Check The OLTC Position For Startup Condition On 9 Step Position. Closed 10BBA10GS001, 10BBA10GS010, 10BBA30GS001
Check The OLTC Position For Startup Condition On 9 Step Position. Closed 10BBA10GS001, 10BBA10GS010, 10BBA30GS001
GT Main Transformer
Avail.
on 9 step position.
Electrical
Power Supply
Avail.
IBS System
&
Emergency. Diesel
Generator
on Service
Ready to Start
Ready to Start.
DC System
Ready to Start.
UPS System
Ready to Start.
Startup
Startup
Startup
Turning Gear
Fire Fighting System
Fire Fighting System
Normalized
All Auto.
Not alarms on Pumps Controllers
Normalized
Ready both CO2 refrigerators
House Filter
Air Compressors
General inspection
Check
Auto
LCI Compartment
Gas Compressors
Pumps cabinet
Inspection
should be opened
Nitrogen Generator
Normalized
on service
Chromatograph
Normalized
ok
Diverter Damper
Note:
Normalized
Auto.
Normalized
Auto
Normalized
Auto.
From DCS Display
Drain System
Normalized
Auto
Procedure
Supply Hydrogen
To Gas Turbine Generator
Pending
Combine Cycle
Sequence Control
Seq. ON
Seq. OFF
HOLD
START CHECKS
L3STCK 0
Customer Permissive to
Start
Emergency Stop PB
Fire Protection System
Problem.
Control System Fault Start
Inhibit
SSOV Start-Up Permissive
This is a hardwired switch provided for customer use from the DCS.
Monitors Isolation valves at inlet bleed heat. Isolation valve must be open. Check limit switch.
L3STCK 1
Any flame detector which registers a flame intensity greater that 20%, with the Minimum Speed Relay
"dropped out"
or L14HM = 0 will prevent a star
An HMI protective which prevents inadvertent starts by a mistaken keystroke.
This permissive monitors health of Hydraulic Pressure header which services control valves and IGV.
The Generator Breaker needs to be open else the GT will not start.
This permissive monitors Lube Oil Tank Temperature for a minimum value
This prevents a start if any MKVI Trip is active with L4T logical at "1".
This prevents a start if any MKVI Trip is active with L4T logical at "1" AND any of the MKVI hardwired
internal trip
Permissive monitors health of Compressor Bleed Valves VA2-1, -2, -3, -4 by monitoring open and
closed
LCI must report "Ready-to-Start" - No faults within LCI or associated breakers
Permissive looks at 4 situations and initiates a permissive like (> 15 psig, 1 bar) H2 Analyzers #1 & #2
are not in Local Status , Seal Oil Drain is not in Alarm etc
Inlet Bleed Heat control valve VA20-1 is monitored for health.
L3STCK 3
This prevents a start if any MKVI Trip is active with L4T logical at "1".
The permissive requires the Minimum Speed Relay be "dropped-out" or L14HM = 0.
Permissive monitors health of GT & Generator Vibration Velocity seismic transducers.
The permissive monitors health of communications between the Generator Excitation and the MKVI
The permissive monitors health of communications between the LCI's and the MKVI
The permissive monitors readiness of the Generator Excitation.
L3STCK4
2) The turbine shaft will begin to rotate on turning gear the starting device will be energized and accelerate the unit. The HMI display will change to
CRANKING, and On 14% speed, the minimum speed signal 14HM will be displayed on the HMI.
3) The starting device will crank the gas turbine at purge speed for a period of time (purge timer), Ignition sequence is initiated. The HMI display will
change to FIRING.
4) When flame is established, the HMI display will indicate flame based on the status of the flame detectors, after the FSR will transition to warm-up
value, and the HMI display will indicate WARMINGUP, at the end of the warm-up period, with flame established, FSR will begin increasing. The HMI will
indicate ACCELERATING and the turbine will increase in speed and will continue to accelerate. When it reaches 91% speed, the starting device will
disengage, when the turbine reaches operating speed (95%) the Generator field flashing is initiated. If the synchronizing is not selected on the HMI, as
the turbine reaches operating speed, HMI display will change to: RUNNING FULL SPEED NO LOAD AUTO.
5) If Auto-Synch is selected on the HMI automatic synchronizing is initiated. The HMI will read SYNCHRONIZING, The turbine speed is matched to the
system and when the proper phase relationship is achieved the generator breaker will close. The machine will load to Spinning Reserve unless a load
control point BASE, PEAK or PRESELECTED LOAD has been selected, the HMI will display SPINNING RESERVE, once the unit has reached this load point.
Automatic Synchronization:
From FULL SPEED NO LOAD.
1). Select 'AUTO SYNCH' on the HMI Synchronization display.
d. The control system will match generator voltage to line voltage, synchronize the generator to the line frequency, and load the
generator to the spinning reserve value.
Note:
1). If a synch fails for any reason, it may be necessary to either select START on the HMI Main, Startup Display or select RE-SYNC on
the HMI synchronization display to reset the sequence.
2). Once the generator has been connected to the power system, the load may be increased to pick up load, and the generator
excitation may be adjusted to obtain the desired Mvar value.