the case a power plant GSU, it is normal practice to value the load losses
higher when the transformer is operating near its rated load, which is expected
in baseloaded plants.
Note that these simplified LCC methods do not take into account differences
between rated and service voltage, or the effects of any tap-changer settings.
Calculation Case
Sample comparison of two 25MVA-rated unit auxiliary transformers, at 0.85 PF,
at 99.3 and 99.7 % efficiency over 1 year:
Energy Savings = 25MVA x 0.85 x 8,000 hrs/yr x (0.997 0.993) = 680 MWh
Dollar Savings = 680 MWh x $60/MWh = $40,800/yr
Now applying LCC methods to determine the present value of the savings over
20 years at 5% RoR:
PV = $40,800 x ((1 + 0.05)20 - 1 ) / 0.05(1 + 0.05)20
PV = $508,500
Increase cable diameter of smaller cables to one or max. two gauge higher to
achieve multiple benefits:
Lower ohmic losses
More cable of fewer different cable sizes reduces wastage during installation,
gets better terms such as Minimum Order Quantity.
Use VFDs to reduce average current to motor loads
Saves on capital costs and losses in cabling
As with pumping systems, the main equipment is often laid out before the
connections between them are determined. Also analogous to pumping systems is
the unforunate design choice of smallest allowable diameter cables to reduce initial
material costs, at the expense of much larger lifetime operating costs.
Voltage Drop and Power Loss
For cables and lines, the following formulas from ABB Switchgear Manual (2004)
may be used to calculate line voltage drop and power loss in 3-phase systems,
given the resistance of the line RL.
In power plants, the currents in bus ducts between generator and step-up
transformer are very large and may cause circulating currents in the bus ducts
themselves. These currents reduce efficiency and may lead to overheating.
Correct design of the termination of the bus duct at the transformer end can
reduce these losses and the risk of overheating. (ABB Ltd,Transformers, 2007)
To reduce busbar losses, the step-up and unit auxiliary transformers should be
located as close as possible to the generator. (IEEE 2007) . According to (Leonardo
Energy , Busbar Design, 2008), the following procedure will improve the energy
efficiency of busbar designs:
1. Select working and ambient temperatures
2. Assume initial current density of 8 amps/mm2
3. Find appropriate size in standard range
4. Calculate heat generated due to current
5. Calculate heat loss at working temperature
6. If 4>5, increase size and return to 4
7. When 4=<5, this is smallest possible size
Having calculated the size of the bar, there are three further considerations:
voltage drop
short circuit current
skin effect - increases apparent resistance by reducing effective area - important
for thick busbars, high frequencies, harmonics generated by non-linear loads
Module 3 | 221
Busbars are especially long-lived plant components, which gives their running
energy costs more weight in lifecycle calculations. The figure below shows how
these energy costs decrease as cross-section of the busbar increases.
Figure 3.23 Curves showing lifecycle cost for busbars, (Leonardo Energy , Busbar Design, 2008)
Module 3 | 223
Figure 3.24 Transformer electronic control (TEC), ABB Transformers USA, 2006
Modern transformers use these data for hotspot calculation and for optimal control
of the cooling system. The optimal amount of cooling power will minimize lifecycle
costs. In an overloading situation, the controls will start the coolers earlier to avoid
premature ageing of the transformer. The controller also provides temperature
warning and alarms; when a lower temperature limit is exceeded, then the TEC
control will first issue a warning to operators. If temperature continues past the
higher limit, then an alarm is generated and a trip command will be sent to the
protection relay to isolate the transformer.
The extra data from a well-instrumented transformer can be used to perform an
online heat balance which can continuously calculate heat losses from different
sources, as shown in the figure below. These losses can be compared to a model
of the iron and copper losses at the current load level, providing another indicator of
performance.
Figure 3.25 Heat balance monitoring in a transformer, ABB Transformers USA, 2006
Module 3 | 225
Select higher voltage levels for some buses (MV instead of LV).
Use 3-phase transformers instead multiple single phase.
Use large transformers instead of multiple, smaller ones; share
transformers between units.
Upgrade old transformers to achieve higher efficiency, improved
monitoring
Use PF correction, near the inductive sources where possible, to
approach 0.95 PF.
Use a generous cable laying method; avoid methods which lead to
cable derating.
Consider a plant arrangement which reduces length of cable runs &
voltage drops.
Ensure that harmonics are well within tolerance.
Understand motor duty, and size accordingly, following the guidelines
in Motor Sizing and Selection
Ensure phase loads and voltages are balanced.
Module 4
Automation Systems
Module Summary
This module describes the general design and energy impact of the plant
instrumentation, controls and optimization systems. While a detailed presentation of
all relevant automation concepts is beyond the scope of this handbook, this section
examines automation from an energy efficiency perspective and does not provide
guidance on other, critical aspects of automation engineering such as interlock logic,
emergency shutdown sequencing, or fault-tolerant design. For a more complete
guide to all other aspects of automation design, see the standards and references
sections of this handbook.
The information in this module may also be generally applied to process
industries; industry-specific text is shown between rule lines.
Automation Concepts
A process plant is a hierarchy of equipment & control systems: a combination of
hardware, software, people and operating procedures interrelated as shown in the
figure below.
automation integration alone were on the order of 5% of the total energy, on average
for all process industries (US DoE, 2004).
Figure 4.2 Pressure transmitter (left) and process analyzer (right). (ABB,2006)
Analytical Instruments
Analytical instruments are also sensors, but they are more complex than transmitters
and perform chemical composition analysis or other procedures usually resulting in
multiple outputs. Analytics may operate at slower data update rates than process
transmitters, and are typically used for slower-acting control loops, or overall
process quality evaluation and control.
In power plants, analytical instruments are used for measuring CO, NOx, O2, pH
and conductivity. In the burner system, flame scanners are used for combustion
flame stability monitoring. Other analytics are used for measuring flue gas
composition for emissions control and monitoring. A carbon in ash analytical
instrument is for the on-line measurement of unburned carbon in fly ash.
Modern analytical instruments, like process instruments, are placed in-line in with
the process equipment and provide data in real-time, using the same communication
bus technologies as simpler instrumentation. Some analytical instruments, however,
are mounted only intermittently to perform special studies such as corrosion testing
or vibration analysis.
In power plants with fewer instruments, boiler and heat loss efficiency tests
cannot be performed continuously in real time. These older plants require the
temporary mounting of extra instrumentation, whose type and number are
given by the ASME Performance Test Code, such that the desired accuracy
may be achieved. The test codes will allow accurate measurement of efficiency,
in some cases within a range of 0.05%, such as for steam turbine efficiency.
Module 4 | 231
Process Actuators
Actuators are devices that can directly act on the process through physically
directing gas and fluid flows. Some actuators typically found in a process or power
plants are; Dampers, Louvers, Inlet Guide Vanes, Servo valve position controllers,
Variable Frequency Drives, Solenoid (on-off) valves.
Actuators with significant deadband (hysteresis) will have poor control response,
and non-linear actuators will require additional correction (linearization) to behave
well across their entire operating range. Also, a reduced range of action, such as
low turndown, can severely limit a units energy performance at low loads. Another
common problem with process actuators is stiction, in which a large force is required
to overcome static friction between two surfaces in contact.
Figure 4.3 Part-turn actuator for rotary movement of final control elements, (ABB PME120 brochure)
Control Valves
Control valves (CVs) are valves used for automatic control of fluid flow. Valve opening
is controlled by a positioner that may be driven by an electric motor, hydraulic power,
or by compressed air in response to a command from the control system.
Control valves that are oversized will operate in a nearly-closed state for most of
the time. Oversized valves are hard to control and may cause instability during rapid
changes. Control valves are oversized as a result of the oversizing of constant-speed
upstream components, pumps and motors, as described in this handbook. When
the actual flows are much smaller than these components nominal operating points,
then the CV must drop correspondingly more pressure by closing more fully. As
described in the section on pump flow Throttling, the CV wastes energy that should
not have been input to start with. Speed control is the preferred method of flow
control, and eliminates the need for energy wasting throttling control valves.
CVs are mechanical devices that often operate under great fluid pressures and are
prone to stiction in the valve stem and hysteresis. These effects will cause CV control
loops to oscillate and may lead to process instability. There are methods to measure
stiction online, and techniques for tuning PID controllers where stiction is observed
or suspected. CVs and other actuators are usually powered electrically, or from
232 | ABB Energy Efficency Handbook
In power plants, a special kind of control valve is used to throttle the steam
entering various stages within the steam turbine. Known as turbine governors,
these devices are responsible for speed and load control, and for starting
and synchronization. Turbines retrofitted with modern fast-acting hydraulic
actuators provide much improved control response for faster ramp rate and
increased energy efficiency, as described in the section on Turbine-Generator
Control.
In power plants, ID and FD fan control can be made more stable by installing
smart transmitters on older systems still using dampers. These final control
elements must be accurately and speedily positioned for even basic control
schemes to be effective. In some cases, damper movements within 0.25
percent of the devices full range are necessary for precise control and this
capability must be maintained over years of operation.
This section is adapted from an article in Power Engineering by Richard Vesel,
ABB (Vesel 2007):
Dampers for primary and secondary air control, as well as overfire air control,
are typically distributed around the boiler in great quantities (more than 100
in many cases). Advanced combustion control schemes will often require
precision control over most air flows, so outfitting each damper and fan with
active control elements is essential.
Outdated damper driveselectric, hydraulic or pneumaticcan suffer
from a range of problems including insufficient force/torque, slow response
time, stiction and inaccurate response due to hysteresis and other causes.
Operators can find these problems by looking through relevant operating
Module 4 | 233
Sequential Control
Sequential control (or sequential function chart- SFC) is a series of steps (or tasks)
which bring the process through a sequence of well-defined states. This type of
control is commonly used during startup and shutdown procedures, or during
emergency (trip) action. SFC automates traditional checklists for these procedures
and is an important tool for plants with fewer experienced staff. Sequential control
has the potential to speed up these procedures within safety limits, thus saving
energy and unproductive power generation. The intermediate states in the sequence
can be automatically monitored and operators receive alarms if an expected value is
not achieved. A sample SFC program, showing states and transitions between them,
is shown in the figure below.
SFC programming, combined with the communication capabilities of intelligent
Motor Control Centers (MCCs) can turn off motors when not required by the
234 | ABB Energy Efficency Handbook
process. This may sound trivial, but many motors run uselessly because the motor
controls lack the necessary process knowledge that is given by the SFC states. The
MCC provides the necessary data to turn off motors even for very short time periods
without risk of overheating, when it is economical to do so.
Figure 4.4 SFC sample program diagram, (ABB Overview of IEC-61131 Standard, 2006)
Feedback Control
Single loop feedback control is a type of modulating control typically used for level,
flow or temperature control on a single process line or point. Traditional feedback
control typically uses one or more of the following basic regulation methods:
Proportional, Derivative, Integral. When typically combined, these are referred to as
PID control.
PID feedback control is shown in the form of a simplified block diagram in the figure
below:
PID
Plant
Figure 4.4 Basic PID controller block diagram with standard symbols
Module 4 | 235
Process Characteristics
Design and tuning of PID control loops requires an understanding of the physical
process under control. From a basic control standpoint, the process is characterized
by its gain, time constant, dead-time, and its degrees of freedom.
Process gain (K) is the amount a process output changes in response to a
change in input. Process gain can be separated into steady-state and dynamic
components. (ISA 2005). The product of process gain and controller gain is the
loop gain.
Time constant (TC) describes the rapidity of the above response. After one TC
the output variable has reached 63.2% of its final value. More complex processes
may have multiple TCs.
Dead time (DT) is the amount of time it takes for the above response to start after
the input has changed. Transportation lag or thermal inertia are common sources
of dead time.
Degrees of Freedom (n) are the number of independent variables in the process,
which is also the highest possible number of independently-acting controllers for
that process (ISA 2005). The degrees of freedom can be computed by taking the
total number of process variables and subtracting the number of relationships
(physical, chemical etc.) between them.
All the above process characteristics are important for correct loop design and
tuning, hence energy-efficient operation. Oscillations will result if the loop gain > 1.
Response will be too slow if loop gain is very low. The controller gain must therefore
be chosen to provide a total loop gain of about 0.5 to achieve rapid yet stable
performance.
Feedforward Control
Feedback control responds only after a process disturbance has already caused
a change in the output; it is blind to the original disturbance. In many cases,
this disturbance can be measured and even anticipated, as in the case of a
change in process loading. Feedforward control uses this knowledge to compute
an appropriate control response, which is then summed with the output of a
conventional PID controller as shown in the following block diagram.
Module 4 | 237
D(t)
Disturbance
Feedforward
Controller
PID
+
Plant
PID
Flow
System
PID
Inner loop
Outer loop
Heat
Exchanger
Cascade control allows the inner loop to correct quickly for inner loop disturbances,
such as valve hysteresis, leaving the outer loop to respond more quickly to changes
in the controlled variable.
Adaptive Control
In adaptive control, also known as self-tuning or auto-tuning control, the PID
parameters themselves are automatically modified online to respond to the changing
sensitivities of the process. In effect, the parameters which are normally fixed in a
static PID controller become themselves variables in one or more feedback loops.
Some self-tuning controllers operate in static mode most of the time, but will selftune on request from an operator or after a fixed time interval.
Module 4 | 239
Figure 4.7 MPC block diagram showing model and correction blocks
represent capacity limits, such as maximum fuel flow rates to boilers, and generator
constraints (Pekka Immonen et al, Power Engineering, Nov.2008 Coordinated
Control and Optimization of a Complex Industrial Power Plant).
Multi-Level Real-Time Optimization
This section is adapted from material by Pekka Immonen, which was first published
in Power Engineering, Nov.2008 Coordinated Control and Optimization of a
Complex Industrial Power Plant.
A multi-level approach (see Figure) uses real-time optimization (RTO), connected to
advanced process control (APC). At the top level, an optimization program monitors
the current situation in the plant and gathers pricing data over the Internet to make
timely decisions about loading individual equipment in the plant. The optimization
program then dispatches these orders to an advanced control layer, which provides
coordinated, decoupled control of pressure and power generation. The base control
level modulates the actuators affecting the plant to maintain the measured process
quantities at their setpoints.
Figure 4.8 Multi-level real-time optimization, (Immonen, Coordinated Control and Optimization of a
Complex Industrial Power Plant, 2008)
Module 4 | 241
Figure 4.9 Simulation and monitoring with PowerCycle software, ( ABB Switzerland, Power Technology Systems, 2005, PowerCycle brochure)
Supervisory Control
Supervisory Control (SC) is the highest level, providing feedback for such plant
management tasks as economic optimization, decision support, performance monitoring
and load scheduling. This level of control may have a rate of 15 minutes, hours or even
days. SC relies heavily on a Human Machine Interface (HMI) that can calculate and trend
plant overall and equipment efficiencies. SC functions also allows plant management to
monitor plant performance, identify root causes and correct problems.
Module 4 | 243
In power plants the Performance Monitoring Systems (PM) will also calculate
efficiency metrics of individual components such as air heater, condenser,
turbine, combustion, and emissions control equipment.
Convective Heat Exchanger Performance
In power plant, it is important to monitor the performance of superheater,
reheater and economizer for convective heat exchange. The actual
performance value for each section is calculated by measuring water/steamside heat absorption, and performing an iterative gas-side heat balance for
each individual section. Radiation heat transfer is taken into account for the
upper heat transfer sections. The clean surface performance is calculated for
each section using design information and an iterative gas-side heat balance
for each section. The ratio of the actual operating heat transfer rate to the
predicted clean heat transfer rate determines the conditions of each section.
(ABB Switzerland, Power Technology Systems, Optimax Operations Products,
2005)
Furnace Heat Transfer Performance
An iterative heat balance calculation can also be applied to determine the
performance of furnace heat transfer areas. This calculation allows for heat
absorption in the roof and walls of the upper furnace, and the radiation heat
from the lower furnace. These heat transfer performance calculations lead to
244 | ABB Energy Efficency Handbook
(CM) system monitors bearing vibration, eccentricity and axial rotor position on
any type of rotating machinery. These data are integrated into the DCS to leverage
the CS logging, trending and operator alarms functionality. The types of rotating
machinery deserving this form of condition monitoring are: turbines, feedpumps,
fans, pumps, motors, gearboxes and compressors.
Condition Monitoring is distinguished from process monitoring through the use
of models or other calculations to interpret the raw data and report on the actual
condition of the equipment. The large number of rotating machinery in a power plant
would make it difficult for operators to examine trends of each item. This type of
automatic analysis is especially important for vibration data, which is a distribution
of frequencies (a spectrum), which are both difficult and tedious for operators to
interpret. A CM system for vibration monitoring compares baseline spectral data
to current spectral data; any changes in the data are matched to a rules based
algorithm, which in turn determines the cause of the change. The result is actionable
information in the form of specific fault diagnosis, fault severity and maintenance
recommendation.
In power plants: for large journal bearing machines like Main Turbines and
Boiler Feed Pumps, these CM systems use Full Spectrum, Angle of the
Major Ellipse Axis and Aspect Ratio of the Ellipse for Orbit analysis plus
Shaft Centerline Position and Bearing Eccentricity. All these tools, along with
comparisons to user configured Threshold Values, combine to determine the
condition of the machine train, bearing by bearing.
All of these values are stored in a process historian database and then continuously
analyzed using a fouling factor model. This model is simply an energy balance
between the hot and cold streams within the exchanger. If the current overall
co-efficient is 5% or more less than the models prediction (Rajan 2003), then a
maintenance alert is triggered calling for proactive cleaning or problem investigation.
Control Systems
Evolution of Control Systems
Control systems have evolved from analog pneumatic controls to modern
microprocessor-based systems. There are two main branches in this evolution;
programmable logic controllers (PLCs) and Distributed Control Systems (DCS).
PLCs are the simpler of the two, and are most suitable for machinery control and
other areas of discrete manufacturing. A DCS is most suitable for processing the
large number of analog input/output (I/O) in a large power or process plant, and are
therefore often referred to as process control systems The term distributed in
DCS is meant to distinguish these from an earlier, more centralized control system
architecture centered around a process control computer. Another distinguishing
feature of DCS is their use of function blocks rather individual I/O tags for easier
programmability.
Distributed Control Systems (DCS)
A DCS provides all of the background services needed for control, operation and
monitoring:
Connections to various communication busses and networks
Controller CPUs and their associated I/O sub-systems
Human Machine Interface (HMI) for operator control, alarm and status indication
Historian services to log & store large volumes of real-time data
These DCS services can have a significant impact on plant energy efficiency. A
DCS is the only equipment type that spans all the diverse plant units. The reach
of a modern DCS allows improved coordination and plant optimization strategies.
Another source of DCS-related energy efficiency improvement comes with the
inherent tighter control of modern digital control systems, especially when compared
with legacy analog (e.g. pneumatic) control systems which may still live in the parts
of some plants. ARC Advisory Group (Dedham, Mass) estimates there is $65 billion
worth of control systems that are nearing the end of their useful life; at least a third
of these systems are installed in North America, and most of them are more than 20
years old.
Perhaps the most important benefit a DCS can provide to a plants energy efficiency
improvement program comes from this: it is the only plant system which has such a
Module 4 | 247
wide and rich interface to the operators and engineers. Thus, the DCS can leverage
the process knowledge in experienced plant personnel.
Figure 4.10 Control room of Jnschwalde 6x500 MW plant : Before (left) and after (right) a
DCS modernization. Source: ABB Industrial IT for Power Plants.
Figure 4.11 Motor Control Center cabinet, and close-up of motor starter drawer (ABB Oy, 2007)
Module 4 | 249
Module 4 | 251
Module 5
Power Plant Automation Systems
Module Summary
This module describes the energy efficiency aspect of the plant instrumentation,
controls and optimization systems. A detailed presentation of all automation aspects
is beyond the scope of this handbook.
Gross Heat Rate and Capacity
Heat rate is the thermal energy required to produce 1kw-hour of electrical power.
Gross hear rate is the rating for gross power output from the generator terminals.
Since some of the power is used to run internal plant processes, and is thus
routed back into the plant via the unit auxiliary transformer, then the remainder
is delivered as salable power to the network. The thermal energy used to create
those deliverable kw-hours is termed net heat rate. The focus of previous handbook
sections has been on reducing in-house auxiliary loads through more efficient
electrical and mechanical design. These approaches increased net plant capacity,
and had their most direct effect on the net heat rate of the unit.
The focus of this module is on how automation can directly improve unit gross heat
rate though control action on steam cycle parameters. These gains come from
reducing controllable losses, which result from operation of the cycle equipment
away from the best efficiency points for given loads. Mitigating these controllable
losses is the main contribution of automation to improving energy efficiency.
Controllable losses tend to be higher than the cycle designers originally intended
because the plant seldom operates in steady state at its design point. Losses are
correspondingly higher at lower loads and during periods of load disturbances.
Controllable losses worsen under conditions of equipment age, and poor
implementation or tuning of boiler controls.
This section examines automation from an energy efficiency perspective and
does not provide guidance on other, critical aspects of automation engineering
such as safety interlock logic, emergency shutdown sequencing, human factors
engineering, or fault-tolerant design. For a more complete guide to all other aspects
of automation design see the standards and references sections of this handbook.
Module 5 | 253
Figure 5.1 Simplified drum boiler diagram (IEA Coal Online - 2, 2007)
Automation allows tighter integration between generator, turbine and boiler units,
which can give significant energy benefits. Integrated (real-time) control between
plant cycle equipment and between plant units is a particularly valuable technique
to achieve energy savings in co-generation power plants or process plants that
produce some of their own power and heat on-site (US DoE, 2004) p13. Retrofits
that include biomass co-firing can also be made more economic by means of tighter
integration with the energy consuming units.
The average life of a modern automation system varies from 10 to 15 years for
PC-based systems and 15 to 20 years for proprietary distributed control systems.
The cost of upgrading I&C in coal-fired plant is estimated to range from $1 to $6
million (Ferrer, Green Strategies for Aging Coal Plants, 2008). This cost is relatively
small when compared with some other steam plant upgrades of the power cycle
equipment, which may cost up to 5 times as much. DCS vendors (ABB, Seimens,
Emerson) claim heat rate improvements of 2-5 % can result from upgrading to a
modern DCS and advanced control technologies. The improvement could be even
higher if the energy saved from fewer trips were properly accounted for, and if
system-wide real-time optimization were included.
Module 5 | 257
Figure 5.2 Hierarchy of control in a fossil fuel plant, (ABB Solutions for Fossil Fuel Power Plants)
Burner Management
Boiler startup / shutdown system
Fuel management systems : pulverizer, PA fan control
Furnace monitoring: Flame stability
Emissions Control
NOx control
SO2 control
Special monitoring:
Particulate count in flue gas
Condenser & Condensate Controls
Condensate controls (Water level in de-aerator tank etc.)
Coolant controls (circulating water control, cooling tower control)
Fuel Preparation Systems
Soot-Blowing Systems
Water Treatment Systems
Additional plant-wide automation systems
System-wide (multiple unit or site) optimization
Power Management System
Asset Management System
Motor Controls System
The interrelated set of boiler-turbine controls are shown in the figure below:
Figure 5.3 Utility Boiler and Turbine Control System, ABB Power Systems, Application Guide,2008
Module 5 | 259
For a typical PC utility boiler, a cold restart after a complete shutdown may take
between 6 to 12 hours. A unit operating in reduced or banked mode can be hotstarted in a much shorter time. A banked unit operates at much below its capacity,
in anticipation of being dispatched to handle peak loads. This is sometimes referred
to as spinning reserve.
Load Response
Load response is usually dominated by one of the following:
Frequency response: operated at nominal load (one of above) but modulated
to compensate for network frequency disturbances. In frequency response, the
turbine governor responds immediately to the frequency drop that accompanies
an increase in end-user demand for electricity in the network.
Load-following: a unit may be asked to operate anywhere between 30% and
100% of its MCR as part of a load dispatch system, and where it may be required
to change load at a rate of as much as 5% per minute (IEA Coal Online - 2, 2007).
In most response modes, the unit load demand is established by a remote
dispatcher, part of a wide area networked load control system. Load-following is an
increasingly more common mode of operation in deregulated or liberalized markets,
as shown by average availability figures in the region of 85% for sub-critical PC
plants (IEA Coal Online - 2, 2007).
Flow Rates
The plants operation may also be expressed in terms of main steam flow rates to
the high pressure turbine. Some important main steam flow rate terms are:
Valves Wide Open (VWO) plus 5% - condition applies to units specified to run with
a 5% overpressure
260 | ABB Energy Efficiency Handbook
Peak the maximum capacity, which is used for sizing of all other systems,
including auxiliaries. This flow is not maintained for long periods.
Maximum Continuous Rating (MCR) the steady-state maximum flow condition
Minimum flow the minimum stable flow condition
Boiler-Turbine Control
Boiler vs. Turbine Following Modes
The boiler can store energy and supply it to the turbine-generators control valve at a
certain throttle pressure. The control valve regulates steam flow for initial response
to demand. In some turbine-generators, finer control is provided by a bank of
nozzles per turbine stage; at most, only 1 such nozzle will be throttled at any given
time. See the Turbine-Generator section for more description on turbine control
actuators and position control.
The boiler responds much more slowly to demand, through changes to fuel firing
rate, due to its larger mass and thermal storage capacity. In boiler-following mode
the turbine-generator provides megawatt control and the boiler catches up to restore
throttle pressure. In turbine-following mode the boiler provides the initial demand
response by increasing firing rate and hence throttle pressure; the turbine-generator
follows by adjusting its control valves to maintain throttle pressure. Boiler-following
mode is more responsive but less stable than turbine following mode, and puts more
thermal stresses on the turbine.
Constant Pressure vs. Sliding Pressure Operation
In the modes discussed above, the boiler (hence throttle) pressure is basically fixed.
The boiler is fired at a rate that will produce enough steam for the turbine to satisfy
electrical power demand. The turbine steam valve(s) are modulated to maintain a
constant pressure at the turbine inlet. Throttling of the turbine valve at lower loads
will reduce steam pressure and temperature downstream of the turbine inlet, which
reduces turbine efficiency.
In sliding-pressure operation, boiler pressure is allowed to vary with load, the steam
turbine valves may be left open, and steam production is controlled by adjusting
boiler pressure. The boiler must still be fired to produce the required the steam flow
to satisfy demand. Sliding pressure operation is more efficient at lower loads, due
to lower first-stage turbine throttle losses (hence higher, and better controlled inlet
temperatures) and reduced boiler feedwater pump power when compared to the
higher, fixed-pressure operation. The higher first-stage temperature also increases
reheat steam temperature at low load, which further reduced heat rate. Sliding
(or variable) pressure operation, however, is slower to respond to demand - the
typical demand response rate is 50% of the rate under constant pressure operation.
Module 5 | 261
(Babcock & Wilcox, 2005). Boiler thermal stresses are also greater in slidingpressure operation, due to increased cycling of the boiler.
As a matter of practice in sliding-pressure operation, the turbine inlet valves are
generally held at a constant position between 20% and 70% load; outside of this
range, the unit is operated at constant pressure. Between 70 and 100% load, the
operating curves for the two modes are identical (ABB Inc. Plant Automation, 2006).
This level of throttling capability can provide reserve steam to meet sudden increases
from lower demand (IEA Coal Online - 2, 2007).
If rapid response to demand is required, one technique is to divert some steam from
feedwater heating so that it can be instead expanded in the turbine to generate
power; the section on Condensate Controls and the Schwarze-Pump case discuss
some of the efficiency trade-offs for this technique.
Another means of variable pressure control is by the use of large division valves in the
superheater flow links (Black&Veatch 2008) . This method keeps the boiler operating at
higher pressures and therefore does not benefit from BFW pump power reduction.
Sliding pressure method is also suitable for once-through supercritical designs, where
more rapid output changes can be achieved because of their lower thermal inertia.
Once-through boilers can increase output by 5% per minute, compared with a typical
3% per minute for drum boilers (Luby, 2003, as cited in (IEA Coal Online - 2, 2007).
Case Example
Unit C of the E.ON Scholven Power Plant, Germany
Because of the new market situation, unit C, initially intended for base-load
operation, is now being used in the medium load range. An inlet-pressure control
mode (the turbine controlling the pressure and thus supporting the boiler),
plus natural and modified sliding-pressure modes with an adjustable degree of
turbine throttling (turbine or boiler following mode) needed to be implemented.
In order to be able to follow the signal issued by the network controller, the
control concept must provide for frequent load ramps and load deltas with high
load variation rates, without any equilibrium conditions during load reversals for
secondary control purposes.
The primary grid frequency control of the unit is responsible for the balance
between the power generation and load consumption in the grid. The grid
secondary control (load-frequency control) is provided by a load dispatcher,
which regulates the agreed load exchange between the interconnected power
supply partners and the overall grid.
Due to the complexity of the primary and secondary control tasks, a modelbased unit control system (ABBs MODAN) was chosen. The model uses the
two main manipulated variables fuel flow for the boiler and the turbine control
valve in a coordinated mode. This is done by considering internal dynamic
models for live steam pressure and unit load. [If further control actions in the
condensate heating line are available, such as speed-controlled condensate
pumps or valves, the second unit control variant MODAKOND can be applied.]
This control strategy and operating mode has improved plant efficiency for
primary frequency control through reduced throttling of the turbine control
valves. An added benefit has been reduced control activity which allow for
smoother operation of main components like pulverizers, FD and ID fans,
thereby reducing plant operation costs. (This case text provided by ABB AG,
Power Technology Systems, 2006)
Module 5 | 263
Figure 5.5 Boiler automation system for Scholven unit, ABB AG Power Technology Systems, 2006
the operator with the flexibility to choose between base-loading and ramp-loading
(load following). The control technology may be either model-based or using
feedback loops. Feedback control is improved by using feedforward and adaptive
tuning techniques. The increased stability of coordinated control allows the unit to be
operated closer to its optimum at base loads, and more efficiently under low loads.
The combined effect of coordinated control is a heat rate improvement of 4% to 7%
(Ferrer, Small-Buck Change Yields Big-Bang Gain, 2007).
Pre-packaged controls in the turbine-generator equipment may not be able to
participate in a coordinated control scheme. In such cases, it is recommended to
simply remove or bypass these controls in favor of a coordinating controller. See
the Turbine-Generator section for more description on turbine controls.
Coordinated Control Demand Development
In coordinated control, a limited megawatt error signal offsets the throttle pressure
error, allowing the turbine to sustain initial megawatts until the boiler catches up.
A similar strategy provides the boiler demand signal. Adaptive tuning improves the
controllers sensitivity to different process time constants and for changes in energy
storage after large load changes (ABB Inc. Plant Automation, 2006). Dynamic
functions are used as the source of feedforward to overcome inertia in either turbine
or boiler. The boiler feedforward may be a simple model using time delays.
For a description of model-based control, see the Scholven case text in this
handbook. For details on development of the unit load demand signals, see the
references: (ABB Inc. Plant Automation, 2006; ABB Inc. Plant Automation, 2006)
and (Babcock & Wilcox, 2005).
Combustion Control
A combustion control system modulates the supply of fuel to the furnace and
also the amount of air supplied for combustion of that fuel to satisfy the demand
for energy. This fuel/air supply is also known as the firing rate, so this system is
sometimes referred to as firing rate control. The air/fuel ratio of a typical boiler is
controlled to within +/-2% of excess air (ISA 2005)
Fuel Control
A typical PC boiler combustion (or firing rate) control system receives a demand
signal from the integrated boiler-turbine control system and trims it with error signals
from main steam temperature and feedwater flow. The resulting firing-rate demand
is distributed to the subsidiary fuel flow control and air flow control via a fuel-air
master controller. The fuel flow control compares its demand signal to the total fuel
Module 5 | 265
flow for all pulverizers. The resulting command signal is sent to the pulverizers group
master controller which applies the error signal in parallel to all pulverizers, along
with a demanded air flow, which is PID-controlled on each pulverizer (Babcock &
Wilcox, 2005).
Air Flow Control for Combustion
This section is adapted from an article in Power Engineering by Richard Vesel
(Vesel, 2007):
(The drive power aspects of draft fans are discussed in the Drive Power- Fan
sections of this handbook.) Airflow control is essential to efficient and safe
combustion process. Methods of airflow control vary with the basic boiler type;
the descriptions in this section apply to a sub-critical, PC boiler design.
The basic combustion (primary and secondary) airflow control strategy is: the fuel-air
master receives a boiler firing rate demand signal from which it calculates a total air
demand based on current fuel feed rates. The air flow demand is compared with
actual flows summed from transmitters in the primary and secondary air streams.
This error signal is used by the secondary (FD) fan controller to adjust motor speed
or the damper position to modulate the flow.
These final control elements must be accurately and speedily positioned for even
basic control schemes to be effective. Inaccurate or weak damper drives cause poor
combustion control response and reduced efficiency. See the section on Process
Actuators for more details on damper actuators. An opportunity to improve airflow
control method is when a plant must upgrade the main draft air driver systems with
higher power motors to make up for additional resistance from post-combustion
flue gas processing (SCR and FGD among them) as described in the section on
Emissions Controls. A plant can realize large energy benefits by controlling main
air flow with variable speed drives such as VFDs.
Air Flow Control for Draft Control
Furnace draft pressure control is a housekeeping loop within combustion control.
The ID fans serve to regulate furnace draft backpressure so that flue gasses can be
exhausted at the correct flowrate. ID fans are controlled by a feedforward program
based on air flow demand, corrected by a furnace pressure deviation from setpoint.
Air Flow Control and Energy Efficiency
Excess O2, CO and NOx are the critical pieces of information needed to properly
manage combustion air flows. The solution that achieves and maintains essentially
complete combustion while minimizing production of NOx relies on the controlled
feeding of air into the combustion zone at various stages and in just the right
amounts. This promotes burning at temperatures high enough to consume all
266 | ABB Energy Efficiency Handbook
available fuel, but low enough (that is, under 2,800 deg-F or 1550 deg-C) to avoid
production of NOx in great quantities.
Other effects of this staged combustion process are: elevation of flue gas
temperatures and higher temperatures in the upper interior, as well as the backpass
of the boiler. Ash may reach fusion temperatures to form an especially tenacious slag
on boiler tube surfaces. CO-rich dark zones in the lower furnace can chemically
attack boiler tubes, so underfire air has been used to reduce this problem. With
these various competing needs, the air balancing act within the boiler becomes even
more delicate, more difficult to model and control, and harder to maintain under
dynamic load conditions. Poor air control wastes fuel and degrades heat rate, both
of which increase costs.
The problems associated with outdated damper drives are described in Process
Actuators. Plant owners can improve performance and reduce cost of ownership
by replacing traditional fan-motor-damper arrangements with fan-motor variable
frequency drive (VFD) system. A VFD provides variable speed control of a fan
in response to a signal from a controller. Response times for VFD are a bit slower
than direct damper control due to fan and motor inertia. However, if precise control
are used on trimming dampers, then optimal results can still be realized. Dampers
are also increasingly important for control adjustments at speeds less than 33% of
maximum (ISA 2005).
Automation Potential for Energy Efficient Design
Efficiency gains in combustion process have a direct impact on fuel costs (which
are 45-55% of the cost of the generated electricity- (IEA Coal Online - 2, 2007)) and
plant heat rate. The thermal efficiencies of boilers are already high (up to 94%) and,
according to the IEAs Coal Online it appears unlikely that further large gains in the
efficiency of heat recovery from state-of-the-art PC boilers can occur.
Such thermal efficiencies are calculated from steady-state mass and energy
balances, however, they do not consider the detrimental effects of unstable
operation. Unstable firing rates will deter operators from keeping the boiler operating
near its design constraints and optimum efficiency point.
Unstable boiler operation may occur after a retrofit to low NOx burners, or
after switching to different fuels. Other contributors to instability may be due to
uncorrected deadband or non-linearities in the throttle control valve(s). If the current
control system gains are too high, then the response to load demands may also lead
to swings in firing rate. One consequence of swinging between under- and over-firing
is instability in the flue gas and thermal distributions within the furnace, leading to
poor heat transfer at water wall tubing. Another disadvantage of unstable conditions
Module 5 | 267
is revealed in high carbon-in-ash losses; these contribute to a higher heat rate and
indicate incomplete burnout.
It is estimated that stabilizing firing rate, furnace draft and air flow can give 1-2%
improvement in heat rate most units (ABB). A simple approach to curing boiler
instability is to reduce the gain such that ramp rates start low, and then accelerate
if the ramp direction demand persists. (Ferrer, Small-Buck Change Yields Big-Bang
Gain, 2007). This large impact on energy efficiency should put combustion
controls at the forefront of a plant controls assessment and/or combustion
process optimization effort.
Combustion Optimization
Combustion optimization is distinct from combustion control, which is essential to
control firing rate for basic boiler functionality and safety. Optimization improves
upon basic performance. Optimization also implies the use of model-based
techniques such as MPC.
Figure 5.6 Combustion optimization system schematic, (ABB Fossil Fuel Plants, 2005)
with a steam flow feedforward signal to provide the feedwater demand. This demand
is then compared with the water flow measurement to provide an error signal input
to the inner PI control loop. The more accurate feedwater flow control systems
also use shrink-swell compensation to compensate for water density and volume
changes as temperature changes.
Demand for Auxiliary Drivepower
Large demand for auxiliary drive power comes from the main and booster boiler
feedwater pumps (BFPs). The drive power aspects of the BFP are discussed in the
Drivepower-Pump sections of this handbook. BFW pumping is a high-system head
application for VSD speed control; a large part of the speed control range is used in
developing pump head at low flow (ISA 2005). Benefits are therefore lower than in
high-flow, low-head systems, but VSDs are still worthwhile in this application when
compared to throttling.
The ability of VFDs to provide over-speed capacity (within the service factor of the
motor and pump) may be useful in boilers which are designed with extra margin for
overpressure operation. This extra capacity may be needed to supply peak loading
on hot summer days.
Another auxiliary load on many boiler designs comes from the relatively lower power
boiler recirculating pump, which moves water between drum and the boiler water
walls. This auxiliary load is eliminated in supercritical designs and in some HRSG
designs which use natural circulation within the boiler.
Automation Potential for Energy Efficient Design
Stable feedwater flow control allows the unit to operate closer to its design point for
main steam pressure. For a sub-critical unit: each 100 psi increase in main steam
pressure decreases heatrate by 35 Btu per kWh at full load (EPRI report CS-4554).
Steam pressure in a typical boiler is normally controlled to within +/-1% of the
desired pressure (ISA 2005).
Case Example
A feedwater pump use at a U.S. pulp and paper mill. As the peak load does
not exceed 4,000 gpm (25 l/s), and two of the pumps can produce the required
pressure at flow rates of 2,000 gpm (13 l/s) each, operating only two of the
pumps would be sufficient.
The savings achievable from shutting down an extra feedwater pump are sitespecific, depending on the pump size, the type of the drive (motor vs. turbine
Module 5 | 269
Case text and image from (Immonen, Assessing Industrial Power Plant
Operations & Controls, 2003)
hp) for FGR systems due to the higher temperature and higher particulate count in
the extracted flue gas, compared to fresh draft air fans. To avoid excessive blade
erosion under thee harsher conditions, these centrifugal fans typically have a less
efficient forward-curved blade design (as described in the section on Fan Power
and Energy Efficiency) which increases the per unit demand for auxiliary power.
A retrofit of the FGD fan motor to VFD speed control will save auxiliary power,
especially at low loads, compared to other means of flow control.
For FGR fans with inlet dampers for flow control, automation can be used to
program a smaller opening at low loads to minimize plant auxiliary load. Whether
using inlet dampers or VFD, improved flow control will also improve the ability of the
O2 and combustion controls, especially during load changes and under low load
conditions. Adaptive tuning will improve response across a wider load range, and
the distribution of recirculated flue gas may also be optimized for different loading
conditions. Another role for FGR automation is to modify the gas recirculation flow
in order to reduce the thermal stresses seen during the load changes in the lower
operating region.
Turbine-Generator Control
Where the steam flow is used to set the output at part load, there are three potential
means of control (throttle, nozzle and bypass governing) to set the flow rate to adjust
the power output as required. The turbine governor operates to maintain frequency
control during startup or big load changes. After reaching equilibrium, the turbine
then goes into load control mode.
Turbine-generator efficiency is typically 43.4% (IEA Coal Online - 2, 2007), expressed
as a ratio of output electrical power vs. thermal BTU power entering the HP steam
input. Steam turbines cannot use the latent heat of condensation, so this latter
energy is often omitted from turbine efficiency calculations. See the Coordinated
Boiler-Turbine Control section of this handbook on how sliding pressure operating
mode can reduce throttling losses across the turbine control valves compared to
constant pressure operation. Steam extracted from the turbine stages for feedwater
heating reduces unit power generation capacity, but increases thermal efficiency.
The automation potential for controlling this flow is discussed in the section on the
Condensate System.
Module 5 | 271
Figure 5.7 Turbine Generator unit photo, (ABB Solutions for Fossil Fuel Power Plants brochure, 2007)
Upgrading turbine valve servo drives and their controls can improve accuracy to
+/-1%. Other advantages of the improved linearity and optimized positioning
times are: improved dynamics, smoother operation, reduced throttling losses, and
enhanced stability; the following case history describes the benefits in more detail.
Figure 5.8 Upgraded turbine valve servo drive photo, (ABB Utilities GmbH, 2004)
Case Example
Upgraded Turbine Components and Unit Controls
Blnod Power Plant Units 3 &4, EDF, France
The fossil-fueled units 3 & 4 of EDFs CPT Blnod power plant are more than
30 years old located at Pont a Mousson, Lorraine, France. The maximum net
output of the plant is 265 MW.
Figure 5.9 CPT Blnod Power Plant Units 3 &4, EDF, France
Module 5 | 273
Upgrading measures were sought which could improve the maneuverability and
efficiency of the plant. The three technical upgrade requirements were:
Fast power output increase for the purpose of primary grid frequency
control; at an amplitude of up to 25 MW within 30 sec
Participation in tlrglage; the load ramps being specified by the load
dispatch center for the purpose of secondary frequency control, at an
amplitude of up to 50 MW and a gradient of 7 MW/min
Higher economic efficiency achieved by an enhanced operational efficiency
Plant measurement data and operational experience indicated that the older
electrical-hydraulic and mechanical components of the turbine would need an
upgrade to ensure the required dynamic response, in conjunction with a new
digital turbine controller.
The new digital turbine controller is of a modular and flexible design and
provides in combination with new mechanical-hydraulic activation devices
for the HP and IP control valves the basis for meeting the dynamic demands
of the process. The previous mechanical linkage facilities and drives showed
excessive clearance and effects of wear and tear. They were replaced by new
low-maintenance servo drives which were adapted to the specific needs of the
turbine.
The new model-based boiler-turbine unit control system coordinates
the operation of the boiler and the turbo-generator set. The unit control
explicitly allows for the dynamic and highly varying behavior of the two major
components, i.e. the boiler (dynamically slow) and the turbo-generator set
(dynamically very fast). Positioning interventions are done via the turbine
control valves and the fuel setpoint of the boiler. As a result, the operation can
take place both in coordinated boiler-following mode, with the turbine being
output-controlled, and in turbine-following mode, with the boiler being outputcontrolled. The output setpoint is adjusted to the level requested by the power
purchaser via an external grid controller and is additionally superimposed on
the manually-specified basic unit setpoint.
The economic efficiency of the plant has been enhanced by migrating from
constant-pressure mode to sliding-pressure mode. This way, it was possible
to reduce the auxiliary power consumption of the feedwater pumps and to
increase the overall efficiency of the units. Other benefits of the upgrade
are: reduced throttling losses of the turbine, improved control accuracy and
smoother operation. Control accuracy is improved from +-10% to +-1%.
With these goals being accomplished, the plant can now demand higher
prices when selling its electricity in the power market, as the price for providing
secondary-frequency power control is determined on the basis of the maximum
possible power amplitude and by the change gradient of the load ramp. Moreover,
the plant is also able to participate in the European power market, although this is
not in-tended at present.
(Case text adapted from ABB Utilities GmbH, 2004 brochure on Upgrade of
Blnod Power Plant )
Module 5 | 275
Figure 5.10 Unburnt fuel and stack loss curves for combustion, (Plantservices.com, 2007)
The O2 control module should also offer automatic override of opacity; this could
promote operator confidence and lead to more time in efficient automatic mode
(Ferrer, Small-Buck Change Yields Big-Bang Gain, 2007).}
The figures below show that improvement potential still exists among industrial
power plants. The leftmost curve shows the O2 variability of boiler A, plotted
against the steam flow. The chart on the right includes a similar plot for boiler B.
Figure 5.11 Boiler excess air control (Immonen, Assessing Industrial Power Plant Operations & Controls,
2003)
Both of the steam generators are swing boilers providing industrial process power
and hence subject to large variations in steam demand. As can be seen, boiler B
controls the flue gas O2 content accurately, along the load based setpoint curve.
The O2 readings of boiler A have a lot of scatter, suggesting that the combustion air
controls could be improved significantly (Immonen, Assessing Industrial Power Plant
Operations & Controls, 2003).
Benefits of Automatic Excess Air Control
Based on findings from numerous improvement projects and assessments, the
typical potential reductions in flue gas O2 range from 0.5% to 2.0%. To estimate
the fuel savings, a rule of thumb could be used stating that one percentage-point
drop in O2 improves the boiler efficiency by 0.5 %. More accurate estimates require
boiler combustion and energy balance calculations. The actual cost reductions
depend on the boiler size and the fuel cost, and the range of savings can be wide.
The documented annual savings from recent industrial power plant projects were
between $30,000 and $200,000 per boiler.
Module 5 | 277
Figure 5.12 Steam temperature control diagram, (ABB Inc. Plant Automation, 2006)
Attemperation flow may also be tapped directly from a special outlet within the main
feedwater pump (IEA Coal Online - 2, 2007). Bypassing feedwater heating has a
negative impact on cycle efficiency. See the Pump sections for discussion on the
pump power requirements for these two alternatives.
Other means to control steam temperatures are; tilting burners away from the
superheater tubes, using bypass dampers in the back-pass or convection portion of
the unit (larger boilers that include these dampers can have 12 or more each of the
superheat and reheat dampers), or using flue gas recirculation (FGR) to moderate
combustion. These methods are typically used for longer-term adjustment (Babcock
& Wilcox 2005) compared to the quick action of spray attemperation to provide
control of transients. Attemperation flows can be eliminated on supercritical boilers
by controlling the firing rate to match the feedwater flow (IEA Coal Online - 2, 2007).
Advanced Steam Temperature Control
Steam temperature excursions are a result of an imbalance between the heat added
to the steam by the firing rate and the heat withdrawn, by the steam flow rate. An
advanced control strategy will control steam temperature for a drum boiler operating
in either constant or sliding pressure mode. Specific algorithms and techniques used
by the advanced control strategy include:
The use of enthalpy calculations to determine the different SSH inlet temperature
set points when operating in a variable pressure mode.
The use of anticipatory logic to account for changes in the boiler energy storage.
The use of an internal model controller (Smith Predictor) to accommodate for long
process time delays (dead time) and lags.
The use of adaptive tuning to provide controller sensitivity adjustment.
Advanced Model-Predictive controls can be applied, as part of an overall cycle
control optimization
Module 5 | 279
Figure 5.13 - Advanced Steam Temperature control system logic, (ABB Inc. Plant Automation, 2006)
In units with bypass dampers for heat or re-heat temperature control, the accuracy
of the control can be improved by using high-torque electric drives for positioning.
One problem inherent with these particular dampers is their constant exposure to
high-temperature corrosive gases and high levels of fly ash. In time, most of these
dampers experience increasing stiction and eventually will degrade into limited
range of motion or completely frozen states. See the section Dampers and Louvers
for more details on these actuators. Upgrading to intelligent drives with built-in
diagnostic capability can provide an early warning of damper stiction problems and
allow for proactive maintenance on the damper mechanism. Properly operating
superheat and reheat damper drives mitigate attemperator spray flows and ash build
up, in turn reducing both sootblowing and periodic maintenance in this section of
the boiler. Both produce reductions in controllable losses, which improves plant heat
rate (Vesel 2007).
Benefits of Advanced Steam Temperature Control
The benefits of advanced steam temperature control are:
Improved temperature control on process transients caused by changing load,
sootblowing, starting and stopping of mills in service
Improved steady state temperature control when operating under conditions of
reduced pressure, slagging.
Faster ramp rate
Improved steam temperature control will also reduce the need for attemperation, which
improves plant heat rate. (Ferrer, Small-Buck Change Yields Big-Bang Gain, 2007).
Provides design flexibility to control main steam temperature on drum boilers in
either a fixed or variable pressure operation.
280 | ABB Energy Efficiency Handbook
Case Example
U.S. pulp and paper mill
An example of steam temperature increase potential is shown in Figure below
(Immonen, Assessing Industrial Power Plant Operations & Controls, 2003). The
steam temperature is shown as a function of the boiler load, to reveal possible
load dependency. As load dependent behavior is not obvious in the example,
the temperature variations may be attributed to poor control. The standard
deviation of the temperature was found to be 8 F (5 C), while the average
temperature was 34 F (19 C) below the design. Therefore, the operators
tended to maintain a safety margin of 4 times the standard deviation between
the maximum and the temperature setpoint.
By means of better control, the standard deviation could drop to one half,
or 4 F (2.3 C). By using a commonly accepted safety margin of 3 times
the standard deviation, the average temperature could be increased to 913
F. At this U.S. pulp and paper mill, savings were available from increased
backpressure power generation, replacing approximately 0.8 MW of more
expensive purchased power. While the annual savings here were approximately
$130,000, the range of savings can be wide, anywhere from $20,000 to
$300,000 per year, or beyond, on relatively small power boiler systems.
Module 5 | 281
Case text and figure provided by: (Immonen, Assessing Industrial Power Plant
Operations & Controls, 2003)
The following calculation case quantifies some of the benefits of advanced steam
temperature control:
Calculation Case
Advanced Steam Temperature Control System
This calculation assumes a 500 MW unit with an initial ramp rate of 5MW/min and a
main steam temperature set point of 1000 F. The fuel savings realized from the initial
assumptions are threefold: 1) increasing the main steam temperature set point to
its design value of 1005 F thus, improving the unit heat rate 2) improving the ramp
rate to 10 MW/min thus, reducing the need to purchase power and 3) reducing the
number of unscheduled boiler outages as the result of superheater tube leaks. Total
fuel savings in excess of $600,000.00 per year is possible with the Advanced Steam
Temperature Control System. The calculation of the fuel savings is as follows;
1. Increasing main steam temperature to design;
Main Steam Temp Improvement: 5 F (2.8 C)
Unit capacity: 500 MW @ 80% capacity
Fuel Cost: $1.75/MBTU (1MBTU = 1055 MJ)
Main Steam Temp Dev Value: 1.5 BTU/(KWH F)
Annual savings = (1.5 BTU/(KWH F) x (5 F) x (1.75 $/MBTU) x (500 mw x 0.8) x
(24 HR/DAY) x (365 DAYS/YR) = $46,000/YR.
The following non-energy efficiency benefits are significant and are quantified below:
2. Improving the unit ramp rate to 10 MW/min;
MWHR/ramp: 18.75 MWHR/ramp
Purchase power penalty: $20/MWHR
Number of ramps per year: 250
Annual savings = (18.75 MWHR/ramp) x (250 ramp/YR) x (20 $/MWHR) = $93,750/YR
3. Avoiding unscheduled outages for superheater tube failure;
Unit capacity: 500 MW
Purchased power penalty: $20/MWHR
Unit downtime per tube failure: 100 HR
Number of tube failure per year: 0.5
Annual savings = (500 MW) x ($20/MWHR) x (100HR) x (0.5/YR) = $500,000/YR.
Case text and values provided by: (Immonen, P., ABB Inc. Plant Automation, 2006)
Module 5 | 283
Figure 5.14 Boiler startup optimization model dada flow., ABB AG Power Technology, 2007
within 10 to 20 percent of the normal costs of fuel and auxiliary power, for each
power plant startup. Startup times can generally be reduced by increasing the
loading of critical thick-walled components or by better exploiting the margins
through more homogenized thermal loading. Applying predictive startup optimization
in order to reduce the startup time is advisable if the permissible heat-up stress
margin is not fully exploited, or if the load is distributed unevenly during startup.
Energy efficiency improvements come from reduced startup fuel burned and/
or shorter startup times. Startup automation with optimization also leads to more
consistent startups and lowers the risk of an aborted startup, with the consequent
loss of input energy. Coal-fired power plants offer high additional savings potentials,
provided that it is possible to shift from startup fuel to coal at an earlier point.
Energy savings accumulate for units in cycling duty. In particular, in the case of
frequent brief standstills, when numerous startups are run under similar conditions,
the spread of startup costs is obviously reduced. On average, the use of startup
optimization results in a significant reduction of startup costs. Even in the case of
brief standstills, startup costs can be high, as a high live-steam temperature has to
be built up to approach the still high temperatures in the turbine. Taken together, the
above improvements increase efficiency by approximately 1% during startup, and
also decrease emissions values.
Case Example
Boiler Startup Optimization
The figure below shows a comparison of two startup procedures in the
Ingolstadt power plant, unit 4: with BoilerMax (bold lines) and without
BoilerMax (thin lines). The upper diagram shows the fuel quantity F_F and the
HP bypass position Y_HPB. The diagram in the middle shows the live steam
flow F_LS and the generator output P_Gen. The diagram at the bottom shows
the temperature differentials DT_SH4H and DT_SH5H occurring in HP headers
of the two last superheater levels.
The diagrams show that it was possible to run a similar boiler startup while realizing
an approximate 20% reduction of fuel consumption. Such fuel savings are possible,
since the steam flow used for starting-up can be decreased by simultaneous and
coordinated reduction of the opening of the HP bypass station. In addition, the
startup time is slightly reduced.
Module 5 | 285
Figure 5.15 Comparison of two startups with model-based startup optimization. (shown in the
heavier dashed and solid lines) and without (thinner lines) ABB AG Power Technology brochure
for E.ON Ingolstadt plant, 2007
Emissions Controls
Emissions Concepts
The flue gas contains particulates and other products of combustion which must be
cleaned to levels required by environmental regulations (in the USA, these are given
by the Clean Air Act Amendments, CAAA). Particulates are removed by electrostatic
precipitators (ESPs) or fabric filters.
Sulfur dioxide (SO2) is removed by one of the various flue gas desulphurization
(FGD) processes. The wet scrubber process using limestone as the sorbent is the
most widely used method. NOx production can be controlled in-furnace by low-NOx
burners, air staging, and the use of a re-burn fuel in the upper part of the boiler. NOx
can also be removed by injection of ammonia or an ammonia- based compound into
the combustion products, with or without the use of a catalyst, processes known as
selective catalytic and non-catalytic reduction (SCR or SNCR) (IEA Coal Online - 2,
2007).
Flue Gas Desulfurization (FGD)
One way to limit extra auxiliary loads associated with FGD is to switch to fuels lower
in sulfur. The EPRI CQIM model described in the section on Fuel Handling Systems
provides estimates for the amount of auxiliary power required for different coal types.
Methods to improve the contact between the limestone slurry and the flue gas
improve absorption will serve to reduce the auxiliary drivepower required for
circulating pumping. Innovative methods using open-spray tower absorbers may
reduce auxiliary loads by up to 1% of total generation (Sayer, 1995).
Seawaters alkaline composition enables it to absorb SO2. Seawater FGD scrubbing
may be one of the lowest energy alternatives, where environmental agencies
grant approval. Most Recent Developments and Optimization Aspects for FGD
Technologies Dr. W. Schttenhelm et al, Power-Gen Europe, Barcelona, Spain,
May 25-27, 2004. Seawater FGD techniques eliminate the need for slurry injection
and recycle pumping. Dry FGD processes may offer lower auxiliary loads, but with
a lower SO2 removal rate (Sayer, 1995). The gypsum or sulfuric acid byproducts of
FGD processes can be sold to other industries, which may change the cost-benefit
comparisons.
Figure 5.16 Flow diagram of a typical supercritical PC plant with pollution control (cited in IEA Coal
Online - 2, 2007) Rousaki and Couch,2000)
Module 5 | 287
Flow control through use of VFD speed control can reduce pump and fan auxiliary
power by 75% at low loads, and will correct for oversizing at full loads, reducing
power by 15%. Efficient motors and drive-trains can further reduce power by 5%.
A peaking plant that applies the suggested drivepower improvements can
substantially reduce the unit auxiliary load.
{Note that gas-fired plants, on the other hand, may only require 1% of generating
output for reducing nitrogen oxides (C.P.Robie,P.A.Ireland, for EPRI, 1991), and
newly available low NOx combustors and burner tuning methodologies can
completely eliminate post-combustion NOx treatments.}
Automation Potential for Energy Efficient Design
A low-capital cost technology to complement low-NOx burners is improved
combustion control. Using the automation techniques of co-coordinated boilerturbine control and advanced realtime control of burners, air flow and gas
recirculation can reduce NOx emissions without any increase in auxiliary power.
See the section on Excess Air Control for details on reducing NOx using control
techniques. Continuous monitoring of flue gas is vital for low-NOx burner or
combustion methods due to the risk of higher levels of unburned carbon and CO
emissions; see the section on Instruments and Actuators for more details on
analytical devices.
Automation for stabilizing firing rate after a low-NOX burner conversion can also
reduce heat rate. Combustion Optimization Solutions (COS) use model-based
predictive control techniques to reliably find the most suitable setpoints for improving
the heat rate and reducing emissions like NOx. Every ton of NOx production that
is avoided during the combustion process, is eliminated from the cost of NOx
mitigation or from offset credit purchase requirements. The value of this ranges from
$1500 to $3500 per ton at current (2009) pricing.
Automation through intelligent flow control in open-spray FGD systems is an
important criterion for the effectiveness of the system. Particle capture in baghouses
is directly related to the pressure drop; controlling this through fan speed may
increase effectiveness over a wider operating range.
More advanced powering systems may also help improve the effectiveness of ESPs
through variation of voltages and polarities. Further advantage may be gained
through coordinating ESP and fan flow control for optimum particulate removal at
lowest power consumption. Precipitators and bag filters are not required to work at
maximum capacity when the plant works at partial load.
Module 5 | 289
Condenser Systems
Figure 5.17 Condenser cooling system towers, (ABB Ltd., Power Generation Unit, 2006)
needed to drive pumps or fans to circulate the cooling media. The main auxiliary
drivepower loads are circulating water pumps and cooling tower pumps and fans.
In water-cooled systems, the amount of condenser cooling water required is approx.
0.35 to 0.75 GPM (1.3 to 2.7 l/m) per kW of generating capacity. An approximate
figure for power required to circulate this water is 10hp (7500 W) per MW of
generating capacity.
In air-cooled condenser designs, the exhaust steam flows through finned tubes
and ambient air is pushed through the fins with the help of a large fan. Air-cooled
condensers typically operate at a higher temperature than water-cooled versions,
which reduces cycle efficiency. An approximated rule of thumb is that for every ten
deg-F increase in condensor temperature, there is a 2% heat rate increase.
Drivepower Potential for Energy Efficient Design
Lowering the temperature of the coolant will directly improve the plant heat rate. The
condenser efficiency improvement potential is large, given that condensing wastes
half of the input heat energy in the cycle.
Location is an important factor in the configuration of the condenser system, as
is the design of the LP turbine and the condenser hardware. The condenser is the
plant unit most affected by seasonal temperature variations, which have an impact
on the thermal efficiency of the entire cycle according to the rules of thumb in
Parameters for Increased Thermal Efficiency.
Applying the principles from the drivepower module will result in high-efficiency,
speed-controlled cooling water pumps delivering cooling effect at a lower pumping
power over a broader range of flow. The reduced auxiliary load will lower the net
heat rate. The favorable economics of efficient circulation may prompt higher flow
designs to deliver more cooling and therefore a reduced heat rate due to improved
thermodynamics.
Drivepower demands in air-cooled systems can be further reduced through use
of high-efficiency components. Fans with aerodynamic improvements can give up
to 80% savings and may be relatively easy to retrofit. Larger cooling tower crosssections equipped with larger fans using Low Face Velocity (LFV) designs will use
much less power, according to the fan affinity laws described in Fan Power and
Energy Efficiency.
Adding a micro-mist to the inlet air can provide additional evaporative cooling
effect, up to 15 F (8 C) in some industrial scale systems (RMI, 2007) High-quality,
right-sized motors combined with VFD for flow control as described below can
Module 5 | 291
Figure 5.18 Optimized fin fan schematic, Rocky Mountain Institute, 2007)
Multiple cooling towers each with one or two speed fans are usually brought online
individually to handle changes in unit load. Operating all available towers in parallel,
each equipped with VFD for fan speed control, provides much improved energy
efficiency. This latter design maximizes the surface area for heat transfer and
minimizes the fans electrical drivepower requirements (Rumsey, 2003).
Automation Potential for Energy Efficient Design
Improved and integrated control of condenser coolant systems can provide some
surprising efficiency gains. As with other power plant systems, correct and adaptive
tuning will allow the condenser coolant systems to deliver at optimum efficiency over
a wider range of ambient coolant temperatures and plant loading.
Model-based optimization techniques may also be useful to determine the most
efficient cooling water/air flow rates given the increased pumping power - see the
case description in the box text below. Automation can also be used to reduce the
auxiliary load of these large circulating systems by optimal cycling of the pumps
throughout a range of unit operating conditions. Pump system efficiency can be
further increased by using constant speed motors for primary pumps, but equipping
the secondary pumps with VFDs for trimming flow control.
For cycle designers, it may be useful to think of the LP turbine as a source of steam
heat for a combined heat and power plant, even if the heat is only to be used inplant. Using the steam productively may increase backpressure, but this again is an
optimization problem that can be solved using the techniques described in previous
sections. Some applications for in-plant CHP are the HVAC system, and fuel drying or
pre-heating; these options are explored in the module on High Performance Design.
Case Example
Maasvlakte 540 MWe coal-fired plant in the Netherlands
For the Maasvlakte plant in the Netherlands, thermodynamic modeling showed
that there was a different optimum flow-rate depending on the temperature
of the cooling water (which varies at the plants location from 1C to 20C).
At 4C, the optimum flow rate was 12.2 m/s, while at 20C it was 18.8 m/s.
Results from this modeling exercise were confirmed by actual plant data. An
average reduction in the condensor cooling-water temperature from 20C to
15C at this plant reduced the heat rate by almost 1%.
(Case data from Kromhaut and others, 2001, and cited in (IEA Coal Online - 2,
2007)
Condensate System
Condensate System Concepts
The purpose of this system is to collect the condensate (boiler feedwater) leaving the
condenser, remove non-condensable gases, raise its temperature through a series
of feedwater heaters and then deliver it to the deaerator for additional heating and
temporary storage. From the deaerator, the feedwater goes to the boiler feed pump
where it is pumped up to near boiler drum pressure at the inlet of the economizer.
Increasing the boiler feedwater temperature effectively increases the upper
temperature of the thermodynamic cycle, raising the efficiency. Heating the
feedwater using steam extracted from the turbine stages is more thermodynamically
efficient than using other nearby sources, such as fuel in the furnace. Up to 30% of
steam may be extracted for this purpose, typically at a intermediate and high turbine
Module 5 | 293
pressure stages. Designs with higher steam pressures allow a greater number of
extraction points and hence greater number of heaters in the train.
Demand for Auxiliary Drivepower
This systems main requirements for auxiliary drivepower come from the condensate
and booster pumps. The relatively low-power vacuum pumps are not considered in
this discussion. The condensate pump is a low suction head extraction pump which
must deliver sufficient discharge head to overcome pressure drops through several
feedwater heaters. A booster pump is also sometimes used after the de-aerator
to raise pressure to a level sufficient for flow through the high-pressure feedwater
heaters. The power demand and control of the main boiler feedwater pump is
discussed in the Feedwater control section.
Drivepower Potential for Energy Efficient Design
The general case for efficient condensate pump drive power is made in section on
Pump Systems.
Automation Potential for Energy Efficient Design
Although not strictly auxiliary systems, the feedwater heaters (heat exchangers) and
de-aerators energy efficiency could benefit from continuous monitoring at inlets and
outlets for early indication of plugging or fouling problems.
It is almost always more thermodynamically efficient to add another feedwater
heater; Welford and others (2002) cited a 0.15 percentage-point efficiency rise for
the whole unit through an increase of 20C (36 F) in the final feedwater temperature.
(IEA Coal Online - 2, 2007) Reliability and cost issues, however, often limit the
total number of heaters; a total of 6-8 heaters is typical. For a small increment in
cost, the feedwater heaters reliability can be increased by adding instrumentation
and continuous on-line condition monitoring. Such extra reliability may favor
an additional feedwater heater and be justified by the resulting increased cycle
efficiency. One new approach to feedwater heating involves the use of on-site solar
equipment to provide thermal energy for feedwater heating during the days peak
demand hours.
The steam bypass valves can also benefit from condition monitoring. The enthalpy
drop across these valve is large. Valve leakage can be detected by instrumentation
on the downstream side of the bypass line. Similar monitoring can be installed on
steam traps in all bypass lines. Valve functionality can be continuously monitored for
stiction and other control problems which lead to unnecessary loss of steam energy.
In a poorly maintained system of steam traps, annual energy losses can easily reach
six figure costs.
The model-based optimization techniques developed for combined heat & power
(CHP) systems may be applied to feedwater heater train and de-aerator system to
achieve the optimal balance between use and production of steam, and allocation
to the most efficient heaters (or other users). Such a control strategy could improve
the off-design performance of the system, especially at lower-load operation. In
industrial boiler systems, the de-aerator and other components with an inventory
of steam or water may be used in a steam-leveling strategy to absorb process
load swings and increase efficiency (Immonen, Assessing Industrial Power Plant
Operations & Controls 2003).
In some units, peaking power supply is achieved by deliberately taking one or
more of the top feedwater heaters out of service (Babcock & Wilcox 2005). This
practice allows more steam to pass through the turbine, but at a significant cycle
energy efficiency penalty. According to EPRI Report CS 4554, taking one top (highpressure) feedwater out of service increases the heatrate by 94 BTU/kWh, which
corresponds to a 1% drop in efficiency in a typical PC unit.
Sometimes efficiency is temporarily sacrificed for higher ramp rates, as described in
the following case text; the control strategy for faster ramping temporarily shuts off
the flow to one or more LP feedwater heaters. Operators must be made aware that
protracted operation in this mode will significantly increase fuel cost and emissions.
Case Example
Schwarze Pumpe, Power Plant, Germany
Schwarze Pumpe in Germany provides an example of large, flexible PC units
where two 800 MWe supercritical lignite-fired boilers have been designed to
operate at sliding pressure to down to 40% output, with high rates of change,
and short hot start-up times. A dynamic control system covers the whole plant,
including firing and emissions control as well as the steam cycle. A 6% load
change per minute is achievable at Schwarze Pumpe with only minor effects
on the main steam and hot reheat steam temperatures, and without turbine
throttling or using the storage capacity of the boiler.
Very rapid ramping (for example, by 50 MWe in seconds) requires the use
of a degree of steam reserve and temporary changes in feedwater heating.
Temporarily diverting steam away from feedwater heating so that more passes
through the later turbine stages will have a very negative effect on efficiency in
the short term, but this matters less than meeting demand over these transient
periods.
(Case text provided by IEA Coal Online 2, 2007)
Module 5 | 295
control equipment. Coal with lower heating values will therefore use a higher
percentage of auxiliary power for each unit of converted energy. Also, coals with
higher sulfur content will require increased auxiliary power to drive FGD processes.
Drivepower Potential for Energy Efficient Design
The flow control design guidelines described in the drivepower module showed how
speed control is most efficient at less than full rated speeds. The bypass method
for speed control still used in some coal milling operations is therefore a candidate
for design improvement by applying VFDs for speed control.
Case Example
Milling Applications: VFD drive instead of Bypass
In a boiler installation, 20 coal mills with a drive output of 710 kW each are
used. A speed-controlled drive with a control coupling or with an AC drive
is used to replace the bypass method. The possible saving with a control
coupling is about 11 GWh and with an AC drive 23 GWh as shown below. (For
a description of bypass flow control, see Pump Flow Control Methods)
Pulverizer Applications
In order to accommodate the larger range of operation asked of plants today, as
described in the section Plant Operating Modes, the designer should consider
specifying more, but smaller pulverizers rather than fewer, larger ones. The full load
fuel flow rates provided by the basic thermal balance will provide the upper limit of
combined pulverizer capacity. A pulverizers capacity loss due to wear will consume
Module 5 | 297
more power as grinding surfaces wear; this increase in power consumption should be
part of the sizing criteria for pulverizers. It is common practice to include primary air
fan power consumption together with pulverizer power. When pulverizer wear is taken
into account, one industry estimate of combined power requirement is 22 kWh/ton
(24kWh/metric ton) of coal for a load-following unit. (Babcock & Wilcox 2005).
When pulverizers operating at this capacity are in a typical older PC unit with
heatrate of 10,000 BTU/kWh, fired on coal with a heating value of 10,000 BTU/lb,
they will consume about 1% of the input fuel energy. This percentage increases with
decreasing coal heating value, increasing plant heat rate, and increasing moisture
content of the coal.
Automation Potential for Energy Efficient Design
Automation which can shut down one or more pulverizers for low load operation
should be coordinated with the combustion and steam temperature control systems
to avoid instability immediately after shutdown/startup. This simple automation
modification saves energy on units with larger boiler turndown, as is the case in
units which are being repurposed from baseload to dispatchable or load-following
duty. The automation of pulverizer operation within the combustion control
system, however, must accommodate the limited turndown capability of individual
pulverizers, which can individually operate in stable fashion only down to about 50%
of rated capacity. (Black & Veatch 1996, p.182)
Another potential improvement is to enable online monitoring of the relative flow of
coal in the pipes to individual pulverizers. This data can be used by the combustion
controls to achieve better balancing of fuel flow to burners in the boiler burner
array. Full closed loop combustion control, with coal-flow monitoring and and air/
fuel balancing of the the burner array is technically feasible and cost effective at this
time, but the industry is very slow to consider, adopt and apply this technology.
Sootblowing Systems
Sootblowing System Concepts
Accumulation of ash and other products of combustion on the heat transfer surfaces
will reduce heat transfer and increase plant heat rate. Sootblowing systems typically
use steam or compressed air cannons to remove soot from boiler tube surfaces
and structures. There are also mechanical vibration, and sonic soot remediation
systems which fall into this general category. Plants which have switched from
their design fuel to other, lower-quality fuels are particularly susceptible to more
ash-related problems. If internal boiler combustion levels or distributions are not
managed well, large fused-ash accumulations may form, which may eventually break
off and fall, damaging boiler and tubes in the process.
298 | ABB Energy Efficiency Handbook
Module 5 | 299
Module 6
Case Studies In Integrative Design
Module Summary
This module defines a base case plant unit and shows the cumulative effects of
drivepower, electrical power system and automation system improvements. Capital
investment costs and operating costs are also estimated, for the purpose of a
lifecycle cost calculation. This case study will attempt to quantify the benefits in
many scales: efficiency/heatrate, ROI payback, fuel amount & cost, NOx & CO2
costs, and power generated available for sale.
Power plants using pulverized coal fuel are averaging 30-35% efficiency,
compared to 45% and higher for supercritical or combined cycle designs.
This very rough comparison provides some indicators as to where one should
focus energy efficiency efforts when confronted with an existing plant or when
evaluating alternatives to the standard design of a new plant.
Module 6 | 303
Phase
Energy Audit
Design Assessment
Data gathering
Analysis
Efficiency calculations
Proposals
investment
automation changes
Ranking
Payback based on
solely energy-saving
improvements
For power plants, the thermal analysis is the first step in the analysis, as
this will provide the basic combustion air, fuel, flue gas and feedwater flow
requirements (Babcock & Wilcox 2005). Based on these flows, the major
pressure drops may then be calculated, followed by the remaining pipe or duct
resistance calculations.
Figure 6.2 Cumulative efficiency gains in entire pumping system, (deAlmeida, 2006)
Even small gains in component efficiency can lead to very large overall efficiency
gains. For example, if each of the above components has 80% efficiency, then
overall system efficiency Esys is:
Esys = 0.8*0.8*0.8*0.8 = 41%.
But increasing individual efficiency by just 10% will have a multiplicative effect on
overall efficiency:
Esys = 0.9*0.9*0.9*0.9 = 66%
The compounding effect of a 10% increase in component efficiencies thus gives a
60% improvement overall (old 41% x 1.60 = new 66%).
For the auxiliary systems which are the subject of this handbook, an integrative
approach which considers drivepower, electric power supply, and process
automation as a whole can lead to a more balanced and energy efficient design.
The component efficiencies in the simplified example given above are seldom
static in the real world. Usually, these component efficiencies are dynamic and
will change with process flow as shown in the figure below. An integrative design
approach considers efficiency over the entire flow range, opening the door for even
greater magnification on the gains from efficient designs. For a more complete list of
Integrative Design principles, see the Appendix section.
Module 6 | 305
Figure 6.3 Typical efficiency vs. flow for drivepower components (ABB PumpSave User Manual 4.0)
The design methods and recommendations for auxiliary and automation systems
described in this module are largely applicable to many other fossil steam plant
designs and situations as well. The table below lists all the proposed auxiliary
designs for improved energy efficiency. The numbered proposals are singled out for
detailed description and benefits analysis in the following sections.
#
Project or Case
flow control
old system
4
Coordinated boiler-turbine
operation
temperature control
upgrade
Environmental upgrade
Module 6 | 307
Project or Case
System
Table 6.1 Suggested improvement retrofit projects; selected projects are numbered
Target Improvement
8%
Units
2%
Fewer trip
20%
Reduced CO2
8%
8%
2.50
993 1000
deg-F
(+4 C)
2,380 2430
PSI
(345 kpa)
975 993
deg-F
(+10 C)
30
klb/hr
(13.6 tonne/hr)
40
klb/hr
(18.1 tonne/hr)
BTU/kWh
(265 kJ/kWh)
lb/MMBTU (g/MJ)
15%
Implementation Issues
Energy efficiency improvement efforts typically follow the project phases described
in the module on Managing Energy Efficiency Improvements in this handbook.
For an existing facility, measurement, prioritization and budget limitations will
ultimately decide which of the proposed improvements are implemented. There is
also a preferred technical order to the improvements proposed in the table, which
follows the levels in the hierarchy of plant automation described in the Automation
section. Higher levels of automation are generally dependent on lower levels.
308 | ABB Energy Efficency Handbook
Module 6 | 309
Value
Units
500
MWe
70.0
8,895
BTU/lb
0.00890
MBTU/lb
112.423
lb/MBTU
$2.470
$/MMBTU
$0.0220
$/lb
$0.048/kg
$2,000
$/ton
$2200/tonne
Fuel % Carbon
48.6
$5.00
$/ton
0.210
lb/MBTU
10,211
BTU/kWh
Fuel Cost
SI Units
20.6 MJ/kg
$5.50/tonne
Parameter
Value
Units
8000
hr
SI Units
$93
$/hp
$125/kW
$100
$/hp
$135/kW
$0.05
$/kWh
$0.007
$/kWh
Discount rate
5.0%
20
years
0.1
3,066,000,000
kWh
31,306,926
MMBtu
$0.025
$/kWh
Parameter
Value
Units
10,000
$/MVA
350
Mwe
$3,000
$/kW
$1,500
$/kW
$50,000
$/MVAR
33 1015 J
SI Units
% Full flow
% Total
Annual hrs
Capacity factor %
100%
400
5%
90%
10
800
9%
80%
20
1600
16%
70%
25
2000
18%
60%
25
2000
15%
50%
10
800
5%
40%
400
2%
30%
0%
20%
0%
100
8000
70%
Load Name
Boiler feedwater
ID
BFW
Rated
In
Rated
Control
Load
Operat-
hp
use
Set hp
method
factor
ing hp
%
Gross
14,000
28,000
Slip
0.81
22,680
4.8%
pump
Condensate pump
HW
2,250
2,250
Throttling
0.75
1,688
0.4%
Circulating water
CW
3,400
6,800
Throttling
0.85
5,780
1.2%
FD
2,250
4,500
Inlet vane
0.52
2,340
0.5%
pump
Forced draft fan
(blower)
Primary air fan
PA
2,250
4,500
Inlet vane
0.49
2,205
0.5%
ID
4,500
9,000
Inlet vane
0.78
7,020
1.5%
41,713
BCW
600
1,800
Throttling
0.82
1,476
0.3%
SW
400
400
Throttling
0.82
328
0.1%
FGDS
600
600
Throttling
0.82
492
0.1%
CT
600
1,200
Inlet vane
0.82
984
0.2%
Pulverizers
PV
450
2,250
Bypass
0.66
1,485
0.3%
Air compressor
AIR
480
480
Bypass
1.66
797
0.2%
AUX
4,300
4,300
N/A
0.53
2,279
0.5%
FGD
6,500
6,500
Inlet vane
0.66
loads
FGD booster fan
TOTAL
SCR circulating
66,480
SCR
400
400
Throttling
0.82
4,290
0.9%
54,171
11.5%
328
0.1%
pump
Table 6.7 Auxiliary systems fan and pump drivepower
Module 6 | 311
FD
ID
FGD
Fan type
centrifugal
centrifugal
backward
forward
cfm
450,000
600,000
centrifugal
forward
1,200,000
in water*
12
17
18
80.00%
55.00%
60%
96%
inlet vanes
inlet vanes
96%
inlet vanes
96%
4.1kv
4.1kv
4.1kv
Transmission efficiency
100%
100%
100%
gpm
BFW
CW
HW
2800
180,000
5500
lb/cu.ft
62.4
62.4
62.4
Efficiency
85%
85%
85%
Static head
ft
10
Nominal head
ft
900/2300
55
650
Max head
ft
1000/2500
75
750
slip
%
95%
throttling
95%
Throttling
95%
4.1kv
4.1kv
4.1kv
Transmission efficiency
98.50%
98.50%
98.50%
FD
ID
FGD
Number in operation
hp
1065
3190
6184
kWh
3,472,721
10,403,631
20169878
kWh
2,474,608
7,413,469
14372748
kWh
998,113
2,990,162
5,797,130
Efficiency gain %
28.7%
28.7%
28.7%
$2,495
$7,475
$14,493
lbs
1,088,493
3,260,924
6,322,065
$23,915
$71,645
$138,900
$6,637
$19,885
$38,551
MMBTU/year
9,682
29,005
56,234
tons
970
2,905
5,633
$4,849
$14,527
$28,165
0.03%
0.10%
0.19%
$37,897
$113,532
$220,108
Investment cost
$99,045
$296,670
$575,112
Payback period
years
2.4
2.4
2.4
$373,234
$1,118,190
$2,167,925
premium
Divide lbs by 2.2 to get kg. Multiply MMBtu by 1055 to get MJ.
Module 6 | 313
BFW
CW
HW
Number in operation
hp
11,423
3240
1170
kWh
41,109,000
15,758,502
5,216,951
kWh
34,942,500
7,372,117
2,716,618
kWh
6,166,500
8,386,385
2,500,333
Efficiency gain %
15.0%
53.2%
47.9%
$15,416
$20,966
$6,251
lbs
6,724,882
9,145,779
2,726,740
$147,750
$200,939
$59,908
$41,007
$55,769
$16,627
MMBTU/year
59,817
81,351
24,254
tons
5,992
8,149
2,430
$29,959
$40,744
$12,148
0.20%
0.27%
0.08%
$234,133
$318,419
$94,934
Investment cost
$1,062,293
$301,320
$108,810
Payback period
years
4.5
1.0
1.2
$1,855,521
$3,666,885
$1,074,277
Divide lbs by 2.2 to get kg. Multiply MMBtu by 1055 to get MJ.
Module 6 | 315
Motor
FD
ID
FGD
Hp
2,250
4,500
6,500
85.0%
85.0%
85.0%
97.0%
97.0%
97.0%
96.5%
96.5%
96.5%
99.0%
99.0%
99.0%
Oversized hp
hp
1,185
1,310
316
Oversized %
52.7%
29.1%
4.9%
5.3%
2.9%
0.5%
kWh
651,714
1,707,351
2,820,990
Efficiency gain %
18.8%
16.4%
14.0%
$1,629
$4,268
$7,052
lbs
710,727
1,861,954
3,076,433
$15,615
$40,908
$67,591
$4,562
$11,951
$19,747
MMBTU/year
6,321
16,562
27,364
tons
633
1,659
2,741
$3,166
$8,295
$13,706
0.02%
0.06%
0.09%
$24,973
$65,423
$108,096
Investment cost
$106,500
$319,000
$618,400
Payback period
years
4.3
4.9
5.7
$204,719
$496,328
$728,715
Table 6.11 Main motor and drivetrain benefits for fans, per motor
BFW
CW
HW
hp
14,000
3,400
2,250
85.0%
85.0%
85.0%
98.5%
97.0%
97.0%
96.5%
96.5%
96.5%
99.0%
99.0%
99.0%
Oversized hp
hp
2,578
160
1,080
Oversized %
18.4%
4.7%
48.0%
1.8%
0.5%
4.8%
kWh
5,689,926
2,201,555
954,702
Efficiency gain %
13.8%
14.0%
18.3%
$14,225
$5,504
$2,387
lbs
6,205,154
2,400,908
1,041,151
$136,331
$52,750
$22,875
$39,829
$15,411
$6,683
BTU/year
55,194,843,186
21,356,078,337
9,261,039,336
tons
5,529
2,139
928
$27,644
$10,696
$4,638
0.19%
0.07%
0.03%
$218,030
$84,360
$36,583
Investment cost
$1,142,250
$324,000
$117,000
Payback period
years
5.2
3.8
3.2
Divide lbs by 2.2 to get kg. Multiply MMBtu by 1055 to get MJ.
Table 6.12 Main motor and drivetrain benefits for pumps , per motor
Module 6 | 317
means the average main steam temperature can be maintained at 993F, an increase
of 18 F. Similar improvements were obtained for the reheat steam temperature.
Main Benefits Analysis
For a sub-critical unit: each 50F increase in main steam temperature decreases
heatrate by 70 Btu per kWh at full load, and which corresponds to an increase
in cycle efficiency of approximately 0.7% (Babcock & Wilcox 2005). For reheat
temperature increase of 50F the heatrate decrease is 65 Btu per kWh. The 18 F
increase in main steam temperature yielded the following benefits.
Results
Units
Baseline
Reduced Baseline
Amount of
BTU/h
4,248,000,000
4,227,000,000
20,218,000
Fuel Input
lbs/h
477,546
475,274
2273
$/year
$76,469,102
$76,105,142
363,960
lbs/h
850,988
846,938
4,050
Tons CO2/yr
3,727,327
3,709,586
17,740
Reduction
Rating x Annual Capacity Factor
Divide lbs by 2.2 to get kg. Multiply MMBtu by 1055 to get MJ.
Retrofit Description
In conjunction with the controls retrofit, the response was re-programmed to be
slower at start of a ramp, and greater acceleration is allowed when drum pressure is
greater than 1260 psig.
Main Benefits Analysis
These modifications, in conjunction with the upgraded advanced steam temperature
controls, reduced instability and superheat and reheat attemperation spray flows to
30 klb/hr and 40 klb/hr respectively, with the following estimated benefits:
Results
Units
Baseline
Reduced Baseline
Amount of
BTU/h
4,247,776,000
4,178,413,824
69,362,176
Fuel Input
lbs/h
477,546
469,749
7798
$/year
$76,469,102
$75,220,434
$1,248,668
lbs/h
850,988
837,092
13,896
Tons CO2/yr
3,727,327
3,666,463
Reduction
on Rating x Annual Capacity
Factor
60,864
1.633%
Divide lbs by 2.2 to get kg. Multiply MMBtu by 1055 to get MJ.
Table 6.14 Effect on baseline performance of decreased superheat and reheat attemperation flows
Module 6 | 319
Units
Baseline
Reduced
Amount of
Baseline
Reduction
BTU/h
4,247,776,000
4,229,430,400
18,345,600
Fuel Input
lbs/h
477,546
475,484
2062
$/year
$76,469,102
$76,138,842
$330,260
lbs/h
850,988
847,313
3,675
Tons CO2/yr
3,727,327
3,711,229
16,098
Divide lbs by 2.2 to get kg. Multiply MMBtu by 1055 to get MJ.
Results
Units
Baseline
Reduced
Amount of
Baseline
Reduction
BTU/h
4,247,776,000
4,241,369,600
6,406,400
Fuel Input
lbs/h
477,546
476,826
720
$/year
$76,469,102
$76,353,773
$115,329
lbs/h
850,988
849,704
1,283
Tons CO2/yr
3,727,327
3,721,705
5,621
on
Factor
Divide lbs by 2.2 to get kg. Multiply MMBtu by 1055 to get MJ.
Table 6.16 Effect on baseline performance of improved feedwater level & pressure control
Gen Step-Up
Aux 1A
Aux 1B
FGD Boost
Primary
kV
19
19
19
19
Secondary
kV
525
6.9
6.9
13.8
Rating MVA
MVA
520
40
40
10
Existing PF
N/A
0.91
0.85
0.85
0.85
99.1%
97.2%
97.2%
97.2%
New PF
N/A
0.94
0.9
0.9
0.9
New efficiency
99.7%
98.0%
98.0%
98.0%
MVAR
159.5
21.1
21.1
5.3
MW
361.5
36.0
36.0
9.0
MW
11.5
2.0
2.0
0.5
Cable type
n/a
4x3C,
4x3C,
4x3C,
4x3C, 100mm
300mm
100mm
100mm
Cable length
ft
150.0
700.0
700.0
700.0
MVA
384.6
40.0
40.0
10.0
on capacity factor)
Divide lbs by 2.2 to get kg. Multiply MMBtu by 1055 to get MJ.
The base case units GSU and auxiliary transformers are old. The PF on the
generator and plant network sides is relatively low.
Module 6 | 321
Retrofit Description
New, right-sized transformers, active power factor correction on auxiliary network to
increase power factor.
Main Benefits Analysis
Improvements
Annual energy saving due to
Gen Step-Up
Aux 1A
Aux 1B
FGD Boost
kWh
16,800,000
1,348,564
1,348,564
337,141
kWh
84,000,000
8,428,523
8,428,523
2,107,131
kWh
100,800,000
9,777,087
9,777,087
2,444,272
transformer
Annual energy saving due to PF
increase
Annual energy saving kWh
Efficiency gain %
0.6%
0.8%
0.8%
0.8%
$252,000
$24,443
$24,443
$6,111
lbs
109,927,528
10,662,410
10,662,410
2,665,603
$2,415,179
$234,260
$234,260
$58,565
$670,320
$65,018
$65,018
$16,254
MMBTU/
977,805
94,842
94,842
23,710
tons
97,945
9,500
9,500
2,375
$489,727
$47,501
$47,501
$11,875
year
3.29%
0.32%
0.32%
0.08%
$3,827,226
$371,221
$371,221
$92,805
Investment cost
$8,200,000
$400,000
$400,000
$100,000
Payback period
years
2.2
1.03
1.03
1.03
$39,495,700
$4,226,240
$4,226,240
$1,056,560
Divide lbs by 2.2 to get kg. Multiply MMBtu by 1055 to get MJ.
Summary of Benefits
The combination of all the energy efficiency retrofit improvements, shown in the table
below, reduced the heat rate in the base case plant by 8%, with a payback of less
than 2 years.
Automation
Drivepower
Elec System
Total
Results
Improvement
Improvement
Improvement
Improvement
New
Baseline
Average Heat
BTU/h 87,960,600
71,272,115
135,981,755
295,214,470
3,278,635,530
lbs/h
9,889
8,013
15,287
33,189
368,593
Fuel Cost
$/year
$1,332,255
$1,079,490
$2,059,585
$4,471,330
$49,658,345
$/year
$0
$390,876
$734,337
$1,125,213
lbs/h
17,622
14,278
27,242
59,142
656,833
CO2 Emission
tons
77,183
62,540
119,321
259,044
2,876,928
CO2/
$
$385,917
$312,698
$596,604
$1,295,220
$14,384,640
Heat Rate
BTU/
2.46%
1.99%
3.80%
8.26%
10211
Improvement
kWh
Saved Electric
$0
$144,500
$276,067
$420,567
Input Rate
per year
Saved Electricity
Premium
CO2 Emission
Rate per hour
yr
CO2 Charge
per year
9431
Power Sales
Unit Capacity
MW
0.00
7.23
14.02
21.25
Total Annual
$1,718,172
$1,927,565
$3,666,594
$7,312,331
Investment Cost
$1,500,000
$6,516,935
$9,100,000
$17,116,935
Payback Period
years
0.87
3.4
2.5
2.4
$19,912,221
$17,504,785
$39,593,865
$74,010,872
Savings
Divide lbs by 2.2 to get kg. Multiply MMBtu by 1055 to get MJ.
Module 6 | 323
Figure 6.4 Screenshot of the ABB Power Systems Valuation Tool, Version 3, 2009
Module 7
Managing Energy Efficiency Improvement
Module Summary
This module presents tools and methods for managing energy efficiency evaluations
and improvement efforts. This module provides methods for assessing energy
performance and for executing energy improvement design and engineering projects.
The information in this module may be generally applied to process industries;
industry-specific text is shown in a shaded box.
Status
Actual capacity
Number of trips
many
> 25%
in manual control
Amount of operator tweaking, length and
yes, often
Plant documentation
Module 7 | 325
leaders to enforce some best practice workflow rules. Further benefits would be
gained if the cost-analysis functions could have built-in support for some of the most
common life cycle cost (LCC) energy calculations.
Integrated design tools make it easier to configure modeling and analysis tools
described in the next section - the effort involved in collecting data from multiple
incompatible tools can otherwise be as much effort as creating the model itself.
Modeling and Simulation Tools
Modeling tools can perform the necessary energy and mass balances to give an
integrated view of the plant performance. Configuring and running such simulations,
however, requires special training and is usually reserved for R&D or thermodynamic
engineers who may not be part of a retrofit project team. As a result, the potential of
these tools is not realized in many projects.
Ease of use is greatly increased by having a pre-built library of components which
can be assembled according to the plant PFDs. One vendor, AspenTech, claims
that their process engineering design tools can provide 5-20% energy saving due to
built-in energy pinch analysis, process simulation, and model-based cost analysis.
Other modeling tools which have pre-built components and functionality for power
plant modeling are GEs Gate Cycle and ABBs PowerCycle packages. PowerCycle
enables design of thermodynamic loops similar to a P&I scheme and to generate the
mathematical model automatically in the background. The tool has a comprehensive
library, which contains major plant components and its connections as well as
modules for control of variables and signal transmission.
Formal Energy Optimization Methods
Steam power plant modeling tools generally use one or more of the following formal
energy analysis methods:
A description of these methods is beyond the scope of this handbook, but details
can be found in some of the texts listed in the References section.
Module 7 | 327
Figure 7.2 Sample PFD on left, Sample P&ID on right, (Wikipedia / Chemical Engg World)
The figure above shows the typical plant project phases, and the figure
below shows some pitfalls in each of these steps which can lead to an
energy-inefficient outcome.
Figure 7.3 Indicators of project management problems with energy efficiency impact
Module 7 | 329
Figure 7.4 Project hours reduction with a systems approach Honours,E.C. (2004) cited in (Natural
Edge Project, 2007)
Module 7 | 331
Module 8
High Performance Energy Design
Module Summary
This module presents energy-efficiency designs and technical innovations which
may be above the investment and risk thresholds of a modest retrofit project. The
constraints of legacy equipment in retrofit projects also limit the potential to designin large energy efficiency gains. A new plant or unit project, however, provides a
chance for the designer to use best-in-class equipment and methods across all
systems. In new projects, the energy targets can be ambitious and should aim for
the maximum allowed by the process thermodynamics.
The information in this module section is specific to power generation industries
or process plants with on-site power generation. Many sections, however, are also
broadly applicable to all industrial steam generation processes.
parameters, lower system inertia, and much greater efficiency. Greater familiarity
with the capabilities of control system technology will help engineers to push
the envelope even further to ultra-supercritical designs, achieving synergies with
developments in metallurgy.
The higher pressures of supercritical designs increase the auxiliary drive power
required by the boiler feedwater pumps. This extra power is worth the gain in
thermodynamic efficiency - for otherwise similar configurations, the move from
high subcritical to low supercritical steam conditions is said to confer an efficiency
advantage of approximately two percentage points (Weirich and Pietzonka, 1995).
Circulating Fluidized Bed (CFB) Furnaces
In CFB combustion designs, the fuel is spread over a deep wide area (the bed)
and hot air is forced through the bed to supply combustion and to lift and separate
the individual fuel particles so that they behave like a fluid, In the context of CO2
reduction, CFB can accommodate a wider variety of fuels, including biomass. CFB
furnaces can co-fire with up to 20% biomass (Ferrer, Green Strategies for Aging Coal
Plants, 2008).
Auxiliary drivepower enters the picture through the fuel preparation required for
handling and feeding a variety of fuels, and also in higher-volume ash-removal
systems. This is balanced against the reduction in power required for fine
pulverization of the fuel, which is unnecessary in CFB boilers.
Waste to Energy
A facility with CFB combustion may be equipped with recycling capacity for RefuseDerived Fuel (RDF) and therefore qualify for more environmentally sustainable energy
production. On-site processing of the RDF will require significant amounts of auxiliary
power, however.
Combined Cycle Gas Turbines
CCGT plants adds a Brayton gas turbine cycle ahead of the Rankine water-steam
cycle to achieve even higher efficiencies. The exhaust from the gas turbine is a
source of heat for the heat recovery steam generator (HRSG). Some PC steam
plants may lend themselves to conversion to CCGT by installing gas fired gas
turbines at site and use gas turbine exhaust heat to heat boiler feedwater. In such
cases both the coal fired boiler and the gas turbine are used at the same time. This
conversion design is especially useful on coal fired boilers that were de-rated due to
excessive NOx or furnace slagging (Eng-Tips Power Generating Forum, Dave Fitz,
2006).
Auxiliary electric drivepower is necessary for gas turbine startup and fuel pumping
requirements, but auxiliary control can play an even larger role in energy efficient
operation of CCGT plants through optimal operation and allocation of the multiple
sources and sinks for heat and power generation and consumption.
Integrated Gasification - Combined Cycle IGCC
The IGCC process burns coal, but it begins with a low-oxygen gasification unit to
produce synthetic gas, which is then combusted in the gas turbine of a CCGT unit.
IGCC plants have lower emissions of pollutants and higher efficiencies than PC
steam plants. IGCC is key to realizing the industrys vision of clean coal, but some
challenges remain before plants can be scaled up to match the largest coal plants
today. The capital cost of an IGCC plant is estimated to be 10-16% higher than a PC
plant of similar capacity (Pew Center on Global Climate Change 2005). Recent price
volatility in natural gas are delaying the anticipated trend toward IGCC plant types,
as discussed in Trends in Steam Plant Designs and Efficiency. In one recent
project in Netherlands (ABB/Nuon), the gasifier converts coal and biomass into
syngas, which is used to fuel the combined-cycle units.
Significant new auxiliary drivepower is needed for coal slurry pumps and air/oxygen
compressors, as well as an extra pumping of economized boiler feedwater to the
syngas cooler.
Gas-Gas Reheat for Flue Gas Desulfurization (FGD)
Flue gas reheat after flue gas desulphurization (FGD) systems can scavange
additional heat from the thermodynamic cycle if they use steam heating, as
commonly applied in the USA, but newer FGD systems have feed/effluent gas/gas
heat-exchangers that avoid losses from this source (IEA Coal Online - 2 2007). See
the section on Automation Emissions Controls for details. This type FGD design,
however, requires additional auxiliary speed control and automation.
Powering and Re-Powering with Biomass
Biomass combustion is mainly carbon-neutral and should therefore be exempt from
any potential CO2 charges. Most power plants fired on PC can co-fire up to 4-5%
biomass without significant degradation and without furnace re-design (Ferrer, Green
Strategies for Aging Coal Plants, 2008). The practical upper limit to co-firing with
biomass in existing PC plants may be as high as 20% (Pew Center on Global Climate
Change 2005), but at the expense of decreased efficiency. According to Robinson
and co-authors in their Assessment Potential of CO2 Reductions due to Biomass,
2003, co-firing with 10% biomass can achieve carbon mitigation at a cost of $8-$27
per metric ton CO2.
Module 8 | 335
Wood shavings and straw have been the most common source of biomass, but
recent US energy legislation enables the use of other sources such as fresh wood
(Lahoda, Arndt, & Hanstein, 2006). The reliability of an economical supply of wood
fuel is an important requirement for continually high biomass co-firing. The definition
of biomass in the EU is limited to about 15 different materials; all else is considered
simply waste and may not be processed into energy that is considered carbonneutral.
Repowering a PC furnace to burn a higher proportion of biomass requires design
changes and possibly a complete conversion to a new furnace technology, such as
that described in the section on Circulating Fluidized Bed Furnaces. Maintaining
steam and re-heat steam temperature is another challenge when firing with larger
fractions of biomass. By increasing stability, auxiliary automation systems can help
increase the plant efficiency to levels required for economic biomass co-firing while
maintaining megawatt output.
Auxiliary fan power systems are also critical to the economic co-firing with biomass.
Drivepower must be efficient and sufficient to provide the increased excess air, which
ranges from 15% to 50% for bark, wood and most biomass fuels (Babcock & Wilcox
2005). The controllability of VFD-equipped draft fan systems allows for more efficient
operation for varying proportions of biomass. Biomass fuels have varying particle
sizes, are more volatile when dry and therefore they tend to burn more in suspension
compared to coal (Babcock & Wilcox 2005). Automatic control of VFD-equipped
draft air flows can provide a more uniform distribution, as described in Air Flow
Control for Combustion, and hence more complete and efficient combustion.
Biomass need not be co-fired in the main boiler furnace to provide its heat benefits
to the main cycle. Heat from external biomass combustion can be used to preheat air or feedwater for the main boiler. Separate biomass combustion may be an
alternative source of steam for a low-level banking of the unit.
Combined Heat and Power / Co-Generation
Also known by acronyms CHP or COGEN, this plant design puts the turbine
steam to productive use for industrial processes or for district heating. Location is
a powerful determinant of the viability of a CHP design, as is the existing turbine
design when plant conversion is being considered. A variant on CHP uses steam or
heated water for desalination purposes. The energy efficiency bonus of eliminating
condenser heat waste is illustrated in the Sankey energy flow diagram below:
71
Losses
Power
Station Fuel
(106)
Condensing
Power Plant
Electricity
35
165
Boiler Fuel
(59)
CHP
Fuel
Electricity
CHP
Boiler
Plant
Heat
50
100
Heat
Losses
Losses
9
15
Figure 8.1 Sankey energy flow diagram for CHP vs. conventional steam plant, Ref : ABB
The energy balance shows that the thermal efficiency of CHP plants is high (85%+)
and approaches (and is ultimately limited by) the efficiency of the boiler itself. A
full accounting of all benefits of CHP to industrial users and society in general is
available in Small is Profitable (Lovins,A, 2006).
There is significant potential for CHP: as of 2008 only 9% of all electrical power
generation comes from co-generation plants (2008, US DoE).
Energy Storage Systems
Power plant units can operate continuously at their optimal efficiency design loads
if there is an economical way to store the produced energy for transmission at later
periods of high demand. Another advantage of energy storage is that it displaces
spinning reserve or banked plants.
Pumped Storage
Locations fortunate enough to have nearby volumes at higher elevations may use
these for energy storage. Drivepower from periods of low demand is used to pump
water to the lake at higher elevation, from which hydro power can be generated
during (peak) periods of higher demand.
Battery Storage
Battery storage and inverter technology for energy storage (see case below) is a
viable replacement for fossil fueled spinning reserve.
Module 8 | 337
Case Example
Battery Energy Storage System
Golden Valley Electric Association in Fairbanks, Alaska contracted with ABB to
construct a Battery Energy Storage System (BESS). The BESS will automatically pick
up 26 megawatts of load for 15 minutes, or 40 MW for 7 minutes. The switch from
power line to battery and back to power line is seamless and goes unnoticed by the
customers, so the prime function of the BESS is to provide spinning reserve in case
of power plant or transmission line equipment failure.
The two primary subsystems in BESS are the IGCT converter and the Ni-Cd
battery. The battery is the energy storage medium. The IGCT converter is the
interface between the DC battery voltage and the 60 Hz AC GVEA system voltage.
The converter transformers match the converter output to the 138 kV system
voltage. The BESS can be programmed for the following modes: Spinning Reserve,
Automatic Scheduling, Support for Scheduled Load Increase, Automatic Generation
Control, Var Support, Power System Stabilizer and Charging.
Carbon Capture and Storage
There are many technologies proposed for capturing then storing the CO2 released
during fossil fuels combustion. Post-combustion ammonia absorption is the nearest
to market, and will require significant additional amounts of auxiliary drivepower for
circulation pumping, CO2 liquification, and high pressure pumping into permanent
storage locations, Optimization and automation of the CCS system will also play
a key role in making this technology viable. However, current energy consumption
estimates for the new auxiliary systems required for CCS are from 25-35% of gross
plant output. This implies that for every standard PC plant of a given size, say
500MW net output, that is replace by a CCS plant, up to 40% more coal will have to
be consumed to get the same net electrical output. That is, three new SC units will
have the output of two old subcritical units.
Activity
Risk
Reward
LOW
MED
MED
MED
MED
LOW
LOW
MED
LOW
MED
MED
HI
MED
MED
MED
MED
HI
HI
HI
HI
ash in the flue gas is removed by existing fabric bag filters or electrostatic
precipitators, and can be used in high-quality cement production.
Install FGD systems which can process FGD by-products into fertilizer or
sulfur-based chemicals for other processing plants
Use turbo-expanders on blow-down lines to recycle blow-down steam
thermal, kinetic energies.
Buy energy efficiency as a service provided by vendors willing to stand by
their claims for their equipment and designs. Vendors and engineering service
providers could provide premium/penalty contract options for efficiency
improvement guarantees.
Draw some of the intake air for Forced Draft (FD) fans from inside the main
unit building, near the top. This recycles heat lost from much auxiliary
equipment, plus the heat losses through boiler furnace refractory linings
(which deteriorate with age). Integrate the FD fan intake with the building
HVAC system to ensure satisfactory air flows. Consider ductwork to lead
heated air from the step-up transformer fan cooling system to the FD fan
intake.
Use the low-cost waste heat from the LP turbine in an absorption chiller,
assuming there is a nearby demand for cooling. This chiller may be costeffective even if applied only to in-plant and office HVAC cooling needs.
Apply flue gas and/or condenser waste heat towards additional coal drying,
especially if lignite coal is used; lignite has a high moisture content. According
to EPRI, a CFB dryer technology which removes nearly a quarter of the coals
moisture before the coal is fed into the power plant boiler may yield a 2.8% to
5.0 % efficiency improvement. (EPRI, 2005)
Use acoustic detonation waves for cleaning ash deposits from boiler heating
surfaces, a lower energy alternative than current sootblowing practice..
Use co-generation with solar-thermal energy. Though still in the conceptual
design phase, the technologies exist to provide heat for feedwater heating
and/or steam generation from a solar-thermal plant, thus reducing fossil fuel
consumption. (EPRI, 2008)
Use engineered osmosis to recover waste heat from condenser systems.
EO uses special membranes for separation of water, driven by low amounts
of heat from condenser cooling systems. This technology could be used in
conjunction with desalination facilities.
Module 8 | 339
Appendix A
Technical Symbols
The following tables of common electrotechnical symbols and SI units are from ISO
31 and IEC 60027. This ISO standard 31 is being superseded by the harmonized
ISO/IEC 80000 standard.
Mathematical Symbols for electrical quantities (general)
Symbol
Quantity
SI unit
V/m
C/m
electric potential
F/m
electric capacitance
A/m
x, ,
S/m
electric conductance
electric resistance
electromotive force
apparent power
w, (va)
active power
reactive power
W, (var)
phase displacement
rad
load angle
rad
rad
admittance
resistance
conductance
reactance
susceptance
impedance
F/m
rad
Quantity
SI unit
magnetic flux
Wb
A/m
magnetomotive force
permeability
H/m
H/m
inductance
L mn
mutual inductance
efficiency
slip
number of pole-pairs
w, N
number of turns
n tr (t)
transformation ratio
overvoltage factor
relative permeability
kr
Note: For US/English version of these symbols, see IEEE 280 Standard Letter
Symbols for Quantities Used in Electrical Science and Electrical Engineering
Appendix B
Steam Plant Cycle & Equipment
Thermodynamic Cycle
The following diagrams and text are adapted from (IEA Coal Online - 2, 2007)
The proportion of the heat supplied that is converted into mechanical work is
referred to as the efficiency of the cycle. For the ideal engine, the efficiency is related
to the initial and final temperatures of the system, as follows: h = (T1T2)/T1 (1)
where h is the efficiency and T1 and T2 are the upper and lower (initial and final)
temperatures between which the engine operates, expressed in degrees Kelvin. The
lowest temperature in the steam-turbine cycle depends on the temperature of the
coolant water that cools the steam and condensate leaving the low-pressure outlet
of the turbine system. The idealized thermodynamic steam-water (Rankine) cycle,
with superheating, is illustrated on the figures below. Pressure vs. Volume (right side)
and Temperature vs. Entropy (left side)
Figure B.1 Idealized Rankine cycle P-V and T-S diagrams, (IEA Coal Online - 2, 2007)
Sites with access to cold sea water can reach lower bottom-end temperatures in the
cycle, and so achieve higher efficiencies. For an upper temperature of 600C (typical
of a state-of-the-art supercritical turbine) and lower temperature of 20C (typical for
sea-water cooling at a North European coastal location), the theoretical maximum
efficiency given by equation (1) is 66%. In practice, steam-cycle efficiencies are
much lower, in the low 40s% for sub-critical boiler units.
Appendix B | 343
Figure B.2 Steam cycle fluid flow and main equipment, (IEA Coal Online - 2, 2007)
Cycle Operation
A drum-type subcritical PC boiler takes the pressurized and preheated boiler
feedwater from around 250260C up to the evaporation point, then superheats
it to 540C or above before sending to the high- pressure turbine. In the steam
turbine, the steam is expanded while its energy is converted into mechanical work
as it passes over static and moving blades within high-pressure (HP), intermediatepressure (IP) and low-pressure (LP) turbines, which are usually compounded on to
one shaft that drives the generator. .All large steam-turbine cycles incorporate reheat
of the intermediate-pressure steam from the high-pressure turbine exit, and multiple
stages of feedwater pre-heating using steam extracted from the turbine to maximize
efficiency. Steam emerging from the LP turbines is condensed, then pumped back to
the boiler after pre-heating, thus completing the cycle
The thermal efficiency of state of-the-art PC plants is 4547%, LHV (Lower Heating
Value) basis, at cold sea-water cooling locations. Such plants use main steam
conditions well into the supercritical range, with pressures approaching 30 MPa and
temperatures around 600C Because of the degree of scope for achieving further
efficiency improvements through moving to even higher steam conditions, materialsdevelopment programs are in progress in different parts of the world to reach them.
Together with cycle design advances, these are expected to realize power-plant
efficiencies well beyond 50%, LHV basis (IEA Coal Online - 2, 2007).
Boiler Operation
The figure below shows a drum-type subcritical boiler in simplified diagrammatic
form. The economizer, forming the last stage of the boilers convective section,
takes the incoming feed-waters temperature to about 60C below evaporation
temperature for sending on to a steam drum/evaporator recirculation loop. The
economizer takes the flue gases down to around 350C. Lower-temperature heat,
down to about 100150C, is recovered by transferring the heat to the incoming
combustion air using an air heater. This final stage of heat recovery is the air heater,
which generally takes the flue gas temperature down from the economizer exit
temperature of 350400C to 120150C
Figure B.3 Steam generator main equipment, (IEA Coal Online - 2, 2007)
Evaporation takes place using mainly radiant heat, which is transferred to watercarrying tubes forming the wall of the furnace zone of the boiler. The ensuing water/
steam mixture passes to a large steam drum, which allows the steam to separate,
and the water returns to the evaporator. Either forced or natural circulation is used
to send the water round the loop. Steam leaving the drum is then sent to the
primary superheater. In both subcritical and supercritical boilers, the superheat and
reheat heat-transfer surfaces are mounted above the furnace and in the convection
section of the boiler. Super-heaters and re-heaters are generally of a pendant and/or
horizontal type, each with at least two stages (for simplicity, only two for superheat
and one for reheat are shown on the figure)
Appendix B | 345
Appendix C
Integrative Design Principles
Integrative Design is founded on Whole System Thinking principles. These
principles also appear in the related fields of System Engineering, Sustainability
Engineering, Industrial Ecology, and meta-design. Integrative design principles
are reminders to engineers to look in the places where people, by nature, are not
equipped to easily visualize. The four corners which may hide design problems and
opportunities are:
Hidden Quantity
Reason why
periphery
the subjective
Appendix C | 347
Bottom-up thinking moves in the opposite direction of the process flow of fluid, heat
or even of information & signals. Start with what you need to have or deliver, then
work back to supply.
Start downstream to design systems with lower capacity requirements
Reduce and rationalize end-use demand first : gather data to estimate the
REAL end-use loading, then work backward to the power source, reducing
losses along the way, Finally, size the supply according to the now-reduced
loads
Keep capacity design margins small
It will be cheaper to add extra capacity when requirements increase. Consider
a parallel standby unit instead of oversizing the main unit.
Recover and re-use process energy
Use any means, mechanical or chemical, to retrieve what the process doesnt
want...
Compounding over Time
Efficiencies compound upward along the flow path, and, because energy is an
operating cost, these savings also compound over time.
Compounding over Capital Cost
There is third major compounding effect, and that is the capital equipment cost.
A reduction of downstream loads usually means that upstream supply equipment
can be safely downsized, which also usually means lower installed costs. Take full
advantage of this effect by doing a bottom-up energy assessment of the candidate
designs when the plant is still on the drawing board, rather than waiting for a retrofit.
Think Interfaces: to see things at the edges
Put system before components
Put application before equipment
Practice good thermal integration
Connect sources with sinks, aspire to know and use all the available energy
(exergy), including ambient energies...
Harmonize the interfaces in both project and plant
In your project - between the disciplines & between suppliers. In the plant between diverse process units & between black-boxes.
348 | ABB Energy Efficiency Handbook
Appendix C | 349
References
ABB AG, Power Technology Systems. Unit C of the Scholven Power Plant
Automated with System 800xA. ABB Power Generation Solutions & Products.
2006. http://library.abb.com/global/scot/scot221.nsf/veritydisplay/407efc39c
6bf8878c125723d0037c852/$File/Unit%20C%20of%20the%20Scholven%20
Power%20Plant%20F%20DEABB%201249%20%2006%20E.pdf (accessed Oct
2008).
ABB Drives. Dimensioning a Drive: Technical Guide #7. 2002.
ABB Drives. Direct Torque Control: Technical Guide No.1. 2002.
ABB Inc. Effects of AC drives on Motor Insulation: Technical Guide #102. 1998.
ABB Inc. Plant Automation. Application Guide - Steam Temperature Control. ABB,
2006.
ABB Inc. Plant Automation. Application Guide : Boiler-Turbine Coordinated
Control. ABB, 2006.
ABB Industry Oy. Direct Torque Control, Technical Guide No. 1. 1999. http://
www.abb-drives.com/StdDrives/RestrictedPages/Marketing/Documentation/files/
PRoducts/DTCTechGuide1.pdf.
ABB Ltd,Transformers. ABB Transformer Handbook. 2007.
ABB Ltd., Power Generation Unit. Power Generation Solutions & Products.
Solutions for Fossil Fuel Power Plants. ABB. 2006. http://library.abb.com/global/
scot/scot221.nsf/veritydisplay/82660b404a03faa3c12571d300536bf1/$File/
ABB%20Solutions%20for%20FPP_S_DEABB%201297%2006%20E_23.pdf.
ABB Motors & Drives. ABB Sustainability Guide #1. ABB. Nov 2007. http://
search.abb.com/library/ABBLibrary.asp?DocumentID=3AFE68902037&Language
Code=en&DocumentPartID=1&Action=Launch.
. ABB Technical Application Paper: Three-phase asynchronous motors. ABB.
2007. www.abb.com.
ABB Oy. Drives. 100 Top Energy Saving AC Drive Tips. ABB Drives. ABB. May
2006.
ABB Oy. Drives. Energy Efficiency Presentation, ABB Drives. Jan 9, 2008.
. Guide to Variable Speed Drives (Guide #4). ABB. 2002.
. Using Variable Speed Drives in Pump Applications: Application Guide No.2.
ABB. 2006.
ABB Power Products. Switchgear Manual. 2006.
ABB Switzerland, MV Drives. Guide to Standard Medium Voltage Variable Speed
Drives. ABB. 2002.
References | 351
On-Line Resources
Supplier Corporate Sites:
ABB Inc., http://www.abb.com/energyefficiency
ABB Power Generation Solutions & Products has brochures, case studies
Alstom Power, http://www.power.alstom.com/home/
Info on power plant integration
Siemens Power Generation, http://www.powergeneration.siemens.com
Pages & tech papers on steam power plants
Honeywell ACS, Power Solutions, http://hpsweb.honeywell.com/Cultures/enUS/IndustrySolutions/Power
Schneider Electric, http://www.criticalpowernow.com/
White papers, efficiency calculators , but focus on low voltage
Engineering Services Corporate Sites:
Foster-Wheeler Global Power Group , http://www.fwc.com/GlobalPowerGroup/
Many good technical papers on CFB, biomass co-firing, materials
Black & Veatch Energy , http://www.bv.com/markets/energy/
Article on coal plant retrofits
www.bv.com/services/Climate_Change_Solutions/En...
GE Power, http://www.gepower.com/home/index.htm
Has design guides and handbooks, section on Clean Coal (IGCC)
Bechtel Power, http://www.bechtel.com/power.html
Has several project cases
Burns & Roe Power and Energy , http://www.roe.com/power_index.htm
Not much online
KBR (Kellogg,Brown & Root) , http://www.kbr.com/publications/coal.aspx
Articles on coal gasification
Intergraph Process,Power & Marine , http://www.intergraph.com/ppm
2D, 3D design software packages
AspenTech , http://www.aspentech.com/
Modeling and simulation software tools
CH2M Hill, http://www.ch2m.com/corporate/services/sustainable_solutions
EPC with good energy efficiency credentials
References | 355
Arup, http://www.arup.com/
EPC with good energy efficiency credentials, mostly built environment
Rumsey Engineers, http://www.rumseyengineers.com/
Specialist in energy efficiency engineering, mostly HVAC
Southern Company, http://www.southerncompany.com/planetpower
One example of a utility with a progressive energy efficiency profile
Journals, Articles & News Sites:
Energy Central , http://www.energycentral.com/
Have a large tech white paper library
Power Engineering International, http://pepei.pennnet.com/
Good articles on steam plant efficiency, retrofits
Plant Engineering LIVE, http://www.plantengineering.com/
Many white papers, links on energy efficiency
Plant Systems, http://www.plantservices.com/
Excellent VFD articles, sustainability links
Connecting Industry, http://www.connectingindustry.com/
Section on energy management
International Journal of Energy Research
http://www3.interscience.wiley.com/journal/3343/home
Academic Sites:
The Natural Edge Project, http://www.naturaledgeproject.net
Course in whole system design, with pumping system case
Engineering News Record, Power & Industrial, http://enr.construction.com/
infrastructure/power_industrial/default.asp
Industry news
Energy Storm, http://www.energystorm.us/
Citations, abstracts only
University of Pittsburgh, Mascaro Sustainability Initiative, http://www.
mascarocenter.pitt.edu/
Mostly built environment, but some power infrastructure as well
Massachusetts Institute of Technology, Engg Systems Div. http://esd.mit.edu/
NTNU Norway , http://www.ntnu.no/
MITs Center for Engineering Systems Fundamentals , http://cesf.mit.edu/
For schools : start when they are young!
References | 357
Revision History
Ver
Date
Author
Change Description
2.4
23.03.2009
RPM
3.0
26.03.2009
RPM
3.1
12.04.2009
RWV
ABB Ltd
P.O. Box 8131
CH 8050 Zurich Switzerland
Phone: +41 (0) 43 317 7111
Fax: +41 (0) 43 317 7321
www.abb.com
Note:
We reserve the right to make technical
changes or modify the contents of this
document without prior notice. With
regard to purchase orders, the agreed
particulars shall prevail. ABB does
not accept responsibility whatsoever
for potential errors or possible lack of
information in this document.
We reserve all rights in this document
and in the subject matter and
illustrations contained therein. Any
reproduction in whole or in parts is
forbidden without prior written consent
of ABB.
Contact us