17b Transformer Class Exercise Solution r13
17b Transformer Class Exercise Solution r13
X3
H2
X2
H1
X1
n
X0
Exercise 1.2:
H3
X3
H2
X2
H1
X1
N
H0
Page 1 of 10
Exercise 2.1: Determine the CT connections and transformation ratio for the
following step-down transformer. Assume the differential protection is
a traditional electromechanical relay. The transformer is 138/22 kV,
Dy1 (DAB-Wye), 60 MVA.
H1
High-Side CT
600/5 MR
600-500-450-400
300-250-200-150
100-50/5
X1
X3
H3
Low-Side CT
2000/5 MR
2000-1600-1500-1200
1100-800-500-400-300/5
X0
H2
X2
H3
(C)
IC
H2
(B)
H1
(A)
IB
IA
300/5
251.02 / 150
IC
Ic
1574.6/ 120
1600/5
x3
(c)
300/5
251.02 / 90
IB
Ib
1574.6 / 120
1600/5
x2
(b)
300/5
251.02/ 30
IA
Ia
1574.6 / 0
1600/5
x1
(a)
4.18/ 150
8.52/ 150
4.18/ 90
8.52 / 90
4.18/ 30
8.52 / 30
Relay Taps:
2.9 3.2 3.5 3.8 4.2 4.6 5.0 8.7
All currents are in Amps.
All angles are in degrees
Page 2 of 10
Low-Voltage Side: 22 kV
I RATED =
60000
= 251.02 A
3 138
I rated =
60000
= 1574.6 A
3 22
300/5
1600/5
I A =
251.02 / 30
= 4.18/ 30 A
300 / 5
I B =
251.02 / 90
= 4.18/ 90 A
300 / 5
I C =
251.02/ 150
= 4.18/ 150 A
300 / 5
1574.6 / 30
= 8.52 / 30 A
1600 / 5
1574.6 / 90
I b = 3
= 8.52 / 90 A
1600 / 5
1574.6 / 150
I c = 3
= 8.52/ 150 A
1600 / 5
I a = 3
Differential current before balancing with the relays TAP compensation = |8.52-4.18| = 4.34 A
TAP Selection: 4.2
8.52 8.7
4.18 4.2
Mismatch: M =
100 = 1.63% (See Table I at the end of this section).
8.7
4.2
Page 3 of 10
Exercise 2.2: Determine the TAP value and the compensation matrix for each side of
the differential protection shown in the figure. Determine the value of
current for each branch of the circuit. Fill in all the blanks. The
transformer is 138/22 kV, Dy1 (DAB-Wye), 60 MVA.
251.02 / 150
H3
(C)
251.02 / 90
H2
(B)
251.02 / 30
H1
(A)
1600/5
300/5
1600/5
300/5
1600/5
1574.6 / 120
x2
(b)
1574.6 / 0
x1
(a)
4.92 / 120
4.18/ 90
4.92 / 120
4.18/ 30
4.92/ 0
TAP2=
1/TAP2
1/TAP1
4.18
1.0/ 150
1.0/ 120
1.0/ 90
1.0/ 120
1.0/ 30
1.0/ 0
COMPENSATION
MATRIX
COMPENSATION
MATRIX
4.92
1 -1 0
1
0 1 -1
3
-1 0
1.0 / 30
1.0/ 90
1.0/ 150
Page 4 of 10
x3
(c)
4.18/ 150
TAP1=
1574.6 / 120
1.0/ 30
DIFF.
1.0/ 90
1.0 / 150
Low-Voltage Side: 22 kV
I RATED =
60000
= 251.02 A
3 138
I rated =
60000
= 1574.6 A
3 22
300/5
1600/5
251.02/ 30
= 4.18/ 30 A
300 / 5
251.02/ 90
= 4.18/ 90 A
I B =
300 / 5
251.02/ 150
= 4.18/ 150 A
I C =
300 / 5
I A =
TAP1 =
60 1000 1
3 138 300 / 5
= 4.18
I a =
1574.6/ 0
= 4.92/ 0 A
1600 / 5
I b =
1574.6/ 120
= 4.92/ 120 A
1600 / 5
I c =
1574.6/ 120
= 4.92/ 120 A
1600 / 5
TAP 2 =
60 1000 1
3 22 300 / 5
= 4.92
I AT =
4.18/ 30
= 1.0/ 30 A
4.18
4.18/ 90
=
I BT
= 1.0 / 90 A
4.18
4.18/ 150
=
I CT
= 1.0 / 150 A
4.18
=
I aT
I Acomp = 1/ 30 A
I Bcomp
= 1/ 90 A
I Ccomp
= 1/ 150 A
4.92 / 0
= 1.0 / 0 A
4.92
4.92/ 120
=
= 1.0 / 120 A
I bT
4.92
4.92 / 120
=
= 1.0/ 120 A
I cT
4.92
I bcomp
= (1 / 3 )(1.0 / 120 1.0 / 120) = 1/ 90 A
I ccomp
= (1 / 3 )(1.0 / 120 1.0/ 0) = 1/ 150 A
Differential Current = 0
Page 5 of 10
Exercise 3.1: Determine the CT connections and transformation ratio for the
following step-up transformer. Assume the differential protection is a
traditional electromechanical relay. The transformer is 138/12 kV, Yd1
(Wye-DAC), 30 MVA.
High-Side CT
600/5 MR
600-500-450-400
300-250-200-150
100-50/5
H1
X1
H0
X3
H3
H2
Low-Side CT
2000/5 MR
2000-1600-1500-1200
1100-800-500-400-300/5
X2
H3
(C)
150/5
125.5/ 120
IC
Ic
1443.4 / 90
1500/5
x3
(c)
H2
(B)
150/5
125.5/ 120
IB
Ib 1443.4/ 150
1500/5
x2
(b)
H1
(A)
150/5
125.5/ 0
1443.4/ 30
1500/5
x1
(a)
IA
Ia
4.81/ 90
7.24/ 90
4.81/ 150
7.24/ 150
4.81/ 30
7.24 / 30
Relay Taps:
2.9 3.2 3.5 3.8 4.2 4.6 5.0 8.7
All currents are in Amps.
All angles are in degrees
Page 6 of 10
Low-Voltage Side: 12 kV
I RATED =
30000
= 125.5 A
3 138
125.5/ 30
= 7.24 / 30 A
150 / 5
125.5/ 150
= 7.24 / 150 A
I B = 3
150 / 5
125.5/ 90
= 7.24 / 90 A
I C = 3
150 / 5
I A = 3
I rated =
30000
= 1443.4 A
3 12
1443.4 / 30
= 4.81/ 30 A
1500 / 5
1443.4 / 150
= 4.81/ 150 A
I b =
1500 / 5
1443.4 / 90
= 4.81/ 90 A
I c =
1500 / 5
I a =
Differential current before balancing with the relays TAP compensation = |7.24-4.81|=2.43 A
TAP Selection: 5.0
7.24 4.81
5.0
3.2
100 = 3.8% (See Table II at the end of this section)
Mismatch: M =
7.24
5.0
Page 7 of 10
Exercise 3.2: Determine the TAP value and the compensation matrix for each side of
the differential protection shown in the figure. Determine the value of
current for each branch of the circuit. Fill in all the blanks. The
transformer is 138/12 kV, Yd1 (Wye-DAC), 30 MVA.
125.5/ 120
H3
(C)
125.5/ 120
H2
(B)
125.5/ 0
H1
(A)
1500/5
150/5
1500/5
150/5
1500/5
1443.4/ 90
x3
(c)
1443.4 / 150
x2
(b)
1443.4 / 30
x1
(a)
4.18/ 120
4.81/ 90
4.18/ 120
4.81/ 150
4.18 / 0
4.81/ 30
TAP2=
4.18
1 0
1
-1 1
3
0 -1
1/TAP1
1/TAP2
1.0/ 120
1.0 / 90
1.0/ 120
1.0/ 150
1.0 / 0
1.0 / 30
-1
0
COMPENSATION
MATRIX
COMPENSATION
MATRIX
1.0 / 90
Page 8 of 10
4.81
1 0 1
1.0/ 30
1.0/ 30
1.0 / 150
TAP1=
DIFF.
1.0 / 150
1.0 / 90
Low-Voltage Side: 12 kV
I RATED =
30000
= 125.5 A
3 138
I rated =
30000
= 1443.4 A
3 12
150/5
1500/5
125.51/ 0
= 4.18/ 0 A
150 / 5
125.51/ 120
= 4.18/ 120 A
I B =
150 / 5
125.51/ 120
= 4.18/ 120 A
I C =
150 / 5
I a =
I A =
TAP 2 =
30 1000 1
= 4.18
3 138 150 / 5
1443.4/ 30
= 4.81/ 30 A
1500 / 5
1443.4/ 150
= 4.81/ 150 A
I b =
1500 / 5
1443.4/ 90
= 4.81/ 90 A
I c =
1500 / 5
TAP1 =
30 1000 1
= 4.81
3 12 1500 / 5
I AT =
4.18/ 0
= 1.0/ 0 A
4.18
4.18/ 120
=
= 1.0/ 120 A
I BT
4.18
4.18/ 120
=
I CT
= 1.0 / 120 A
4.18
=
I aT
I acomp
= 1/ 30 A
I Bcomp
= (1 / 3 )(1.0 / 120 1.0 / 0) = 1/ 150 A
I bcomp = 1/ 150 A
I ccomp
= 1/ 90 A
I Ccomp
= (1 / 3 )(1.0/ 120 1.0 / 120) = 1/ 90 A
4.81/ 30
= 1.0 / 30 A
4.81
4.81/ 150
=
= 1.0/ 150 A
I bT
4.81
4.81/ 90
=
= 1.0/ 90 A
I cT
4.81
Differential current = 0
Page 9 of 10
Table 1 shows mismatch (sign considered) for different electromechanical relay taps used
for the example in Exercise 2.1.
Table 1
TAP2
2.9
3.2
3.5
3.8
4.2
4.6
5
8.7
TAP 1
2.9
3.2
3.5
3.8
4.2
4.6
5
8.7
-103.83 -124.91 -146.00 -167.08 -195.20 -223.31 -251.43 -511.48
-84.72 -103.83 -122.94 -142.05 -167.52 -193.00 -218.48 -454.16
-68.89 -86.36 -103.83 -121.30 -144.59 -167.89 -191.18 -406.66
-55.55 -71.64 -87.74 -103.83 -125.28 -146.74 -168.19 -366.66
-40.74 -55.30 -69.86 -84.42 -103.83 -123.24 -142.65 -322.21
-28.50 -41.79 -55.09 -68.38 -86.10 -103.83 -121.55 -285.50
-18.22 -30.45 -42.68 -54.91 -71.22 -87.52 -103.83 -254.66
47.18 33.38 21.95 12.32
1.63
-7.77 -17.14 -103.83
Table 2 shows mismatch (sign considered) for different electromechanical relay taps, for
example in Exercise 3.1.
Table 2
TAP2
Page 10 of 10
2.9
3.2
3.5
3.8
4.2
4.6
5
8.7
TAP 1
2.9
3.2
3.5
3.8
4.2
4.6
5
50.52 36.41 24.72 14.87
3.93
-5.38 -14.55
66.09 50.52 37.62 26.75 14.68
4.71
-3.81
81.66 64.63 50.52 38.64 25.43 14.53
5.36
97.23 78.74 63.42 50.52 36.18 24.34 14.40
117.99 97.56 80.62 66.36 50.52 37.43 26.44
138.76 116.37 97.83 82.21 64.85 50.52 38.48
159.52 135.19 115.03 98.05 79.19 63.61 50.52
351.56 309.23 274.15 244.61 211.79 184.68 161.90
8.7
-99.31
-80.62
-65.14
-52.10
-37.62
-25.65
-15.60
50.52