Power System Analysis (Jan-2014)
Power System Analysis (Jan-2014)
Set No: 1
3. A Threee bus power system shown in below fig. The systems parameters
parameters are given in
table1 and load & generator date in ttable2.
able2. The voltage at bus 2 is maintained at 1.03
P.u. The max and min. Reactions
Reactions power limits of the generation at bus 2 are 35 and 0
MVAr respectively. Taking
aking bus 1 as slack bus obtain the load flow solution using N
N-R
methods after first iteration.
[15]
Impedance
Zik (P.u)
0.08 + j0.24
0.02 + j0.06
0.06 + j0.018
||''|''||''||''''''|
Bus Voltage
Vi
1.05 + j0.0
1.03 +j0.0
-
Generation
Load
MW MVAr MW
MVAr
0
0
20
50
20
0
0
60
25
R10
Set No: 1
4. Determine the Zbus for the power system networks shown in below fig.
1
0.25
G1
X ' g1 = 0.1
G2
X T 1 = 0.02
X T 2 = 0.01
X ' g 2 = 0.15
0.15
0.3
[15]
3
5. The system shown in Fig below shows an existing plant consisting of a generator of
100 MVA, 30 KV, with 20 percent sub transient reactance and a generator of 50
MVA, 30 KV with 15 percent reactance, connected in parallel to a 30-KV bus bar.
The 30-KV bus bar feeds a transmission line via the circuit breaker C which is related
at 1250 MVA. A grid supply is connected to the substation bus bar through a 500
MVA, 400/30KV transformer with 20 percent reactance. Determine the reactance of a
current limiting reactor in ohm to be connected between the grid system and the
existing bus bar such that the short circuit MVA of the breaker C does not exceed.
[15]
6. The one-line diagram of a simple power system is shown in Fig below. Each generator
is represented by an emf behind the transient reactance. All impedances are expressed
in per unit on a common MVA base. All resistances and shunt capacitances are
neglected. The generators are operating on no load to their rated voltage with their emfs
in phase. A three-phase fault occurs at bus 1 through a fault impedance of Zf=j0.08 per
unit.
(a) Using the venins theorems obtain thee impedance to the point of fault and the fault
current in per unit.
(b) Determine the bus voltage and line current during fault.
[8+7]
2 of 3
||''|''||''||''''''|
R10
Set No: 1
7. The reactance data for the power system shown in fig below in per unit on a common
base is as follows:
Obtain the thevenin sequence impedance for the fault at bus 1and compute the fault
current in per unit for the following faults.
3 of 3
||''|''||''||''''''|
[4+4+4+3]
[8+7]
R10
Set No: 2
1. Two generators are connected in parallel to a 6.6 KV bus. One of the generator has a
rating of 20 MVA and a reactance of 15 % while the second generator is rated at 15
MVA and has a reactance of 12 %. Calculate the P.u reactance of 50 MVA and 6.6 KV
base. What is the P.u reactance of a single equivalent generator on 50 MVA and 6.6 KV
base?
[15]
2. In fig shows the one-line diagram of a simple three-bus power system with generation
at bus 1is V1 = 1.00 o per unit. The scheduled loads on buses 2 and 3 are marked on the
diagram. Line impedances are marked in per unit on a 100 MVA base. For the purpose
of hand calculations, line resistances and line charging susceptance re neglected.
(0)
(0)
Using gauss-Seidel method and initial estimates of V2 = 1.0 + j 0andV3 = 1.0 + j 0
, determine V2 and V3. Perform two iterations.
[15]
3. In the two bus system shown in fig below, bus 1 is a slack bus with V 1 = 1.0 0 P.u. A
load of 100 MW and 50 MVAr is taken from bus 2. The line impedance is
Z12=(0.12+j0.16) pu on a base of 100 MVA. Using Newton-Raphson method, obtain the
0
voltage magnitude and phase angle of bus 2. Start with an initial estimate of V 2 = 1.0
and 2(0) = 0 0 . Perform two iterations.
[15]
1 of 2
||''|''||''||''''''|
R10
Set No: 2
5. The system shown in fig below is initially on No load with generators operating at their
rated voltage with their emfs in phase. The rating of the generators and the transformers
and their respective percent reactance are marked on the diagram. All
All resistances are
neglected. The line impedance is j160 ohms. A three phase balanced fault occurs at the
receiving end of the transmission line. Determine the short circuit current and the short
circuit MVA.
[15]
2 of 2
||''|''||''||''''''|
R10
Set No: 3
1. A 500 MVA, 15 kV, 3 generator has a sub transient reactance of 0.2 P.u. The
generator supplies two motors over a transmission line having transformers at both ends
of the system. The motor have rated inputs of 35 MVA and 15 MVA both 30 kV the
with 0.13 P.u sub transient reactance. The rating of the sending end transformer, Tr1 is
50MVA, 11/132 kV = Y with leakage reactance of 0.1 P.u. Transformer, Tr2 at the
receiving end has 3 single phase transformers connected has a 3 phase unit. The rating
of each individual transformer is 18 kVA, 33/76 kV with leakage reactance of 0.13 P.u.
Series impedance of the line is (20+j50). Draw the impedance diagram with all
impedance marked in P.u . Select the generator rating as the base.
2. In the fig shown in below the one line diagram of a simple three phase bus power
system with generation at buses 1 and 3. The voltage at bus 1 is V 1 = 1.025 0 per
unit. Voltage at bus 3 is fixed at 1.03 P.u with a real power generation of 300 MW. A
load consisting of 400 MW and 200 MVAr is taken from bus 2. Line impedances are
marked in per unit on a 100 MVA base. For the purpose of hand calculations, line
resistances and line charging susceptances are neglected.
(a) Using Gauss-Seidal method and initial estimates of
V2(0) = 1.0 + j 0andV3(0) = 1.03 + j 0
(b) And keeping
iterations.
V3 = 1.03
3. In the two bus system shown in fig below bus 1 is a slack bus with V 1 = 1.0 0 P.u. A
load of 150 MW and 50 MVAr is taken from bus 2. The line admittance is
y12 = 10 73.74 P.u on a base of 100 MVA. The expression for real and reactive
power at bus 2 is given by
2
Q2 = 10 V2 V1 sin(106.26 0 2 + 1 ) 10 V2 sin(73.74 0 )
Using Newton-Raphson method, obtain the voltage magnitude and phase angle of
(0)
(0)
bus 2. Start with an initial estimate of V2 = 1.0 and 2 = 0 . Perform two
iterations.
[5+5+5]
1 of 3
||''|''||''||''''''|
R10
Set No: 3
load with a resistance of 37 ohms per phase is connected to the supply. Determine
(a) The symmetrical components of voltage
(b) The phase voltages (c) The line currents
[5+5+5]
7. The zero, positive and negative sequence bus impedance matrices for a three bus power
system are
0.20 0.05 0.12
0.16 0.10 0.15
0
1
2
Z bus = j 0.05 0.10 0.08 P.u and Z bus = Z bus = j 0.10 0.20 0.12 pu
0.12 0.08 0.30
0.15 0.12 0.25
Determine the pu fault current and the bus voltage during the fault for
[4+4+4+3]
(a) A bolted three phase fault at bus 1. (b) A bolted single line to ground fault at bus 1.
(c) A bolted line to line fault at bus 1. (d) A bolted double line to ground fault at bus 1.
[4+4+4+3]
2 of 3
||''|''||''||''''''|
R10
Set No: 3
8. (a) Derive an expression for the critical clearing angle for a power system consisting of
a single machine supplying to an infinite bus, for a sudden load increment.
(b) A 4 Pole, 50Hz, 11kV generator is rated 75 MW and 0.86 P.f lag the machine rotor
has a moment of inertia of 9000kg.m2. Ffind the inertia constant in MJ/MVA and M
constant or momentum in M-J sec/elec degree
[8+7]
*****
3 of 3
||''|''||''||''''''|
R10
Set No: 4
Generator:
Motor:
40MVA
35MVA
25kV
11kV
X=20%
X=30%
Y-Y transformer:
Y- transformer
40MVA
30MVA
33 Y-220Y kV
11 -220Y kV
X = 15%
X=15%
Ybus
3 j5
= 1.2 + j 6
1.5 + j 6
1 .2 + j 6
4 j12
3 + j6
1 .5 + j 6
3 + j 6
5 j 6
Bus number
Generation
Ge
Load
Bus voltage (P.u)
MW
MVAr
MW
MVAr
1
0
0
0
0
1.04 + j0.0
2
0
0
200
125
1.2 + j0.0
3
100
70
50
20
1.0 + j0.0
4. Impedances connected between various buses as follows:
X10 =1.2 ,
X30 = 1.3,
X12=0.23,
X23 = 0.35,
X24 = 0.12 and X43 = 0.3,
where 0 is reference bus. All impedances are in P.u. find the bus impedance matrix for the
networks connecting above impedances
5. An interconnected generator reactor is shown in below figure the base values for the given
percentage reactance are the rating of the individual pieces of equipment. A 3 short
circuit occurs at print F. Determine the fault current and fault MVA at F. Assume bus
bus-bar
voltage as 11kV
15MVA
10MVA
G2
G3 20 MVA
G1
10%
7%
15
15%
F
10 MVA
12%
||''|''||''||''''''|
7.5 MVA
4%
R10
Set No: 4
I a = 1030 0 A
I b = 15 50 0 A
IC
7. An alternator of rating 10 MVA, 50Hz and has sequence reactance of 25%, 10 % and 5% to
position. Negative and zero respectively. It is connected to a line of having 3 conductors of 1
CM diameter arranged triangle spacing of4.5m side. The generator is excited to given 25kV
on open circuit. Fine the current in the line when to lines are short circuited at a distance
15km long the line. Assume resistance is zero.
8. (a) Explain the steady state stability with power angle characteristics.
(b) Find the critical clearance angle of the following system, for a 3 fault at the point F.
The generator is delivering 1.0 P.u power under pre fault conditions
*****
2 of 2
||''|''||''||''''''|