DAS Program Generic 20140611 Product Selection Guide
DAS Program Generic 20140611 Product Selection Guide
5067 Mini-BDFB
DC-DC Up-Converter
Micro-BDFB / SPDU
Infinity S Power System
GECriticalPower.com
Power Express
Class 2 Distribution
The GE Power Express Class 2 Distribution is a 1RU shelf that provides 32 100VA limited
circuits for safe powering of remote loads. NEC Class 2 rating allows for power cabling to be
deployed in data cable raceway instead of conduit thus reducing labor time and increasing
speed to market. The GE Power Express Class 2 Distribution incorporates 4 replaceable
Who We Are:
GEs Critical Power business provides
mission-critical customers such as data centers,
healthcare facilities and telecommunication
plug-in-play modules that generate 8 100VA circuits each. Each circuit is internally fused
within the module eliminating the possibility of users plugging an incorrect rated fuse. This
guarantees that each circuit maintains compliance to the tested Class 2 safety rating under
UL. Each shelf is designed to support an alarm card for stand-alone deployment and can
be uplinked over the RS-485 data bus through the RJ-45 connections on the rear of the
shelf. This uplink allows each shelf to interface a GE Pulsar Plus controller (commonly used
What We Do:
in our Infinity Power Systems) allowing local access, alarming and control of each circuit in
every shelf as well as remote interface over the controller LAN connection.
No Pluggable Fuses
DC Energy Systems
Power Switching
Embedded Power
GECriticalPower.com
Input
Input
Voltage Range
Input Current
-42Vdc to -60Vdc
20A per module (80A per shelf) at -40Vdc
Output Circuits
Automatic Power Limit
Voltage Range
Max Current
Environmental
Operating Temperature
Storage Temperature
Humidity
Altitude
Heat Dissipation
-40C to +65C
-40C to +85C
< 95% non-condensing
4000M max
57 BTU per module (227 BTU Max per shelf)
Input
Output
Data
Alarm
Mechanical
Length (inch/mm)
Width (inch/mm)
Height (inch/mm)
Weight (lb/Kg)
Shelf
11.25 (286mm)
17.5 (445mm)
(19 Rack Mount)
1.75 (44.5mm) (1RU)
6.5 lbs (2.95kg)
Module
7.625 (194mm)
3.44 (88mm)
1.72 (44mm)
0.8 lbs (.363kg)
Safety
RoHS
EMC
ESD
Voltage Range
Input Current
Inrush Current
Holdup Time
-40Vdc to -72Vdc
75Adc max
100Adc max
6ms
Output
Voltage Default
Voltage Adjust Range
Rated Output Current
Rated Output Power
Ripple (5Hz to 20MHz)
-RMS
-Peak to Peak
Over Voltage Protection
-Delayed
-Immediate
Over Temperature
-Warning
-Shutdown
54Vdc
44 - 58 Vdc
0.1 to 46.3A
2500W
250mVrms
500mVpk-pk
60Vdc
65Vdc
5C
20C
General
Connections
NEBs
Cooling
Heat Dissipation
Environmental
Operating Temperature
Storage Temperature
Power De-Rating
Relative Humidity
Altitude
Audible Noise
Mechanical
Shelf
Module
Length (inch/mm)
Width (inch/mm)
17.06 (433mm)
17.5 (445mm )
(19 Rack Mount)
1.75 (44.5mm) (1RU)
8.75 lbs (4.0kg)
13.85 (351.2mm)
4 (101.6mm)
Height (inch/mm)
Weight (lb/Kg)
1.63 (41.4mm)
5 lbs (2.27kg)
RoHS
EMC
ESD
Ordering Information
Power Express
Ordering Code
Description
Ordering Code
Description
150031971
CC109157657
CC109170528
150036109
CC848817651
150027362
DC to DC Up-Converter System
GECriticalPower.com
efficient footprint. The SPS shelf is 1.75 high, 10.3 deep and mounts in 19-inch or 23-inch
wide frames, with three power slots for rectifiers and distribution. The Pulsar Edge controller
has Ethernet connectivity to facilitate remote network management to monitor and control
rectifiers, batteries, and distribution. SPS is a reliable DC power solution where system
height and depth are restricted.
converged networks
Large plant features in a small
plant package
3000 Watts / 60 Amps single shelf
Shelf Options
capacity in 1RU
10.3 inches (264mm) depth is ideal
where space is restricted
95% Efficiency
SPS TE Rectifier
This hardened rectifier is a single phase, hot
pluggable, fan cooled rectifier that provides
up to 1600 Watts of high availability
DC power. The constant output power
characteristics, extended temperature
range, universal AC input, and compact size
are key attributes that make this rectifier
the right choice for your power needs.
GECriticalPower.com
SPS TE Rectifiers
The SPS TE rectifiers are single phase, hot-pluggable, fan cooled rectifiers that provide highly
reliable DC power. As cost-effective rectifiers that occupy just 1RU, its shallow depth is an ideal
power solution for space critical applications. The constant output power characteristics as
well as the extended temperature range, universal AC input voltage range and compact size
are key attributes that make this rectifier the right choice for your power needs.
These rectifiers are applicable for indoor and outdoor environments especially where
equipment depth and height are restricted. The SPS TE rectifiers communicate digitally to
the Pulsar Edge controller family over a RS485 bus to add extensive monitoring and alarm
management facilities. Its flexible and sophisticated feature set makes this front-end supply
an excellent choice for power in a variety of application spaces.
Applications
Telecommunications networks
Routers/switches
Data networks
PBX
Indoor/outdoor wireless
Transmission
Key Features
Extended temperature range
Hot pluggable
Universal AC input
RoHS compliant
Input
EP0500UTEZ
EP1000UTEZ
EP1600UTEZ
Voltage Range
- Low-Line
- High-Line
90-175Vac (500W)
176-264Vac (500W)
90-175Vac (1000W)
176-264Vac (1000W)
90-175Vac (1200W)
176-264Vac (1600W)
Input Current
6.25-4.5A @ 90-120Vac
2.55A @ 230Vac
12.5-9.3A @ 90-120Vac
5.1A @ 230Vac
15-12A @ 90-120Vac
7.5A @ 230Vac
Input Frequency
45 65Hz
45 65Hz
45 65Hz
Inrush Transient
25 Apk
25 Apk
25 Apk
Power Factor
~1.0
~1.0
~1.0
Efficiency
95%
95%
95%
<5%
<5%
<5%
Holdup Time
42-58Vdc
42-58Vdc
42-58Vdc
Voltage Nominal
54.5V
54.5V
54.5V
10Adc max
10Adc max
20Adc max
20Adc max
24Adc max
32Adc max
Psophometric Noise
<5 mV max
<5 mV max
<5 mV max
Ripple
<200 mVpkpk
<200 mVpkpk
<200 mVpkpk
Overvoltage Protection
59.5Vdc
59.5Vdc
59.5Vdc
Output
Serial Interface
GECriticalPower.com
Environmental
Operating Temperature
Storage Temperature
Power Derating
Humidity
Altitude
4000M max
Audible Noise
< 55dBA
Mechanical
Length (inch/mm)
8.11 / 206.0
Width (inch/mm)
4.98 / 126.5
Height (inch/mm)
1.64 / 41.6
Weight (lb/Kg)
3.08 / 1.4
Evaluated by independent NRTL test lab to Telcordia GR63, Issue 4 & GR 1089, Issue 6
Safety
RoHS
EMC
CISPR22 (EN55022) Class B and FCC-CFR, Part 15, sub-part B Class B with shelf; GR1089 Class A
ESD
EN61000-4-2, Level 4
Outline Drawing
GECriticalPower.com
Applications
Telecommunications networks
Digital subscriber line (DSL)
Indoor/outdoor wireless
Routers/switches
Fiber in the loop
Transmission
Data networks
PBX
Key Features
GECriticalPower.com
Agency Certifications
Operating Voltage
24 Vdc, 48 Vdc
(Range: 18 to 60 Vdc)
Input Power
Less than 7W
0 - 95% (non-condensing)
Physical Specifications
Display
EMC
Electrostatic Discharge
EN 61000-4-2 level 4
Radiated Emissions
Safety
Controller
Ordering Code
Description
CC109142238
SPS841A_3C3R Controller
CC109156898
SPS841A_0I5R Controller
150027896
SPS841A_9I0R Controller
Photo
Rectifier Module
Ordering Code
Description
150027894
500W Rectifier
EP0500-UTEZ
CC109165602
1000W Rectifier
EP1000-UTEZ
CC109165610
1600W Rectifier
EP1600-UTEZ
GECriticalPower.com
Photo
Description
Rectifier
Slots
Battery
Breakers
LVD
CC109148136
J2007003L001
Bulk
CC109146503
J2007003L001A
Bulk
Rear
None
Rear
None
CC109148144
J2007003002
6 GMT's
Front
LVBD
CC109165890
J2007003002D
CC109151536
J2007003002A
6 GMT's / Door
Front
LVBD
6 GMT's
Front
LVBD
CC109165916
CC109156907
J2007003002AD
6 GMT's / Door
Front
LVBD
J2007003002X
6 GMT's
Front
None
CC109165908
J2007003002XD
6 GMT's / Door
Front
None
CC109156915
J2007003'002AX
6 GMT's
Front
None
CC109165924
J2007003002AXD
6 GMT's / Door
Front
None
CC109158696
J2007003002AXB
6 GMT's
Front
None
CC1091659232
J2007003002AXBD
6 GMT's / Door
Front
None
CC109146511
J2007003004
10 GMT's
Rear
LVBD
CC109156923
J2007003004X
10 GMT's
Rear
None
150026024
J2007003004XB
10 GMT's
Rear
None
CC109151544
J2007003004A
10 GMT's
Rear
LVBD
CC109156931
J2007003004AX
10 GMT's
Rear
None
150024564
J2007003004AXB
10 GMT's
Rear
None
CC109156114
J2007003011
12 GMT's
Rear
None
CC109159372
J2007003014
Rear
LVBD
Rear Terminal
150033629
J2007003014LA
Rear
LVLD
150030787
J2007003014XA
Rear
None
DC Output
10
AC Input
CC848776105
CC848890153
CC848820317
CC848865980
847861192
CC848817651
CC848885698
CC848890203
CC848850792
CC848853614
CC848850842
CC848890211
CC848847368
CC848887158
CC848847780
848748987
GECriticalPower.com
Description
Load Breaker
Positions
Battery Breaker
Positions
LVD
150030465
12
LVBD
150032350
24
LVBD
Photo
Bulk Shelves
Ordering Code
Description
150028854
AC Input
Rectifier
Slots
Controller
Support
DC
Output
Rear AC
Terminal
No
Rear Bulk
Photo
Description
Load
Breaker
Positions
Battery
Breaker
Positions
LVD
150032397
LVBD
150032400
No
150032401
36
No
GECriticalPower.com
Photo
11
Notes
12
GECriticalPower.com
SPDU
Secondary Power Distribution Unit
The GE SPDU serves as a secondary power distribution center for +24Vdc or -48Vdc DC
power delivered from a battery plant to the load equipment. The 4U (7 in.) tall configuration
is versatile with 19 or 23 rack or wall mounted panels with fuse or circuit breakers options,
single or dual (A/B) load bus, and 600A carrying capacity per panel (300A per bus in dual
load bus configurations.) A digital meter monitors voltage and current of each load bus.
4 RU size
plant to load equipment
GECriticalPower.com
13
Specifications
Mechanical
Height
7 in. (175.7mm)
Width
Depth
5 in. (127mm)
Weight
Agency Certifications
Telcordia
UL
Canada/US UL60950/UL1801
CE
CE mark
EMI/EMC
14
GECriticalPower.com
Description
CC109160883
Group 2: 23 SPDU, dual bus, dual shunt, smart meter, 22 breaker/fuse positions
Amperage
CB Positions (Poles)
10
407998145
10
407998152
10
10
407998160
15
10
407998178
16
10
407998186
20
10
407998194
25
10
407998202
30
10
408213486
40
407998210
45
407998228
50
407998236
60
407998244
70
407998251
80
407998269
90
407998277
100
CC848808551
100
408185353
125
408185346
150
1/0
408564941
200
2/0
CC408573975
225
4/0
408535752
250
4/0
407998137
848631479
2-pole adapter bus kit (includes bus for hole lug on 5/8 centers and hardware),
order one per breaker
GPS 4827 only
848745662
3-pole adapter bus kit (includes bus for 5/16 hole lug on 1 centers and hardware),
order one per breaker
GPS 4827 only
GECriticalPower.com
Photo
15
Notes
16
GECriticalPower.com
With offerings in 19 and 23 the 5067 can support single, dual or four load buses with a
carrying capacity of up to 600A per load. The need to specify distribution components at
the time of order is unnecessary, plug-in breakers or fuses can be easily installed when the
panel arrives on-site or deferred for future needs.
Digital Meter
GECriticalPower.com
point of load
High density models available with
48 circuits in 16RU
Digital metering, extended alarms and
load disconnect are options for most
configurations
Flexible circuit breakers and fuses
can be added as needed, lower initial
deployment costs
17
Specifications
Current
6180638P
Mechanical
6180638P
Maximum Load
1200A
Width (inch/mm)
23 / 584
Per Load
600A
Depth (inch/mm)
15.25 / 387
Load Complement
2 or 4
Height (inch/mm)
27.97 / 710
Distribution Positions
48 plug in
Evaluated by independent NRTL test lab to Telcordia GR63, Issue 4 & GR 1089, Issue 6
Safety
Outline Drawing
6180638P
6180638P-3
18
GECriticalPower.com
Description
6180638P
Basic Mini BDFB, 2 load, 600A per load, 48 plug in distribution positions, single bus
See Tables A, B, C, D & E for distribution components
6180638P-3
4082260P
(2) required; recommended for use with the 3" closed channel relay racks for correct spacing from the rear.
Amperage
Positions (Poles)
3050107P-2
2A
3050107P-5
5A
3050107P-10
10A
3050107P-15
15A
3050107P-20
20A
3050107P-25
25A
3050107P-30
30A
3050107P-40
40A
3050107P-50
50A
3050107P-60
60A
3050107P-70
70A
3050107P-80
80A
3050107P-100
100A
6426491P-150
150A
GECriticalPower.com
Photo
19
Notes
20
GECriticalPower.com
The RBA72 Power Cabinet is equipped with the Infinity S DC energy system that supports
dual voltage (-48V/+24V) operation. The cabinet provides individual compartments for the
power equipment and batteries. A dual loop heat exchanger allows for temperature control
of the battery compartment while allowing the equipment to run at its designed range for
maximum cooling cost efficiency.
-48V up to 1,600A
(86KW) or +24V up to
1,600A (44KW)
The Infinity Series offers DC rectifiers and converters for both +24V to -48V and -48V to +24V
applications. For easy module selection, the rectifiers and converters are color coded to
quickly identify voltage, module type and input voltage type (AC or DC).
Benefits
Reliability
Investment Protection
Module Compatibility
Intelligence
On Time Delivery
MWBE warehouse utilized for
immediate availability
24/7 technical support
Common building blocks for both positive
and negative output models
GECriticalPower.com
21
Applications
Telecommunications Networks
Routers/Switches
Data Networks
Indoor/Outdoor Wireless
Transmission
Hot pluggable
220/110V AC input
RoHS compliant
Key Features
Specifications
Input
NE100AC24ATEZ
NE100ECO24ATEZ
NE050AC48ATEZ
NE050ECO48ATEZ
NE075AC48ATEZ
NE030DC48A
NE040DC48AZ
NE075DC24A
Voltage Range
95-275Vac
95-275Vac
95-275Vac
21-30Vdc
21-30Vdc
42-60Vdc
Input Current
15-12A @ 100-120Vac
15-12A @ 200-240Vac
15-12A @ 100-120Vac
15-12A @ 200-240Vac
63A @ 27Vdc
81A @ 21Vdc
94A @ 27Vdc
108A @ 21Vdc
41A @ 54.5Vdc
54A @ 42Vdc
Input Frequency
45 66Hz
45 66Hz
45 - 66Hz
Power Factor
Efficiency
Total Harmonic
Distortion
Voltage Adjust
Range
21-29Vdc
42-58Vdc
42-58Vdc
46-57Vdc
46-57Vdc
23-28Vdc
Voltage Nominal
27.25V
54.5V
54.5V
52.0V
52.0V
27.2V
Regulation
(with controller)
0.5%
0.5%
0.5%
0.5%
0.5%
0.5%
Ripple
100mVrms
100mVrms
100mVrms
100mVrms
100mVrms
100mVrms
30A @52.0V
-
40A @52.0V
-
75A @27.2V
-
154W / 525
BTU/hr
202W / 689
BTU/hr
Output
Output Current
- High-Line
- Low-Line
Heat Dissipation
@ max out
22
114A @24V
100A @27.25V
44A @27.25V
57A @48V
50A @54.5V
22A @54.5V
85A @48V
75A @54.5V
22A @54.5V
GECriticalPower.com
Environmental
Operating Temperature
-40C to +75C (-40F to 167F) Full capacity up to 55C; output derates 2%/C from 55C to 75C
Storage Temperature
Humidity
Altitude
4000M (for altitudes above 2000M, peak operating temperature de-rates 0.656 C /100M; 4000M peak temperature rating is 62 C
Mechanical
Length (inch/mm)
13.85 / 351.8
Width (inch/mm)
5.23 / 133
Height (inch/mm)
1.63 / 42
Weight (lb/Kg)
5.05 / 2.2
Evaluated by independent NRTL test lab to Telcordia GR63, Issue 4 & GR 1089, Issue 6
Safety
CE mark to Low Voltage Directive 2006/95/EC and EMC Directive 2004/108/E (Rectifiers only)
UL 60950-1, 2nd Ed. Recognized
CSA C22.2 No. 60950-1-07, 2nd Ed. + A1:2001 (MOD) Certified
RoHS
Compliant to RoHS EU Directive 2002/95/EC; RoHS 6/6 models with Z suffix (RoHS 5/6 all other models)
EMC
European Directive 2004/108/EC; EN55022, Class A; EN55024; FCC, Class A; GR1089-CORE, Issue 6
ESD
EN61000-4-2, Level 4
Outline Drawing
GECriticalPower.com
23
Telecommunications Networks
Routers/Switches
Data Networks
PBX
Indoor/Outdoor Wireless
Transmission
Applications
Key Features
24
GECriticalPower.com
Operating Voltage
24 Vdc, 48 Vdc
(Range: 18 to 60 Vdc)
NEBs
Input Power
Less than 7W
Safety
0 - 95% (non-condensing)
RoHS
EMC
Physical Specifications
Display
No Alarms
No Alarms
GECriticalPower.com
Agency Certifications
NEBs Level 3
EMC
Safety
25
Infinity M may be configured as a +24V or -48V single voltage power system or as a dual voltage power
system that supports rectifiers and converters. The primary voltage is supported by +24V or -48V
rectifiers and battery reserve, while secondary voltage is supported by DC-DC converters. Infinity-M
includes dedicated 24V, 48V and return buses. The primary voltage capacity is 1,600A at 24V and 1,600A
at 48V. Secondary voltage capacity is up to 600A. The system includes low voltage battery disconnect
option for the primary voltage. A low voltage load disconnect option can be used for load shedding to
maintain critical loads.
Applications
Wireless Telecom Networks
Indoor/Outdoor Wireless
Data Networks
Central Office
Hot pluggable
220/110 V AC input
RoHS compliant
Key Features
Specifications
Input
Min
Typ
Max
175Vac
85Vac
220Vac
110Vac
275Vac
140Vac
Frequency
45Hz
60Hz
66Hz
Power Factor
98%
Voltage Range
- High-Line
- Low-Line
99.5%
Efficiency
Approaching 97%
5%
Primary Output
Nominal Voltage
Output Current
Vo Setpoint (factory)
Vo Range
+24Vdc
-48Vdc
1,600A
1,600A
+27.2V 1%
-54.5V 1%
+21Vdc to +29Vdc
Regulation
-42Vdc to -58Vdc
0.5%
Secondary Output
Nominal Voltage
Output Current
Vo Setpoint (factory)
Vo Range
Regulation
-48Vdc
+24Vdc
600A
600A
-54.5V 1%
+27.25V 1%
-42Vdc to -58Vdc
+21Vdc to +29Vdc
0.5%
Mechanical
26
21 / 533.4
350 / 159 (Base System with 4 power shelves and 7ft frame, no rectifiers)
GECriticalPower.com
Environmental
Operating Temperature
Storage Temperature
Relative Humidity
Altitude
4000M (for altitudes above 2000M, peak operating temperature de-rates 0.656 C /100M; 4000M peak temperature rating is 62 C
Evaluated by independent NRTL test lab to Telcordia GR63, Issue 4 and GR1089-CORE, Issue 6
Safety
CSA C22.2 No. 60950-1-07, 2nd Ed. + A1:2001 (MOD) Certified for Canada and U.S.; UL60950-1 1st Ed.
RoHS
EMC
European Directive 2004/108/EC; EN55022, Class A; EN55024; FCC, Class A; GR1089-CORE, Issue 6
Agency Certifications
CSA
CSA C22.2 No 60950-1-07, 2nd Ed. + A1:2001 (MOD) and UL 60950-1 1st Ed
EMI/EMC
NEBS LEVEL 3
GR1089-CORE, Issue 6
GECriticalPower.com
27
Ordering Code
Model
Frame
CC109152220
7ft x 23
(Approx 34 open
at bottom)
System Width 23
7ft x 23
(Approx 30 open
at bottom)
System Width 23
7ft x 23
(Approx 30 open
at bottom)
System Width 23
-48V
800A
CC109152212
-48V
1200A
CC109159224
-48V
1200A
Picture
Ordering Code
Model
Frame
CC109146610
7ft x 23
(Approx 34 open
at bottom)
System Width 23
42 x 23
System Width 23
7ft x 23
(Approx 30 open
at bottom)
System Width 23
48V, 800A
24V, 300A
CC109136917
48V, 1000A
24V, 300A
CC109142007
48V, 1200A
24V, 300A
28
Picture
GECriticalPower.com
Ordering Code
Model
Frame
CC109141974
7ft x 23
(Approx 34 open
at bottom)
System Width 23
7ft x 23
(Approx 34 open
at bottom)
System Width 23
7ft x 23
(Approx 34 open
at bottom)
System Width 23
7ft x 23
(Approx 34 open
at bottom)
System Width 23
24V, 1200A
48V, 120A
CC109141990
24V, 1600A
48V, 120A
CC109141966
24V, 1200A
48V, 120A
150021839
24V, 1200A
48V, 120A
GECriticalPower.com
Picture
29
Applications
Wireless Telecom Networks
Transmission
Indoor/Outdoor Wireless
Data Networks
Key Features
Dual Voltage Flexibility
Hot pluggable
220/110 V AC input
RoHS compliant
Specifications
Input
Min
Typ
Max
175Vac
85Vac
220Vac
110Vac
275Vac
140Vac
Frequency
45Hz
60Hz
66Hz
Power Factor
98%
99.5%
Voltage Range
- High-Line
- Low-Line
5%
Primary Output
Nominal Voltage
24Vdc
-48Vdc
Output Current
1,200A
800A
Vo Setpoint (factory)
Vo Range
27.2Vdc1%
-54.5Vdc1%
+21Vdc to +29Vdc
-42Vdc to -58Vdc
Regulation
0.5%
Secondary Output
Nominal Voltage
Output Current
Vo Setpoint (factory)
Vo Range
-48Vdc
300A
-54.5Vdc1%
27.25Vdc1%
-42Vdc to -58Vdc
Regulation
Mechanical
30
+24Vdc
120A
+21Vdc to +29Vdc
0.5%
System Only
84 / 2134
23 / 584.2
26 / 660.4
21 / 533
21 / 533
292 / 132
GECriticalPower.com
Environmental
Operating Temperature
Storage Temperature
Relative Humidity
Altitude
4000M (for altitudes above 2000M, peak operating temperature de-rates 0.656 C /100M; 4000M peak temperature rating is 62 C
Evaluated by independent NRTL test lab to Telcordia GR63, Issue 4 and GR1089-CORE, Issue 6
Safety
CSA C22.2 No. 60950-1-07, 2nd Ed. + A1:2001 (MOD) Certified for Canada and U.S.; UL60950-1 1st Ed.
RoHS
EMC
European Directive 2004/108/EC; EN55022, Class A; EN55024; FCC, Class A; GR1089-CORE, Issue 6
Agency Certifications
CSA
CSA C22.2 No. 60950-1-07, 2nd Ed. + A1:2001 (MOD) and UL 60950-1 1st Ed.
EMI/EMC
European Directive 2004/108/EC; EN55022, Class A; EN55024; FCC, Class A; GR1089-CORE, Issue 6
NEBS LEVEL 3
GECriticalPower.com
31
-48V
225A
-48V
600A
-48V
600A
Description
225A Infinity S
Power System
equipped with 3
universal positions
and 20 distribution
positions selectable
between -48V Load
and Battery
400A Infinity S
Power System
equipped with 12
universal positions
and 20 distribution
positions selectable
between -48V Load
and Battery
600A Infinity S
Power System
equipped with
12 universal
positions and 40
total distribution
positions, 20
of which are
selectable between
-48V Load and
Battery
Ordering
Code
Model
No
150033064
NES48-19-AC5-PS3-DC1E
LVBD
150032370
NES48-19-AC5-PS3-DC1E-LVBD
No
150033067
NES48-19-AC5-PS12-DC1E
LVBD
150033075
NES48-19-AC5-PS12-DC1E-LVBD
No
150033072
NES48-19-AC5-PS12-DC2E
LVBD
150033080
NES48-19-AC5-PS12-DC2E-LVBD
Ordering
Code
Model
AC Input
LVD
Frame
Photo
-48V
200A
-48V
600A
-48V
800A
Description
200A Infinity S
Power System
equipped with 4
rectifier positions
and 26 distribution
positions selectable
between -48V Load
and Battery
600A Infinity S
Power System
equipped with 16
rectifier positions
and 26 distribution
positions selectable
between -48V Load
and Battery
800A Infinity S
Power System
equipped with
16 rectifier
positions and 52
total distribution
positions, 26
of which are
selectable between
-48V Load and
Battery
AC Input
LVD
Frame
Photo
No
150029007
NES48-23-AC5-PS4-DC1E
LVBD
150029001
NES48-23-AC5-PS4-DC1E-LVBD
No
150029010
NES48-23-AC5-PS16-DC1E
LVBD
150029004
NES48-23-AC5-PS16-DC1E-LVBD
No
150029012
NES48-23-AC5-PS16-DC2E
LVBD
150029006
NES48-23-AC5-PS16-DC2E-LVBD
Additional Infinity S Configurations are available. Please contact your GE representative for more information.
32
GECriticalPower.com
400A
800A
800A
1000A
Description
400A Infinity S
Power System
equipped with 8
universal positions
and 26 distribution
positions,
selectable
between -48V
Load and +24V
Converter Load
800A Infinity S
Power System
equipped with
16 universal
positions and 52
total distribution
positions, 26
dedicated to -48V
and 26 of which
are selectable
between -48V
Load and +24V
Converter Load
800A Infinity S
Power System
equipped with 8
universal positions
and 26 distribution
positions,
selectable
between +24V
Load and -48V
Converter Load
1000A Infinity S
Power System
equipped with
16 universal
positions and 52
total distribution
positions, 26
dedicated to +24V
and 26 of which
are selectable
between +24V
Load and -48V
Converter Load
Ordering
Code
Model
No
150033100
NES4824-23-AC5-PS8-DC1E
LVBD
150033375
NES4824-23-AC5-PS8-DC1E-LVBD
No
150027199
NES4824-23-AC5-PS16-DC2E
LVBD
150033295
NES4824-23-AC5-PS16-DC2E-LVBD
No
150027200
NES4824-23-AC5-PS16-DC2E-7FTR
LVBD
150030947
NES4824-23-AC5-PS16-DC2E-LVBD7FTR
No
150033378
NES2448-23-AC5-PS8-DC1E
LVBD
150033379
NES2448-23-AC5-PS8-DC1E-LVBD
No
150027199
NES2448-23-AC5-PS16-DC2E
LVBD
150033295
NES2448-23-AC5-PS16-DC2E-LVBD
No
150027200
NES2448-23-AC5-PS16-DC2E-7FTR
AC Input
LVD
Frame
Photo
Additional Infinity S Configurations are available. Please contact your GE representative for more information.
GECriticalPower.com
33
Cabinet Specifications
RBA72 Power / Battery Cabinet with 3 strings @ -48 VDC, 540 total Ah
1 & 2 Conduit
knockouts on
both sidewalls,
lower rear wall,
and cabinet
floor
OR
550A 48V Capacity with N+1 Redundancy
Note: Rectifier and Converter Modules
are not included
Door mounted heat exchanger
(electronics cooling)
Available equipment space (2 RU) for
RayCap Remote Head Surge Protection
Door mounted ventilation system
(battery cooling)
Battery Cabinet
Electronic compartment
- GE 14 position circuit breaker
panel assembly
- Bus bar kit that handles (4) sets of
410 AWG
- (6) 100A battery breakers
(trip and alarm off)
34
GECriticalPower.com
Mechanical
Power Cabinet
Battery Cabinet
Height
72 inches
72 inches
Width
30 inches
36 inches
Depth
39 inches
39 inches
Weight
Cooling Technology
Alarms
Door intrusion, blown fuse, fan fail, AC fail, high temperature, rectifier fail, battery breaker fail, high/low input voltage,
battery on discharge
Not included
Outline Drawing
860508670-01.ai
2" Conduit
knockouts (6)
Front Door
RBA72 Cabinet Dimensions and Door Clearances (90 and 110 Open)
" (99
7m
860508670-11.ai
m)
Top View
90
72.0"
(1829 mm)
Front
Top View
110
Front
39.3
m)
30.0" (762 m
Front
Door
34.0" (865 mm)
GECriticalPower.com
35
-48V
Ordering Code
Model
150024099
Picture
Includes the dual voltage Infinity S power system that is rated @ 550A N+1
and is capable of supporting 3 battery strings.
+24V
-48V
150024100
36
Ordering Code
Description
150032279
GECriticalPower.com
Reliability
families by integrating the high efficiency Infinity TE rectifier platform and the time-tested
distribution found in the GPS4848. Utilizing the 1U 50A 48Vdc rectifiers, a fully equipped bay
only requires 15.75 inches allowing for as much as 54 inches of distribution panels. With this
increased density, a single bay GPS4827 system provides ampacity and distribution for most
Controller continuity
medium and small applications but retains all the features found with the larger GPS4848.
Intelligence
Bay Options
4 6 week availability
Investment Protection
Module compatibility
Power shelf growth
Flexible upgrade options
On Time Delivery
24/7 technical support
Standard building blocks
Infinity Rectifiers
GECriticalPower.com
37
Cabinet Specifications
Mechanical
Height
Width
Depth
Thermal
12 Rectifiers
24 Rectifiers
36 Rectifiers
Environmental
Operating Temperature Range
EMC
Immunity
GR1089, EN55024
Agency Certifications
UL
Canada/US UL60950/UL1801
EMI/EMC
AC Input Specifications
FOR
CODE
G026
G028
EXTERNAL BREAKER
SIZE
QTY
CONDUIT
QTY & SIZE
20A
(12) 2-POLE
1 (2")
(24) 8 AWG
(1) 8 AWG
20A
(12) 2-POLE
2 (1.5")
(24) 8 AWG
(2) 8 AWG
20A
(12) 2-POLE
4 (1")
(24) 10 AWG
(4) 10 AWG
40A
(6) 2-POLE
2 (1")
(12) 8 AWG
(2) 8 AWG
20A
(36) 2-POLE
4 (1.5")
(72) 8 AWG
(4) 8 AWG
20A
(36) 2-POLE
3 (2")
(72) 8 AWG
(3) 8 AWG
20A
(36) 2-POLE
9 (1")
(72) 10 AWG
(9) 10 AWG
40A
(18) 2-POLE
3 (2")
(36) 4 AWG
(3) 6 AWG
60A
(12) 2-POLE
4 (1.5")
(24) 4 AWG
(4) 6 AWG
38
GECriticalPower.com
Outline Drawing
GECriticalPower.com
39
Ordering Code
Model
150024267
1800A
AC Input
PHS - PHS
or PHS - N
Picture
36 AC
Feeds
Vertical Distribution
Available 48
Secondary Bays
Picture
150033463
600A
PHS - PHS
or PHS - N
12 AC
Feeds
Vertical Distribution
Available 59
Group Code
108971474
G43A
108987678
G98B
Vertical Space
(in.)
Group Code
12
108908070
G43
108908104
G98B
108908104
G53
NA
NA
Panel Description
Fuse Panels
CC109133113
108985235
40
G53A
GECriticalPower.com
Description
850019233
Optional bus bar that provides 16 output terminations. (one required per cabinet)
Description
CC848805160
External Return Bus Kit: Option for termination of all distribution return cables. 1 per cabinet, rated at 1800 Amps.
The external return bus kit is an alternative to internal return buses when many large cables are required.
GECriticalPower.com
41
Model
CC109160834
100A
Photo
NE100AC24ATEZ
150025075
100A
CC109163473
CC109158878
75A
NE075AC48ATEZ
50A
NE050AC48ATEZ
150025074
50A
Converters
Ordering Code
Model
CC109112471
Photo
NE030DC48A
30A
150023619
40A
CC109142881
75A
42
Ordering Code
Model
CC848817651
CC848817635
CC848817643
Photo
GECriticalPower.com
Amperage
CB Positions (Poles)
10
407998145
10
407998152
10
10
407998160
15
10
407998178
16
10
407998186
20
10
407998194
25
10
407998202
30
10
408213486
40
407998210
45
407998228
50
407998236
60
407998244
70
407998251
80
407998269
90
407998277
100
CC848808551
100
408185353
125
408185346
150
1/0
408564941
200
2/0
CC408573975
225
4/0
408535752
250
4/0
407998137
CC848756916
2-pole Adapter bus for 100-150A breakers; used for -20 on 5/8 lugs
(order 2 per 2 pole breaker to accommodate load and return lugs)
Infinity M & S only
850021775
2-pole Adapter bus for 100-150A breakers; used for 3/8 on 1 lugs
(order 2 per 2 pole breaker to accommodate load and return lugs)
Infinity M & S only
CC848756924
850021955
848631479
2-pole adapter bus kit (includes bus for hole lug on 5/8 centers and hardware), order
one per breaker
GPS 4827 only
848745662
3-pole adapter bus kit (includes bus for 5/16 hole lug on 1 centers and hardware), order
one per breaker
GPS 4827 only
Photo
Note: For 70-100A single pole breakers, one breaker space must be left open in the adjacent position when powering breaker above 80% capacity under normal loading conditions.
GECriticalPower.com
43
Amperage
CB Positions (Poles)
CC408574404
125
CC408574420
200
2/0
CC109106548
Photo
Amperage
405006222
0.25A
Photo
3150439
0.5A
401841473
1A
405673146
1.33A
405181983
2A
406976985
3A
406159061
5A
405725433
7.5A
406159236
10A
407845197
12A
406473959
15A
CC109103157
Bullet Style Fuse Holder and TPS Fuses Infinity M & Infinity S Only
44
Ordering Code
Amperage
WP-92461 List
406700617
15
104
10
406700625
20
105
10
406700633
25
106
10
406700641
30
107
10
406700658
40
108
10
406700674
50
109
406700682
60
110
406700690
70
111
406794784
100
402328926
Photo
GECriticalPower.com
Amperage
408472322
406622456
402328926
406794776
70
408239648
80
406794784
100
406925685
125
406794792
150
1/0
406794818
200
4/0
406794982
225
4/0
406794842
250
4/0
406794867
300
2 x 4/0
406794875
400
2 x 4/0
406794883
500
2 x 4/0
406794891
600
3 x 4/0
Photo
Terminal Lugs for Bullet Style Breakers and TPS Fuses (1/4 bolt on 5/8 centers) Infinity M & Infinity S Only
Ordering Code
WP-91412 List
406021626
75
405347519
405347576
405348202
54
405347683
Photo
Terminal Lugs for Battery and Large Breakers (3/8 bolt on 1 centers)
406338665
405348228
405348236
1/0
2/0
1/0
406021725
2/0
405348251
4/0
405347923
4/0
Terminal Lugs for Battery and Large Breakers (3/8 bolt on 1 centers) Large Wire Lugs for Infinity M
407890763
350
407890748
350
406335141
750
407890730
750
GECriticalPower.com
45
Description
CC109142980
Photo
150026698
CC848817024
10 ft wire set
CC109157434
20 ft wire set
CC848822560
1 ft wire set
848719803
5 ft wire set
CC848822321
10 ft wire set
850027334
20 ft wire set
108958422
CC848791517
CC848797290
6 ft wire set
848719829
10 ft wire set
CC848791500
4 ft wire set
848652947
10 ft wire set
555052-1
Temperature/Voltage probes are needed for battery monitoring. They are connected to each battery or battery string to provide slope thermal compensation, temperature
alarms and voltage imbalance alarms.
Temperature Measurement
46
GECriticalPower.com
Description
150029836
150029837
150029839
Picture
Battery shelves, breaker kits, and DC cables with connectors. Does not include the power
system or frame.
CC848842955
CC408627533
GECriticalPower.com
47
Management Visibility
Training
GE offers on-site and classroom training options based on
certification curriculum. Technical training can be tailored to
individual customer needs. Training enables customers and
partners to more effectively manage and support the power
infrastructure. We have built our training program on practical
learning objectives that are relevant to specific technologies or
infrastructure design objectives.
Warranty
GE is committed to providing quality products and solutions. We
have developed a comprehensive warranty that protects you and
provides a simple way to get your products repaired or replaced as
soon as possible.
For full warranty terms and conditions please go to
www.gecriticalpower.com.