CONSTRUCTION METHODS
1. Codes and Regulations
All work shall be done in accordance with the requirement of
the latest edition of the PHILIPPINE ELECTRICAL CODE
and the NATIONAL SAFETY CODE, with the applicable
ordinances of the local government, and with the
requirements of the local power company that will eventually
furnish the service. Nothing contained herein or shown on
the plans shall be constructed as to conflict with the
requirements of these codes, which are hereby made part of
the work of this item.
2. Contractor Submittals
The Contractor shall be required to submit shop drawings
which shall include outline dimensions, mounting
connections and clearance, ratings, elementary wiring
diagrams, interconnection wiring diagrams, together with
catalogs and descriptive data for the following:
a.
b.
c.
d.
Lighting panels
Streetlights, including lighting standard poles.
Photocell switch
Manufacturers Data. When data that described more
than one type, size, model, or item is submitted, clearly
mark the data to indicate which type, size, model, or item
is being provided. Data shall be sufficient to show
conformance to specified requirements:
1. Luminaires
2. Lighting Standard poles
3. Photocell Switch
e. Shop Drawings:
Luminaires: Include dimension, accessories and
installation and construction details. Photometric data,
including Zonal lumen data, average and minimum ration
aiming diagram and computerized candlepower
distribution data shall accompany shop drawings.
Poles. Include dimensions, wind load determined in
accordance with AASHTO LTS-1, pole deflection, pole
class, and other applicable information and pole design
calculations.
shall
be
Attachment:
Fasten
to
indicate
structural