Single Phase Transformer
Single Phase Transformer
TRANSFORMER THEORY
Construction of Transformer
Fig 1
A transformer is a static (or stationary) piece of apparatus by means
of which electric power in one circuit is transformed in to electric power of
the same frequency in another circuit. It can raise or lower the voltage in
a circuit but with a corresponding decrease or increase in current. The
physical basis of transformer is mutual induction between two circuit
linked by a common magnetic flux.
In this simplest form, it consist of two inductive coils which are
electrically separated but magnetically linked through a path of low
reluctance as shown in fig.(1). The two coils posses high mutual
inductance. If one coil connected to source of alternating voltage an
alternating flux is setup in the laminated core, most of which is linked
with the other coil in which it produces mutually induced emf (according
to faradays law of electromagnetic induction e = -N d/dt).
If the second coil circuit is closed, a current flows in it and so electric
energy is transferred (entirely magnetically) from the first coil to the
second coil, The first coil in which electric energy is fed from the a.c.
supply mains is called primary winding and the other from which energy
is drawn out is called secondary winding.
In brief a transformer is a device that.
1
Fig 2
An ideal transformer is one which has no losses i.e. its winding have no
ohmic resistance there is no magnetic leakage & hence which has no I 2R
and core losses. In other words, an ideal transformer consists of two
purely inductive coils wound on a loss free core.
An ideal transformer is a lossless device .
It has the following properties:
Working of Transformer:
Consider an ideal transformer fig.2 (a). Whose secondary is open &
whose primary is connected to sinusoidal alternating voltage V 1, this
potential difference causes an alternating current to flow in the primary.
Since the primary coil is purely inductive and there is no output
(secondary being open). The primary draws the magnetizing current I
only. The function of this current is merely to magnetize the core; it is
small in magnitude and lags V1 by 900. This alternating current I at an
alternating flux which at all times proportional to the current.
(Assuming permeability of the magnitude circuit to be constant) and
hence, is in phase with it. This changing flux is linked both with the
primary and the secondary windings.
Therefore, it produces self-induced emf in the primary. This selfinduced emf E1 is, at every instant, is equal to and in opposition to V 1. It is
also known as counter emf or back emf of the primary.
Similarly, there is produced in the secondary an induced emf E2
which is known as mutually induced emf, this emf is anti-phase with V 1
and its magnitude is proportional to the rate of change of flux and the
number of secondary turns.
The instantaneous values of applied voltage, induced emfs, flux and
magnetizing current are shown by sinusoidal waves in fig. 2(b). Fig.2(c)
shows the vectorial representation of the effective values of the above
quantities.
Emf Equation of A Transformer:-
Fig 3
3
(t ) m sin t
d m sin t
dt
N m cos t
E1(max) N m 2fN m
E1( rms)
N m 2fN m
4.44 fN m
2
2
E1
It means that
winding.
turns
E2
N 2
N 1
= 4.44f m
Fig 4
VOLTAGE TRANSFORMATION RATIO(k):
E2
N2
N 1
E1
=k
V1 1
V
2
I 1
Hence current are in the inverse ratio of the (voltage) transformer ratio.
Rating of the transformer
KVA rating allows you to find the maximum current that the given
transformer can sustain.
VA V1 I1 V2 I 2
I1FL = KVA /
V1
I2FL
= KVA /
Losses
in transformer
Copper loss / Winding loss
Iron loss / core loss
Hysteresis loss
Eddy current loss
Magnetic leakage
Copper Loss
5
respect to the input. The higher the efficiency, the better the system.
Output Power
100%
Input Power
Pout
100%
Pout Plosses
Efficiency,
V2 I 2 cos
100%
V2 I 2 cos Pc Pcu
Phasor Diagrams:
Phasor diagram of ideal transformer under no load condition
Phasor diagram of practical transformer under no load condition
Phasor diagram of practical transformer under load condition
Phasor diagram of practical transformer considering winding and
leakage losses under load condition
Phasor diagram of practical transformer on load:
TRANSFORMER with losses but no magnetic leakage:We will consider the cases
(1) when such a transformer is on no load and
(2) when it is loaded.
Transformer on no load :
Fig 5
Even when the transformer is on no load the primary input is not wholly
reactive. The primary input under no load conditions has to supply.
8
(1)
Iron losses in the core i.e. hysteresis loss and eddy current loss
and
(2)
A very small amount of copper loss in primary (there being no
cu loss and it is open). Hence the no load primary input current I o is
not at 900 behind V1 but lags it by angle o<900. No load input power
Wo = V1 I 0 Cos o
Where cos o is primary power factor under no load condition. No load
condition of an actual transformer is shown vector ally in fig. (5). Form fig.
(5) Primary current I0 has two components.
(1)
(2)
The other component is in quadrature with V 1 and is known as
magnetizing component I because its function is to sustain the
alternating flux in the core. It is wattles.
I = I0 sin o. Obviously I0 is the vector sum of I w and I Hence I02 =
(I2 +Iw2).
Note:(1)
The no load primary current I0 is very small as compared to the
full load primary current. It is about 1% of the full load current.
(2)
As I0 is very small the no load primary cu loss in negligible small
which means that no load primary input is practically the iron loss in
transformers.
(3)
As it is principally the core loss which is responsible for shift in
the current vector angle o is known as hysteresis angle of advance.
Practical transformer on load:
Fig 6
Fig 7 (a)
(b)
(c)
Or
N2 x I2 = N1 x I2
I2 =
N2
I2
N1
= kI2
Hence, when transformer is no-load, the primary winding has two currents
in it; one is I0 and the other is I2 which is anti-phase with I 2 and k times in
magnitude. The total primary current is the vector sum of I 0 & I2.
In fig.7 are shown the vector diagrams for a loaded transformer
when the load is non-inductive and it is inductive. Voltage transformation
ratio of unity is assumed so that primary vectors are equal to the
secondary vectors. With reference to fig.7 (a) I 2 is secondary current in
phase with E2. It causes primary current I2 which is anti-phase with it and
equal to it in magnitude (since k=1). Total primary current I 1 is the vector
sum of I0 & I2 and lags behind V1 by an angle 1.
In fig.7.b Vectors are drawn for an inductive load. Here I 2 lags E2 by
2. Current I2 is again anti-phase with I 2 and equal to it in magnitude. As
before, I1 is the vector sum of I2 and I0 and lags behind V1 by 1. It will be
observed that 1 is slightly greater than 2. But if we neglect I0 as
compared to I2 in fig.7.c, Then 1 = 2 moreover under this assumption:
N1I2 = N1I1 so It shows that under full load conditions, the rate of primary
and secondary currents is constant. This important relationship is made
the basis of current transformer a transformer which is used with a lowrange ammeter for measuring current in circuits where the direct
connection of the ammeter is impracticable.
Transformer with winding resistance but no magnetic leakage:An ideal transformer was supposed to possess no resistance but in an
actual transformer, there is always present some resistance of the
primary and secondary windings. Due to this resistance, there is some
voltage drop in the winding. The result is that:
(1) The secondary terminal voltage V 2 is vectorially less than the
secondary induced emf E2 by an amount I2R2 where R2 is the resistance of
secondary winding. Hence, V2 is equal to vector difference of E 2 and
resistive voltage drop I2R2.
So V2 = E2 I2R2 vector difference
11
Fig 8
Equivalent Resistance:-
Fig 9
In fig. (9) Is shown a transformer whose primary and secondary have
resistance of R1 and R2 respectively to the winding.
It would now be shown that the resistance of the two winding can be
transferred to any one of the two winding. The advantage of
concentrating both the resistance in one winding is that it makes
calculations very simple and easy because one has than to work in one
winding only. It will be proved that a resistance of R 2 in secondary is
R2
R2
k2
R2
equivalent to
in primary. The value
will be denoted by . The
equivalent secondary resistance as referred to primary. The copper loss
in secondary is I22R2. This loss is supplied by primary which takes a
R2
I22R2 = I12
R2
or
R2
I2
I2
I1
I 1
.R2
k
Hence
R2
R2
k2
(a)
Fig 10
.
R1
(b)
R2
= R1 +
k2
R2
R2
= R1 +
k2
= R2 +
= R2 + k2R1. The fact is shown in fig. 10(b) where all the
resistance of the transformer has been concentrated is the secondary
winding.
Note:
(1)
A resistance of R1 in primary is equivalent to k 2R1 in secondary.
Hence it is called the equivalent primary resistance as referred to
secondary i.e. R1.
R2
k2
(2)
A resistance of R2 in primary is equivalent to
in primary.
Hence it is called the equivalent secondary resistance as referred to
primary i.e. R2/.
13
(3)
Total effective resistance of the transformer as referred to
primary is
R 01 = primary resistance + equivalent secondary resistance as
referred to Primary
R2
(4)
k2
R 01 = R1 + R2 = R1 +
.
similarly total transformer resistance referred to secondary is
/
R2
R02 = R2 + R = R2 +
/
2
k2
MAGNATIC LEAKAGE:
Fig 11 (a)
Fig 11 (b)
If it is found that all the flux linked with primary does not link the
l1
el1
l1
.The flux
l1
is in
Similarly secondary amp.turns (or mmf) acts across points c & d setup
leakage flux
l2
drop in each
other words
primary and
internal emf
I1
X 2 eL 2
I2
(2)
The primary voltage
will have to supply reactive drop I 1X1 in
addition to I1R1. Similarly, E2 will have to supply I2R2 and I2X2.
Transformer with Resistance and leakage Reactance:-
Fig 12
In fig. (12) are shown the primary and secondary windings of
transformer with reactance taken out of the windings. The primary
2
impedance is given
2
Z 2 R2 X 2
Z 1 R1 X 1
given
. The resistance and leakage reactance of each
winding is responsible for some voltage drop in each winding. In
primary the leakage reactance voltage drop is I 1X1 (usually 1 or 2% of
V1). Hence V1 = E1 + I1 (R1 +jX1) = E1+I1Z1.
Similarly, there are I2R2 and I2X2 drops in secondary which combine
with V2 to give E2.
E2 = V2 + I2(R2 +jX2) = V2+I2Z2.
15
The vector diagram for such a transformer for different kinds of loads is
shown in fig. (13). In these diagram, vector for resistive drops are
drawn parallel to current vectors whereas reactive drops are
perpendicular to the current vectors. The angle 1 between V1 & I1
gives the power factor angle of the transformer.
If may be noted that leakage reactance can also be transformed from
one winding to the other in the same way as resistance.
X2
X2 =
/
k2
& X1 =
/
X2
k 2 X1
k2
k 2 X1
Z 01 R01 X 01
Fig 13 (a)
&
Z 02 R02 X 02
Fig 13 (b)
Fig 13 (c)
16
Fig 13 (d)
Fig 13 (e)
17
Fig 14
In fig. (14) V2, V1, 2 are known hence E2 can be found by adding
vectorially I2R2 and I2X2 to V2. Similarly V1 is given by the vector addition
of I1R1 and I1X1 to E1. All the voltage on the primary side can be
transferred to secondary side as shown in fig. (14) Where the upper
part of the diagram has been rotated through 180 0. However it should
be noted that each voltage or voltage drop should be multiplied by
transformation ratio k. The side of the diagram has been shown
separately in fig. (15) laid horizontally where vector for V 2 has been
taken along X-axis.
18
Equivalent Circuit:-
19
Z1
Z m (Z 2 Z L )
/
Z m (Z 2 Z L )
Z = Z1 + Zm ll (Z +Z ) = (
)
/
/
/
Where Z2 = R2 +jX2 & Zin = impedance of exciting circuit
/
2
/
L
Z1
V 1 = I1 [
Z m (Z 2 Z L )
/
Z m (Z 2 Z L )
].
20
Fig 21
The purpose of this test is to determine no load loss or core loss and no
load I0 which is helpful in finding X0 and R0.
One winding of the transformer- whichever is convenient but usually high
voltage winding is left open and the other is connected to its supply of
normal voltage and frequency. A wattmeter W, voltmeter V and an
ammeter A are connected in the low voltage winding i.e. primary winding.
With normal voltage applied to the primary, normal flux will be setup in
the core, hence normal iron losses will occur which is recorded by the
wattmeter. As the primary no load current I 0 is small (usually 2 to 10% of
rated), copper loss is negligibly small in primary and nil in secondary
21
22
Fig 23
This is an economical method for determining the following.
(1) Equivalent impedance (Z01 or Z02), leakage reactance (X01 or X02) and
total resistance (R01 or R02) of the transformer as referred to the winding in
which the measuring instruments are placed.
(2) Copper loss at full load (and at any desired load this load is used in
calculating the efficiency of the transformer.
(3) Knowing Z01 or Z02, the total voltage drop in the transformer as
referred to primary or secondary can be calculated and hence regulation
of the transformer determined.
In this test, one winding, usually the low voltage winding is short circuited
by a thick conductor as shown in fig. (23).
in fig. (24). If Vsc is the voltage required to circulate rated load currents,
then Z01 = Vsc / I1
Also W = I12 R01 so R01 = W / I12
So X01 = (Z012 R012 )1/2
In fig.25 (a) is shown the equivalent circuit vector diagram for the short
circuit test. The
entire voltage Vsc is consumed in the impedance drop of the two winding.
If R1 can be
measured than knowing R01 we can find R2/ = R01 R1. The impedance
Triangle than be
divided into the appropriate equivalent triangle for primary and
secondary as shown in
fig.25(b).
Why transformer rating in kva.
As seen Cu loss of transformer depends on current and iron loss on
voltage. Hence total
Transformer loss depends on volt-ampere (VA) and not on phase angle
between voltages
& current i.e. it is dependent of load power factor. That is why rating of
transformer is in
KVA and not in kW.
Regulation of a transformer:When a transformer is loaded with a constant primary voltage the
secondary voltage
24
The lesser this value, the better the transformer, because a good
transformer should keep its secondary terminal voltage as constant as
possible under all conditions of load.
LOSSES IN TRANSFORMER
In a static transformer, there are no friction or windage losses,
hence the only losses occurring are,
1. Core or Iron loss: - It includes both hysteresis and eddy current loss.
Because the core flux in a transformer remains practically constant for all
loads (its variations being 1 to 3 % from no load to full load), the core loss
is practically the same at all loads.
Hysterysis loss Wh = Bmax 1.6 f V Watts
Eddy current loss = We = P Bmax 2 f2 t2 Watts
These losses are minimized by using steel or high silicon content for
the core and by using very thin laminations. Iron or core losses is found
from OC test, the input of the transformer when no load measures the
core loss.
2. Copper loss: - This loss is due to the ohmic resistance of the
transformer winding. Total copper loss = I 12 R1 + I22 R2 = I12 R01 = I22 R02. It is
clear that Cu loss is proportional to I 2 or (KVA)2 . In other words, Cu loss at
half and full load is one fourth of that at full load. The value of the Cu loss
is found from the SC test.
Efficiency of a transformer:25
I1 R01
V1I1 cos
-
Wi
= 0 - R01
V1 cos
Wi
V1I12 cos
Or Wi = I1 2 R01 = I2 2 R02
Cu Loss = Iron Loss.
The output current corresponding to maximum is I 2 = ( Wi / R02).
Note: 1. If we are given iron loss and full load Cu loss, then the load at
which two losses would be equal( corresponding to maximum ) is given
by
26
day
Kwh)
Why transformer rating in KVA?
As seen, Copper loss of a transformer depends on current and iron loss on
voltage. Hence total transformer loss depends on Volt-Ampere (VA) and
not on the phase angle between voltage and current i.e. it is independent
of load power factor. That is why rating of transformer is in KVA and not
on KW.
TRANSFORMER PROBLEMS
27
28
31