Comparing UPS System Design Configuration
Comparing UPS System Design Configuration
All content in this presentation is protected 2008 American Power Conversion Corporation
Introduction
1. UPS (Uninterruptible Power Supply) system is implement between
public utility power and critical load
2. There are five main UPS system design configurations:
a.
b.
c.
d.
e.
Capacity
Isolated Redundant
Parallel Redundant
Distributed Redundant
System plus System
Availability needs
Risk tolerance
Types of loads
Budgets
Existing infrastructure
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Availability
Driving force behind the UPS configuration is demand for availability
Availability is the estimated percentage of time that electrical power
will be online and functioning properly to support the critical load
All UPS systems (and electrical distribution equipment) require regular
intervals of maintenance. Availability of a system is dependent on:
As the UPS goes higher on the scale of availability, the upfront cost
also increases
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
$$$
$$$$
$$$$$
$$$$$$
What is N?
UPS configurations are often described by nomenclature: N
N can simply be defined as the need of the critical load
It is the power capacity required to feed the protected equipment
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
$$$
$$$$
$$$$$
$$$$$$
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
The main or primary UPS module that normally feeds the load,
where the isolation or secondary UPS feeds the static bypass of the
main UPS module
Requires that the primary UPS module have a separate input for the
static bypass circuit
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Isolated
Redundant
(Figure)
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Isolated
Redundant
(Single Point of Failure)
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
$$$
$$$$
$$$$$
$$$$$$
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Parallel Redundant
Lightly - loaded UPS modules are typically less efficient than a
module that is loaded closer to its capacity
Table below shows the typical running load for a system using various
UPS module sizes, all feeding a 240 kW load
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
$$$
$$$$
$$$$$
$$$$$$
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
$$$
$$$$
$$$$$
$$$$$$
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Summary
The power infrastructure is critical to the successful operation of a
data centers equipment.
There are various UPS configurations that can be implemented, with
advantages and limitations of each.
By understanding the businesss availability requirements, risk
tolerance, and budget capability, an appropriate design can be
selected.
As demonstrated in the analysis of this paper, 2(N+1) architectures
fed directly to dual-corded loads provide the highest availability by
offering complete redundancy and eliminating single points of failure.
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09
Schneider Electric Critical Power & Cooling Services Danny Phang, 3/3/09