Understanding Common-Mode Signals
Understanding Common-Mode Signals
Further details about these basic conditions appear in a later section. Before examining those details, however, it
is useful to understand different cable configurations, signal-grounding conventions, and shield-grounding
practices.
Figure 1. This generalized system transmits data between two widely separated buildings, and shows the earth
currents created between ground points in a single-phase power-distribution system. Similar currents are
created in 3-phase, Y-connected systems.
Bonding a power-line subscriber's neutral line to a ground rod sunk in the earth at the power-entry point
establishes the power-line neutral as a safety ground. From that point, a bare or green-insulated wire carries the
safety-ground reference to all electrical outlets and installed equipment throughout the premises. Industrial
chassis frames are bonded to the safety ground at the chassis' power-input point, where it becomes frame
ground.
Circuit common is often connected to the chassis at one or more points, but a single ground point per chassis is
best. In some cases, the circuit common might be isolated from the frame ground. Leakage currents that flow in
the safety-ground wire from machine windings to the case, or more commonly, that flow between the ground
and earth due to AC primary or secondary neutral currents in the power-distribution system, can produce a
potential difference between the neutral and frame ground.
Ground differentials can vary from several volts to several tens of volts. The greatest differentials are found in
single-phase or 3-phase Y-distribution systems, in which the portion of neutral current flowing in the earth can
be 10% to 70% of the total neutral current flowing in the primary circuit. Voltage measurements between
ground points are typically 0.2VRMS to 5VRMS, and (rarely) as high as 65VRMS between widely separated grounds.
Figure 2. These transmission-cable configurations show the locations of possible noise sources.
Table 1. Electrical Cable Types and Applications
Description
Electrical Return Route Typical Applications
Single-Wire Line
Earth or frame
Shield
Single-Wire
Shielded Cable
Radiated E, EM,
or M
If radiated or
conducted noise
enters an
unshielded
portion of the
main conductor
or appears
between source
common and a
ground point at
cable ends
Earth currents
en4
Notes
Receiving circuit
must be insensitive
to the sum of en1
+ en2 at load.
Radiated E,
EM, or M
along length
of shield
Conduction by
electrical currents
flowing in
external ground
path if both ends
of shield are
grounded.
Copper shield
ineffective for
inductively-coupled
noise. en1 is
insignificant if:
inductive coupling
is absent; shielding
is complete from
source to load; and
ground points are
connected directly
to circuit common
at source and load.
en1 and en2 will
Unshielded Parallel
Pair
Unshielded Twisted
Pair (UTP), or
Unshielded Multiple
Twisted-Pair
Radiated E, EM,
or M
Radiated E,
EM, or M
partially cancel if
the lines are
parallel and closely
spaced.
Twisted lines make
en1 and en2 equal
Radiated E, EM,
or M
Radiated E,
EM, or M
in amplitude and
phase. Receiving
circuit must reject
the VCM signal.
Neither en3 nor en4
Shielded Twisted
Pair (STP), or
Shielded Multiple
Twisted-Pair
Radiated M
Radiated M
Radiated E,
EM, or M
along length
of shield
Conduction by
electrical currents
is flowing in the
external ground
path if both ends
of the shield are
grounded.
appear in the
signal path, but
could cause
circulating current
if both ends of the
shield are
grounded.
Receiving circuit
must reject VCM
signal if en1 and
en2 are present.
Source Floats
At load only
Load Floats
At source only
Two-wire parallel: Each conductor carries an equal amount of signal current, but in opposite directions. Table
4 lists line-grounding connections for various conditions.
Table 4. Line Grounding for Two-Wire Parallel Cables
When
Shield Is Grounded Conditions
Source Floats
At load only
Source is battery-powered.
Load Floats
At source only
At neither end
Unshielded twisted pair(s): Any driving or receiving circuit probably includes a connection to local common or
frame ground, but connecting the transmission line itself to frame ground is unnecessary and undesirable. A
differential-mode or balanced-signal source (such as unshielded RS-422 and RS-485 data-transmission circuits)
transmits data signals to a remote location where source and load circuits are both referenced to local ground or
common. Transformer-coupled applications include 10/100 Base-T Ethernet cables.
Shielded twisted pair(s): Grounding the shield of any shielded pair shunts to ground any unwanted signals or
noise intercepted by the shield. Typical shield materials (copper and aluminum) shield the internal conductors
from signals coupled capacitively or electromagnetically, but not from those coupled inductively.
For any shielded pair(s) carrying balanced signals, you should connect the shield to ground at one end, usually
the receiving end. If the transmitting-location ground carries a noise signal different from that at the receiving
location, grounding the shield at both ends causes current flow along the shield. Grounding at both ends is
acceptable if there is no substantial potential difference between the two ground locations. This configuration
includes shielded RS-422 and RS-485 data-transmission circuits. RS-485 Application Guidelines specify
connecting the shield to earth ground, either directly or through a fusible resistor at one or both ends of the
cable shield.
Signal-Mode Definitions
Electrical signals carried on cables can be described as normal mode, differential mode, or common mode.
A normal-mode signal is any type (other than common mode) that appears between a pair of wires, or
on a single wire referenced to (or returned through) the earth, chassis, or shield. Normal-mode signals
are read between two wires in a balanced or unbalanced transmission path. (For a balanced 2-wire path,
one wire is driven positive while the other is driven negative by an equal amount, both with respect to a
static or no-signal condition in which both lines assume the same voltage level relative to circuit
common.)
A differential-mode signal appears differentially on a pair of wires in an ungrounded cable
configuration.
A common-mode signal appears equally (with respect to local circuit common) on both lines of a 2wire cable not connected to earth, shield, or local common. Usually, but not always, this is an unwanted
signal that should be rejected by the receiving circuit. Common-mode voltage (VCM) is expressed
mathematically as the average of the two signal voltages with respect to local ground or common:
Figure 3 shows a 3V differential-mode signal riding on a 2.5V common-mode signal. The DC offset is typical of
differential-mode data transmitters operating from a single supply. The common-mode voltage can be AC, DC, or
a combination of AC and DC. (Figure 3 represents the simplest case, a DC common-mode voltage with no AC
component.)
Figure 4. Three types of common-mode signal (eGD, eLC, and EOS) can be present in a 2-wire data-transmission
system.
Signal common can assume a common-mode voltage equal to the vector sum of the ground-potential difference,
the driver-offset voltage, and any longitudinally coupled noise voltage generated along the signal path between
transmitter and receiver:
EOS is typically a DC offset introduced by a differential-mode driver operating from a single supply, as
represented in Figure 3.
eGD is a noise signal representing the difference in ground potentials at the transmitting and receiving
locations. It is usually an AC signal containing the fundamental and possibly several harmonics of the
power-line frequency.
eLC is a longitudinally coupled noise signal occurring equally on both transmission lines due to capacitive,
electromagnetic, or inductive coupling from extraneous sources.
arises equally on each of two tightly twisted wires. Otherwise, a normal-mode signal would be present due to the
line's asymmetry with respect to disturbing fields.
The load must also be symmetrical; the resistive and capacitive load impedances on both lines of the twisted pair
must be matched. Inductively coupled signals can be prevented only by using magnetic shielding. (Note that any
wire carrying signal current is a source of magnetic radiation.)
All the techniques shown in Figure 6 can couple a signal across the isolation barrier in the presence of high
values of VCM. Each depends on the use of an isolated power supply, which is usually transformer coupled.
Isolation voltage limits are determined by the transformer and by the type of isolation chosen. Isolation to 2500V
or more is practical with transformer-, optical-, and capacitive-coupling techniques; resistive coupling is usually
limited to the range of 50V to 100V.
Figure 6. The isolation techniques and typical components shown achieve high common-mode-signal rejection.
Resistive coupling involves transferring data across a resistive attenuator, which attenuates both the data and
the common-mode signals. Thus, resistive isolation is limited by the fraction of VCM that can be accommodated
by the receiving circuit, while reliably detecting a small fraction of the original data signal.
In Figure 6, the various isolation drivers treat the requirement for isolated power in different ways. Today's
inductively-coupled devices make no provision for the power supply, and therefore require external isolated
supplies. Some capacitor-coupled devices include transformer drivers, but they require external transformers.
Maxim's MAX3157 and MAX3250 drivers contain isolated supplies and require external, low-profile, ceramic
charge-pump capacitors. Members of the MAX1480 and MAX1480E families, however, contain fully isolated
supplies including transformers.
Thus, you can choose the cable type and isolation technology intelligently, once the source and magnitude of an
intruding common-mode signal is known. You need only measure or calculate the magnitude of the disturbing
signals, and then select your components to meet the overall requirements of the system.
References
1. From a 1995 survey of 48 utilities, by the Minnesota Public Utilities Commission: http://www.
strayvoltage.org/stories/index.php3?Story=20000213_attorneygeneral.inc
2. Documented information is difficult to discover. The cited numbers were obtained in private
communication with engineers at BC Hydro Power, British Columbia, Canada.
3. TIA/EIA TELECOMMUNICATIONS SYSTEMS BULLETIN TSB89, Application Guidelines for TIA/EIA-485-A,
Telecommunications Industry Association, June 1998
4. TIA/EIA STANDARD TIA/EIA-485-A, Electrical Characteristics of Generators and Receivers for Use in
Balanced Digital Multipoint Systems, Telecommunications Industry Association, March 3, 1998.
A similar version of this article appeared in the April 17, 2003 issue of EDN magazine.
MAX3250: