Cable Support Systems

Cable ladders

07

Index


Bends
90 Bend 15
90 Bend 55
S-bend 67

page
87
94
91

Brackets
Angle bracket 5L, 5LS
Bracket 60/40
Clamp 12
Combi bracket 53
End bracket HT-11
End connection 10
Lighting bracket 200
Pendant bar 1
Profile support piece 46
Rail fixing support 24/20F,
24/20FS
Rod bracket 82
Wall bracket 11/25, 11/75
Wall bracket 20
Wall bracket 20F
Cable ladders
Cable ladder view
Cable ladder KHZ
Cable ladder KHZP
Cable ladder KHZPS
Cable ladder KHZPV
Cable ladder KHZSP
Cable ladder KHZSPZ
Cable ladder KHZV

72
75
108
66
73
82
95
75
93
69
36
84
70
70
46
24
25
23
27
21
22
26

Cable rollers
Cable roller 38 Rign roll
Cable roller S
Cable roller set 66

115
114
115

Cantilever arms
Cantilever arm 30
31
Cantilever arm 50L, 50, 50F 32
Cantilever arm 50i
30
Cantilever arms
accessories
Back plate 40
Mounting rail 40

35
35

Ceiling brackets
Beam clamp 5BK
Ceiling bracket 5
Ceiling bracket 5TP
Ceiling bracket 5TPA
Ceiling bracket TF-10, TF-16
Pendant base plate 520

63
61
64
65
60
62

Ceiling plates
Ceiling plate 20F
Ceiling plate 20FS

71
71

Clamps
Cable clamp A
Cable clamp ER
Cable clamp R
Hook 8

109
112
110
108


Insert piece EM
Profile clamp 41
Profile clamp 42
Profile clamp 43
Couplings
Angle plate 33/1, 33/2
Coupling 22
Coupling 44
Coupling 51
Fixed take-off hook 4
Junction coupling 14
Take-off hook 47

page
111
83
34
34
86
81
96
97
82
88
92

Covers
Cover W5
Cover 90 bend
Cover clamp
Cover joint
Cover T-junction
Profile support piece 37

117
120
119
118
121
119

Cover plates
Cover 64
Cover plate 65
Junction box cover
Protecting cover

104
104
105
122

Dividers
Distance piece W39
Dividing strip 39

103
103

End plugs
Cross member plug 27
End plug 28, 28i
End plug 28C,D,E,F
Profile protection 28P
Fixings
Concrete screws
Expansion bolts

84
85
86
85
137
134

Installation examples
Cable ladders
154
Frame installations
153
Installation summeries
KHZ
16 17
KHZP
16 17
KHZPS
16 17
KHZPV
18 19
KHZSP, KHZSPZ
16 17
KHZV
18 19
Suspension components 28 29
Installation plates
Installation plate 60
Installation plate 61
Installation plate 62
Joints
Dropper joint 32
Intermediate connection
bolt 29

100
102
101
80
79

page

Joint 21
Joint 45
Joint 9
Pendant joint 2J, 2FJ, 20J
Reducer 31
Screw set M12
(KHZV/KHZPV)
Junctions
T-junction 16
T-junction 56
X-junction 17
Junction box plates
Earth clamp W79
Junction box plate 35P
Junction box plate 35S
Lashing wires
Lashing wire
Marking plates
Marking plate 93

page

Screw set 2S
Screw set 20S
Screw set 22S
Screw set M12
(joint KHZV/KHZPV)
Screw set W34
Spring nut M8, M10
T-bolt 26F

130
131
133

88 Steel wire installation


94 system HT
89 Angle bracket 5L
Carrying bracket HT-152
Carrying bracket HT-31
99 Carrying bracket HT-33/34
98 Carrying sling HT-51
99 End bracket HT-11
Pipe HT-68, HTR-68
Steel wire
105 Tightening loop HT
Wall bracket HT-14

124
126
125
126
127
124
127
123
128
125

78
92
79
74
80
95

130
130
130
95

116 Support brackets


Support bracket 3
38
Support bracket 6
41
Mesh trays
40
Ceiling bracket WN16
76 Support bracket HSO
Ceiling mesh tray WN2
76
Fixing tray N for casting-in 107 Surface treatment
Corrosion classes
7
Current load of cables
9
Mounting rails
10
Mounting rail 40
35 Environment/Quality
9
Mounting rail WMS25
113 Installation regulations
Potential balancing
13
Product certificates
10 12
Paint
Surface treatments
8 9
Anti-corrosive paint
Galvafroid
116
Repair paint
116 Tele-conduits
Tele-conduit 36
106
Pendant/Fixing rails
Fixing rail 24/26x53 for
Vertical pieces
42
casting-in
56 Threaded rod M10 W76
Vertical piece 2
44
Fixing rail JSA 24/26x48 for
46
casting-in
56 Vertical piece 2F
43
Pendant/Fixing rail 24/20
57 Vertical piece 2FPK
48
Pendant/Fixing rail 24/20F 58 Vertical piece 20
50
Pendant/Fixing rail 24/20FS 59 Vertical piece 20F
52
Pendant/Fixing rail 24/34
54 Vertical piece20FS
Pendant/Fixing rail 24/48
55
Risers
Riser 18
Riser coupling 49

90
93

Round bar fixings


Round bar fixing for ceilings
Round bar fixing for floors
Round bar fixing for walls
View Round bar fixings

67
68
68
67

Screw sets
Back nut M8
Clamp set M6
Expansion bolts
Screw M10x20

Wibe reserve the right to make changes to manufacture and design without prior notice.

131
132
134
131

Cable ladders
Cable ladders view

Corrosion classes

Surface treatments, Environment/quality, Product certificates, Potential balancing

Installation summaries KHZSP, KHZSPZ, KHZPS, KHZ, KHZP and KHZV, KHZPV
Cable ladders KHZSP, KHZSPZ, KHZPS, KHZ, KHZP, KHZV/KHZPV
Installation summary Suspension components

16-17 o 18-19
21
28-29

Cantilever arms, Back plates, Mount.rails, Profile clamps

30

Support bracket 3, HSO, -6,

38

Threaded rod M10 W76, Vertical pieces

42

Pendant/Fixing rails

54

Ceiling brackets

60

Round bar fixings, Wall brackets, Ceiling plates

67

Angle/end brackets, Pendant joints/bar, Ceiling mesh tray

72

Joints, Couplings

78

Details for KHZV, KHZPV

92

Junction box plates, Installation plates, Cable dividers

98

Covers, Tele-conduit, Fixing tray N for casting-in

104

Cable clamps, Cable rollers

109

Covers and Accessories

117

Steel wire system HT

123

Screw sets

130

Expansion bolts, Concrete screws

134

Frame installations, Installation examples - cable ladders

153

Wibe in Mora, Sweden

There is always a next time.


Usually its a matter of a few extras, sometimes more radical changes. New and
old have to fit together regardless. Hand in glove even in 15 years time.
We delivered our first and the worlds first cable ladder just over 75 years
ago. And we can still supply additions to it if necessary. We carry over 10,000
items in our range. Just over a hundred are ladders and trays. The remainder
consists of components to meet every possible requirement. And some pretty
impossible ones too.
So dont just think about this time, think about the next time.
We are the biggest supplier on the market. More concretely, we provide cable
ladders and cable trays, lighting trunking and installation rails, steel wire systems, integrated ceilings and Defem wire trays. We hot dip galvanize in one
of the most modern plants in Scandinavia and do powder coating in one that is
just as technologically advanced.
Wibe is the market leader in telescopic masts and masts for lighting and communication. We have experience from thousands of projects, from planning, to
fitting and erection, to commissioning and service.

Wibe is part of the worldwide Schneider Electric group, which also includes leading brands such as Eljo, Lexel, Merlin Gerin, Telemecanique and Thorsman.

Reference installations

Cable ladders - view


KHZSP-KHZSPZ

8,5 x 18

18

KHZPS

30

Length
Width
Pre-galvanized
Hot dip galvanized
Zinkpox coated white
Stainless steel AISI 316L

8,5 x 18

18

30

3,4,6 m
200-600 mm

Length
Width
Pre-galvanized
Hot dip galvanized
Zinkpox coated white
Stainless steel AISI 316L

6m
150-1000 mm

Cable ladders - view


KHZ

KHZP

17

8,5 x 17

18
21
30

Length
Width
Pre-galvanized
Hot dip galvanized
Zinkpox coated white
Stainless steel AISI 316L

6m
150-600 mm

Length
Width
Pre-galvanized
Hot dip galvanized
Zinkpox coated white
Stainless steel AISI 316L

3, 6 m
150-1000 mm

Cable ladders - view


KHZV

KHZPV

17

8,5 x 17

18
21
30

Length
Width
Pre-galvanized
Hot dip galvanized
Zinkpox coated white
Stainless steel AISI 316L

6m
200-600 mm

Length
Width
Pre-galvanized
Hot dip galvanized
Zinkpox coated white
Stainless steel AISI 316L

6m
200-1000 mm

Corrosion classes
Corrosion classes
The life expectancy of a cable support system is dependent on the
environment in which it is placed. Therefore, it is important to
establish the corrosive properties of an environment to ensure that
the right treatment and the right material are chosen.
To achieve this, several corrosion classes have been drawn up in
accordance with BSK99.

The table below shows various corrosion classes. As a guide, we


have included the surface treatment recommended by Wibe for the
different classes.
On the next page, we briefly outline the various surface treatments
and materials.

As regards environmental corrosion, a steel design component can usually be assigned to one of the corrosion classes (C1-C5-M)
as shown in table 1:23a. Reference values for the average level of corrosion in steel and zinc are given in table 1:23c.
The corrosion classes comply with those stipulated in SS-EN ISO 12944-2.
Table 1:23a
Corrosion classes as stipulated by SS-EN ISO 12944-2 with atmospheric corrosion levels and examples of the environment in which
they are most suitable for use.

Surface treatments
Electro-galvanized Fzb
Some of Wibes products are electro-galvanized in accordance with
ISO 2081. Such products are intended for use only in warm, dry
areas with negligible pollutant levels.
Pre-galvanized Fzs
Products are manufactured from Z 275 pre-galvanized sheet steel in
accordance with SS-EN 10327:2004. Surface sections created
during cutting and drilling will, under normal conditions, repair themselves, providing the plant with superb anti-corrosion protection.
Hot dip galvanized Fzv
Wibe has one of the most modern hot dip galvanization plants in the
Nordic countries. The hot dip process is continuous, guaranteeing a
high and even quality.
Once manufactured products are hot dip galvanized in accordance
with SS-EN ISO 1461 whilst nuts and bolts are hot dip galvanized in
accordance with SS-EN ISO 10684:2004. This form of galvanization
affords very good value-for-money anti-corrosion protection in
atmospheres with a pH value of between 6 and 13. However, in acidic
environments where pH levels fall below 6 and in alkaline environments where the pH value exceeds 13, the protective zinc layer
breaks down relatively quickly.

The rate of dissolution is determined by the pH value of pure zinc


in distilled oxygenated water that has been pH adjusted to various
levels using HCl or NaOH.
NB The curve only applies to conditions shown, and gives only an
indication of the propensity for corrosion without consideration to
time.
Zinkpox
The Zinkpox method involves applying a homogenous polyester
coating to the zinc layer.
Besides resisting light-initiated degeneration and weathering, this
powder coating has excellent mechanical properties as regards
impact resistance and adhesion.
It is also resistant to most chemicals.
Compared to hot-dip galvanizing, applying a polyester coating to the
zinc layer more than doubles the service life of treated components.
The zinc layer prevents the development of filiform corrosion. This
might otherwise degrade the coating. Consequently, the polyester
coating is subject only to atmospheric attack and thus protects the
zinc layer.
In addition to extremely good corrosion protection, the Zinkpox
method also offers a choice of colours. Powder coating is a very
environment-friendly way of achieving a coloured surface. Because
the coating contains no solvents, it has largely replaced solventbased liquid coatings.
Where installations are visible, cable ladders and fittings can be
finished in a coating that matches the surrounding dcor.

Modern coating plant


Before powder coating, the galvanized components undergo meticulous pre-treatment. This ensures superb adhesion.
The certified coating plant that treats our components uses a modern
and environment-friendly process. There are seven pre-treatment
stages; alkaline degreasing, rinsing, rinsing, phosphating, rinsing,
passivation and rinsing with de-ionised water.
Immediately after pre-treatment, the components are dried in a
tunnel oven. They are then powder coated in an automatic booth.
This guarantees that all the components are correctly processed.
The coating is cured in a tunnel oven. To achieve the perfect curing
curve, temperature regulation in each section of the oven is stepless.
At no stage in the process are the components touched by human
hand. An electronically controlled conveyor takes care of all the
necessary handling. The end result of this certified, environmentfriendly process is a weather-resistant surface that demonstrates
high durability in the face of chemical and mechanical attrition.
Mechanical properties of the polyester coating
(Very high resistance to light-initiated degeneration and weathering)

Erichsen cupping......................
Impact resistance, ASTM..........
Mandrel bend test.....................
Cross-cut test..........................
Film hardness..........................

DIN 53156............ > 7 mm


D2794 reverse......> 20 IP
DIN 53152............ < 4 mm
DIN 53151................GTO
DIN 53153............ < 90

Stainless steel
Wibe stainless steel products, manufactured in accordance with
SS 2333/AISI 304, or in accordance with SS 2348/AISI 316L, are
designed for use in highly aggressive environments, either indoors or
outdoors, on industrial sites where there are high levels of potent
airborne pollution such as in certain chemical industries, celluloserelated industries, refineries or artificial fertiliser factories, high
humidity tunnels, etc.
Stainless steel products are also ideal for use in environments where
special hygiene requirements are in force, such as dairies, abattoirs,
other food industries and pharmaceuticals factories.
Stainless steel AISI 304 or AISI 316L?
The deciding factor in choosing between stainless steel AISI 304 or
AISI 316L is the aggressiveness of the environment in which it is to
be used, and for this atmospheric chlorine content plays a significant
role. Environments with a high chlorine content - coastal areas being
a prime example - are aggressive, and usually require the use of AISI
316L materials.
When assessing the needs of factories, consideration should be
given to the materials previously used to suspend equipment such as
pipe tubing, and from this determine whether stainless steel
AISI 304 or AISI 316L material is required.
Factors to consider when installing Stainless Steel Cable Ladder Systems
1. Transport/handling
Make sure that no iron objects come into contact with the stainless
steel products.
2. Storing
Never store stainless steel products near where iron products are
machined, for example, close to cutting and grinding operations.
3. Welding
Welding during installation should be avoided where possible. If
welding must be performed, make sure that only methods suitable for
stainless steel are used.

Surface treatments
4. Tools
When cutting or grinding, always use cutting wheels and grinding
tools which are free from iron. Do not use tools that have been
previously used for cutting or grinding products containing iron.
When drilling, use an HSS-drill. To maximize the useful life of the drill,
employ a cooling fluid during drilling.
When installing, conventional assembly tools can be used. However,
when using a nut tightener, ensure that the thread is first lubricated
to prevent jamming.
Never mix untreated or galvanized products with stainless steel!
5. Measures
If a blue annealing appears when cutting, grinding or drilling, remove
it with pickling paste, making sure that the paste is then carefully
washed away with water.

If selective corrosion appears it can be removed by:


a) Washing away with water (high pressure if possible).
b) Polishing with a cleaning cloth or a fine emery paper (wet or dry)
and washing with water.
c) Grinding with a fine-grained wheel and washing with water.
d) Pickling with pickling paste, making sure that the pickling paste
is then carefully washed away with water.
6. When using pickling paste or similar products
Always study the safety code for the product prior to use.

Installation regulations
Installation of cables on Ladder
The installation of cables on ladders comes within the IEE Regulations for Electrical Installations.
Because Wibe ladder has rungs which occupy less than 10% of the
plan area under the cables, the installation is defined as cables in
"free air" (Method 12 of Table 9A of the IEE Regulations).
Cable spaces in accordance with Method 12 do not require any derating factor for installation.
Cables touching must be de-rated in accordance with table 9B.
Extract from table 9B
Method of
installation

Correction Factor Cg
Number of circuits of multicare cables
2

Single layer
multicare touching
on ladder supports

0.86

0.82

0.80

0.79

0.78

0.78

Extract from table 9A


Sheathed single-core cables in free air (any supporting metalwork
under the cables occupying less than 10% of the plan area):
1. Two or three cables vertically one above the other, distance
between cables equal to the overall cable diameter (De):
Distance from the wall not less than 0.5 De.
2. Two or three cables horizontally, with spacings as above.
3. Three cables in trefail, distance between wall and surface of
nearest cable 0.5 De or nearest cables 0.75 De.
1.

2.
0.5 De min

0.78

0.5 De min De min


De min

0.77

Installation of Cable Ladder


The installation of cable ladder is a structural steel support design
question which does not have any regulations. Full design data is
given in the Wibe data sheets in this catalogue showing all maximum
and recommended loadings.
Any support system which is supported at intervals and loaded will
deflect between the support intervals. Graphs are given in this
catalogue to show the deflection against loading for various support
distances.

Vertical
surface
of wall

De

De min
De min

3.
0.75 De min

0.5 De min

Current load of cables


Installation instructions
Installation
The ladders and trays shall be installed in such a way that, as often
as possible the cables can be laid directly in place rather than being
pulled through.
Ladders and trays for current carrying cables along the ceiling shall
be installed in such a way that the distance from the top of the ladder
or tray to the ceiling shall not be less than 300 mm.
The free vertical distance between parallel ladders and trays shall be
at least 200 mm.
Ladders and trays near walls shall be installed with a minimum free
distance of 50 mm to the wall, so that cables can pass between the
ladders and the wall.
Ladders and trays along partition walls shall be installed with
minimum free distance of 100 mm to the wall.
Sharp edges and screw ends on ladders or trays should be removed
before the cables can be installed.
Expansion bolts for the installation of brackets/fixings shall be
installed with such a distance between them, that the designated load
for ladders and trays will not be exceeded. When selecting the
distance between cantilever arms or brackets/fixings, the bearing
strength and designated load of the ladders and trays must be taken
into consideration.

Reinforced heavy duty cable ladders


Ladders shall be designed for a uniform load of at least 600 N per
1000 mm ladder length with a distance of 6000 mm between
brackets/fixings. They shall also be able to carry an occasional point
load as to the heavy duty ladders.
Heavy duty cable ladders, cable trays
Ladders and trays shall be designed for a uniform load of at least
200 N per 1000 mm ladder length and 100 mm width with a distance
of 2000 mm between brackets/fixings. They shall also be able to
carry an occasional point load of 1000 N with a double safety factor
measured between supporting points 3 and 4 when using an
installation with six supporting points.
Light duty cable ladders, cable trays
Ladders and trays shall be designed for a uniform load of at least
100 N per 1000 mm ladder length and 100 mm width with a distance
of 2000 mm between brackets/fixings.

Environment/quality
Environmental policy

Certification

AB Wibe shall actively strive to minimise any negative impact its


operations may have on the environment.
Besides working in a way that prevents pollution, we shall also
ensure that, given Wibes production and quality requirements, the
most environment-friendly solutions are always chosen. All of this
shall be within a framework of continual improvement.
Our environmental initiatives shall go beyond what is required by
legislation.
In its work for the environment, Wibe shall maintain suitable
dialogues and collaborations with all interested parties.
The environmental policy shall always be available to the public.
The companys environmental reviews shall be the base on which
our environmental goals and programmes are founded.
We shall achieve the above by:

Environmental product declarations are available for all Wibe


products. These can be ordered direct from Wibe.
Declarations may also be downloaded from the Wibe website at
www.wibe.se
Our product sheets and brochures are marked successively with the
name of the environmental document (WEF-0001-).

Ensuring that, throughout manufacture and design, full attention


is paid to ecological considerations, quality requirements, health
factors and environmental sustainability
Setting up environment-focused collaborations with suppliers and
customers
Giving training on our environmental initiatives and promoting staff
involvement
Maximising efficiency in the use of energy and raw materials
Minimising the production of waste that cannot be recycled within
our operations
Ensuring that chemicals and dangerous waste are handled in the
best possible manner
Continuously evaluating the success of our initiatives

Product certificates

10

Management system - Quality and Environment


Wibe has a third-party certified management system
for quality and environment in accordance with
ISO 9001:2000 and ISO 14001:2004.
CE-marking of products
is placed on the product or on the packing according to "Declaration
of Conformity" (D o C),
applicable to Wibe Cable ladders, Cable trays and Lighting trunkings.
EMC directive 89/336 EEC
Above mentioned products are neutral according to the EMC directive 89/336 EEC.
Low voltage directive 73/23 EEC
According to the low voltage directive we refer to:
SFS 1993:1068 Regulations concerning electrical material.
SFS 1993:1068 General obligations regarding electrical material.
Wibe fulfils the demands according to the harmonized standard SSEN 6153 Edition 1:2002.

Product certificates

11

Product certificates

12

Potential balancing
Resistance testing of Wibe cable ladders has been performed by the Swedish National Testing & Research Institute in Bors
and Wibe test laboratory.
The tests have been carried out according to SS-EN 61537, IEC 61537 and EL-AMA SBD 2.

13

14

15

Installation summary
67

16
30

70

12, 13

61

57, 58

73

48
71

8
57, 58
30

47

68
37

57, 58
74 7

20

60

69

37
73
14
5
21

32

26

68

44

66

65
19

39

10

1
49
10
21

36

32

31

23

31

10

11

72
18

43
42

6 9

11
73
41
59

73

22

73
38

29
21
59

54

26
10
64
25
24
17

16

15

63
11
19

6 27

62

33

50
49

35
56
5

10
40

53
30
34

44

52

46

65

55

45

28

21

Components _______________________________ Page


1 Cable ladder KHZSP, KHZSPZ _____________ 21-22
2 Cable ladder KHZ _______________________
24
3 Cable ladder KHZPS, KHZP _______________ 23,25
4 Cantilever arm 50i _______________________
30
5 Cantilever arm 50, 50L, 50F _______________
32
6 Profile clamp 42 _________________________
34
7 Back plate 40 ___________________________
35
8 Mounting rail 40 _________________________
35
9 Support bracket 3, Support bracket 6 ________ 38,41
10 Vertical pieces __________________________ 43-53
11 Pendant/Fixing rails ______________________ 54-59
12 Fixing rail 24/26x53 for casting-in ___________
56
13 Fixing rail JSA 24/26x40 for casting-in________
56
14 Ceiling bracket 5 ________________________
61
15 Pendant base plate 520 ___________________
62
16 Round bar fixings(ceiling,wall,floor) __________ 67-68
17 Rail fixing support 24/20F, 24/20FS__________
69
18 End bracket HT-11_______________________
73
19 Pendant joint 2J, 2FJ, 20J _________________
74
20 Pendant bar 1 __________________________
75
21 Joint 21 _______________________________
78
22 Joint 9 ________________________________
79
23 Intermediate connection bolt 29_____________
79
24 Dropper joint 32 _________________________
80
25 Reducer 31 ____________________________
80
26 Coupling 22 ____________________________
81
27 Fixed take-off hook 4 _____________________
82
28 End connection 10 _______________________
82
29 Profile clamp 41 _________________________
83
30 Wall bracket 11/25, 11/75 _________________
84
31 Cross member plug 27____________________
84
32 End plug 28, 28i _________________________
85
33 Profile protection 28P_____________________
85
34 End plug 28E, 28D, 28C, 28F ______________
86
35 Angle plate 33/1, 33/2 ____________________
86
36 90 bend 15 ____________________________
87
37 Junction coupling 14 _____________________
88
38 T-junction 16 ___________________________
88
39 X-junction 17 ___________________________
89
40 Riser 18 _______________________________
90
41 Junction box plate 35P____________________
98
42 Junction box plate 35S____________________
99
43 Earth clamp W79 ________________________
99
44 Ceiling bracket TF10 and TF16 _____________
60
45 Support bracket HSO_____________________
40
46 Installation plate 60 ______________________
100
47 Installation plate 62 ______________________
101
48 Installation plate 61 ______________________
102
49 Dividing strip 39 _________________________
103
50 Distance piece W39 ______________________
103
52 Cover plate 65 __________________________
104
53 Junction box cover _______________________
105
54 Tele-conduit 36 _________________________
106
55 Clamp 12 ______________________________
108
56 Hook 8 ________________________________
108
57 Cable clamp A and R _____________________ 109-110
58 Insert piece EM _________________________
111
59 Cable clamp ER _________________________
112
60 Lashing wire____________________________
105
61 Mounting rail WMS25_____________________
113
62 Cable roller S ___________________________
114
63 Cable roller 38 Rign roll/Cable roller set 66 ___
115
64 Marking plate 93 ________________________
116
65 Threaded rod M10W76 ___________________
42
66 Cover W5 ______________________________
117
67 Cover joint _____________________________
118
68 Profile support piece 37 ___________________
119
69 Cover clamp____________________________
119
70 Cover 90 bend _________________________
120
71 Cover T-junction_________________________
121
72 Protecting cover _________________________
122
73 Screw sets _____________________________ 130-133
74 Expansion bolts _________________________ 134-135
Fixings-concrete screws __________________ 137-152
Fixing tray N for casting-in _________________
107

17

Installation summary
45
18
44
6
42, 43
47
49
3

4
33

26
27

34

9, 10
(14, 15)

4
33
27
35
24

38
1

48
16

33

31
28
20
33
19
12
32
33

33

37
7 48
36
33

33

33

33
4
33

30

29
12

36
23
25

40

21
21

18

47
46
17

13

20
22
4

39

2
38
3
50
8

29

41

Components _______________________________
1 Cable ladder KHZV ______________________
2 Cable ladder KHZPV_____________________
3 Cantilever arm 50F ______________________
4 Profile clamp 43 ________________________
5 Dividing strip 39_________________________
6 Mounting rail 40_________________________
7 Support bracket 3 _______________________
8 Vertical piece 20 ________________________
9 Vertical piece 20F _______________________
10 Vertical piece 20FS ______________________
12 Pendant/Fixing rail 24/48 _________________
13 Pendant/Fixing rail 24/20 _________________
14 Pendant/Fixing rail 24/20F ________________
15 Pendant/Fixing rail 24/20FS _______________
16 Ceiling bracket 5 ________________________
17 Pendant base plate 520 __________________
18 Round bar fixings (ceiling, wall, floor) ________
19 Rail fixing support 24/20F, 24/20FS _________
20 Pendant joint 2J, 2 FJ, 20J ________________
21 End connection 10 ______________________
22 Profile clamp 41 ________________________
23 Wall bracket 11/25, 11/75 ________________
24 Cross member plug 27 ___________________
25 End plug 28E, 28D, 28C, 28F ______________
26 Joint 45 _______________________________
27 Take-off hook 47 ________________________
28 Profile support piece 46 __________________
29 Riser coupling 49 _______________________
30 Marking plate 93 ________________________
31 90 bend 55 ____________________________
32 T-junction 56 ___________________________
33 Screw set M12 _________________________
34 Lighting bracket 200 _____________________
35 Coupling 44 ____________________________
36 Coupling 51 ____________________________
37 Junction box plate 35P ___________________
38 Junction box plate 35S ___________________
39 Installation plate 60 ______________________
40 Installation plate 61 ______________________
41 Cover plate 65__________________________
42 Cable clamp A and R ____________________
43 Insert piece EM _________________________
44 Cover W5 _____________________________
45 Cover joint _____________________________
46 Profile support piece 37 __________________
47 Cover clamp ___________________________
48 Screw sets_____________________________
49 Expansion bolts_________________________
50 Profile protection 28P ____________________
Fixings - concrete screws _________________

Page
26
27
32
34
103
35
38
48
50
52
55
57
58
59
61
62
67-68
69
74
82
83
84
84
86
92
92
93
93
116
94
94
95
95
96
97
98
99
100
102
104
109-110
111
117
118
119
119
130-133
134-135
85
137-152

19

20

Cable ladder KHZSP


WEF-0001

A
mm

B
mm

KHZSP-200
198
164
KHZSP-300
298
264
KHZSP-400
398
364
KHZSP-500
498
464
KHZSP-600
598
564
*EAN-code=732167+Part.no+C (control figure)
The cable ladders must not be used as walkways.

L=6 m
Pre-galv.
Part.No. C*

L=4 m
Pre-galv.
Part.No. C*

L=3 m
Pre-galv.
Part.No. C*

Weight kg
100 m

734488 8
734489 5
734490 1
734491 8
734492 5

718572 6
718573 3
718574 0
718575 7
718576 4

783155 5
783156 2
783157 9
783158 6
783159 3

198
217
237
257
277

Applications
Hospitals, public buildings, schools, storage buildings, small
industries, department stores, offices... whereever there are dry
environments.
Going through a fire wall
When passing through a fire wall, the ladder must be cut on either
side of the fire barrier.
Loadings
The ladders are tested according to IEC 61537,
test model ll - a joint in the intermediate span (position F2).
Guaranteed load
Guaranteed uniformly distributed load supported by Wibe includes
a minimum safety factor of 1.7 towards rupture. The diagram shows
the deflection with Joint 21 for ladder widths up to 600 mm.

21

Cable ladder KHZSPZ


WEF-0001

KHZSPZ-200
KHZSPZ-300
KHZSPZ-400
KHZSPZ-500
KHZSPZ-600
*EAN-code=732167+Part.no+C (control figure)
The cable ladders must not be used as walkways.

A
mm

B
mm

Hot dip galv.


Part.No. C*

Weight kg
100 m

198
298
398
498
598

164
264
364
464
564

734494 9
734495 6
734496 3
734497 0
734498 7

200
220
240
260
280

Applications
Industrial installations both indoors and outdoors.
Going through a fire wall
When passing through a fire wall, the ladder must be cut on either
side of the fire barrier.
Loadings
The ladders are tested according to IEC 61537,
test model ll - a joint in the intermediate span (position F2).
Guaranteed load
Guaranteed uniformly distributed load supported by Wibe includes
a minimum safety factor of 1.7 towards rupture. The diagram shows
the deflection with Joint 21 for ladder widths up to 600 mm.

22

Cable ladder KHZPS


WEF-0001

A
mm

KHZPS-150
147
KHZPS-200
197
KHZPS-300
297
KHZPS-400
397
KHZPS-500
497
KHZPS-600
597
KHZPS-800
797
KHZPS-1000
997
*EAN-code=732167+Part.no+C (control figure) **Produced to order
The cable ladders must not be used as walkways.

B
mm

Pre-galv.
Part.No. C*

Weight kg
100 m

111
161
261
361
461
561
761
961

725350 0
725351 7
725352 4
725353 1
725354 8
725355 5
781099 4**
725356 2

225
235
255
275
300
315
410
490

Applications
Hospitals, public buildings, schools, storage buildings, small
industries, department stores, offices... whereever there are dry
environments.
Going through a fire wall
When passing through a fire wall, the ladder must be cut on either
side of the fire barrier.
Loadings
The ladders are tested according to IEC 61537,
test model ll - a joint in the intermediate span (position F2).
Guaranteed load
Guaranteed uniformly distributed load supported by Wibe includes
a minimum safety factor of 1.7 towards rupture. The diagram shows
the deflection with Joint 21 for ladder widths up to 600 mm.
For widths greater than 600 mm contact Wibe or distributor.

23

Cable ladder KHZ


WEF-0001

KHZ closed
Closed
A
mm

B
mm

Hot dip galv.


Part. No. C*

Hot dip galv.


Part. No. C*

KHZ-150
147 111
768001 6
726416 2**
KHZ-200
197 161
768002 3
726417 9**
KHZ-300
297 261
768004 7
726419 3**
KHZ-400
397 361
768005 4
726420 9**
KHZ-500
497 461
768006 1
726421 6**
KHZ-600
597 561
768007 8
726422 3**
*EAN-code=732167+Part.no+C (control figure) **Produced to order
The cable ladders must not be used as walkways.

Application
Industrial installations both indoors and outdoors.
KHZ (AISI 316L) for installations e.g. in food industries.
Going through a fire wall
When passing through a fire wall, the ladder must be cut on either
side of the barrier.
Loadings
The ladders are tested according to IEC 61537,
test model ll - a joint in the intermediate span (position F2).
Guaranteed load
Guaranteed uniformly distributed load supported by Wibe includes
a minimum safety factor of 1.7 towards rupture. The diagram shows
the deflection with Joint 21 for ladder widths up to 600 mm.

24

Closed
Stainl. steel
(AISI316L)
Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 m

727376 8**
727377 5**
727378 2**
727379 9**
727380 5**
727381 2**

714058 9
714059 6
714061 9
714062 6
714063 3
714064 0

270
280
300
320
340
360

Cable ladder KHZP


WEF-0001

KHZP-150
KHZP-200
KHZP-300
KHZP-400
KHZP-500
KHZP-600
KHZP-800
KHZP-1000

L
mm
6000
6000
6000
6000
6000
6000
6000
6000

A
mm
147
197
297
397
497
597
797
997

B
mm
111
161
261
361
461
561
761
961

KHZP-150
3000
147
111
KHZP-200
3000
197
161
KHZP-300
3000
297
261
KHZP-400
3000
397
361
KHZP-500
3000
497
461
KHZP-600
3000
597
561
KHZP-800
3000
797
761
KHZP-1000
3000
997
961
*EAN-code=732167+Part.no+C (control figure) **Produced to order

Hot dip galv.


Part. No. C*
718562 7
718563 4
718564 1
718565 8
718566 5
718567 2
721960 5
718568 9
783516 4**
783517 1**
783518 8**
783519 5**
783520 1**
783521 8**
783522 5**
783523 2**

Stainl. steel
(AISI316L)
Part. No. C*
727382 9
727383 6
727384 3
727385 0
727386 7
727387 4
782128 0**
782129 7**

ZINKPOX
White
Part. No. C*
718591 7
718592 4
718593 1
718594 8
718595 5
718596 2
728033 9**
718597 9**

Weight kg
100 m
260
270
290
315
340
360
490
560

783524 9**
783525 6**
783526 3**
783527 0**
783528 7**
783529 4**
783530 0**
783531 7**

260
270
290
315
340
360
490
560

The cable ladders must not be used as walkways.


Application
Industrial installations both indoors and outdoors.
Going through a fire wall
When passing through a fire wall, the ladder must be cut on either
side of the fire barrier.
Loadings
The ladders are tested according to IEC 61537,
test model ll - a joint in the intermediate span (F2).
Guaranteed load
Guaranteed uniformly distributed load supported by Wibe includes
a minimum safety factor of 1.7 towards rupture. The diagram shows
the deflection with Joint 21 for ladder widths up to 600 mm.
For widths greater than 600 mm contact Wibe or distributor.

25

Cable ladder KHZV


WEF-0001

A
mm

B
mm

KHZV-200
197
161
KHZV-300
297
261
KHZV-400
397
361
KHZV-500
497
461
KHZV-600
597
561
*EAN-code=732167+Part.no+C (control figure)
The cable ladders must not be used as walkways.

Hot dip galv.


Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 m

712015 4
712017 8
712019 2
712018 5
712020 8

714198 2
714200 2
714202 6
714201 9
714203 3

440
460
480
500
530

Application
The ladder is designed for extreme support distances and loadings.
Going through a fire wall
When passing through a fire wall, the ladder must be cut on either
side on the fire barrier.
Loadings
The ladders are tested according to IEC 61537,
test model ll for bracket distance up to and including 4 m,
test type V for bracket distance more than 4 m.
Guaranteed load
Guaranteed uniformly distributed load supported by Wibe includes
a minimum safety factor of 1.7 towards rupture. The diagram shows
the deflection for ladder widths up to 600 mm.

26

Cable ladder KHZPV


WEF-0001

A
mm

B
mm

Hot dip galv.


Part. No. C*

KHZPV-200
197
160
717982 4
KHZPV-300
297
260
717983 1
KHZPV-400
397
360
717984 8
KHZPV-500
497
460
717985 5
KHZPV-600
597
560
717986 2
KHZPV-1000
997
960
716400 4
*EAN-code=732167+Part.no+C (control figure) **Produced to order
The cable ladders must not be used as walkways.

ZINKPOX
White
Part. No. C*

Weight kg
100 m

723390 8**
723391 5**
723392 2**
723393 9**
723394 6**
716401 1**

426
448
470
493
515
703

Application
The ladder is designed for extreme support distances and loadings.
Going through a fire wall
When passing through a fire wall, the ladder must be cut on either
side on the fire barrier.
Loadings
The ladders are tested according to IEC 61537,
test model ll for bracket distance up to and including
4 m, test type V for bracket distance more than 4 m.
Guaranteed load
Guaranteed uniformly distributed load supported by Wibe includes
a minimum safety factor of 1.7 towards rupture. The diagram shows
the deflection for ladder widths up to 600 mm.
For widths greater than 600 mm contact Wibe or distributor.

27

Suspension components

40

16

31
39
40
33

32
39

25

26
12
11

30
17
17

30
29

11

16

25
24

24

10
9

15

24

20

4 3

16

23

40

21

15
23

4 6 39

22
6
7
8

28

17
38

38

38

Suspension components _____________________

14
28
13

44

36

41

37
5

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44

Page

Cantilever arm 50i _______________________


30
Cantilever arm 30________________________
31
Cantilever arm 50L, 50, 50F _______________
32
Profile clamp 42 _________________________
34
Back plate 40 ___________________________
35
Support bracket 3________________________
38
Support bracket 6________________________
41
Support bracket HSO_____________________
40
Vertical piece 2FPK ______________________
43
Vertical piece 2 _________________________
44
Vertical piece 2F ________________________
46
Vertical piece 20 ________________________
48
Vertical piece 20F _______________________
50
Vertical piece 20FS ______________________
52
Pendant/Fixing rail 24/34 __________________
54
Pendant/Fixing rail 24/48 __________________
55
Pendant/Fixing rail 24/20 __________________
57
Pendant/Fixing rail 24/20F _________________
58
Pendant/Fixing rail 24/20FS________________
59
Pendant joint 2J _________________________
74
Pendant joint 2FJ ________________________
74
Pendant joint 20J ________________________
74
Threaded rod M10W76 ___________________
42
Ceiling bracket TF-10, TF-16 _______________
60
Ceiling bracket 5 ________________________
61
Pendant base plate 520 ___________________
62
Rail fixing support 24/20F, 24/20FS__________
69
Ceiling plate 20F, 20FS ___________________
71
Pendant bar 1 __________________________
75
Bracket 60/40___________________________
75
Beam clamp 5BK ________________________
63
Ceiling bracket 5TP ______________________
64
Ceiling bracket 5TPA _____________________
65
Angle bracket 5L ________________________
72
Angle bracket 5LS _______________________
72
Wall bracket 20, 20F _____________________
70
Wall bracket 11/25, 11/75 _________________
84
End plug 28E, 28D, 28C, 28F ______________
86
Screw sets _____________________________
130
T-bolts ________________________________
133
Round bar fixing for ceilings________________
67
Round bar fixing for walls__________________
68
Round bar fixing for floors _________________
68
Clamp set M6___________________________
132
Fixings - expansion bolts, concrete screws ____ 137-152

37
3
42

43
19
18

27

34,35

29

Cantilever arm 50i


Used for lighter mountings on walls, vertical pieces or pendant/fixing rails.

WEF-0001
10,5 x 20
20

Plate thickness 1.5 mm


B=100

B=200

B=300

B=400

For ladder width


mm

L
mm

Cantilever arm 50i-100


100
150
Cantilever arm 50i-200
200
250
Cantilever arm 50i-300
300
350
Cantilever arm 50i-400
400
450
*EAN-code=732167+Part.no+C (control figure) **Produced to order

H1
mm

H2
mm

Pre-galv.
Part. No. C*

Pre-galv.
White
Part. No. C*

Weight kg
100 pcs

80
85
110
115

32
28.5
33.5
31

791412 8
791413 5
791414 2
791415 9

791416 6**
791417 3**
791418 0**
791419 7**

19
29
46
83

Use and installation

Installation of cantilever arm


mounted to wall using Expansion
bolt M8.
Breaking load - see below.

Installation of cantilever arm


using T-bolt M8 on Fixing rail
24/26 x 53 for casting-in or
Pendant/Fixing rail mounted on
the wall.

Breaking load F

Cantilever arm 50i-100


Cantilever arm 50i-200
Cantilever arm 50i-300
Cantilever arm 50i-400

30

Mounted on wall
kg
230
215
220
335

Installation of cantilever arm


Cable ladder KHZSP mounted
using T-bolt M8 on vertical piece. on Cantilever arm 50i, Profile
Check breaking load of vertical
clamp 42 is used.
piece.

Cantilever arm 30
For installation inside cable ladder KHZSP

WEF-0001
11 x 22
27

185

80

Cantilever arm 30-200


Cantilever arm 30-300
Cantilever arm 30-400
Cantilever arm 30-500
Cantilever arm 30-600
*EAN-code=732167+Part.no+C (control figure)

A
mm

Pre-galv.
Part. No. C*

Weight kg
100 pcs

184
284
384
484
584

727777 3
727778 0
727779 7
727780 3
727781 0

90
110
120
140
160

Use and installation

Installation of cable ladder


KHZSP. Place the ladder on the
outer tab and press it over the
inner tab. When necessary, the
ladder can be locked with a Profile clamp 43.

Installation on Vertical piece 2F.


Cable ladder KHZSP can be
adjusted max 40 mm.

Installation direct on wall. Cable


ladder KHZSP is adjustable from
015 mm to the wall.

Breaking load for cantilever arm


on wall, see table below.

When you mount cable ladders


that are 500-600 mm wide it
might be necessary with a reinforcement of the outer edge of
the cantilever arm. Installation
band and stretching screw can
be used for mounting in the ceiling or on a vertical piece.

Loading table
Cantilever arm type

Max load F on cantilever arm


at a deflection of 3
kN
kg

30-200
30-300
30-400
30-500
30-600

2.0
1.9
1.2
0.8
0.6

200
190
120
80
60

Deflection at 3 deflection
of cantilever arm
mm

Breaking load
kN

kg

10
15
20
26
31

2.3
3.5
3.0
2.4
2.0

230
350
300
240
200

31

0
0

Cantilever arm 50L,50


and 50F
For mounting on walls, pendant/fixing rails or vertical pieces.

Cantilever arm 50L and 50


50L,50/100-300 50L,50/400-600
40

D x 19

50

WEF-0001

50/700-1000
50

D x 19

D x 19
28

20
20
H

Cantilever arm 50F


50F/200-600
D x 19

60

9 x 26

D x 19

25
20
H
F

15

A
mm

D
mm

F
mm

H
mm

T
mm

Hot dip galv.


Part. No. C*

150
200
250
298
348
447
548
646
150
200
250
300
350
450
550
650
750
850
950
1050
245
345
445
547
647
1052

12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
14
14
14

34
36
39
56
60
70
77
84
34
36
39
56
60
70
77
84
90
95
100
105
72
79
86
93
100
160

85
85
85
105
105
120
140
150
85
85
85
105
105
120
140
150
150
160
160
170
148
175
175
180
180
240

4
4
4
4
4
5
6
6
4
4
4
6
6
8
8
10
10
10
10
10
8
8
8
10
10
12

725105 6
725106 3
725107 0
725108 7
725109 4
725110 0
725111 7
725112 4
723432 5
723433 2
723434 9
723435 6
723436 3
723437 0
723438 7
723439 4
727125 2
727126 9
727127 6
727128 3
718624 2
718625 9
718626 6
718627 3
718628 0
712465 7

*EAN-code=732167+Part.no+C (control figure) **Produced to order

32

9 x 36

50F/1000

50

15

50L-100
50L-150
50L-200
50L-250
50L-300
50L-400
50L-500
50L-600
50-100
50-150
50-200
50-250
50-300
50-400
50-500
50-600
50-700
50-800
50-900
50-1000
50F-200
50F-300
50F-400
50F-500
50F-600
50F-1000

9 x 26

25
20
D

20
H

21

50

25

25
20

Stainl. steel
(AISI316L)
Part. No. C*

725618 1
725619 8
725620 4
725621 1
725622 8
725623 5
725624 2
725625 9

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

725113 1**
725114 8**
725115 5**
725116 2**
725117 9**
725118 6**
725119 3**
725120 9**
723440 0
723441 7
723442 4
723443 1
723444 8
723445 5
723446 2
723447 9
727782 7**
727783 4**
727784 1**
727785 8**
714021 3
714700 7
714022 0
718793 5
714023 7
714024 4

24
28
34
46
54
103
160
191
24
28
34
52
60
118
172
215
270
310
350
390
95
125
170
220
250
770

Cantilever arm 50L,50


and 50F
Use and installation

Installation of a cantilever arm to


a wall using an Expansion bolt.
Breaking load see below.

Installation of a cantilever arm


using a T-bolt on a Fixing rail
24/26 x 53 rail for casting-in or
Pendant/Fixing rails mounted on
the wall.
Breaking load see below.

Mounting of a cantilever arm


using a T-bolt on a Pendant/
Fixing rail mounted on a wall.

Installation of a cantilever arm


using T-bolt with vertical pieces.
Breaking load see below.
Also check breaking load of the
vertical piece.

Profile clamp 43 is used for


attaching a KHZV onto a
Cantilever arm 50F.

For attaching a KHZSP, KHZ,


KHZPS or KHZP cable ladder,
mount Profile clamp 42. If it is
only necessary to fix the cable
ladder at the outer end of the
bracket, use selftapping sheet
screws or suchlike with 5 mm
dia. holes in the bracket and in
the side section.

Cantilever arm 50F mounted


upside down can be used for
installation of tilted protective
roofs.

Use Cantilever arm 50/700-1000


as support when cable ladders
have to pass columns etc.

Breaking load F
F

Type of cantilever arm


50L-100
50L-150
50L-200
50L-250
50L-300
50L-400
50L-500
50L-600
50-100
50-150
50-200
50-250
50-300
50-400
50-500
50-600
50-700
50-800
50-900
50-1000
50F-200
50F-300
50F-400
50F-500
50F-600
50F-1000

Mounted on P/F rail 24/48


with T-bolt 26F

Mounted on wall
kN
1.5
1.5
1.5
2.0
2.0
3.0
3.0
3.0
3.0
3.0
2.5
4.0
4.0
6.5
7.0
7.0
6.0
5.5
5.3
5.0
10.0
10.0
11.0
10.0
10.0
11.0

kg
150
150
150
200
200
300
300
300
300
300
250
400
400
650
700
700
600
550
530
500
1000
1000
1100
1000
1000
1100

kN
1.5
1.5
1.5
2.0
2.0
3.0
3.0
3.0
3.0
3.0
2.5
4.0
4.0
6.5
7.0
7.0
5.5
5.2
4.8
4.2
10.0
10.0
9.0
8.0
8.0
8.0

kg
150
150
150
200
200
300
300
300
300
300
250
400
400
650
700
700
550
520
480
420
1000
1000
900
800
800
800

33

Profile clamp 42
For installation where the cable ladder is to be fixed to
cantilever arms, support brackets etc.

Pre-galv.
Part. No. C*

Profile clamp 42
721121 0
(screw M8 + nut supplied)
*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Hot dip galv.


Part. No. C*

Stainl. steel
(AISI316L)
Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

705611 8

725763 8

714164 7

11

Use and installation

Use Profile clamp 42 for attaching


KHZSP, KHZPS, KHZ and KHZP to
Cantilever arm 50 and Support
bracket 3. For small loads, mount the
ladder with a clamp on each cantilever arm, alternately right side and
left side.

For installation of KHZSP, KHZPS,


KHZ and KHZP on Support bracket
3, Profile clamp 42 is used.

To lock Angle plate 33/2, fit 2 Profile


clamps 42.

Cable ladders can be mounted


directly on Vertical piece 20 or 20F
with Profile clamp 42.
Use T-bolt for mounting.
Convenient at vertical installations in
shafts.

Profile clamp 43
For installation where cable ladder KHZV and KHZPV is to be
fixed to cantilever arms, support brackets etc.

Profile clamp 43 (screw M8+nut supplied)


*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Hot dip galv.


Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

707511 9

714165 4

Use and installation

Use Profile clamp 43 to attach


KHZV/KHZPV to Cantilever arm 50.
For small loads, mount the ladder
with a clamp on each cantilever
arm, alternating right side and left
side.

34

Pendant/Fixing rail 24/48, mounted


under Cable ladder KHZV with Profile clamp 43, here used as carrier of
lighting fittings.

Back plate 40
For installation behind Cantilever arm 50 to reduce the surface
pressure on porous walls.

WEF-0001

60
20
14,5
150

Plate
thickness
mm

Back plate 40
6
*EAN-code=732167+Part.no+C (control figure)

Hot dip galv.


Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

768738 1

714029 9

55

Use and installation

Mount Back plate 40 as shown


in the illustration to reduce the
surface stress on porous walls.

By using Back plate 40, a cantilever arm can be mounted on the


side of Vertical piece 20F.

Mounting rail 40
For installation behind Cantilever arm 50 to reduce the surface
pressure on porous walls.
The rail permits vertical adjustment of the cantilever arm.

Hot dip galv.


Part. No. C*

Mounting rail 40
717001 2
*EAN-code=732167+Part.no+C (control figure)

WEF-0001

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

717006 7

56

Use and installation

Mounting rails reduce the surface Cables may be mounted on


stress on porous walls.
walls using Mounting rail 40 and
Mount the cantilever arm using T- a suitable Cable clamp Type A.
bolt, which permits height adjustment.

35

Rod bracket 82
Rod bracket 82 is adapted to fit both on Cantilever arm 50 and
on Cantilever arm 80.

Rod bracket 82
*EAN-code=732167+Part.no+C (control figure)
Use and installation

Rod bracket 82 mounted on


Cantilever arm 50. Screw set
22S and Profile clamp 42 are
to be used.

36

Rod bracket 82 mounted on


Cantilever arm 80. Screw set
22S and Profile clamp 42 are
to be used.

WEF-0001

Hot dip galv.


Part. No. C*

Weight kg
100 pcs

786768 4

360

Suspension components

37

Support bracket 3
Used for centre installation of cable ladders on
pendant/fixing rails and vertical pieces.

Pre-galv.
Part. No. C*

WEF-0001

Hot dip galv.


Part. No. C*

Support bracket 3-150


720761 9
Support bracket 3-200
721869 1
720762 6
Support bracket 3-300
721870 7
720763 3
Support bracket 3-400
721871 4
720764 0
Support bracket 3-500
721872 1
720765 7
Support bracket 3-600
721873 8
720766 4
* EAN-code=732167+Part.no+C (control figure) **Produced to order

Stainl. steel
(AISI316L)
Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

726433 9**
726434 6
726435 3
726436 0
726437 7**
726438 4

721862 2
721863 9
721864 6
721865 3
721866 0**
721867 7

26
33
58
78
120
145

Stainless steel AISI 316L

3/150-200

3/300-600
L
Support bracket 3-150
150
Support bracket 3-200
200
Support bracket 3-300
300
Support bracket 3-400
400
Support bracket 3-500
500
Support bracket 3-600
600
Breaking load-symmetrical loading

Stainl. steel
L
154
204
306
406
506
606

70
70
100
150

b
100
100
100
100
140
140

100
100
100

100

Breaking load F

F
2

38

F
2

Support bracket 3-150


Support bracket 3-200
Support bracket 3-300
Support bracket 3-400
Support bracket 3-500
Support bracket 3-600

kN

kg

16
16
16
12
12
10

1600
1600
1600
1200
1200
1000

Support bracket 3
Use and installation

Mount Support bracket 3 on


Vertical piece 2 with Screw
set 22S.

Mount Support bracket 3 on


Vertical piece 2F with Screw
set 22S.

Mount Support bracket 3 on


Pendant/Fixing rail 24/34 with
Screw set 22S.

Mount Support bracket 3 on


Support bracket 3 installed on
Pendant/Fixing rail 24/20 or 24/ Pendant rail 24/20F with Screw
48 with Screw set 22S.
set 2S.

Support bracket 3 can be


mounted on floor or under data
floor with a suitable vertical
piece.

For installation of KHZSP, KHZ,


KHZP and KHZPS on Support
bracket 3 Profile clamp 42 is
used.

When attaching Support bracket


3 using clamp set M6 the tab
must be bent up using a hammer
or pair of pliers.

End bracket HT-11 permits the


mounting of crossing cable
ladders at different levels with
Support bracket 3 mounted on
pendant/fixing rail.

Mount Support bracket 3 on


Vertical piece 20 with Screw
set 20S.

When attaching KHZV/KHZPV to


Support bracket 3, use Profile
clamp 42.

Mount Support bracket 3 on


Vertical piece 20F with Screw
set 2S.

Support bracket 3 mounted on a


rock bolt with Clamp set M6.

39

Support bracket HSO


Support bracket HSO mounted with Threaded rod M10 or
M16 is used for installation of cable ladders.

Support bracket HSO-150 M10


Support bracket HSO-200 M10
Support bracket HSO-300 M10
Support bracket HSO-400 M16
Support bracket HSO-500 M16
Support bracket HSO-600 M16
(Nuts M10, M16 and Washer HSO M16 not included)
*EAN-code=732167+Part.no+C (control figure)

WEF-0001

A
mm

D
mm

Plate
thickness
mm

Hot dip galv.


Part. No. C*

Weight kg
100 pcs

210
260
360
460
560
660

12
12
12
18
18
18

2
2
2
2
2
2

791063 2
791064 9
791065 6
791066 3
791067 0
791068 7

39
48
66
84
103
121

Washer HSO M16 is used for centered mounting with Support bracket HSO M16 and Threaded rod M16.

Washer HSO M16


*EAN-code=732167+Part.no+C (control figure)

Hot dip galv.


Part. No. C*

Weight kg
100 pcs

791092 2

8.7

Use and installation

Support bracket HSO M10


installed with Threaded rod
M10 W76.

40

Centered installation with


Support bracket HSO M10,
widths 150-300, Threaded rod
M10 W76 and 2 Nuts M10.

Centered installation with


Support bracket HSO M16,
widths 400-600, Threaded rod
M16, 2 Nuts M16 and Washer
HSO M16.

Profile clamp 42 is used to attach


the cable ladder to the support
bracket.

Support bracket 6
For centre installation of cable ladder KHZSP. Thickness of material 2.5 mm.

Support bracket 6-200


Support bracket 6-300
Support bracket 6-400
Support bracket 6-500
Support bracket 6-600
*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Pre-galv.
Part. No. C*

Weight kg
100 pcs

170
270
370
470
570

727582 3
727583 0
727584 7
727585 4
727586 1

27
45
63
81
99

Support bracket 6 mounted with


Pendant rail W32, Pendant
attachment W21 and Screw set
W37.

Profile clamp 43 can be used to


fix the cable ladder to the support
bracket.

Use and installation

Support bracket 6 must be


mounted inside cable ladder
KHZSP.

Support bracket 6 mounted with


Threaded rod M10 W76. Nut
M10 must be used.

Breaking load-symmetrical loading

Support bracket 6-200


Support bracket 6-300
Support bracket 6-400
Support bracket 6-500
Support bracket 6-600

Breaking load with


Threaded rod M10 W76
kN
kg
5.0
500
4.8
480
3.0
300
2.2
220
1.7
170

Breaking load with


Pendant attachment W21
kN
kg
3.4
340
3.4
340
3.0
300
2.2
220
1.7
170

41

Threaded rod M10 W76


Threaded rod M10 W76 is used for installations of cable ladders.
Joint nut M10 is used for joining of Threaded rods M10 W76.

WEF-0001

M10

L
mm

Electro-galv.
Part. No. C*

Threaded rod M10 W76-2000


2000
716792 0
Threaded rod M10 W76-3000
3000
716793 7
Joint nut M10
724806 3**
*EAN-code=732167+Part.no+C (control figure) **Produced to order

Stainl. steel
(AISI316)
Part. No. C*

Electro-galv.
White
Part. No. C*

723925 2**
723926 9**
724807 0**

718795 9**
718797 3**

Weight kg
100 pcs

100
150
7.2

Nut M10 for assembling of Threaded rod M10 W76 on Support bracket 6.

Nut M10
*EAN-code=732167+Part.no+C (control figure)

Hot dip galv.


Part. No. C*

Stainl. steel
(AISI316)
Part. No. C*

Weight kg
100 pcs

723938 2

723939 9

1.1

Use and installation

Support bracket 6 mounted with


Threaded rod M10 W76.
Nut M10 must be used.

42

When joining two pieces of


Threaded rod M10 W76 use
Joint nut M10.

Vertical piece 2FPK


For installations in ceilings close to wall.

L
mm

WEF-0001

Hot dip galv.


Part. No. C*

Vertical piece 2FPK-300


280
788655 5
Vertical piece 2FPK-500
500
788656 2
Vertical piece 2FPK-750
730
788657 9
Vertical piece 2FPK-1000
1000
788658 6
*EAN-code=732167+Part.no+C (control figure) **Produced to order

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

788660 9**
788661 6**
788662 3**
788663 0**

120
155
205
250

Loadings

Vertical piece 2FPK mounted in


the inner hole.
Breaking load=1400 kg
(14 kN) at symmetrical loading.

Vertical piece 2FPK mounted in


the outer hole.
Breaking load=200 kg
(2kN) at symmetrical loading.

Deflection of Vertical piece 2FPK


is reduced by installing Pendant
bar 1. Loadings in accordance
with table below.

Max permitted load F at max permitted deflection 1/20 of the length L of the cantilever arm in accordance to standard IEC 61537.
Cantilever arm
Without
Pendant bar 1
With
Pendant bar 1-500

50-200 L=250
50-400 L=450
50-600 L=650
50-200 L=250
50-400 L=450
50-600 L=650

2FPK-300
kg
140
145
105

2FPK-500
kg
130
135
100

2FPK-750
kg
100
95
80
155
165
115

2FPK-1000
kg
80
75
60
125
120
90

Use and installation

Vertical piece 2FPK can be


mounted in ceiling close to wall.

Vertical piece 2FPK mounted


horizontally on wall or vertical
piece as carrier of gypsum
boards.

Vertical piece 2FPK can be used


as carrier of gypsum boards in
order to build in cable ladder
passages.

Vertical piece 2FPK is suitable


for floor mounting.

43

Vertical piece 2
Used for installation of Support bracket 3. Symmetrical loading.
Not suitable for KHZV and KHZPV.
Can be joined to Pendant/Fixing rail 24/34 with Pendant joint 2J.

L
mm

Hot dip galv.


Part. No. C*

WEF-0001

Stainl. steel
(AISI316L)
Part. No. C*

ZINKPOX
White
Part. No. C*

Vertical piece 2-300


279
717191 0
725557 3
716283 3
Vertical piece 2-400
392
717192 7
725558 0
716284 0
Vertical piece 2-500
504
717193 4
725559 7
716285 7
Vertical piece 2-700
729
717194 1
725560 3
716286 4
Vertical piece 2-1000
1022
717195 8
725561 0
716287 1
*EAN-code=732167+Part.no+C (control figure)
Use and installation
At asymmetrical loading of KHZ, KHZP, KHZSP or KHZPS width 600, Vertical piece 2F or 20 must be used.

Mount Vertical piece 2 using an


Expansion bolt alt. Concrete
screw.

44

Mount Vertical piece 2 on a


Fixing rail 24/26x53 for casting-in
using T-bolt.

On beams in ceilings, mount


Vertical piece 2 as in the figure
above. When the beam flange
thickness does not exceed 13
mm, use Beam clamp 5BK-10
and T-bolt 26F/40. For flange
thicknesses not exceeding 30
mm use Beam clamp 5BK-30
and T-bolt 26F/50.

Weight kg
100 pcs

52
62
72
93
120

In ceilings with trapezoidal profile


sheeting, mount Vertical piece 2
as shown above.

Vertical piece 2
Use and installation

WIBE

On Vertical piece 2, mount


Support bracket 3 using Screw
set 22S.

Vertical piece 2 can be joined to


achieve the required length using
Pendant/Fixing rail 24/34 and
Pendant joint 2J.

Cantilever arm 50 can, using End


bracket HT-11, be mounted at
90 to the pendant/fixing rail.
Only for lightweight mounting,
such as data cables and
suchlike.

End bracket HT-11 permits the


mounting of crossing cable ladders at different levels on the
same pendant/fixing rail.
Breaking load

Breaking load for Vertical piece 2


with a symmetrical loading =
1400 kg (14 kN).
See also Breaking load for
Support bracket 3.

45

Vertical piece 2F
Used for installation of Support bracket 3 or Cantilever arm 50.
Can be joined to Pendant/Fixing rail 24/48 with Pendant joint 2FJ.

L
mm

Vertical piece 2F-280


280
Vertical piece 2F-370
370
Vertical piece 2F-505
505
Vertical piece 2F-730
730
Vertical piece 2F-1000
1000
Vertical piece 2F-1500
1495
*EAN=732167+Part.no+C (control figure)

WEF-0001

Hot dip galv.


Part. No. C*

Stainl. steel
(AISI316L)
Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

717196 5
717197 2
717198 9
717199 6
717200 9
787276 3

725562 7
725563 4
725564 1
725565 8
725566 5
787278 7

717201 6
717202 3
717203 0
717204 7
717205 4
787277 0

80
100
130
170
220
290

Breaking load

Loading table
Vertical piece 2F installed as a cantilever arm

Pendant type

Breaking load for Vertical piece 2F Deflection of Vertical piece 2F is


= 2300 kg (23 kN) at symmetrical reduced by installing Pendant bar 1
loading.
alt. Pendant/Fixing rail and Bracket
60/40. Loadings in accordance with
table below.
Max. loading F at 3 deflection of cantilever arm
Cantilever arm
2F-280
type
kN
kg
50-200
1.15 115
Without bar
50-400
1.4
140
50-600
1.25 125
50-200
With bar
50-400
1-300
50-600
50-200
With bar
50-400
1-500
50-600
50-200
With bar
50-400
1-800
50-600

46

2F-370
kN
kg
1.1
110
1.35 135
1.1
110

Ladder width
150
200
300
400
600
2F-505
kN
kg
1.0
100
1.25 125
0.9
90
1.2
120
1.5
150
1.3
130

Vertical piece 2F with


Pendant bar 1-300
2F-730
2F-1000
3
Break.
3
Break.
defl.
load
defl.
load
90
120
60
75
95
125
65
80
100
135
70
90
105
140
75
100

100
120
2F-730
kN
kg
0.9
90
0.85
85
0.7
70
1.0
100
1.1
110
1.0
100
1.2
120
1.4
140
1.25 125

2F-1000
kN
kg
0.8
80
0.6
60
0.55
55
0.85
85
0.65
65
0.6
60
0.95
95
0.8
80
0.7
70
1.35 135
1.25 125
1.2
120

2F-1500
kN
kg
0.38
38
0.35
35
0.30
30

0.71
0.57
0.49
0.72
0.75
0.66

71
57
49
72
75
66

Vertical piece 2F
Use and installation

Mount Vertical piece 2F using


Expansion bolt alt. Concrete
screw.

On Fixing rail for casting- in,


mount Vertical piece 2F using
T-bolt.

On beams in ceilings, mount


Vertical piece 2F as shown in the
figure above. When the beam
flange thickness does not exceed
13 mm, use Beam clamp 5BK-10
and T-bolt 26F/40. For flange
thicknesses not exceeding 30
mm use Beam clamp 5BK-30
and T-bolt 26F/50.

In ceilings with trapezoidal


sheeting, mount Vertical piece 2F
as shown above.

On Vertical piece 2F, mount


Cantilever arm 50 using T-bolt.

On Vertical piece 2F, mount


Support bracket 3 using Screw
set 22S.

Vertical piece 2F can be joined to


achieve the required length using
Pendant/Fixing rail 24/48 and
Pendant joint 2FJ.

Vertical piece 2F may be


equipped with a protective
orange End plug 28E.

Cantilever arm 50 can, using End


bracket HT-11, be mounted at
90 to the pendant/fixing rail.
Only for lightweight installation
of data cable type and suchlike.

Cable ladders mounted on


Vertical piece 2F and Support
bracket 3 can be used for cable
installations in raised access
floors.

For installation on floor the cable


ladders can be mounted with
Vertical piece 2F, Profile clamp
41 and T-bolt.

End bracket HT-11 permits


mounting of crossing cable
ladders on different levels on the
same pendant/fixing rail.

47

Vertical piece 20
Used for vertical installation with Cantilever arm 50 from a ceiling or on a floor.
Can also be installed as a cantilever arm on a wall.
Cable ladders are fixed with profile clamps.

L
mm

Vertical piece 20-505


505
Vertical piece 20-730
730
Vertical piece 20-1000
1000
Vertical piece 20-1500
1495
Vertical piece 20-2000
1990
Vertical piece 20-3000
2980
*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Hot dip galv.


Part. No. C*

Stainl. steel
(AISI316L)
Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

715723 5
715724 2
715725 9
715726 6
715727 3
715728 0

725567 2
725568 9
725569 6
725570 2
725571 9
725572 6

716276 5
716277 2
716278 9
716279 6
716280 2
716281 9

250
330
440
620
800
1180

Use and installation

On fixing rail for casting- in,


mount Vertical piece 20 using
T-bolts.

On beams in ceilings, mount


Vertical piece 20 as shown in the
figure above. When the beam
flange thickness does not exceed
13 mm, use Beam clamp 5BK-10
and T-bolt 26F/40. For flange
thicknesses not exceeding 30
mm use Beam clamp 5BK-30
and T-bolt 26F/50.

In ceilings with trapezoidal profile


sheeting, mount Vertical piece 20
as shown above.

Vertical piece 20 is also suitable


for floor mounting.

Vertical piece 20 can be joined to


achieve the required length using
Pendant/Fixing rail 24/20
and Pendant joint 20J.

Using End bracket HT-11,


Cantilever arm 50 can be
mounted at 90 to the pendant/
fixing rail.
Only for lightweight mounting of
data cable type and suchlike.

Vertical piece 20 may be used for


vertical mounting in a shaft, for
example. Mount Wall bracket 11
or Profile clamp 42 using T-bolts.
The vertical piece may also be
mounted horizontally as a
cantilever arm, such as when
passing columns.

Vertical piece 20 may be


equipped with a protective
orange End plug 28D.

48

Vertical piece 20
Use and installation

Mount Vertical piece 20 using


Expansion bolt.

On vertical piece, mount Canti- On Vertical piece 20, mount


lever arm 50 using T-bolt. For
Support bracket 3 using Screw
loadings see Cantilever arm 50. set 20S.

Breaking load

Symmetrical loading:
Breaking load for vertical piece
= 3000 kg (30 kN).

Asymmetrical loading:
M=FxA
See also max loading for
Cantilever arm 50 installed on
pendant/fixing rail, page Cantilever arm 50L, 50 and 50F.
For values outside diagram please contact Wibe.
Bending torque M is total sum of F x A (kgcm).
F = Cantilever arm loading (kg)
F = Loading (kg/m) x arm distance (m).
A = Distance between loading and pendant
centre line (cm)
A = Ladder width + 7.7 cm
2

Example:
Conditions:
- 2 m bracket distance
- 30 kg/m ladder
- Two ladders, 400 and 600 mm
- One-side loading
- Pendant 20-1000
- Bending?
M = F x A (kgcm)
M = 30 x 2 x (40 + 7.7) + 30 x 2 (60 + 7.7)
2
2
(F1)
(A1)
(F2)
(A2)
M = 3 924 kgcm bending as per diagram, about 6 mm.

Break load torque 19 000 (kgcm)


L=Pendant length

Loading table for Vertical piece 20 installed as a cantilever arm


kg

Pendant type
Width
Ladder type
150
200
300
400
600

Vertical piece 20 with Pendant bar 1-300


20-730
20-1000
20-1500
3
Break.
3
Break.
3
Break.
defl.
load
defl.
load
defl.
load
330
380
180
210
105
155
350
400
200
240
110
160
375
425
225
270
115
165
400
450
250
300
120
170

280
320
130
180

kg

Vertical piece 20 without Pendant bar 1


20-730
20-1000
20-1500
3
Break.
3
Break.
3
Break.
defl.
load
defl.
load
defl.
load
190
230
130
165
70
115
200
250
140
170
70
115
215
280
150
175
75
120
230
310
160
180
80
125
280
370
170
190
90
130

49

Vertical piece 20F


Vertical piece 20F can be mounted from the ceiling or on the floor.
Suitable for rather heavy loadings.

B
mm

C
mm

Vertical piece 20F-1000


50
280
Vertical piece 20F-1500
70
195
Vertical piece 20F-2000
5
195
Vertical piece 20F-3000
70
280
*EAN-code=732167+Part.no+C (control figure)

WEF-0001

L
mm

Hot dip galv.


Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

995
1490
1985
2980

718249 7
718250 3
718251 0
709799 9

718484 2
718485 9
718486 6
716282 6

590
790
990
1240

Use and installation

Mount Vertical piece 20F using


Expansion bolt alt. Concrete
screw.

Floor mounting example.

50

Cantilever arm 50 can be


mounted using T-bolt. For loads
on Cantilever arm 50, see Cantilever arm 50L, 50 and 50F.

Using End bracket HT-11,


Cantilever arm 50 can be
mounted at 90 to the vertical
piece. Only for lightweight
mounting of data cable type or
suchlike.

Vertical piece 20F mounted on


floor can be fixed using Vertical
piece 2 as ceiling bracket,
adjustable in the pendant.

Vertical piece 20F


Loading table

Symmetrical loading
Breaking load for Vertical piece
20F = 5000 kg (50kN)

Asymmetrical loading
Vertical piece 20F mounted in
ceiling, see diagram.

For values outside diagram please contact Wibe.


Bending torque M is total sum of F x A (kgcm).
F = Cantilever arm loading (kg)
F = Loading (kg/m) x arm distance (m).
A = Distance between loading and pendant
centre line (cm)
A = Ladder width + 9.4 cm
2

Example:
Conditions:
- 2 m arm distance
- 50 kg/m ladder
- Two ladders, 400 and 600 mm
- One-side loading
- Pendant 20F-1500
- Bending?

Break load torque 30 000 (kgcm)


L=Pendant length

M = F x A (kgcm)
M = 50 x 2 x (40 + 9.4) + 50 x 2 (60 + 9.4)
2
2
(F1)
(A1)
(F2)
(A2)
M = 6 880 kgcm bending as diagram, about 6 mm.

51

Vertical piece 20FS


The Vertical piece 20FS can be mounted from the ceiling or on the floor.
Suitable for very heavy loadings.

L
mm

Hot dip galv.


Part. No. C*

Vertical piece 20FS-1500


1495
718718 8
Vertical piece 20FS-2000
1990
718719 5
Vertical piece 20FS-2500
2485
718720 1
Vertical piece 20FS-3000
2980
718721 8
*EAN-code=732167+Part.no+C (control figure) **Produced to order

WEF-0001

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

720521 9**
720522 6**
720523 3**
720524 0**

1460
1810
2160
2520

Use and installation

Mount Vertical piece 20FS using


Expansion bolt alt. Concrete
screw.

Mount Cantilever arm 50 using


T-bolt. For loads on Cantilever
arm 50, see Cantilever arm 50L,
50 and 50F.

Using End bracket HT-11, Cantilever arm 50 can be mounted at


90 to the vertical piece. Only for
lightweight mounting of data
cable type or suchlike.

Vertical piece 20FS is suitable for


floor mounting.

52

Vertical piece 20FS


Loading table

Symmetrical loading
Breaking load for Vertical piece
20FS = 5000 kg (50 kN)

Asymmetrical loading
Vertical piece 20FS mounted in
ceiling, see diagram.

For values outside diagram please contact Wibe.


Bending torque M is total sum of F x A (kgcm)
F = Cantilever arm loading (kg)
F = Loading (kg/m) x arm distance (m).
A = Diastance between loading and pendant
centre line (cm)
A = Ladder width + 10.4 cm
2
Break load torque 60 000 (kgcm)
L = Pendant length

Example:
Conditions:
- 2 m arm distance
- 75 kg/m ladder
- Two ladders, 400 and 600 mm
- One-side loading
- Pendant 20FS-1500
- Bending?
M = F x A (kgcm)
M = 75 x 2 x (40 + 10.4) + 75 x 2 (60 + 10.4)
2
2
(F1)
(A1)
(F2)
(A2)
M = 10 620 kgcm bending as per diagram, about 5 mm.

53

Pendant/Fixing rail 24/34


For mounting of support brackets, cantilever arms etc.

WEF-0001

Transverse force

Pendant/Fixing rail 24/34

L2
mm

Pre-galv.
Part. No. C*

P/F-rail 24/34
292.5
725357 9
P/F-rail 24/34
382.5
725358 6
P/F-rail 24/34
495
725359 3
P/F-rail 24/34
697.5
725360 9
P/F-rail 24/34
990
725361 6
P/F-rail 24/34
2970
721102 9
*EAN-code=732167+Part.no+C (control figure)

lx

Wx

ly

Wy

2.17 cm4

1.03 cm3

0.36 cm4

0.39 cm3

Hot dip galv.


Part. No. C*

Stainl. steel
(AISI316L)
Part. No. C*

715879 9

725574 0
725575 7
725576 4
725577 1
725578 8
725579 5

ZINKPOX
White
Part. No. C*

Weight kg
100 st

716309 0

23
31
40
56
80
240

Use and installation

WIBE

Vertical piece 2 may be joined to


Pendant/Fixing rail 24/34 and
Pendant joint 2J to achieve a
suitable length.

54

Ceiling bracket 5 and 1 Screw


set 22S together provide a
vertical piece that can be
mounted with up to 20 slope.

Mount Support bracket 3 using


Screw set 22S.

Side mounting of pendant/fixing


rails may be done using 2
Expansion bolts alt. 2 Concrete
screws.

Pendant/Fixing rail 24/48


For mounting of support brackets, cantilever arms etc.

Plate thickness
mm

lx

7.93 cm4

Pendant/Fixing rail 24/48

L6
mm

WEF-0001

Pre-galv.
Part. No. C*

Hot dip galv.


Part. No. C*

P/F-rail 24/48
2970
731717 2
705093 2
P/F-rail 24/48
5940
731721 9
731719 6
*EAN-code=732167+Part.no+C (control figure) **Produced to order

Transverse force
Wx
3.30 cm3

ly

Wy

2.23 cm4

1.52 cm3

Stainl. steel
(AISI316L)
Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

728595 2
731727 1**

716306 9
731724 0**

520
1120

Use and installations

Vertical piece 2F may be joined


using Pendant/Fixing rail 24/48
and Pendant joint 2FJ to achieve
the required length.

Ceiling bracket 5 and 1 Screw


set 22S together provide a
vertical piece that can be
mounted with up to 20 slope.
Only for mounting support
brackets.

Mount Support bracket 3 using


Screw set 22S.

Mount Cantilever arm 50 using


T-bolt.

Cables are mounted on a


Pendant/Fixing rail 24/48 using
cable clamps of type A.

55

Fixing rail 24/26x53


for casting-in
For casting-in in walls and ceilings.

WEF-0001

lx

Fixing rail 24/26 x 53 for casting-in

10.39 cm4

Transverse force
Wx
ly
3
3.92 cm
2.78 cm4

Wy

Hot dip galv.


Part. No. C*

Weight kg
100 pcs

1.90 cm3

768063 4

970

*EAN-code=732167+Part.no+C (control figure)


Use and installation

Fixing rail 24/26 x 53 for castingin in walls and ceilings. Mount


cantilever arms with T-bolt 26F.

Max. pull-out load:


1000 kg/ 0.5 m of casting-in
fixing rail (Concrete class K200).

Fixing rail JSA 24/26x48 for


casting-in
For casting-in in walls and ceilings. Filled with cellular plastic to prevent concrete piercing into the rail.

Pre-galv.
Part. No. C*

Fixing rail JSA 24/26 x 48 for casting-in


Strap iron JSA (13 pcs/rail)
*EAN-code=732167+Part.no+C (control figure)

732468 2

WEF-0029

Hot dip galv.


Part. No. C*

Weight kg
100 pcs

732227 5

700
13

Use and installation

50

Push the strap iron JSA through


the loop of the rail and bend to
required shape before embedment.

56

Take away the cellular plastic


with a tool (screwdriver etc)
where the T-bolt shall be
mounted.

Cantilever arms must be mounted with T-bolt 26F. Max


permissible extraction force: 1000 kg/0.25 m rail when every second
loop is equipped with strap iron. The first and the last loop, however,
must always be equipped with strap iron. (Concrete class K25).

Pendant/Fixing rail 24/20


For mounting of support brackets, cantilever arms etc.

WEF-0001

Transverse force

Pendant/Fixing rail 24/20

lx

Wx

ly

Wy

15.86 cm4

6.62 cm3

11.50 cm4

4.10 cm3

Pendant/Fixing rail 24/20


*EAN-code=732167+Part.no+C (control figure)

Hot dip galv.


Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

709795 1

716307 6

1130

Use and installation

Vertical piece 20 may be joined


using Pendant/Fixing rail 24/20
and Pendant joint 20J. Only for
symmetrical loading.

Mount Cantilever arm 50 using


T-bolt.

Mount Support bracket 3 using


Screw set 20S.

Pendant/Fixing rail 24/20 may be


mounted as a riser between the
floor and ceiling using 4 Angle
brackets 5L and 4 T-bolts.

Cable ladder may be mounted


vertically or horizontally on
Pendant/Fixing rail 24/20 using
Wall bracket 11/25 or 11/75 and
T-bolt.

Pendant base plate 520 can be


mounted as a ceiling or floor
attachment.

Pendant/Fixing rail can be


mounted on beam or wall with
Wall bracket 20.

57

Pendant/Fixing rail 24/20F


For mounting of support brackets, cantilever arms etc.

WEF-0001

Transverse force

Pendant/Fixing rail 24/20F

lx

Wx

ly

Wy

15.86 cm4

6.62 cm3

44.00 cm4

9.89 cm3

L
mm

Pendant/Fixing rail 24/20F-3000


2970
Pendant/Fixing rail 24/20F-6000
5940
*EAN-code=732167+Part.no+C (control figure) **Produced to order

Hot dip galv.


Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

709798 2
718808 6

716308 3**
720525 7**

1160
2370

Use and installation

WIBE

Mount Cantilever arm 50 using


T-bolt.

Mount Support bracket 3 using


Screw set 2S.

Pendant/Fixing rail 24/20F can


be mounted on beam or wall with
Wall bracket 20F.

Pendant/Fixing rail 24/20F can


be mounted as a riser between
the ceiling and floor using 4
Angle brackets 5L and 4 T-bolts.

Mount Pendant/Fixing rail 24/20F


between a floor and ceiling using
2 Rail fixing supports.

Cable ladder can be mounted


vertically or horizontally on Pendant/Fixing rail 24/20F using Wall
bracket 11/25 or 11/75.

58

Pendant/Fixing rail 24/20FS


For mounting of cantilever arm etc.

WEF-0001

Transverse force

Pendant/Fixing rail 24/20FS

lx

Wx

ly

Wy

30.20 cm4

12.55 cm3

85.00 cm4

16.20 cm3

L
mm

Pendant/Fixing rail 24/20FS


5940
*EAN-code=732167+Part.no+C (control figure) **Produced to order

Hot dip galv.


Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

709031 0

720526 4**

4200

Use and installation

Mount Cantilever arm 50 using


T-bolt.

Pendant/Fixing rail 24/20FS can


be mounted as a riser between
the ceiling and floor using 4
Angle brackets 5L and 4 T-bolts.

Mount Pendant/Fixing rail


24/20FS between floor and
ceiling using 2 Rail fixing
supports.

Cable ladders can be mounted


vertically or horizontally on
Pendant/Fixing rail 24/20FS
using Wall bracket 11/25 or 11/75
and T-bolt.

59

Ceiling bracket TF
For installation with Threaded rods.

WEF-0001

TF-10

TF-16

Ceiling bracket TF-10 (nut M10 incl.)


Ceiling bracket TF-16 (nut M16 incl.)
*EAN-code=732167+Part.no+C (control figure)
Use and installation

Ceiling bracket TF-10 or TF-16


installed with Threaded rod M10
or M16.

60

Hot dip galv.


Part. No. C*

Weight kg
100 pcs

788164 2
788165 9

15
30

Ceiling bracket 5
For installation with Pendant/Fixing rails 24/34 and 24/48.

Pre-galv.
Part. No. C*

WEF-0001

Hot dip galv.


Part. No. C*

Stainl. steel
(AISI316L)
Part. No. C*

ZINKPOX
White80
Part. No. C*

Weight kg
100 pcs

718640 2

725573 3

716293 2

35

Ceiling bracket 5 (screw excl.)


721101 2
* EAN-code=732167+Part.no+C (control figure)
Use and installation

Max 20

Using Pendant/Fixing rail 24/34


or 24/48, 1 Ceiling bracket 5 and
1 Screw set 22S it is possible to
make a vertical piece that can be
installed at an angle of up to 20.
Breaking load for rail 34:
1000 kg (10 kN).
Breaking load for rail 48:
1200 kg (12 kN).

Mount Ceiling bracket 5 to the


back of the pendant/fixing rail by
turning the ceiling bracket 90
and inserting the tab into the hole
in the rail. Then turn the ceiling
bracket back and lock it in the
required position using 1 Screw
set 22S.
When mounting it at a horizontal
ceiling, lock the screw in the slot
recess for better lateral stability.
Ceiling bracket 5 can be tilted
max. 20.

Pendant/Fixing rail 24/20 can,


using 2 Ceiling brackets 5 and 2
T-bolts, be mounted between
floor and ceiling (see also Angle
bracket 5L).

Pendant/Fixing rail 24/20F can,


using 4 Ceiling brackets 5 and 4
T-bolts, be mounted between
floor and ceiling (see also Angle
bracket 5L).

61

Pendant base plate 520


Used as a ceiling or floor base plate for Pendant/Fixing rail 24/20 in any desired length.

Pendant base plate 520 (4 Screws MVBF 8x80 and nuts incl.)
*EAN-code=732167+Part.no+C (control figure) **Produced to order
Anvndning och montage

Vertical pieces of the required


length can be mounted using
Pendant base plate 520 and
Pendant/Fixing rail 24/20.
Screws and nuts are included.

62

WEF-0001

Hot dip galv.


Part. No. C*

ZINKPOX
White80
Part. No. C*

Weight kg
100 pcs

718253 4

718488 0**

400

Beam clamp 5BK


For installation of Vertical pieces 2, 2F or 20 on I-beams.

Beam clamp 5BK-10 (for flange thickness max 13 mm)


Beam clamp 5BK-30 (for flange thickness 14-30 mm)
*EAN-code=732167+Part.no+C (control figure)

WEF-0001

A
mm

Hot dip galv.


Part. No. C*

ZINKPOX
White80
Part. No. C*

Weight kg
100 pcs

30
50

715675 7
718243 5

716294 9
718487 3

15
18

Use and installation

On ceiling beams, mount


Vertical piece 2, 2F or 20 using
2 Beam clamps 5BK, Pendant/
Fixing rail 24/48 and Screw set
22S. For Beam clamp 5BK-10,
use T-bolts 26F/40.
For Beam clamp 5BK-30, useTbolts 26F/50.

Alternatively, a Pendant/Fixing
rail 24/20 may be used. This will
require 4 T-bolts.

63

Ceiling bracket 5TP


For installation of Vertical pieces 2, 2F and 20 in ceilingswith a trapezoidal sheet profile.

Pre-galv.
Part. No. C*

Ceiling bracket 5TP


725362 3
*EAN-code=732167+Part.no+C (control figure)

Hot dip galv.


Part. No. C*

ZINKPOX
White80
Part. No. C*

Weight kg
100 pcs

713153 2

716295 6

12

Use and installation

In ceilings with trapezoidal


sheeting, mount Vertical piece 2,
2F or 20 using 2 Ceiling brackets
5TP, Pendant/Fixing rail 24/48,
2 T-bolts and Screw set 22S.

64

WEF-0001

Alternatively Pendant/ Fixing rail


24/20 may be used. This will
require the use of 4 T-bolts.

Ceiling bracket 5TPA


Used for mounting in trapezoid plate.

Ceiling bracket 5TPA


(screw MVBF 8x16 + nut M6MF8 incl.)
*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Pre-galv.
Part. No. C*

Hot dip galv.


Part. No. C*

Pre-galv.
White80
Part. No. C*

Weight kg
100 pcs

732177 3

733487 2

733486 5

14

Breaking load

Ceiling bracket 5TPA can be


loaded with F=150 kgs without
deformation. As to loading
figures for thin plate or fixing
elements, please follow the
suppliers recommendations.

Use and installation

Ceiling bracket 5TPA can be


mounted in trapezoid plate with
blind rivets or suitable screws.
The bracket is adjustable from 35
to 95 mm.

Pendant attachment W21 or


Tube pendant attachment W73
can be mounted in Ceiling
bracket 5TPA with the existing
screw.

Install Mounting rail 40 between


2 Ceiling brackets 5TPA if the
vertical piece must be adjusted
sideways.

Pendant M8 or M10 W76


installed in Ceiling bracket 5TPA.

Ceiling bracket 5 or Ceiling


attachment W31 can be mounted
with the existing screw.

Vertical piece 2 or 2F can be


mounted with the existing screw.

65

Combi bracket 53
Used for mounting cable ladders and trays on seamed roofing sheet etc.

WEF-0001,-0031

Hot dip galv.


Part. No. C*

Combi bracket 53
Insulating plate 54
*EAN-code=732167+Part.no+C (control figure)

Plastic
Part. No. C*

Weight kg
100 pcs

787223 7

26
2

782353 6

Breaking load*
Type of roofing sheet

Insulating plate

Permitted load

Bandsheet Prelac
Copper sheeting
Bandsheet Prelac
Copper sheeting

No
Yes
No
Yes

F1=100 kg
F2=50 kg
F3=100 kg
F4=50 kg

* Loading values and fixing of roof sheet - follow the suppliers recommendations
Test have been made of:
Bandsheet Prelaq BLX t=0.6 SSAB tunnplt
Copper sheeting annealed SS 5015-80 t=0.6
Tightening torque at test=60Nm
Use and installation

Combi bracket 53 mounted on


seamed roofing sheet.

Alternative mounting of Combi


bracket 53.

In order to avoid contact between


Combi bracket 53 and copper
sheeting, Insulating plate 54
must be used.

Alternative mounting of Combi


bracket 53 and Insulating plate
54.

Cable ladder mounted across the


seams of the roofing sheets with
Combi bracket 53, Wall bracket
11/25 and Screw set 22S.

Cable ladder mounted along the


seams of the roofing sheets with
Combi bracket 53, Wall bracket
11/25, Screw set 22S, Pendant/
Fixing rail 24/48 and T-bolt 26F.

Wire tray mounted along the


seams of the roofing sheets
with Combi bracket 53 and
accessories from the Wire tray
programme.

Wire tray mounted across the


seams of the roofing sheets
with Combi bracket 53 and
accessories from the Wire tray
programme.

66

View - Round bar fixings

Round bar fixing for ceilings


Fixing suitable for ribbed bars 15-25 mm.

Round bar fixing for ceilings


*EAN-code=732167+Part.no+C (control figure) **Produced to order

WEF-0001

Hot dip galv.


Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

718311 1

718489 7**

120

Use and installation

Round bar fixing for ceilings.


Suitable for ribbed bars 15-25
mm. Mounted on Support
bracket 3 with Screw set 22S.

67

Round bar fixing for floors


Fixing suitable for ribbed bars 15-25 mm.

Round bar fixing for floors


*EAN-code=732167+Part.no+C (control figure) **Produced to order

WEF-0001

Hot dip galv.


Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

718312 8

718490 3**

90

Use and installation

Fixing suitable for ribbed bars


15-25 mm.

Round bar fixing for floors.


Mounted on pendant/fixing rail
with T-bolts.

Round bar fixing for walls


Fixing suitable for ribbed bars 15-25 mm.

Round bar fixing for walls


*EAN-code=732167+Part.no+C (control figure)
Use and installation

Round bar fixing for walls.


Mounted on pendant/fixing rail
with T-bolts.

68

WEF-0001

Hot dip galv.


Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

718313 5

718491 0

86

Rail fixing support


Used with Pendant/Fixing rails 24/20F and 24/20FS
for mounting between floor and ceiling.

A
mm

WEF-0001

B
mm

C
mm

Rail fixing support 24/20F


100
165
135
Rail fixing support 24/20FS
120
185
155
*EAN-code=732167+Part.no+C (control figure) **Produced to order

Hot dip galv.


Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

718850 5
718851 2

720527 1**
720528 8**

167
190

Use and installation

Simple mounting between floor


and ceiling using 2 Rail fixing
supports 20F or 20FS.
1. Mount one of the rail fixing
supports in the ceiling.
2. Adjust the pendant length.
3. Mount the rail fixing support
for floor mounting on the
pendant.
4. Insert the pendant in the rail
fixing support in the ceiling.
5. Attach the bottom rail fixing
support securely to the floor.

69

Wall bracket 20
To be used at installation of Pendant/Fixing rail 24/20 to ceiling beam or wall.

Wall bracket 20
*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Hot dip galv.


Part. No. C*

Weight kg
100 pcs

723450 9

47

Use and installation

For cable ladder installations


along a beam. Pendant/Fixing
rail 24/20 must be mounted with
2 Wall brackets 20 and 2 T-bolts
26F-30 placed in the centre outlet. This installation is also used
for fixing to wall.
Max vertical load 700 kg (7 kN).

For cable ladder installations


across a beam. Pendant/Fixing
rail 24/20 shall be mounted with
2 Wall brackets 20 and 2 T-bolts
26F-30 in the side-outlets.

Wall bracket 20F


To be used at installation of Pendant/Fixing rail 20F to ceiling beam or wall.

Wall bracket 20F


*EAN-code=732167+Part.no+C (control figure)
Use and installation
Pendant/Fixing rail 24/20 F must
be mounted with 2 Wall brackets
20F and 2 T-bolts 26F-30 for
cable ladders along beams.
This installation is also used for
fixing to wall.
Max. vertical load 700 kg (7 kN).

70

WEF-0001

Hot dip galv.


Part. No. C*

Weight kg
100 pcs

723451 6

69

Ceiling plate 20F


Ceiling plate 20F is used as a pre-drilled attachment for Vertical piece 20F to a steel member.
The ceiling plate is welded in position.

Ceiling plate 20F


*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Hot dip galv.


Part. No. C*

Weight kg
100 pcs

718849 9

200

Use and installation

The ceiling plate is welded to the


steel member. Permission to weld on
the steel member is required.
Remove all zinc at the
weld. Post-treat using Galvafroid.

Use Ceiling plate 20F as a fully


drilled attachment for Vertical piece
20F against a steel member. Secure
the ceiling plate by welding. Remove
all zinc at the weld. Post-treat using
Galvafroid.

Ceiling plate 20FS


Ceiling plate 20FS is used as a pre-drilled attachment for Vertical piece 20FS to a steel member.
The ceiling plate is welded in position.

Ceiling plate 20FS


*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Hot dip galv.


Part. No. C*

Weight kg
100 pcs

720536 3

310

Use and installation

The ceiling plate is welded to the


steel member. Permission to weld on
the steel member is required.
Remove all zinc at the weld. Posttreat using Galvafroid.

Use Ceiling plate 20FS as a fully


drilled attachment for Vertical piece
20FS against a steel member.
Secure the ceiling plate by welding.
Remove all zinc at the weld.
Post-treat using Galvafroid.

71

Angle bracket 5L and 5LS


Used when assembling pendant/fixing rails to frames for switching cabinets and electrical
control centres. For fixing an upright between floor and ceiling. Assembled with a T-bolt.

WIB

WEF-0001

Angle bracket 5L

Angle bracket 5LS


Plate
thickness
mm

Hot dip galv.


Part. No. C*

Angle bracket 5L
4.0
731791 2
Angle bracket 5LS
6.0**
709801 9
*EAN-code=732167+Part.no+C (control figure)
**Plate thickness for Stainl. steel (AISI316L) is 5 mm.

Stainl. steel
(AISI316L)
Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

731793 6
725636 5

731792 9
720529 5

15
50

Use and installation

Installation examples for installation of pendant/fixing rails to different frameworks for installation of control panels, electric distribution boards, etc. Use Angle bracket 5L.

Mounting of a pendant/fixing rail


against a floor with Angle bracket
5L or 5LS.

72

Angle bracket 5L can be


mounted inside the ladder profile
and thus be used as an end
connection against wall or floor.

Mounting of a pendant/fixing rail


on a wall. Use Angle bracket 5L
or 5LS.

End bracket HT-11


Used for assembling pendant/fixing rails to frames for switching cabinets and electrical control centres.
Also suitable for assembling pendant rails for crossing cable runs.

End bracket HT-11


*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Plate
thickness
mm

Hot dip galv.


Part. No. C*

Weight kg
100 pcs

4.0

717618 2

41

Use and installation

The HT-11 can be used when


mounting together 2 Pendant/
Fixing rails 24/34, for example
when assembling a stand.

The HT-11 can be used when


mounting together 2 Pendant/
Fixing rails 24/48 with the
opening towards the attachment,
for example when assembling a
stand.

The HT-11 can be used when


mounting together 2 Pendant/
Fixing rails 24/48, with the rear
towards the attachment.

End bracket HT-11 permits


mounting of crossing cable
ladders in various planes on
the same vertical piece.

Cantilever arm 50 may, using


End bracket HT-11, be mounted
at 90 to the vertical piece. Only
for lightweight mounting of data
cable type or suchlike.

End bracket HT-11 must be


installed on ceiling beams with
Expansion bolts.

73

Pendant joint 2J, 2FJ and 20J


Used for joining pendant/fixing rails and vertical pieces.

Pendant joint 2J

WEF-0001

Pendant joint 2FJ


Pre-galv
Part. No. C*

Hot dip galv.


Part. No. C*

Pendant joint 2J
721119 7
713177 8
Pendant joint 2FJ
713178 5
Pendant joint 20J
713173 0
2J and 2FJ: 4 screw M8x16 + nuts incl,
20J: 4 screw M8x70 + nuts incl.
Powder coated joints have screws+nuts of stainless steel (AISI 316L)
*EAN-code=732167+Part.no+C (control figure)
Use and installation
2J

For joining of Vertical piece 2 and


Pendant/Fixing rail 24/34.

74

2FJ

For joining of Vertical piece 2F


and Pendant/Fixing rail 24/48.

Pendant joint 20J


Stainl. steel
(AISI316L)
Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

726484 1
726485 8

716303 8
716304 5
716302 1

43
46
94

20J

For joining of Vertical piece 20


and Pendant/Fixing rail 24/20.
Only for symmetrical loading.

Pendant bar 1
Installed in order to reduce the deflection of long Vertical pieces 2F, 20 and 20F.

Pendant bar 1/300-800

WEF-0001

Pendant bar 1-1500


A
mm

B
mm

Pendant bar 1-300


80
300
Pendant bar 1-500
130
500
Pendant bar 1-800
215
800
Pendant bar 1-1500
May vary
*EAN-code=732167+Part.no+C (control figure) **Produced to order

Hot dip galv.


Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

717640 3
717641 0
717642 7
718903 8

717643 4**
717644 1**
717645 8**
720530 1**

50
80
125
560

Use and installation

To reduce deflection of Vertical


piece 2F at heavy loads on
Cantilever arm 50 the Pendant
bar 1 can be used. Install with
T-bolt and Expansion bolt.

To be mounted to strengthen
Vertical piece 20 when mounted
horizontally. Use T-bolt and
Expansion bolt.

Mount this stay to reduce


deflection of long Vertical pieces
2F, 20 and 20F.

Bracket 60/40
To be used with Pendant/Fixing rail 24/48 to reduce deflection of long vertical pieces.

Plate
thickness
mm

Bracket 60/40
3.0
*EAN-code=732167+Part.no+C (control figure) **Produced to order

WEF-0001

Hot dip galv.


Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

718904 5

720531 8**

10

Use and installation

Use Bracket 60/40 together with Pendant/Fixing rail 24/48 to


reduce the deflection of long Vertical pieces 2F, 20, 20F or 20FS.
Cut the pendant/fixing rail to a suitable length on site.

75

Ceiling mesh tray WN2


For installation in ceilings. Wire 4.4 mm.

WEF-0001

2000

Electro-galv.
Part. No. C*

Hot dip galv.


Part. No. C*

Ceiling mesh tray WN2


100 60
727991 3
727992 0**
*EAN-code=732167+Part.no+C (control figure) **Produced to order

Stainl. steel
(AISI316)
Part. No. C*

Electro-galv.
White
Part. No. C*

Weight kg
100 pcs

727993 7**

727994 4**

100

Use and installation

Mounted in ceilings with Ceiling


bracket WN16.

Mounted under cable ladders


with Ceiling bracket WN16 and
Screw set W37 or Screw set 2S.

Mounted under desks with


Ceiling bracket WN16.

Ceiling bracket WN16


For installation of Ceiling mesh tray WN2.

Electro-galv.
Part. No. C*

WEF-0001

Hot dip galv.


Part. No. C*

Ceiling bracket WN16


727995 1
727996 8**
*EAN-code=732167+Part.no+C (control figure) **Produced to order
Use and installation

Ceiling mesh tray WN2 must be


mounted with Ceiling bracket
WN16.

76

Ceiling mesh tray WN2 mounted


under cable ladders with Ceiling
bracket WN16 and Screw set
W37 or Screw set 2S.

Stainl. steel
(AISI316)
Part. No. C*

Electro-galv.
White
Part. No. C*

Weight kg
100 pcs

727997 5**

727998 2**

77

Joint 21
For straight, rigid joining of cable ladders, bends, junctions and risers.
Plate thickness = 2 mm. See also values for potential balancing.

Pre-galv.
Part. No. C*

Hot dip galv.


Part. No. C*

Joint 21
791196 7
791199 8
(M6 screw included)
*EAN-code=732167+Part.no+C (control figure) **Produced to order

WEF-0001

Pre-galv.
White
Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

791197 4**

791200 1

46

Stainless steel AISI316L

Joint 21
(M6 screw included)
*EAN-code=732167+Part.no+C (control figure)

Stainl. steel
(AISI316L)
Part. No. C*

Weight kg
100 pcs

725751 5

37

Use and installation

Joint 21 is used for straight, robust joining of cable ladders and when
fitting 90 bends, T- and X-branches, vertical bends and for vertical
ladder mounting. It also reduces the transition resistance and prevents the ladders from slipping apart.

78

Joint 9
For straight joining of KHZ, KHZP and KHZPS.

Pre-galv.
Part. No. C*

WEF-0001

Hot dip galv.


Part. No. C*

ZINKPOX
White80
Part. No. C*

Weight kg
100 pcs

705304 9

714066 4

16

Joint 9
721115 9
*EAN-code=732167+Part.no+C (control figure)
Use and installation

Joint 9 is used in straight joints of


KHZ, KHZP and KHZPS.
NOTE! The teeth shall face
downwards as shown in the
figure. Under load, the ladders
are prevented from slipping
apart. If the joint is above a
bracket, the teeth should face
upwards.

Intermediate connection bolt 29


Used at the transition from a broad to a narrower KHZ.

WEF-0001

Bolt diam x length


mm

Hot dip galv.


Part. No. C*

Weight kg
100 pcs

M10 x 235
M10 x 335
M10 x 435
M10 x 535
M10 x 635

705392 6
705394 0
705395 7
705396 4
705397 1

14
19
24
29
34

Intermediate connection bolt 29-200


Intermediate connection bolt 29-300
Intermediate connection bolt 29-400
Intermediate connection bolt 29-500
Intermediate connection bolt 29-600
*EAN-code=732167+Part.no+C (control figure)
Use and installation

Intermediate connection bolts are


used for changing from a broad
toa narrower ladder. The broader
ladders last rung is cut to permit
the narrower ladder to fit in.
The intermediate connection bolt
is mounted through the rungs of
the KHZ ladder.

Intermediate connection bolts


can also be used for transition
from one wide ladder to two
narrower ones.

Intermediate connection bolt also


permits formation of angles.

79

Dropper joint 32
A dropper joint to form vertical branches in centre position under/on top of cable ladders.

Dropper joint 32 (screw M6 incl)


*EAN-code=732167+Part.no+C (control figure) **Produced to order

WEF-0001

Hot dip galv.


Part No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

734713 1

780874 8**

75

Use and installation

May also be used together with


Riser 18 to form vertical
branches on top of Cable ladder
KHZ, KHZP, KHZSP, KHZSPZ
and KHZPS.

To be used together with Riser


18 to form vertical branches
under Cable ladder KHZ, KHZP,
KHZSP, KHZSPZ and KHZPS.

Reducer 31
For transition joining from a wide to a narrower cable ladder.

A
mm

Reducer 31-100
100
Reducer 31-200
200
Reducer 31-300
300
Reducer 31-400
400
*EAN-code=732167+Part.no+C (control figure) **Produced to order

WEF-0001

Hot dip galv.


Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

734171 9
734172 6
734173 3
734174 0

735433 7**
735434 4**
735435 1**
735436 8**

43
59
74
89

Use and installation

To be installed in the ladder


profile and used together with
1 Joint 19 or 21 at one-side
transition joining of KHZ, KHZP,
KHZSP, KHZSPZ and KHZPS.

80

May also be used at centered


transition joining.

Coupling 22
Used for horizontal or vertical branches at any desired angle.

Pre-galv.
Part. No. C*

Coupling 22
721122 7
*EAN-code=732167+Part.no+C (control figure)
**Stainless steel screws and nuts are used

WEF-0001

Hot dip galv.


Part. No. C*

ZINKPOX
White**
Part. No. C*

Stainl. steel
(AISI316L)
Part. No. C*

Weight kg
100 pcs

718409 5

718410 1

725760 7

21

Use and installation

Coupling 22 is used for horizontal branching to the required angle.


The cut length of the ladder ends determines the angle.
Angle plate 33 is always recommended for horizontal branches.
Mount Profile protection 28P. To be cut when required.

Coupling 22 is used to form vertical angles of the required size.

Coupling 22 is used to form vertical branches of the required angle.


Mount Profile protection 28P. To be cut when required.

Use 4 Coupling 22 to form a horizontal bend in different angles.


The cut lengths of the ladder ends determine the angle.

As an alternative at transition
joining of KHZSP, KHZPS, KHZ
and KHZP use 1 Joint 21 and
2 Couplings 22.

Clamp 12 and one part of


Coupling 22 can be used for
branching under the cable
ladder - allowing angles from
0-180.

Vertical branching under the


cable ladder with one part of
Coupling 22 and plate screw.

Use 2 Coupling 22 for vertical


branching under the cable
ladder.
Note! The screw of Coupling 22
must be turned so that its head
will be placed against the side
profile of the cable ladder. Bend
the coupling with a screwdriver
according to the above.

81

Fixed take-off hook 4


Used for 90 horizontal branches.

WEF-0001

Alum.
Part. No. C*

Fixed take-off hook 4


709017 4
*EAN-code=732167+Part.no+C (control figure)

Alum.
White
Part. No. C*

Weight kg
100 pcs

714067 1

Use and installation

Fixed take-off hook 4 is used at


90 horizontal branches.
Coupling 22 can also be used for
straight angle formation.

KHZSP, KHZSPZ, KHZPS, KHZ


and KHZP can be used to form
90 angles from KHZV/KHZPV
using Fixed take-off hook 4.
Mount Profile protection 28P.

5 mm dia. hole for any locking


against the section using
sheet screws or blind rivets.

Angle plate 33 is always


recommended at horizontal
branches.

End connection 10
Used for the connection of a ladder vertically to a floor, or horizontally to a wall.

End connection 10
*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Alum.
Part. No. C*

Alum.
White
Part. No. C*

Weight kg
100 pcs

709018 1

714085 5

Use and installation

The End connection 10 is


mounted at the ladder end
vertically against floors or
horizontally against walls.

82

Mount the End connection 10


using Expansion bolts.

Max. tilt permitted = 3 mm before


tightening the screw.

Profile clamp 41
Profile clamp 41 is used to install a pendant/fixing rail or
mounting plate etc. on the cable ladder profile.

Pre-galv.
Part. No. C*

Profile clamp 41
725363 0
*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Hot dip galv.


Part. No. C*

ZINKPOX
White
Part. No. C*

Stainl. steel
(AISI316L)
Part. No. C*

Weight kg
100 pcs

720824 1

721945 2

783374 0

10

Use and installation

Mounting of pendant/fixing rail on


cable ladder profile.
Use Screw set 22S.

Installation of mounting plate for


apparatuses.
Use Screw set 22S.

Mounting cable ladder on floor


pendants.
Use T-bolts against the opening
of the fixing rail.

Mounting of cable ladders on wall


pendants, such as in shafts.
Use T-bolts against the opening
of the fixing rail.

83

Wall bracket 11/25 and 11/75


For vertical or horizontal installation of cable ladders against a wall.

WEF-0001

11/75

11/25
A
mm

Pre-galv.
Part. No. C*

Wall bracket 11/25


25
721105 0
Wall bracket 11/75
75
721106 7
(Screw MVBF 8x40+nut incl) **Screw+nut in AISI316L
*EAN-code=732167+Part.no+C (control figure)

Hot dip galv.


Part. No. C*

Stainl. steel
(AISI316L)
Part. No. C*

ZINKPOX
White**
Part. No. C*

Weight kg
100 pcs

713204 1
713203 4

725774 4
725775 1

713208 9
713207 2

24
30

Use and installation

Vertical mounting (max load-F)


Wall bracket 11/25: 300 kg (3 kN)
Wall bracket 11/75: 300 kg (3 kN)
When mounting against a rung the max load is
500 kg (5 kN) for wall bracket 11/25.
Horizontal mounting (max load-F)
Wall bracket 11/25: 250 kg (2.5 kN)
Wall bracket 11/75: 100 kg (1.0 kN)

Mount wall brackets


against walls using Expansion
bolts.

Pendant/fixing rails can be


mounted on cable ladders using
wall brackets for mounting equipment cubicles etc.
Mount wall brackets on
Pendant/fixing rails using Screw
set 22S.

Cross member plug 27


Cross member plugs are installed in the ends of the rungs of
KHZ and KHZV in premises with a high corrosion risk.

Cross member plug 27


*EAN-code=732167+Part.no+C (control figure)

WEF-0018

Grey plastic
Part. No. C*

Weight kg
100 pcs

726668 5

0.15

Use and installation

Mount Cross member plug 27


in KHZ and KHZV rung tube
ends in premises with high
relative humidity where the risk
of corrosion is great.

84

End plug 28/28i


Mount in ladder ends for sealing or protection.

WEF-0003 and 0024

End plug 28

End plug 28i

End plug 28
End plug 28i
*EAN-code=732167+Part.no+C (control figure)

White plastic
Part. No. C*

Red plastic
Part. No. C*

Weight kg
100 st

735446 7

709019 8
731994 7

0.8
0.4

Use and installation

Mount End plug 28 in ladder


ends as protection.

Mount End plug 28i inside the


ladder ends for sealing.
Joining with Joint 19 or 21 can be
made with End plug 28i left in the
ladders ends.

Profile protection 28P


Increases the contact surface of the cables, when pulled over
the side profile of the ladder.

Profile protection 28P


*EAN-code=732167+Part.no+C (control figure)

WEF-0012

Grey plastic
Part. No. C*

Weight kg
100 pcs

732151 3

80

Use and installation

Mount Profile protection 28P in order to increase the contact surface


of the cable, when pulled over the side profile of the ladder. Cut when
required.

Profile protection 28P can be cut


in suitable lengths and equipped
with an information label. Easy to
mount on the ladder side profile.

85

End plug 28C,D,E and F


Used for mounting in pendant ends to provide protection against personal injury.

End plug 28C


End plug 28D
End plug 28E
End plug 28F
*EAN-code=732167+Part.no+C (control figure)

WEF-0003

Orange plastic
Part. No. C*

Weight kg
100 pcs

789875 6
709020 4
709021 1
789876 3

0.5
1
0.5
4

Use and installation

End plug 28F fits Vertical piece


20FS and Pendant/Fixing rail
24/20FS.
End plug 28D fits Vertical piece
20 and Pendant/Fixing rail 24/20.

End plug 28C fits Vertical piece 2


and Pendant/Fixing rail 24/34.
End plug 28E fits Vertical piece
2F and Pendant/Fixing rail 24/48.

Angle plate 33
Angle plates are always recommended with 90 horizontal T-junctions.
Suitable for all Wibe cable ladders.

Angle plate 33/1

WEF-0001

Angle plate 33/2

Stainl. steel
(AISI316L)
Part. No. C*

Pre-galv.
White
Part. No. C*

Angle plate 33/1


768733 6
727340 9
Angle plate 33/2
721114 2
707748 9
727197 9
*EAN-code=732167+Part.no+C (control figure) **Produced to order

714030 5**

Pre-galv.
Part. No. C*

Hot dip galv.


Part. No. C*

Use and installation

Angle plates are always


recommended at 90 horizontal
junctions.

86

To lock Angle plate 33/2,


fit Profile clamp 42.

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

714168 5**

50
90

90 bend 15
The cable ladders are joined to the bend with Joint 21.

WEF-0001

Interior

90bend 15-150
90bend 15-200
90bend 15-300
90bend 15-400
90bend 15-500
90bend 15-600
90bend 15-800
90bend 15-1000

R
mm

A
mm

268
268
268
268
268
268
268
268

547
597
697
797
897
997
1197
1397

Pre-galv***
Part. No. C*

723061 7
723062 4
723063 1
723064 8
723065 5

Hot dip galv.


Part. No. C*

Stainl. steel
(AISI316L)
Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

716066 2
716067 9
716069 3
716070 9
716071 6
716072 3
721961 2
716073 0

727346 1
727347 8
727348 5
727349 2
727350 8
727351 5
783376 4
783377 1

716074 7**
716075 4**
716077 8**
716078 5**
716079 2**
716080 8**
728043 8**
716081 5**

220
240
290
340
390
440
640
760

Hot dip galv.


Part. No. C*

Stainl. steel
(AISI316L)
Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

727352 2**
727353 9**
727354 6**
727355 3**
727356 0**
727357 7**

716186 7**
716187 4**
716189 8**
716190 4**
716191 1**
716192 8**
728052 0**
728053 7**

320
370
460
550
640
760
1060
1280

Exterior

90bend 15-150
90bend 15-200
90bend 15-300
90bend 15-400
90bend 15-500
90bend 15-600
90bend 15-800
90bend 15-1000

R
mm

A
mm

554
604
704
804
904
1004
1204
1404

703
933
1133
1333
1533
1733
2133
2533

Pre-galv.
Part. No. C*

716179 9**
716180 5
716182 9
716183 6
716184 3
716185 0
723057 0
723260 4

*EAN-code=732167+Part.no+C (control figure) **Produced to order


***Pre-galv. bends have open side profiles.
Note! R and A must be reduced with 5 mm for bends of stainless steel.
Use and installation

Join cable ladder to 90 bend


using Joint 21.

87

Junction coupling 14
For T-and X-junctions. Suits cable ladder KHZ, KHZP, KHZSP,
KHZSPZ and KHZPS all ladder widths.

WEF-0001

WIBE

Pre-galv.
Part. No. C*

Hot dip galv.


Part. No. C*

Junction coupling 14
723212 3
725096 7
*EAN-code= 732167+Part.no+C (control figure) **Produced to order

Stainl. steel
(AISI316L)
Part. No. C*

Pre-galv.
White
Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

727195 5

723213 0**

790906 3

49

Use and installation


For T-junctions, use 2 Junction
couplings 14.
A bracket should be placed
under the connecting ladder
close to the connection. Profile
protection 28P is recommended.
To be cut to required length.

For X-junctions, use 4 Junction


couplings 14.
A bracket should be placed
under the connecting ladders
close to the connection. Profile
protection 28P is recommended.
To be cut to required length.

T-junction 16
The cable ladders are joined to the T-junction with Joint 21.

A
mm

L
mm

Hot dip galv.


Part. No. C*

T-junction 16-150
547
944
716193 5
T-junction 16-200
597
997
716194 2
T-junction 16-300
697
1097
716196 6
T-junction 16-400
797
1197
716197 3
T-junction 16-500
897
1297
716198 0
T-junction 16-600
997
1397
716199 7
T-junction 16-800
1197
1597
721962 9**
T-junction 16-1000
1397
1797
716200 0
*EAN-code=732167+Part.no+C (control figure) **Produced to order
Use and installation

Join the cable ladders to


T-junction using Joint 21.

88

WEF-0001

Stainl. steel
(AISI316L)
Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

727358 4**
727359 1
727360 7
727361 4
727362 1
727363 8
783378 8
783379 5

716201 7**
716202 4**
716204 8**
716205 5**
716206 2**
716207 9**
783380 1
716208 6**

300
320
390
440
530
600
750
860

X-junction 17
The cable ladders are joined to the X-junction with Joint 21.

X-junction 17-150
X-junction 17-200
X-junction 17-300
X-junction 17-400
X-junction 17-500
X-junction 17-600
X-junction 17-800
X-junction 17-1000
*EAN-code=732167+Part.no+C (control figure) **Produced to order

WEF-0001

A
mm

Hot dip galv.


Part. No. C*

547
997
1097
1197
1297
1397
1597
1797

716209 3
716210 9
716212 3
716213 0
716214 7
716215 4
721963 6**
716216 1

ZINKPOX
White
Part. No. C*

716217 8**
716218 5**
716220 8**
716221 5**
716222 2**
716223 9**
716224 6**

Weight kg
100 pcs

380
400
500
550
600
860
1070
1220

Use and installation

Join the cable ladders to the


X-junction using Joint 21.

89

Riser 18
The cable ladders are joined to the Riser with Joint 21.

Hot dip galv.


Part. No. C*

Riser 18-150
718176 6
Riser 18-200
718177 3
Riser 18-300
718179 7
Riser 18-400
718180 3
Riser 18-500
718181 0
Riser 18-600
718182 7
Riser 18-800
721964 3
Riser 18-1000
718183 4
*EAN-code=732167+Part.no+C (control figure) **Produced to order
Use and installation

Join the cable ladders to


Riser 18 using Joint 21.

90

WEF-0001

Stainl. steel
(AISI316L)
Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

727370 6
727371 3
727372 0
727373 7
727374 4**
727375 1

718184 1**
718185 8**
718187 2**
718188 9**
718189 6**
718190 2**
728034 6**
718191 9**

180
190
210
230
250
270
310
350

S-bend 67
To be used as a transition between cable ladders mounted on different levels.

S-bend 67
*EAN-code=732167+Part.no+C (control figure) **Produced to order

WEF-0001

Hot dip galv.


Part. No. C*

Weight kg
100 pcs

788638 8**

70

Use and installation

S-bend 67 can be mounted vertically or horizontally between cable


ladders by using Dropper joint 32 or Joint 21.

If necessary, mount End plug 28


at the end of the ladder profiles.

91

Joint 45
Fitted as a joining plate in a cut KHZV/KHZPV ladder.

WEF-0001

13

20 35

Joint 45 (screws M8 och M12 + nuts are supplied)


*EAN-code=732167+Part.no+C (control figure)

Hot dip galv.


Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

707609 3

714227 9

50

Use and installation

3
2

2
3

Cable ladders can be joined


using separate joints:
Cut the ends clean. Place the
joints outside the ladders and
mark where the holes shall be
drilled. Drill 9 mm dia. holes.

- Insert the joint plates into the


ladders and bolt them fast.

The holes are laterally displaced


to avoid play in joints.
If the ladders are mounted with
arch pipes downwards, use holes
1 and 3.

The holes are laterally displaced


to avoid play in joints.
If the ladders are mounted using
arch pipes facing upwards, use
holes 1 and 2.

Take-off hook 47
Used on KHZV/KHZPV ladders to make 90 branches.

Take-off hook 47 (screw M12 + nuts are supplied)


*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Hot dip galv.


Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

791350 3

791401 2

27

Use and installation

Use Take-off hook 47 to make


90 branches.

92

The extra hole, 4.5, is to be


used when earthing is demanded
or if vertical locking of the ladder
is needed. A self-drilling screw
must be used.

Profile support piece 46


Fitted between the ladder and the vault pipe when a support bracket
is positioned between existing profile support pieces.

Profile support piece 46


(screw MVBF8x16+nut are supplied)
*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Hot dip galv.


Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

708001 4

714179 1

15

Use and installation


If a support bracket is placed
between two profile support
pieces, a Profile support piece 46
must be mounted between the
arch pipes and the ladder.
If the load amounts to half the
permitted load, Profile support
piece 46 may be excluded.

Profile support piece 46 can be


installed as a fixing for different
applications.

Riser coupling 49
Fitted at a 90 vertical coupling.

WEF-0001

Riser coupling 49-200


Riser coupling 49-300
Riser coupling 49-400
Riser coupling 49-500
Riser coupling 49-600
Riser coupling 49-1000
*EAN-code=732167+Part.no+C (control figure) **Produced to order

Hot dip galv.


Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

716389 2
716390 8
716391 5
720517 2
716392 2
716393 9**

716395 3**
716396 0**
716397 7**
720518 9**
716398 4**
716399 1**

220
230
240
245
250
280

Use and installation

Mount Riser coupling 49 to form


a 90 branch on KHZV/KHZPV.
This provides a large radius for
cables.
Mount it using 2 Screw sets M12,
Part. No. 706415.

93

90 bend 55
Fitted at a 90 horizontal coupling of KHZV and KHZPV.

A
mm

WEF-0001

Hot dip galv.


Part. No. C*

90 bend 55-200
625
716241 3
90 bend 55-300
725
716243 7
90 bend 55-400
825
716244 4
90 bend 55-500
925
716245 1
90 bend 55-600
1025
716246 8
90 bend 55-1000
1425
716247 5
*EAN-code=732167+Part.no+C (control figure) **Produced to order

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

716248 2**
716250 5**
716251 2**
716252 9**
716253 6**
716254 3**

510
560
620
680
750
1110

Use and installation

For joining to KHZV and KHZPV,


use Screw set M12,
Part. No. 706415.

T-junction 56
Fitted at a T-junction of KHZV and KHZPV.

A
mm

WEF-0001

L
mm

Hot dip galv.


Part. No. C*

T-junction 56-200
625
1050
716255 0
T-junction 56-300
725
1150
716257 4
T-junction 56-400
825
1250
716258 1
T-junction 56-500
925
1350
716259 8
T-junction 56-600
1025
1450
716260 4
T-junction 56-1000
1425
1850
716261 1
*EAN-code=732167+Part.no+C (control figure) **Produced to order
Use and installation

For joining to KHZV and KHZPV,


use Screw set M12,
Part. No. 706415.

94

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

716262 8**
716264 2**
716265 9**
716266 6**
716267 3**
716268 0**

710
790
840
940
1010
1300

Screw set M12


Used for all joints with KHZV and KHZPV.

Screw set M12 (4 bolts M6S 12x25 and 4 nuts M6M 12)
*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Hot dip galv.


Part. No. C*

Stainl. steel
(AISI316L)
Part. No. C*

Weight kg
100 pcs

706415 1

728767 3

20

Use and installation

For joining ladders.

For joints with Riser coupling 49.

For joints with 90 bend 55 and


T-junctions 56.

Lighting bracket 200


Used for the installation of lighting fittings beneath KHZV/KHZPV 200.

Lighting bracket 200


*EAN-code=732167+Part.no+C (control figure) **Produced to order

WEF-0001

Hot dip galv.


Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

718643 3

718644 0**

16

Use and installation

5 mm
Mount Lighting bracket 200 for KHZV/KHZPV between the two lower
tubes. If necessary, 5 mm dia. holes can be used for locking against
the arch tube by means of blind rivets or sheet screws.

95

Coupling 44
For horizontal coupling of KHZV/KHZPV. Also used for branches
and as an end connection against a wall.

Coupling 44 (4 screws M8x30+nuts incl)


*EAN-code=732167+Part.no+C (control figure) **Produced to order

WEF-0001

Hot dip galv.


Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

720815 9

720816 6**

50

Use and installation

Coupling 44 may be bent to the


required angle in a vice, using an
adjustable spanner or suchlike.

Use Coupling 44 as a drilling


pattern on the cut ladder.
Drill 9 mm dia. holes.

Assemble the cut and drilled


ladders using M8x30 mm bolts.
If the angle unit is mounted
against a fixed joint plate use
Screw set M12.

Straight branch.

Angled branch.

Use Coupling 44 as an end


attachment for mounting ladders
against walls or floors.

96

Horizontal angle formation.


Angled cutting of the ladder ends
determines the angle.

Coupling 51
Used as self-supporting vertical coupling of KHZV/KHZPV.

WEF-0001

Screw set M12 for installation on the cable ladder is to be ordered separately.
Hot dip galv.
Part. No. C*

Coupling 51
731837 7
2 screws M12+nuts incl. ***Screws+nuts of stainless steel AISI 316L
*EAN-code=732167+Part.no+C (control figure) **Produced to order

ZINKPOX
White***
Part. No. C*

Stainl. steel
(AISI316L)
Part. No. C*

Weight kg
100 st

731911 4

731914 5**

150

Use and installation

Coupling 51. Used as selfsupporting vertical coupling


of KHZV/KHZPV. Rising.
Adjustable from 10 to 90
gradually in steps of 20.

Coupling 51. Used as selfsupporting vertical coupling


of KHZV/KHZPV. Sloping.
Adjustable from 10 to 90
gradually in steps of 20.

1. Install the plates on the


ladder with Screw set M12.

2. Assemble the ladders in the


3. Move the nut in the centre hole
centre hole with one of the
to the opposite outer hole
included screws/nuts.
and tighten.
Adjust to desired angle and fix
the installation in one of the
outer holes with screw/nut.

97

Junction box plate 35P


Installed between rungs. Locked with appropriate locking tabs for each ladder.

WEF-0001

Unholed

Junction box plate

Pre-galv.
Part. No. C*

35P
718618 1
35P unholed
*EAN-code=732167+Part.no+C (control figure)

Hot dip galv.


Part. No. C*

731745 5

Use and installation

Mount junction box plates


between the ladder rungs.
On KHZSP, KHZSPZ, KHZP and
KHZPS attach junction box
plates by bending the central tab
into the rung perforation using a
screwdriver or suchlike.

98

Stainl. steel
(AISI316L)
Part. No. C*

Mount junction box plates on


KHZ and KHZV by bending the
two outer tabs towards the round
rung using a screwdriver or suchlike.

Pre-galv.
White
Part. No. C*

714510 2
725777 5

Weight kg
100 pcs

28
24

Junction box plate 35S


Installed upright or hanging from the profile. Locked with locking tabs.

WEF-0001

Unholed

Junction box plate

Pre-galv.
Part. No. C*

35S
711205 0
35S unholed
730245 1
*EAN-code=732167+Part.no+C (control figure)

Hot dip galv.


Part. No. C*

Stainl. steel
(AISI316L)
Part. No. C*

Pre-galv.
White
Part. No. C*

Weight kg
100 pcs

731746 2

725776 8

716318 2
730246 8

22
23

Use and installation

Bend the tab towards the ladder


section by using a screwdriver as
a lever for mounting junction box
plates.

Junction box plates can be


mounted in standing or hanging
positions on the side sections.
Strain-relief may be provided
using the outermost holes and
clamps or strips.

Light fittings can also be


mounted on junction box plates.

Earth clamp W79


The earth clamp is used when protective earthing of the junction box plate is required.

Earth clamp W79


*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Electro-galv.
Part. No. C*

Weight kg
100 pcs

716640 4

0.2

Use and installation


Earth clamps are designed for use when protective earthing of the
mounting plate is required for mounting apparatuses as per
relevant heavy current directives. The oblong holes in the junction
box plate (mounting plate) permit movement of the earth clamp so
that it always comes under the casing of the apparatus.
If the apparatuss earth clamp is not approved for joining protective
earth conductors, it must pass unbroken through the apparatuss
earth clamp to the junction box earth clamp (see the fig.).
Wibe junction box plates and earth clamps have been approved by
the National Electrical Inspectorate 85 05 13 as per designation
S24-138/85.

99

Installation plate 60
Large installation plate which can be mounted standing or hanging between the ladder rungs.
Clamp set not included.

Pre-galv.
Part. No. C*

Hot dip galv.


Part. No. C*

Installation plate 60
730387 8
730388 5
Clamp set M6-20SF (only in stainless steel (AISI 316L) Part. No. 725 587 0)
*EAN-code=732167+Part.no+C (control figure) **Produced to order

WEF-0001

Pre-galv.
White
Part. No. C*

730389 2**

Weight kg
100 pcs

270
4

Use and installation

To be used when several outlets and junction boxes must be


mounted on the same junction box plate.

Outlets and junction boxes can easily be pre-mounted and


connected. When the plate is mounted on the cable ladder only
connecting of incoming/outgoing conduits remains.

Installation on cable ladder KHZ and KHZV. Mounted on the upper


side of the rungs with Clamp M6-20SF. Infinitely adjustable across
the ladder.

The Installation plate 60 can also be mounted hanging under cable


ladder KHZ and KHZV.

Installation on cable ladder KHZP, KHZSP, KHZSPZ and KHZPS.


Mounted on the upper side of the rungs, through the perforation,
with Clamp set M6-20SF.

The Installation plate 60 can also be mounted hanging under cable


ladder KHZP, KHZSP, KHZSPZ and KHZPS.

100

Installation plate 62
For installation on wall or floor. Used for mounting of outlets and junction boxes.

B
mm

L
mm

Pre-galv.
Part. No. C*

Installation plate 62/230-500


200 500
781319 3
Installation plate 62/230-1000
200 1000
781320 9
Installation plate 62/430-500
400 500
781321 6
Installation plate 62/430-1000
400 1000
781322 3
Installation plate 62/530-500
500 500
781323 0
* EAN-code=732167+Part.no+C (control figure) **Produced to order

WEF-0001

Hot dip galv.


Part. No. C*

Pre-galv.
White
Part. No. C*

781329 2
781330 8
781331 5
781332 2

781324 7**
781325 4**
781326 1**
781327 8**

Weight kg
100 pcs

94
185
168
333
205

Use and installation

Installation plate 62 mounted


on wall.

Installation plate 62 mounted


on floor.

When mounting on Installation


plate 62 drilling screw 4.2 is
used. (e.g. Thorsman
TSE 4.2 x 13 E15 452 10
TSG 4.2 x 13 E15 460 00
TGE 4.2 x 16 E15 453 02)

101

Installation plate 61
Used on vertical cable ladder installations for mounting of
terminal boxes, contact breakers etc.

B
mm

t
mm

Pre-galv.
Part. No. C*

Installation plate 61-200


200 1.25
732486 6
Installation plate 61-300
300 1.25
732487 3
Installation plate 61-400
400 1.25
732488 0
Installation plate 61-500
500 1.50
732489 7**
Installation plate 61-600
600 1.50
732490 3**
*EAN-code=732167+Part.no+C (control figure) **Produced to order
Use and installation

Used on vertical cable ladder


installations for mounting of
terminal boxes, contact breakers
etc. Mount with selftapping screw
ST4.2 in the side profile.

102

WEF-0001

Hot dip galv.


Part. No. C*

Stainl. steel
(AISI316L)
Part. No. C*

Pre-galv.
White
Part. No. C*

Weight kg
100 pcs

732491 0
732492 7
732493 4
732494 1**
732495 8**

732801 7**
732802 4**
732803 1**
732804 8**
732805 5**

732496 5**
732497 2**
732498 9**
732499 6**
732500 9**

100
140
170
240
270

Dividing strip 39
Used to separate low-tension and high-tension cables. Thickness of plate 0.6 mm

WEF-0001

24
1750

5 x 250

250

H
mm

Pre-galv.
Part. No. C*

Hot dip galv.


Part. No. C*

Dividing strip 39/24


24
718835 2
731747 9
Dividing strip 39/55
55
725785 0
732983 0
*EAN-code=732167+Part.no+C (control figure) **Produced to order

7 x 10

Stainl. steel
(AISI316L)
Part. No. C*

Pre-galv.
White
Part. No. C*

Weight kg
100 pcs

725593 1
725594 8

717950 3
725786 7**

46
73

Use and installation

Mount one or more Dividing strips 39 to separate low and high


tension cables.

Attach Dividing strip 39 to KHZ and KHZV by lashing around the


rungs.

WIBE

Attach Dividing strip 39 to KHZSP, KHZSPZ, KHZPS and KHZP


using Screw set W34 through the rung perforations.

It is advisable to join dividing strips using Distance piece W39.

Distance piece W39


WEF-0021

Distance piece W39 is used for joining Dividing strips 39.

Distance piece W39


*EAN-code=732167+Part.no+C (control figure)

Natural coloured plastic


Part. No. C*

Weight kg
100 pcs

716824 8

Use and installation

WIBE

Mount one or more Dividing strips 39 to


separate low and high tension cables.

103

Cover 64
Used for vertically mounted cable ladders.

B
mm

WEF-0001

Hot dip galv.


Part. No. C*

Cover 64-150
151
782561 5**
Cover 64-200
201
782562 2**
Cover 64-300
301
782563 9**
Cover 64-400
401
782564 6**
Cover 64-500
501
782565 3**
Cover 64-600
601
782566 0**
Cover 64-800
801
782567 7**
Cover 64-1000
1001
782568 4**
*EAN-code=732167+Part.no+C (control figure) **Produced to order

Stainl. steel
(AISI316L)
Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

782585 1**
782586 8**
782587 5**
782588 2**
782589 9**
782590 5**
782591 2**
782592 9**

782569 1**
782570 7**
782571 4**
782572 1**
782573 8**
782574 5**
782575 2**
782576 9**

290
370
540
710
1020
1210
1660
2000

Use and installation

Cover 64 is to be mounted on the


cable ladder with Wall bracket
11/25 or Wall bracket 11/75 and
Screw set 22S.The covers are to
be joined with Cover joints.

Cover plate 65
Used on vertical cable ladder installations as protection of cables near the floor.

B
mm

Pre-galv.
Part. No. C*

Hot dip galv.


Part. No. C*

Cover plate 65-200


200
732475 0
730192 8
Cover plate 65-300
300
732476 7
730193 5
Cover plate 65-400
400
732477 4
730194 2
Cover plate 65-500
500
732478 1
730195 9**
Cover plate 65-600
600
732479 8
730196 6
*EAN-code=732167+Part.no+C (control figure) **Produced to order
Use and installation

Used on vertical cable ladder


installations as protection of
cables near the floor.
Mounted in the side profile with
selftapping screw ST4.2.

104

WEF-0001

Stainl. steel
(AISI316L)
Part. No. C*

Pre-galv.
White
Part. No. C*

Weight kg
100 pcs

732481 1**
732482 8**
732483 5**
732484 2**
732485 9**

718909 0**
718910 6**
718911 3**
718912 0**
718913 7**

930
1140
1350
1560
1780

Junction box cover


For mounting on cable ladder, hot dip galvanized.
Not in stock, only on request.

WEF-0001

Hot dip galvanized


When ordering, specify:
Ladder width and the dimensions D and L
Use and installation

When installing Junction box


cover on cable ladder use Profile
clamp 42.

Lashing wire
For lashing of wires on cable ladders.

HTR-2303 Lashing wire, stainless steel, white PVC


HTR-2313 Lashing wire, stainless steel, black PVC
HT-2304 Lashing wire, white PVC
HT-2314 Lashing wire, black PVC
*EAN-code=732167+Part.no+C (control figure)

WEF-0011

Diam
mm

Breaking load
kg

Part. No. C*

Weight kg
100 m

1.25
1.25
1.5
1.5

92
92
25
25

713686 5
713687 2
713684 1
713685 8

1.3
1.3
1.8
1.8

Use and installation

Cables are easily installed by


lashing around the rungs of KHZ
and KHZV.

Cables are easily installed by


lashing through the perforations
of the rungs or around the rungs
of KHZSP, KHZSPZ, KHZPS,
KHZP and KHZPV.

Cables are easily installed on


KHZSP, KHZSPZ, KHZPS,
KHZP and KHZPV by lashing in
such a way that the lashing wire
is pinched around the rung as
shown.

Dividing strips and tele-conduits


are attached to the ladder by
lashing around the rungs of KHZ
and KHZV.

105

Tele-conduit 36
Tele-conduit is installed where a separate tray is required for low-tension cables.
Knock-out holes in the bottom of the channel permit the cable to pass through.

B
mm

C
mm

Pre-galv.
Part. No. C*

Hot dip galv.


Part. No. C*

Teleconduit 36-50
42
50
725065 3
731748 6
Teleconduit 36-100
92 100
725066 0
731749 3
Teleconduit 36-200
192 200
725067 7
731750 9
***Without knock-out holes
*EAN-code=732167+Part.no+C (control figure) **Produced to order

WEF-0001

Stainl. steel***
(AISI316L)
Part. No. C*

Pre-galv.
White
Part. No. C*

Weight kg
100 pcs

725590 0
725591 7**
725592 4**

725068 4
725069 1
725070 7**

94
142
238

Use and installation

Mount Tele-conduit 36 whenever a special channel is required for low


tension lines.

Whenever you wish to make a


hole to let a cable through, press
the knock-out piece from below
using a screwdriver or suchlike.

Attach Tele-conduit 36 onto KHZ and KHZV by tying with wire round
rungs.

Attach Tele-conduit 36 to KHZSP, KHZSPZ, KHZPS and KHZP using


Screw set W34 through the rung perforations.

106

In the event of special needs,


Thorsmans sealing sleeve
TET 10-14 gland 22.5 or corresponding may be mounted
in the hole.

Fixing tray N for casting-in


A tray for casting-in with a mesh tray mounted on the inside of the tray
for quick and easy lashing of cables.
Pieces of Polystyrene at both ends makes it possible to adjust the
height of the tray. 2 fixing brackets and sealing strips are included.

Fixing tray N-300 for casting-in


Fixing tray N-400 for casting-in
*EAN-code=732167+Part.no+C (control figure) **Produced to order

WEF-0001

A
mm

Pre-galv.
Part. No. C*

Weight kg
100 pcs

330
430

782695 7**
782696 4**

1800
2200

Use and installation

Fixing tray N for casting-in


mounted in the mould.

Fixing tray N adjusted onto the


mould (from out- or inside) with
fixing brackets.

The length is adjustable to ceiling


and floor by moving the pieces of
Polystyrene, total height min
2400-max 3000 mm.

The mesh tray mounted into the


Fixing tray N is used for lashing
of cables.

107

Clamp 12
Used on the Cable ladder side profile for installation of accessories.

A
mm

Hot dip galv.


Part. No. C*

Clamp 12/70
125
728653 9
Clamp 12/120
175
728654 6
(screw not included)
*EAN-code=732167+Part.no+C (control figure) **Produced to order

WEF-0001

Stainl. steel
(AISI316L)
Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

728651 5
728652 2

732977 9**
732978 6**

19
24

Use and installation

When mounted over the cable ladder side profile, Clamp 12 can be
used for installation of antenna brackets, junction boxes and so on.
Use Screw set 2S (for hot dip clamp) or Screw set W37 (for stainless
steel clamp).

Hook 8
For installation of cables beneath Support bracket 3.
Hooks can also be installed in perforated rungs.

Hot dip galv.

AISI316L

Hook 8
**2 nut M6MF8 included
*EAN-code=732167+Part.no+C (control figure)
Use and installation

Hook 8 mounted beneath


Support bracket 3 for installation
of cables.

108

WEF-0001

Hook 8 installed in a perforated


rung.

Hot dip galv.


Part. No. C*

Stainl. steel**
(AISI316L)
Part. No. C*

Weight kg
100 pcs

728642 3

728643 0

Cable clamp type A


For fastening of cables on Pendant/Fixing rail 24/48,
Cable ladders KHZSP, KHZSPZ, KHZPS, KHZP and KHZPV.

Cabel clamp for 1 cable


Cable clamp A for 1 cable

WEF-0001

Cable clamp for 2 cables

Cable clamp A1-12


Cable clamp A1-16
Cable clamp A1-22
Cable clamp A1-28
Cable clamp A1-36
Cable clamp A1-44
Cable clamp A1-52
Cable clamp A1-60
Cable clamp A1-70
Cable clamp A for 2 cables

Cable clamp A2-12


Cable clamp A2-16
Cable clamp A2-22
Cable clamp A2-28
Cable clamp A2-36
Cable clamp A2-44
*EAN-code = 732167 + Part.no + C (control figure)

For cable
mm

Pre-galv.
Part. No. C*

Weight kg
100 pcs

-12
13-16
17-22
23-28
29-36
37-44
45-52
53-60
61-70

718507 8
718508 5
718509 2
718510 8
718511 5
718512 2
718513 9
718514 6
718515 3

3.4
3.7
4.6
5.3
8.8
9.9
11.0
12.5
15.4

For cabel
mm

Pre-galv.
Part. No. C*

Weight kg
100 pcs

-12
13-16
17-22
23-28
29-36
37-44

718516 0
718517 7
718518 4
718519 1
718520 7
718521 4

4.0
4.6
5.9
7.0
11.2
13.3

Use and installation

Use Cable clamp type A to


attach cables to Pendant/Fixing
rail 24/48. Use Insert
piece EM.

Mounting rail 40 with Cable


clamp type A.

Use Cable clamp type A to


attach cables to cable ladders
KHZSP, KHZSPZ, KHZPS,
KHZPV and KHZP. Use Insert
piece EM.

In order to avoid torsion of the


rung, cable clamps can be
mounted opposite each other on
the rung.

Tightening moment
When mounting, Insert piece EM is to be used.
It is important that the clamp is not tightened too hard.
The installer must watch out for deformations when tightening.
Suitable tightening moment for clamps with M6-screw is
0.5-1.0 Nm, and for clamps with M8-screw 1.0-1.5 Nm.

109

Cable clamp type R


For fastening of cables on Cable ladders KHZ and KHZV.

Cable clamp for 1 cable


Cable clamp R for 1 cable

Cable clamp R1-12


Cable clamp R1-16
Cable clamp R1-22
Cable clamp R1-28
Cable clamp R1-36
Cable clamp R1-44
Cable clamp R1-52
Cable clamp R1-60
Cable clamp R1-70
Cable clamp R for 2 cables

Cable clamp R2-12


Cable clamp R2-16
Cable clamp R2-22
Cable clamp R2-28
Cable clamp R2-36
Cable clamp R2-44
Cable clamp R2-52
Cable clamp R2-60
*EAN-code = 732167 + Part.no + C (control figure)

Cable clamp for 2 cables


For cable
mm

Pre-galv.
Part. No. C*

Weight kg
100 pcs

-12
13-16
17-22
23-28
29-36
37-44
45-52
53-60
61-70

769000 8
769001 5
769002 2
769003 9
769004 6
769005 3
769006 0
769007 7
769008 4

5.5
6.3
7.4
8.5
11.1
12.7
14.2
15.5
18.4

For cable
mm

Pre-galv.
Part. No. C*

Weight kg
100 pcs

-12
13-16
17-22
23-28
29-36
37-44
45-52
53-60

769009 1
769010 7
769011 4
769012 1
769013 8
769014 5
769015 2
769016 9

6.8
7.9
9.6
11.3
14.5
17.0
19.2
21.4

Use and installation

Cable clamp Type R is used for


fastening cables on the cable
ladders KHZ and KHZV. Insert
piece EM must be installed.

Tightening moment
When mounting, Insert piece EM is to be used.
It is important that the clamp is not tightened too hard.
The installer must watch out for deformations when tightening.
Suitable tightening moment for clamps with M6-screw is
0.5-1.0 Nm, and for clamps with M8-screw 1.0-1.5 Nm.

110

WEF-0001

Insert piece EM
Insert pieces are to be used in order to prevent pressure on the cable.
The insert piece is placed between the cable and the rung from the
same side whereas the clamp has been fastened to the rung.

Insert piece EM-12


Insert piece EM-16
Insert piece EM-22
Insert piece EM-28
Insert piece EM-36
Insert piece EM-44
Insert piece EM-52
Insert piece EM-60
Insert piece EM-70
*EAN-code=732167+Part.no+C (control figure)

WEF-0006

For cable
mm

Plastic, grey
Part. No. C*

Weight kg
100 pcs

-12
13-16
17-22
23-28
29-36
37-44
45-52
53-60
61-70

709050 1
709051 8
709052 5
709053 2
709054 9
709055 6
709056 3
709057 0
709058 7

0.2
0.2
0.3
0.3
0.5
0.7
0.8
0.9
1.0

Use and installation

Insert pieces EM increase the contact area of the cables.

111

Cable clamp ER
For installation of cables on cable ladders with round or perforated rungs.

WEF-0001
48
10,5
47

29,5

50

Cable clamp ER

Oval rung adapter


For cable
mm

Cable clamp ER
23-28
Cable clamp ER
27-32
Cable clamp ER
30-35
Cable clamp ER
33-38
Cable clamp ER
36-42
Cable clamp ER
40-46
Cable clamp ER
44-50
Cable clamp ER
48-55
Cable clamp ER
51-58
Cable clamp ER
55-62
Cable clamp ER
59-66
Cable clamp ER
63-70
Cable clamp ER
67-74
Cable clamp ER
71-78
Cable clamp ER
74-82
Cable clamp ER
77-85
Oval rung adapter (screw set incl.)
Screw set 74S (2 pcs are required for installation on perforated rungs)
*EAN-code=732167+Part.no+C (control figure)

A
mm

B
mm

80
82
82
85
113
115
117
120
121
156
158
160
163
165
167
169

74
81
88
94
101
108
115
129
130
138
146
150
161
168
176
181

Stainl. steel
(AISI316)
Part. No. C*

Weight kg
100 pcs

736440 4
736441 1
736442 8
736443 5
736444 2
736445 9
736446 6
736447 3
736448 0
736449 7
736450 3
736451 0
736452 7
736453 4
736454 1
736455 8
736456 5
737198 5

44
45
46
47
60
62
63
64
66
78
79
80
81
85
86
87
12
2

Use and installation

Remove the bottom plate of the


clamp and mount it with Oval
rung adapter on cable ladders
with round rungs - KHZ and
KHZV.

Remove the bottom plate of the


clamp and mount it with 2 screw
sets 74S on cable ladders with
perforated rungs - KHZP,
KHZPS, KHZSP, KHZSPZ
and KHZPV.

Remove the locking nut. Open


the clamp.

Mount the cables.

112

Tested at British short-circuit testing station.


Test report no. BS/F 1265
Wibe cable ladder KHZ-600, KHZP-300 and KHZP-600
Cable clamp ER mounted on every rung
Wibe cable ladder KHZ-300
Cable clamp ER mounted on every other rung

Condition after test


400 volt 58 kA symmetrical current (Peak 140 kA) during 0.1 second:
- All clamps remained secure
- Some slight distorsion of the ladder rungs
- The cables were splayed out between the clamps but otherwise in good order
Test report no. BS/F 1268
Wibe cable ladder KHZ-600 and KHZP-600
Cable clamp ER mounted on every other rung

Condition after test


352 volt 64 kA symmetrical current (Peak 140 kA) during 0.1 second:
- All clamps remained secure
- There was distorsion of a number of the ladder rungs
- The cables were splayed out between the clamps but otherwise in good order.

Lock the clamp with the locking


nut. Turn the nut to max. 4-5 Nm.
The rubber lining must touch the
cables but not so tight that the
cables will be deformed.

Mounting rail WMS25


For installation directly on wall for lashing of cables.

WEF-0001

Mounting rail WMS25


*EAN-code=732167+Part.no+C (control figure)

Hot dip galv.


Part. No. C*

Weight kg
100 pcs

725000 4

147

Use and installation

3 mm

Mounting of cables with lashing


wire, strips etc.

The mounting rail is installed


directly onto wall.

113

Cable rollers S
WEF-0007

Wibe cable rollers facilitate the pulling of cables and lines. Cable rollers are easily installed on all Wibe cable ladders. Also fits the external or
internal profile of all 90 bends, T-junctions, X-junctions and risers. The cable roller has a height adjustment of 45 mm to leave room for cables
to pass under the roller.

Cable roller S
*EAN-code=732167+Part.no+C (control figure)

Electro-galv.
Part. No. C*

Weight kg
100 pcs

718660 0

230

Loadings
F1

F2

F2

Permitted loading F1=100 kg (KHZ, KHZP, KHZV) 35 kg (KHZSP)


Permitted loading F2=125 kg (KHZ, KHZP, KHZV) 35 kg (KHZSP)
Permitted loading F3=100 kg (KHZ, KHZP, KHZV) 35 kg (KHZSP)

F3

Use and installation

For fitting on 90, T- and


X-junctions, use the inner
mounting hole.

114

For mounting on ladders, use


the outer mounting hole.

Cable roller 38 Rign roll


Used for mounting on Wibe cable ladders with belonging junctions and branches.

WEF-0001

Part. No. C*

Cable roller 38 Rign roll


Bag
Cable roller set 66 (1 bag+10 pcs Cable roller 38 Rign roll)
*EAN-code=732167+Part.no+C (control figure)

Stainl. steel
(AISI316L)
Part. No. C*

735998 1
780186 2
780187 9

Weight kg
100 pcs

48
230
710

Loadings
Permitted loading F1=20 kg (KHZ, KHZP, KHZV, KHZSP)
Permitted loading F2=50 kg (KHZ, KHZP, KHZV, KHZSP)
Permitted loading F3=50 kg (KHZ, KHZP, KHZV) 25 kg (KHZSP)

Use and installation

Cable roller 38 is to be mounted


on the cable ladder profile.

Use a screw driver when


dismantling the cable roller.

Open the cable roller by


pressing the locking button and
turn the loop aside.

The loop has rollers which


make cable pulling over bends
and junctions very easy.

115

Marking plate 93
A colour marking system that is easy to use when you want to
mark out which type of cable that is placed on the cable ladder.
5 different colours are available.

WEF-0001

Marking plate 93, Yellow


Marking plate 93, Orange
Marking plate 93, Blue
Marking plate 93, Green
Marking plate 93, Black
*EAN-code=732167+Part.no+C (control figure)

Plate
Part. No. C*

Weight kg
100 pcs

737704 6
737705 3
737706 0
737707 7
737708 4

5
5
5
5
5

Use and installation

The Marking plate can be bent


around the side profile on all
Wibe cable ladders.

Repair paint
Galvafroid for repair of damaged places on pre-galvanized or
hot dip galvanized ladders and accessories.
Repair paint for minor damages of powder coated products.

Anti-corrosive paint "Galvafroid", tin


Repair paint White RAL 9003 Gloss 30, spray bottle
Repair paint White RAL 9010 Gloss 80, spray bottle
* EAN-code=732167+Part.no+C (control figure)

WEF-0013, 0016

Volume
l

Part. No. C*

Weight kg
100 pcs

0.3
0.4
0.4

717637 3
739713 6
728027 8

86
60
60

Use and installation

Galvafroid used to increase the


protection of cut or damaged
places.
Applied with a colour brush.

116

Repair paint in spray bottle


for repainting of minor paint
damages.

Cover W5
WEF-0001

Covers are installed to protect the cable runs from dust, dirt and liquids etc.
Outdoors, the covers protect against rain and sun.
All Wibe cable ladders and cable trays can be fitted with covers.
Hot dip galvanized covers are painted on all sides.

Plate thickness = 1 mm

For ladder
width

Pre-galv.

Hot dip galv.

Stainl. steel
(AISI316L)

Pre-galv.
White

ZINKPOX
White

mm

mm

Part. No. C*

Part. No. C*

Part. No. C*

Part. No. C*

Part. No. C*

732264 0
732265 7
732266 4
732267 1
732268 8
732269 5
782213 3**
732270 1

732291 6**
732292 3**
732293 0**
732294 7**
732295 4**
732296 1**
783375 7**
732297 8**

732274 9**
732275 6**
732276 3**
732277 0**
732278 7**
732279 4**

782365 9**
782366 6**
782367 3**
782368 0**
782369 7**
782370 3**
782214 0**
782371 0**

Cover W5-150
150
151
732216 9
Cover W5-200
200
201
732217 6
Cover W5-300
300
301
732218 3
Cover W5-400
400
401
732219 0
Cover W5-500
500
501
732220 6
Cover W5-600
600
601
732221 3
Cover W5-800
800
801
Cover W5-1000
1000
1001
732222 0
*EAN-code=732167+Part.no+C (control figure) **Produced to order

732280 0**

Use and installation


Mount covers to protect the cable
routes from dust, waste, liquids,
etc. Outdoors, covers protect
against rain and sun.
All Wibe cable ladders can be
fitted with covers. Mount covers
using Profile support piece 37
and Cover clamp.

117

Cover joint
Inserted between the covers.
Plate thickness = 0.6 mm

WEF-0001

For ladder
width
mm

B
mm

Pre-galv.
Part. No. C*

Cover joint-150
150
125
712639 2
Cover joint-200
200
175
712640 8
Cover joint-300
300
275
712642 2
Cover joint-400
400
375
712643 9
Cover joint-500
500
475
712644 6
Cover joint-600
600
575
712645 3
*EAN-code=732167+Part.no+C (control figure) **Produced to order
Use and installation

For width 800 or 1000 mm, use a


combination of two smaller joints
(e.g. 400+600 mm). Insert joints
between covers.

118

Hot dip galv.


Part. No. C*

Pre-galv.
White
Part. No. C*

Weight kg
100 pcs

780452 8
780453 5
780454 2
780455 9
780456 6
780457 3

714710 6**
714711 3**
714713 7**
714714 4**
714715 1**
714716 8**

10
20
30
40
50
60

Profile support piece 37


When installing covers, the profile support pieces are mounted
approx. every 0.5 m along both sides of the ladder.

Pre-galv.
Part. No. C*

WEF-0001

Hot dip galv.


Part. No. C*

Profile support piece 37


729217 2
730188 1
*EAN-code=732167+Part.no+C (control figure) **Produced to order

Stainl. steel
(AISI316L)
Part. No. C*

Pre-galv.
White
Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

730190 4

730189 8

782382 6**

Use and installation

Mount the Profile support


piece 37 on the inside of the
hexagonal section. Bend the tab
towards the ladder section using
a screwdriver as a lever.

Profile support piece 37 can be


bent to fit the cover width.

Lock the cover on the Profile


support piece 37 using Cover
clamps.

Profile support pieces 37 can


be mounted as cable supports.
Mount the attachments at
about 0.5 m centres on both
sides of the ladder.

Cover clamp
Cover clamps are required when installing a cover on a Profile support piece 37.

WEF-0001

Stainl. steel
(AISI316L)
Part. No. C*

Pre-galv.
White
Part. No. C*

Zinkpox
White
Part. No. C*

Weight kg
100 pcs

Cover clamp
712668 2
728584 6
728586 0
*EAN-code=732167+Part.no+C (control figure) **Produced to order

714709 0

782384 0**

1.5

Pre-galv.
Part. No. C*

Hot dip galv.


Part. No. C*

Use and installation

Cover clamps are required for


mounting covers on Profile
support piece 37.

119

Cover 90 bend
Fits 90 interior bends. Installed with a Profile support piece 37, Cover clamp and Cover joint.

For ladder
width
mm

B
mm

Pre-galv.
Part. No. C*

Cover 90 bend-150
150
151
732322 7
Cover 90 bend-200
200
201
732323 4
Cover 90 bend-300
300
301
732324 1
Cover 90 bend-400
400
401
732325 8
Cover 90 bend-500
500
501
732326 5
Cover 90 bend-600
600
601
732327 2
Cover 90 bend-800
800
801
781802 0**
Cover 90 bend-1000
1000
1001
732328 9**
*EAN-code=732167+Part.no+C (control figure) **Produced to order

WEF-0001

Hot dip galv.


Part. No. C*

Pre-galv.
White
Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

781433 6
781434 3
781435 0
781436 7
781437 4
781438 1
781793 1**
781439 8**

781804 4**
781805 1**
781806 8**
781807 5**
781808 2**
781809 9**
781810 5**
781811 2**

781751 1**
781752 8**
781753 5**
781754 2**
781755 9**
781756 6**
781794 8**
781757 3**

65
91
143
221
299
390
460
871

Stainless steel (AISI316L)


For ladder width
mm

Cover 90 bend-150
150
Cover 90 bend-200
200
Cover 90 bend-300
300
Cover 90 bend-400
400
Cover 90 bend-500
500
Cover 90 bend-600
600
Cover 90 bend-800
800
Cover 90 bend-1000
1000
*EAN-code=732167+Part.no+C (control figure) **Produced to order
Use and installation

Fasten cover to Profile support


piece 37 using Cover clamp.

120

Mount with Profile support pieces


37, Cover clamps and Cover joints.

B
mm

Stainl. steel
(AISI316L)
Part. No. C*

Weight kg
100 st

147
197
297
397
497
597
797
997

788639 5**
788640 1**
788641 8**
788642 5**
788643 2**
788644 9**
788645 6**
788646 3**

44
62
105
223
310
408
643
926

Cover T-junction
Fits T-junctions. Installed with a Profile support piece 37, Cover clamp and Cover joint.

Cover

For ladder
width
mm

A
mm

B
mm

L
mm

Pre-galv.
Part. No. C*

T-junction-150
150
400 151 651
732345 9**
T-junction-200
200
450 201 701
732346 3**
T-junction-300
300
550 301 801
732347 0**
T-junction-400
400
650 401 901
732348 7**
T-junction-500
500
750 501 1001 732349 4**
T-junction-600
600
850 601 1101 732350 0**
T-junction-800
800
1050 801 1301 781803 7**
T-junction-1000
1000
1240 1001 1501 732351 7**
*EAN-code=732167+Part.no+C (control figure) **Produced to order

WEF-0001

Hot dip
galv.
Part. No. C*

Pre-galv.
White
Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

781440 4**
781441 1**
781442 8**
781443 5**
781444 2**
781445 9**
781796 2**
781446 6**

781812 9**
781813 6**
781814 3**
781815 0**
781816 7**
781817 4**
781818 1**
781819 8**

781765 8**
781766 5**
781767 2**
781768 9**
781769 6**
781770 2**
781797 9**
781771 9**

182
221
312
416
533
676
710
1352

Stainless steel (AISI316L)

Cover T-junction-150
Cover T-junction-200
Cover T-junction-300
Cover T-junction-400
Cover T-junction-500
Cover T-junction-600
Cover T-junction-800
Cover T-junction-1000
*EAN-code=732167+Part.no+C (control figure)

For ladder width


mm

A
mm

B
mm

L
mm

Stainl. steel
(AISI316L)
Part. No. C*

Weight kg
100 pcs

150
200
300
400
500
600
800
1000

402
452
552
652
752
852
1052
1242

147
197
297
397
497
597
797
997

657
707
807
907
1007
1107
1307
1507

788647 0**
788648 7**
788649 4**
788650 0**
788651 7**
788652 4**
788653 1**
788654 8**

95
126
196
394
525
672
1011
1414

Use and installation

Fasten cover to Profile support


piece 37 using Cover clamp.

Mount with Profile support pieces


37, Cover clamps and Cover joints.

121

Protecting cover
To be used as protection against ice and snow.
Meant for cable ladders width 300-400.

A
mm

Protecting cover 300


300
Protecting cover 400
400
*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Plate thickness
mm

Pre-galv.
Part. No. C*

Hot dip galv.


Part. No. C*

Weight kg
100 st

1.5
1.5

786738 7
786739 4

786746 2
786747 9

880
990

Use and installation

To be mounted on ladder KHZ


with Intermediate connection bolt
29. When mounted on other
ladders or when needed, drilling
screw 4.2 is used.

122

The covers can be mounted


edge to edge.

The covers can be mounted with


overlap. The assymmetric hole
pattern can be used to achieve a
good fit.

Steel wire
The steel wire is available in several qualities. To be installed as carrier of one or more cables.

HT-2309 Steel wire galvanized, soft


HT-2311 Steel wire 7 x diam 1.71=16 mm coated, grey
HTR-2322 Steel wire stainless, hard
HTR-2323 Steel wire stainless, hard
HTR-2324 Steel wire stainless, hard
*EAN-code=732167+Part.no+C (control figure)

WEF-0001,0011

Dim
mm

Breaking load
kg

Part. No. C*

Weight kg
100 m

5.0
6.15
2.5
3.0
4.0

700
970
450
700
1200

713679 7
713688 9
713681 0
713682 7
713683 4

15.5
13.5
3.9
5.6
10.0

Use and installation

Steel wire installed in ceiling with beams.

Steel wire installed in ceiling.

123

End bracket HT-11


End bracket for ceiling beam installation.

WEF-0001

End bracket HT-11


*EAN-code=732167+Part.no+C (control figure)

Plate
thickness
mm

Hot dip galv.


Part. No. C*

Weight kg
100 pcs

4.0

717618 2

41

Use and installation

End bracket HT-11 is installed on


ceiling beam with Expansion bolt
or Concrete screw.

Angle bracket 5L
For steel wire installation in ceilings.

WIB

Plate
thickness
mm

Angle bracket 5L
4.0
*EAN-code=732167+Part.no+C (control figure)
Use and installation

Angle bracket 5L is installed in


ceiling with Expansion bolt or
Concrete screw.
Max. permitted loading 600 kg
(6 kN).

124

WEF-0001

Hot dip galv.


Part. No. C*

Stainl. steel
(AISI316L)
Part. No. C*

ZINKPOX
White
Part. No. C*

Weight kg
100 pcs

731791 2

731793 6

731792 9

15

Wall bracket HT-14


Bracket for wall installation.

Wall bracket HT-14


*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Hot dip galv.


Part. No. C*

Weight kg
100 pcs

713671 1

18

Use and installation

Wall bracket HT-14 is installed on wall with Expansion bolt or


Concrete screw.

Carrying bracket HT-31


Carrying bracket for ceiling installation.

Carrying bracket HT-31


*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Hot dip galv.


Part. No. C*

Weight kg
100 pcs

713672 8

Use and installation

Carrying bracket HT-31 is


installed on ceiling beam with
Expansion bolt or Concrete
screw .

125

Carrying bracket HT-33/34


Carrying bracket for ceiling installation

Carrying bracket HT-33


Carrying bracket HT-34
*EAN-code=732167+Part.no+C (control figure)

WEF-0001

A
mm

Pre-galv.
Part. No. C*

Weight kg
100 pcs

14
38

713674 2
713675 9

1
2

Use and installation

Carrying bracket is installed in


ceiling with Expansion bolt or
Concrete screw.

Carrying bracket HT-152


Carrying bracket for I-beam installation.

Carrying bracket HT-152


*EAN-code=732167+Part.no+C (control figure)
Use and installation

Carrying bracket is easily


installed on I-beam.

126

WEF-0001

Hot dip galv.


Part. No. C*

Weight kg
100 pcs

717636 6

38

Carrying sling HT-51


Carrying slings for cables.

Carrying sling HT-51


*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Pre-galv.
Part. No. C*

Weight kg
100 pcs

713676 6

Use and installation

Carrying sling with space for 6


cables max. diam. 16 mm.

Pipe HT-68, HTR-68


Pipe for locking of wire.

WEF-0001

Hot dip galv.


Part. No. C*

Lock HT-68
Lock HTR-68
*EAN-code=732167+Part.no+C (control figure)

Stainl. steel
(AISI316L)
Part. No. C*

Weight kg
100 pcs

713678 0

1
1

713677 3

Use and installation

The steel cable is easily locked


with the pipe.

127

Tightening loop HT
To be installed at the ends of steel wires.
Nut and washer included.

WEF-0001

A
mm

C
mm

D
mm

Hot dip galv.


Part. No. C*

Weight kg
100 pcs

Tightening loop HT-611


125
Tightening loop HT-621
270
Tightening loop HT-631
400
*EAN-code=732167+Part.no+C (control figure)

100
100
150

22
50
50

713689 6
713690 2
713691 9

10
18
29

Use and installation

Tightening loop is installed in


End bracket HT-11 for installation
on ceiling beam.

128

Tightening loop is installed in


Angle bracket 5L for installation
in ceiling.

Tightening loop is installed in Wall bracket HT-14 for installation


on wall.

129

Screw set 2S
WEF-0001
For fastening of Support bracket 3 on Pendant/Fixing rail 24/20F and Angle bracket 5L
to the opening on Pendant rail 24/34 and 24/48.

Screw set 2S (screw MVBF 8x40 + nut M6MF8)


*EAN-code=732167+Part.no+C (control figure)

Hot dip galv.


Part. No. C*

Weight kg
100 pcs

715735 8

2.9

Screw set 20S


WEF-0001
For installation of Support bracket 3 on Pendant/Fixing rail 24/20 and Vertical piece 20,
Angle bracket 5L to the opening on Pendant/Fixing rail 24/48 and 24/20.

Screw set 20S (screw MVBF 8x60+nut M6MF8)


*EAN-code=732167+Part.no+C (control figure)

Hot dip galv.


Part. No. C*

Weight kg
100 pcs

715736 5

3.7

Screw set 22S


WEF-0001
For installation of Support bracket 3 on Vertical piece 2 and 2F,
Support bracket 3 and Ceiling bracket 5 on Pendant/fixing rails 24/34 and 24/48,
Angle bracket 5L against the back of pendant/fixing rail,
Pendant/fixing rails back to back.

Screw set 22S (screw MVBF 8x16+nut M6MF8)


*EAN-code=732167+Part.no+C (control figure)

Hot dip galv.


Part. No. C*

Stainl. steel
(AISI316)
Part. No. C*

Weight kg
100 pcs

713694 0

725582 5

1.9

Screw set W34


WEF-0001
For fastening of dividing strips on KHZSP, KHZSPZ, KHZPS and KHZP.

Screw set W34 (screw MSCS 6x12 + nut M6MF 6)


*EAN-code=732167+Part.no+C (control figure)

130

Electro-galv.
Part. No. C*

Stainl. steel
(AISI316)
Part. No. C*

Weight kg
100 pcs

718473 6

725589 4

0.8

Screw M10 x 20
WEF-0001
Used with Spring nut M10 (AISI 316) for installation of Cantilever arm 50 (AISI 316L)
on Pendant/Fixing rail 24/48.

Screw M6S 10x20


*EAN-code=732167+Part.no+C (control figure)

Stainl. steel
(AISI316)
Part. No. C*

Weight kg
100 pcs

728649 2

2.2

Spring nut M8/M10


WEF-0001
For fastening of accessories (control panels etc.) on Pendant/Fixing rail 24/48.

Spring nut M8
Spring nut M10
*EAN-code=732167+Part.no+C (control figure)

Hot dip galv.


Part. No. C*

Stainl. steel
(AISI316)
Part. No. C*

Weight kg
100 pcs

716407 3

728622 5

2.7
3.9

Back nut M8
WEF-0001
For fastening of vertical pieces etc. in the rungs of KHZSP, KHZSPZ, KHZP, KHZPS and KHZPV.

Mounting with Threaded


rod M8 and Backnut M8 in
the cable ladder rungs.

Back nut M8
*EAN-code=732167+Part.no+C (control figure)

Pendants etc. are mounted with


Bolt M8 and Back nut M8 in the
cable ladder rungs.

Dim
mm

Hot dip galv.


Part. No. C*

Weight kg
100 pcs

M8

718632 7

2.5

131

Clamp set M6
WEF-0001
Used for installation of Support bracket 3 directly on roof bolt.

A
mm

Stainl. steel
(AISI316L)
Part. No. C*

Weight kg
100 pcs

Clamp set M6-25** (2 clamps and 4 locking nuts)


29
720786 2
5
Clamp set M6-20*** (2 clamps and 4 locking nuts)
24
725587 0
4
*EAN-code=732167+Part.no+C (control figure)
** Clamp set M6-25 must be used for Support bracket 3, hot dip and pre-galvanized.
*** Clamp set M6-20 must be used for Support bracket 3, stainless steel AISI316L and Installation plate 60, all surface treatments.
Use and installation

For installation of Support


bracket 3 directly on ribbed bar
16-25 or fully threaded bar
M16-M27.

132

Max. symmetrical loading 300


kg. Make sure the clamps grip
the bar in a correct manner.

T-bolt 26F
Used for mounting with Pendant/Fixing rail 24/48.

WEF-0002

A
L

T-bolt 26F/M8
T-bolt 26F/M10
D

L
mm

A
mm

Electro-galv.
Part. No. C*

T-bolt 26F
M8
30
24
734983 8
T-bolt 26F
M10
30
24
734864 0
T-bolt 26F
M10
40
34
T-bolt 26F
M10
50
44
*EAN-code=732167+Part.no+C (control figure) **Produced to order

Hot dip galv.


Part. No. C*

734744 5
716794 4
716795 1
716796 8

Stainl. steel
(AISI316)
Part. No. C*

734986 9
728596 9
728598 3

Weight kg
100 pcs

4.5
7
7.5
8

Max permitted extraction force

T-bolt 26F M8/M10 + P/F-rail 24/48 + Washer 8.4x19x1.5

T-bolt 26F M8 + P/F-rail 24/48 + Washer 9x35x2

T-bolt 26F M10 + P/F-rail 24/48 + Washer 9x35x2

Use and installation

Installation of Pendant/fixing rail


on floor (or wall) with Angle
bracket 5L and T-bolt.

Check the position mark on the


bolt to ensure the right position of
the T-bolt in the rail.

T-bolt M8 makes it possible to


mount through the perforation
of Pendant/fixing rail 24/48.

133

Expansion bolts
Electro-galvanized, hot dip galvanized or stainless steel AISI316.
For installation of all Wibe cantilever arms and vertical pieces.

D
mm

L
mm

G
mm

WEF-0001

Electro-galv
Part. No. C*

Hot dip galv.


Part. No. C*

Stainl. steel
(AISI316)
Part. No. C*

Expansion bolt M6x40**


6
40
18
782222 5
782237 9
782252 2
Expansion bolt M6x65**
6
65
28
782223 2
782238 6
782253 9
Expansion bolt M8x50**
8
50
25
782224 9
782239 3
782254 6
Expansion bolt M8x95**
8
95
41
782225 6
782240 9
782255 3
Expansion bolt M8x120**
8
120 66
782226 3
782241 6
782256 0
Expansion bolt M10x60
10
60
28
782227 0
782242 3
782257 7
Expansion bolt M10x80
10
80
34
782228 7
782243 0
782258 4
Expansion bolt M10x100
10 100 54
782229 4
782244 7
782259 1
Expansion bolt M12x85
12
85
35
782230 0
782245 4
782260 7
Expansion bolt M12x100
12 100 50
782231 7
782246 1
782261 4
Expansion bolt M12x145
12 145 82
787052 3
787053 0
787054 7
Expansion bolt M16x110
16 110 53
782232 4
782247 8
782262 1
Expansion bolt M16x125
16 125 65
782233 1
782248 5
782263 8
Expansion bolt M16x150
16 150 76
782234 8
782249 2
782264 5
Expansion bolt M20x170
20 170 55
782235 5
782250 8
782265 2
Expansion bolt M20x220
20 220 55
782236 2
782251 5
782266 9
*EAN-code=732167+Part.no+C (control figure)
**M6 and M8 are delivered with an extra washer with a larger diameter. This washer must be mounted close to the cantilever arm or vertical piece. The smaller standard washer must be put on top of the bigger washer close to the nut.
Use and installation

D1= Drill diameter


M = Installation depth
B = Min. drilling depth
T = Material thickness
Data for installation

Dim
M6x40
M6x65
M8x50
M8x95
M8x120
M10x60
M10x80
M10x100
M12x85
M12x100
M12x145
M16x110
M16x125
M16x150
M20x170
M20x220

134

D1
mm
6
6
8
8
8
10
10
10
12
12
12
16
16
16
20
20

B
mm
35
50
45
65
65
50
70
70
80
80
80
105
105
105
130
130

M
mm
30
40
40
55
55
40
60
60
70
70
70
95
95
95
120
120

T
mm
2
15
2
30
55
3
10
30
5
20
65
5
20
45
20
70

Tightening
moment
Nm
7
7
18
18
18
30
30
30
54
54
54
120
120
120
240
240

Weight kg
100 pcs

1.04
1.54
2.22
3.61
4.35
4.44
5.32
6.28
8.17
9.23
12.47
18.57
20.46
23.90
44.83
57.02

Expansion bolts
Extraction force

Permitted extraction force in kN according to ETA approvals, option 4.


Concrete class
Dim

M6x40
M6
M8x50
M8
M10x60
M10
M12
M16
M20

Installation depth
mm

C20/C25 Non cracked


C25

C20/C25 Cracked
C35

30
40
40
55
40
60
70
95
120

1.4
1.8
1.6
2.4
2.1
3.6
6.4
10.0
13.9

2.0
3.0
4.8
6.4
-

Transverse force

Permitted transverse force in kN according to ETA approvals, option 4.


Dim

M6x40
M6
M8x50
M8
M10x60
M10
M12
M16
M20

Installation depth
mm

Concrete class C20/C25


kN

30
40
40
55
40
60
70
95
120

1.1
1.6
1.4
2.4
1.6
3.6
6.4
10.0
13.9

135

Fixing system

136

Concrete screw MMS-S


For installation with cantilever arms and vertical pieces.
Concrete screw with hexagonal head and special thread constructed for safe fixing in concrete or brickwork.
Suitable for fixing of tubes, electrical installations, rails, handrails, machines, ventilating ducts, wood constructions.
Easy to install
High extraction values are obtained due to the special thread. The drill diameter is the same as the root diameter of
the screw which gives a solid fixing inside the hole.
Can be dismounted and reinstalled without reduced extraction force.
A weaker drill can be used compared to using anchor, expansion bolt, screw and plug.
Suitable in environments which are fire classified.
Use and installation

Installation of cantilever arms.

Installation of vertical pieces.

Concrete screw MMS-S


WEF-0001

Electro-galvanized

A = Drill diameter
B = Min. installation depth
C = Min. drilling depth
F = Extraction force kN**
T = Transverse force kN
N = Width of jaws
**For concrete class C25

Part. No. C*

F
kN

T
kN

N
mm

xL
mm

A
mm

B
mm

C
mm

Number/
package

Weight kg
100 pcs

MMS-S 6x401

787067 7

2.40

2.2

10

6x40

30

50

200

0.74

MMS-S

6x501

787047 9

2.80

2.2

10

6x50

30

50

100

0.92

MMS-S

6x601

787048 6

2.80

2.2

10

6x60

30

50

100

1.03

MMS-S 7.5x352

781550 0

2.50

4.8

13

7.5x35

30

50

100

1.2

MMS-S 7.5x402

781551 7

2.50

4.8

13

7.5x40

30

50

100

1.3

MMS-S 7.5x502
MMS-S 10x60
MMS-S 10x70
MMS-S 10x80
MMS-S 12x80

781552 4

3.00

4.8

13

7.5x50

30

50

100

1.4

781553 1
781554 8
781555 5
781556 2

6.10
6.10
7.20
8.00

7.8
7.8
7.8
7.8

16
16
16
18

10x60
10x70
10x80
12x80

8
8
8
10

55
55
55
60

75
75
75
80

50
50
50
25

3.2
3.4
4.0
6.0

1 Washer 7.0x16x1.5 Electro-galv. is included


2 Washer 8.4x19x1.5 Electro-galv. is included

*EAN-code=732167+Part.no+C (control figure)

137

Concrete screw MMS-S


WEF-0001

Hot dip galvanized

A = Drill diameter
B = Min. installation depth
C = Min. drilling depth
F = Extraction force kN**
T = Transverse force kN
N = Width of jaws
**For concrete class C25
Part. No. C*

F
kN

T
kN

N
mm

xL
mm

A
mm

B
mm

C
mm

Number/
package

Weight kg
100 pcs

MMS-S 6x401

790356 6

2.40

2.2

10

6x40

30

50

200

0.74

MMS-S 6x501

790357 3

2.80

2.2

10

6x50

30

50

100

0.92

MMS-S 6x601

790358 0

2.80

2.2

10

6x60

30

50

100

1.03

MMS-S 7.5x352

790359 7

2.50

4.8

13

7.5x35

30

50

100

1.2

MMS-S 7.5x402

790360 3

2.50

4.8

13

7.5x40

30

50

100

1.3

MMS-S 7.5x502

790361 0

3.00

4.8

13

7.5x50

30

50

100

1.4

MMS-S
MMS-S
MMS-S
MMS-S

790362 7
790363 4
790364 1
790365 8

6.10
6.10
7.20
8.00

7.8
7.8
7.8
7.8

16
16
16
18

10x60
10x70
10x80
12x80

8
8
8
10

55
55
55
60

75
75
75
80

50
50
50
25

3.2
3.4
4.0
6.0

10x60
10x70
10x80
12x80

1 Washer 7.0x16x1.5 Hot dip galv. is included


2 Washer 8.4x19x1.5 Hot dip galv. is inclcluded

*EAN-code=732167+Part.no+C (control figure)

Concrete screw MMS-S


Stainless steel AISI316
Concrete screw with soldered phosphatized carbon steel tip.

WEF-0001

L2
L1
A = Drill diameter
B = Min. installation depth
C = Min. drilling depth
F = Extraction force kN**
T = Transverse force kN
N = Width of jaws
**For concrete class C25

MMS-S 7.5x50/653
MMS-S 10x70/85
MMS-S 12x80/100

Part. No. C*

F
kN

T
kN

N
mm

xL1/L2
mm

A
mm

B
mm

C
mm

Number/
package

Weight kg
100 pcs

781557 9

3.00

4.8

13

7.5x50/65

30

85

50

1.9

781558 6
781559 3

7.20
8.10

7.8
7.8

16
18

10x70/85
12x80/100

8
10

55
60

105
120

50
25

4.4
7.6

3Washer 8.4x24x2.0 AISI316 is incl.

*EAN-code=732167+Part.no+C (control figure)

138

Concrete screw MMS-S FL


Electro-galvanized
Concrete screw with flange.

WEF-0001

A = Drill diameter
B = Min. installation depth
C = Min. drilling depth
F = Extraction force kN**
T = Transverse force kN
D = Flange diameter
N = Width of jaws
**For concrete class C25
Part. No. C*

MMS-S FL 6x40
790394 8
MMS-S FL 6x50
790395 5
MMS-S FL 6x60
790396 2
MMS-S FL 7.5x50
790397 9
MMS-S FL 7.5x70
790398 6
MMS-S FL 10x70
790399 3
MMS-S FL 10x80
790400 6
MMS-S FL 12x90
790401 3
MMS-S FL 12x100
790402 0
*EAN-code=732167+Part.no+C (control figure)

F
kN

T
kN

N
mm

xL
mm

D
mm

A
mm

B
mm

C
mm

Number/
package

Weight kg
100 pcs

2.40
2.80
2.80
3.00
3.00
6.10
7.20
8.00
8.00

2.2
2.2
2.2
4.8
4.8
7.8
7.8
7.8
7.8

10
10
10
13
13
16
16
18
18

6x40
6x50
6x60
7.5x50
7.5x70
10x70
10x80
12x90
12x100

15.0
15.0
15.0
17.5
17.5
19.0
19.0
22.0
22.0

5
5
5
6
6
8
8
10
10

30
30
30
30
30
55
55
60
60

50
50
50
50
50
75
75
80
80

100
100
100
50
50
25
25
25
25

0.8
1.0
1.1
1.6
2.0
3.9
4.5
7.7
8.5

Concrete screw MMS-S FL


Hot dip galvanized
Concrete screw with flange.

WEF-0001

A = Drill diameter
B = Min. installation depth
C = Min. drilling depth
F = Extraction force kN**
T = Transverse force kN
D = Flange diameter
N = Width of jaws
**For concrete class C25
Part. No. C*

MMS-S FL 6x40
790376 4
MMS-S FL 6x50
790377 1
MMS-S FL 6x60
790378 8
MMS-S FL 7.5x50
790379 5
MMS-S FL 7.5x70
790380 1
MMS-S FL 10x70
790381 8
MMS-S FL 10x80
790382 5
MMS-S FL 12x90
790383 2
MMS-S FL 12x100
790384 9
*EAN-code=732167+Part.no+C (control figure)

F
kN

T
kN

N
mm

xL
mm

D
mm

A
mm

B
mm

C
mm

Number/
package

Weight kg
100 pcs

2.40
2.80
2.80
3.00
3.00
6.10
7.20
8.00
8.00

2.2
2.2
2.2
4.8
4.8
7.8
7.8
7.8
7.8

10
10
10
13
13
16
16
18
18

6x40
6x50
6x60
7.5x50
7.5x70
10x70
10x80
12x90
12x100

15.0
15.0
15.0
17.5
17.5
19.0
19.0
22.0
22.0

5
5
5
6
6
8
8
10
10

30
30
30
30
30
55
55
60
60

50
50
50
50
50
75
75
80
80

100
100
100
50
50
25
25
25
25

0.8
1.0
1.1
1.6
2.0
3.9
4.5
7.7
8.5

139

Concrete screw MMS-PAN


Electro-galvanized
For installation of Pendant strip W33.
Panheaded concrete screw, electro-galvanized. Torx-recess.

WEF-0001

A = Drill diameter
B = Min. installation depth
C = Min. drilling depth
E = Screw head diameter
F = Extraction force kN**
T = Transverse force kN
**For concrete class C25
Part.No. C*

F
kN

MMS-PAN 5x30
787049 3
0.8
MMS-PAN 5x50
787050 9
1.4
MMS-PAN 6x30
781560 9
2.40
MMS-PAN 7.5x45
781561 6
3.20
MMS-PAN 10x70
781562 3
7.20
*EAN-code=732167+Part.no+C (control figure)

T
kN

Torx

xL
mm

A
mm

B
mm

C
mm

E
mm

Number/
package

Weight kg
100 pcs

1.4
1.4
2.2
4.8
7.8

T-20
T-20
T-30
T-40
T-40

5x30
5x50
6x30
7.5x45
10x70

4
4
5
6
8

25
25
25
30
55

45
45
45
50
75

7.9
7.9
11.5
13
17

200
200
200
100
50

0.32
0.5
0.65
1.10
3.40

Use and installation

Installation of Pendant strip W33. Mounting with JR-clamp.

Concrete screw MMS-PAN SH


Electro-galvanized
For installation of Ceiling attachment W31 or Tube pendant attachment W73.
Concrete screw with extra big panhead, electro-galvanized. Torx-recess.

WEF-0001

A = Drill diameter
B = Min. installation depth
C = Min. drilling depth
E = Screw head diameter
F = Extraction force kN**
T = Transverse force kN
**For concrete class C25

Part. No. C*

MMS-PAN SH 7.5x45
781696 5
*EAN-code=732167+Part.no+C (control figure)
Use and installation

Installation of Ceiling attachment


W31.

140

F
kN

T
kN

Torx

xL
mm

A
mm

B
mm

C
mm

E
mm

Number/
package

Weight kg
100 pcs

3.00 4.8

T-30

7.5x45

30

50

17

100

1.4

Concrete screw MMS-ST


Electro-galvanized
For installation of eye nuts. The screw is specially developed for safe fixing in concrete.
Suitable for tube installations, electrical installations, rails, handrails, machines, ventilating ducts, wood constructions.

WEF-0001

A = Drill diameter
B = Min. installation depth
C = Min. drilling depth
E = Length of thread engagement
F = Extraction force kN**
T = Transverse force kN
N = Widths of jaws
M = English thread
**For concrete class C25
T
kN

N
mm

DxL1
mm

L2
mm

A
mm

B
mm

C
mm

E
mm

Number/
package

Weight kg
100 pcs

MMS-ST 7.5x70
781563 0
3.20 4.8
MMS-ST 10x80
781564 7
6.51 7.8
*EAN-code=732167+Part.no+C (control figure)

10
13

7.5x70
10x80

53
65

M8
M10

6
8

30
55

50
75

13
10

50
50

1.8
3.5

Part. No. C*

F
kN

Use and installation

Installation of eye nut.

Concrete screw MMS-I


Electro-galvanized
For installation of Pendant M8 or M10.
High extraction values are obtained due to the special thread.
The drill diameter is the same as the root diameter of the screw which gives a solid fixing inside the hole.
Can be dismounted and reinstalled without diminished extraction force.
A weaker drill can be used compared to using anchor, expansion bolt, screw and plug.
Suitable in environments which are fire classified.

WEF-0001

A = Drill diameter
B = Min. installation depth
C = Min. drilling depth
F = Extraction force kN**
T = Transverse force kN
N = Widths of jaws
M = Metrisk gnga
**For concrete class C25
T
kN

N
mm

DxL1
mm

MMS-I 7.5x55
781565 4
3.20 4.8
*EAN-code=732167+Part.no+C (control figure)

13

7.5x93

Part. No. C*

F
kN

L2
mm

A
mm

B
mm

C
mm

Number/
package

Weight kg
100 pcs

M8/M10

30

50

100

1.9

Use and installation

Installation of Pendant M8 or
M10.

141

Eye screw MMS-R


Electro-galvanized
For installation of wires in ceiling.

WEF-0001

A = Drill diameter
B = Min. installation depth
C = Min. drilling depth
F = Extraction force kN**
T = Transverse force kN
**For concrete class C25
F
kN

T
kN

xL
mm

A
mm

B
mm

C
mm

Number/
package

Weight kg
100 pcs

2.80

2.2

6x40

30

50

250

0.76

Part. No. C*

MMS-R 6x40
781566 1
*EAN-code=732167+Part.no+C (control figure)

Light concrete screw


WEF-0001

Electro-galvanized
For installation in porous concrete. Torx-recess.

B = Min. installation depth


E = Head diameter
F = Permitted extraction force kN

Part. No. C*

Light concrete screw 8x100


790412 9
*EAN-code=732167+Part.no+C (control figure)

F
kN

Torx

xL
mm

B
mm

E
mm

Number/
package

Weight kg
100 pcs

0.67

T-40

8x100

95

14.8

50

2.4

Expansion nail
Electro-galvanized/ Aluminium
For fixing of light details in concrete.

WEF-0001

A = Drill diameter
B = Min. installation depth
C = Min. drilling depth

Expansion nail 5x22


*EAN-code=732167+Part.no+C (control figure)

Part. No. C*

xL
mm

A
mm

B
mm

C
mm

Number/
package

Weight kg
100 pcs

790413 6

5x22

20

30

250

0.5

Mounting tool for Eye screw MMS-R


Electro-galvanized.

Mounting tool for Eye screw MMS-R


*EAN-code=732167+Part.no+C (control figure)

142

WEF-0001

Part. No. C*

Number/
package

Weight kg
100 pcs

781567 8

5.5

Bitro adapter
Electro-galvanized + plastic.
The Bitro adapter must be installed direct on Hammer drill SDS PLUS.
Drilling machine can be used. Suitable for drilling only in C25 concrete.

Bitro adapter 5, yellow


Bitro adapter 6, green
Bitro adapter 8, red
Bitro adapter 10, blue
*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Part. No. C*

For drill
mm

D
mm

L
mm

Number/
package

Weight kg
100 pcs

781568 5
781569 2
781570 8
781571 5

5
6
8
10

10
10
12
14

73
73
80
80

1
1
1
1

2.5
3.0
4.0
5.0

Use and installation

Turn off the hammer function of the drilling machine. Install the Bitro
adapter on the drill. Check that the adapter locks the drill to avoid
turning. Put in Torxbits or Magnetic socket or Square peg + Socket
16/18. When removing the adapter tilt it lightly and pull the bit,
magnetic socket or the square peg.

When mounting use a drilling machine with torque regulator.


Otherwise be very careful. If you let the machine continue to run
when the screw is in bottom it is very easy to destroy the tip of the
drill or that the drill gets stuck or broken. The risk increases with the
length of the drill.

Magnetic socket for Concrete screw MMS-S


Untreated steel.

WEF-0001

Magnetic socket 10x45


Magnetic socket 13x45**
**Can also be used for MMS-I.
*EAN-code=732167+Part.no+C (control figure)

Part. No. C*

Dim
mm

D
mm

Number/
package

Weight kg
100 pcs

781572 2
781573 9

10x45
13x45

10
13

1
1

2.5
3.0

Socket for Concrete screw MMS-S


Untreated steel.
To be used together with Square peg.

Part. No. C*

Socket 16
781574 6
Socket 18
781575 3
*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Dim
mm

D
mm

Number/
package

Weight kg
100 pcs

16x34
18x34

16
18

1
1

6.0
10.0

143

Bits holder
Stainless steel AISI304.

Bits holder 11x60


*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Part. No. C*

Number/
package

Weight kg
100 pcs

781576 0

2.5

Square peg
Untreated steel.
To be used with Socket 16 and 18.

Square peg 3/8x50


*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Part. No. C*

Number/
package

Weight kg
100 pcs

781577 7

2.0

Torxbits
Untreated steel.
To be used with Concrete screw MMS-PAN SH.

Torxbits TX 30x25
Torxbits TX 40x25
*EAN-code=732167+Part.no+C (control figure)

144

WEF-0001

Part. No. C*

Number/
package

Weight kg
100 pcs

788552 7
788553 4

2
2

0.5
0.6

Hammer drill SDS PLUS


Untreated steel.

Hammer drill SDS PLUS 4x110


Hammer drill SDS PLUS 5x110
Hammer drill SDS PLUS 5x160
Hammer drill SDS PLUS 5.5x110
Hammer drill SDS PLUS 5.5x160
Hammer drill SDS PLUS 6x110
Hammer drill SDS PLUS 6x160
Hammer drill SDS PLUS 6x210
Hammer drill SDS PLUS 7x160
Hammer drill SDS PLUS 7x210
Hammer drill SDS PLUS 8x160
Hammer drill SDS PLUS 8x210
Hammer drill SDS PLUS 10x160
Hammer drill SDS PLUS 10x210
Hammer drill SDS PLUS 12x210
Hammer drill SDS PLUS 16x300
Hammer drill SDS PLUS 20x450

WEF-0001

Part. No. C*

Dim
mm

Cutting length
of the drill
mm

Number/
package

Weight kg
100 pcs

787021 9
781631 6
781632 3
787022 6
787023 3
781633 0
781634 7
781635 4
787025 7
787026 4
781636 1
781637 8
781638 5
781639 2
787027 1
787028 8
787029 5

4x110
5x110
5x160
5.5x110
5.5x160
6x110
6x160
6x210
7x160
7x210
8x160
8x210
10x160
10x210
12x210
16x300
20x450

50
50
100
50
100
50
100
150
100
150
100
150
100
150
150
230
370

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

3.0
3.5
4.0
4.0
4.0
4.5
5.0
5.5
5.5
6.0
6.0
6.5
7.5
9.0
9.5
20.0
56.0

4x 75
5x 85
5x150
5.5x 85
5.5x150
6x100
6x150
7x100
7x150
7x300
8x150
8x200
10x150
10x200
12x200
16x300
20x400

40
50
60
50
90
60
90
60
90
220
90
135
90
135
135
220
230

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

2.0
2.5
2.0
2.0
2.0
2.0
4.0
4.0
4.0
8.0
4.0
6.0
6.0
8.0
10.0
26.0
62.0

Masonry drill WBL/WBE


Tungsten carbide tip.Tool steel shank with plated finish.
Masonry drill WBE 4x 75
787030 1
Masonry drill WBE 5x 85
787031 8
Masonry drill WBL 5x150
787032 5
Masonry drill WBE 5.5x 85
787033 2
Masonry drill WBL 5.5x150
787034 9
Masonry drill WBE 6x100
787035 6
Masonry drill WBL 6x150
787036 3
Masonry drill WBE 7x100
787037 0
Masonry drill WBL 7x150
787038 7
Masonry drill WBL 7x300
787039 4
Masonry drill WBL 8x150
787040 0
Masonry drill WBL 8x200
787041 7
Masonry drill WBL 10x150
787042 4
Masonry drill WBL 10x200
787043 1
Masonry drill WBL 12x200
787044 8
Masonry drill WBL 16x300
787045 5
Masonry drill WBL 20x400
787046 2
*EAN-code=732167+Part.no+C (control figure)

145

Concrete screws - Loadings


Mounting of Wibe concrete screws
To use Wibe concrete screws is both safe and easy. No special tools or machines are required.
The screw performs an exact adapted thread in the bedding which means that no control of the tightening moment is required.
The extraction force of a Wibe concrete screw is better than that of an expansion bolt with the same diameter
You can choose a smaller diameter of a concrete screw than that of an expansion bolt and still receive the same extraction force.
The same concrete screw can be re-used.
Mounting instruction

Use a drill suitable to the screw.


Drill the hole.

Switch off the hammer function.


Mount the Bitro adapter on the
drill. Pull in a bit or socket suitable for the screw to be used.

Mount with drilling machine.


Wibe concrete screws can also
be mounted with regular hand
tools as box sockets.

1. Drill a hole with the same diameter as the root of the screw
(for 6 mm drill 5 mm, for 7.5 mm drill 6 mm, for 10 mm drill 8 mm and for 12 mm drill 10 mm).
The drill depth must be at least 20 mm deeper than the installation depth.
2. Blow the hole free from dust.
3. Mount the concrete screw close to the application bedding, no defined tightening moment is required.
Note - dont tighten the screw with a higher moment than stated on the package or technical data.
Extraction forces, in kN, depending on installation depth in uncracked concrete C25.
Calculated values with a safety factor of 3.0.
Installation depth
mm

25
30
35
40
45
50
55
60
70
80

MMS-5

MMS-6

MMS-7.5

0.8
1.4

2.02
2.40
2.50
2.80
2.80
2.80

2.15
2.50
2.60
3.00
3.20
4.10
6.10
6.51

2.80

MMS-10

3.50
3.80
4.00
4.30
6.10
7.20
7.90

MMS-12

5.50
6.30
7.20
8.00
8.10
10.00

Transverse forces Concrete screw MMS


Dimensioned transverse force in kN.
Concrete screw

Screw diameter mm
Breaking torsional moment (Nm)
Recommended max tightening moment (Nm)

MMS-5

MMS-6

MMS-7.5

MMS-10

MMS-12

1.4

2.2

4.8

7.8

7.8

5
12
10

6
24
10

7.5
28
20

10
80
50

12
120
80

Spacing
The above values are valid when the distance from the nearest corner or free edge to the screw is at least
10 x screw diameter. The spacing between two screws must be minimum 20 x screw diameter.

146

Low density anchor TLF


Hot dip galvanized
For fixing in light concrete or clinker concrete. For medium or heavy installations.
Unique advantages:
Long expansion area and heavy expansion - very high loading values
The expansion can be directed - superior loading values even at small edge distances.
Very quick installation - drives in and expands with a hammer and Hammer tool TLF-S

DxL
mm

D1
mm

Drill diameter
mm

Number/
package

Weight kg
100 pcs

8x 65
12x100
12x145
16x130

13
20
20
25

8
12
12
16

50
25
25
10

1.4
4.7
6.2
10.0

Part. No. C*

Low density anchor TLF 8x65**


781782 5
Low density anchor TLF 12x100
781783 2
Low density anchor TLF 12x145
781784 9
Low density anchor TLF 16x130
781785 6
**One Hammer tool is incl. in each package.
*EAN-code=732167+Part.no+C (control figure)
Loading - All loadings refer to mounting in light concrete Y 500

Max Tightening moment


M=Nm

Extraction force F1
kN

Transverse force
kN

1
6
6
10

0.3
0.6
0.6
0.6

0.3
0.6
0.6
0.6

TLF 8x65 mounted with wood screw TKX Fzb SPAX-5x35


TLF 12x100 mounted with hexagon head wood screw T6S 4.6 Fzv 8x40
TLF 12x145 mounted with hexagon head wood screw T6S 4.6 Fzv 8x40
TLF 16x130 mounted with hexagon head wood screw T6S 4.6 Fzv 10x40
Max permitted load F on Cantilever arm 50

50-200

TLF 8x 65
TLF 12x100
TLF 12x145
TLF 16x130

WEF-0006

50-300

50-400

50-500

50-600

Kg

kN

Kg

kN

Kg

kN

Kg

kN

Kg

kN

26
26
26

0.26
0.26
0.26

25
25
25

0.25
0.25
0.25

22
22
22

0.22
0.22
0.22

23
23
23

0.23
0.23
0.23

21
21
21

0.21
0.21
0.21

Use and installation

Drill with recommended drill


diameter, see above. (Without
pre-drilling in quality Y400 and
Y450).

Low density anchor TLF installed


with Hammer tool TLF-S. Put the
hammer tool into the installation
hole of the low density anchor
and bolt the anchor.

Lower the distance.

Expand the anchor by means of


the Hammer tool.

147

Hammer tool TLF-S


Untreated steel.
For driving in and expansion of the Low density anchor TLF.

Hammer tool TLF-S 12x100


Hammer tool TLF-S 12x145
Hammer tool TLF-S 12x130
*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Part. No. C*

L
mm

Number/
package

Weight kg
100 pcs

781842 6
781843 3
781844 0

180
225
220

1
1
1

23
24
42

Use and installation

Put the Hammer tool into the


installation hole of the Low
density anchor and bolt the
fixing (without pre-drilling in
quality Y400 and Y450).

Lower the distance.

Expand the anchor by means of


the Hammer tool.

Sleeve TLF-H12
Hot dip galvanized.
To be used together with Low density anchor TLF 12x100 or 12x145
in order to raise the transverse force performance.

Sleeve TLF-H12
*EAN-code=732167+Part.no+C (control figure)

Part. No. C*

Number/
package

Weight kg
100 pcs

781867 9

25

1.3

Use and installation

Put the sleeve on the Low


density anchor.
(See instructions for Low density
anchor TLF).

148

WEF-0001

Bolt the Low density anchor with


the sleeve in level with the wall.

Adapter TLF-A12
Electro-galvanized.
To be used together with Low density anchor TLF 12x100 or 12x145
in order to receive an interior M10 thread.
Suits Pendant M10.

Adapter TLF-A12
*EAN-code=732167+Part.no+C (control figure)

WEF-0007

Part. No. C*

Number/
package

Weight kg
100 pcs

781868 6

10

2.1

Use and installation

Screw the Adapter into the


expanding Low density anchor.

Pendant M10 fits in the Adapter.

Angled bracket TLF-F12


Pre-galvanized.
To be mounted with Low density anchor TLF 12x100 or 12x145
and can be used as fixing for band or wire installations.

Angled bracket TLF-F12


*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Part. No. C*

Number/
package

Weight kg
100 pcs

781869 3

25

2.6

Use and installation

Mount the Angled bracket on the


Low density anchor.
(See instructions for Low density
anchor TLF).

Bolt the Low density anchor with


the Angled bracket into the bedding and check that it is secured.

149

Express hanger SVH


Stainless steel AISI316.
For fixing in concrete, natural stone, solid brick or plate.
Used for installation of armatures close to the ceiling (with locking block) as well as
for hanging of integrated ceilings, armatures, electrical-, tube- or ventilating equipment.
Mounting tool SVH-T, for mounting to the right installation depth, is included in the package.
Cover plate is included only for SVH-E1.

Part. No. C*

Express hanger SVH-E1


781870 9
Express hanger SVH-E2**
781871 6
**Cover plate not included.
*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Drill
mm

Min. drilling depth


mm

Number/
package

Weight kg
100 pcs

8
8

30
30

100
500

0.3
0.3

Loading
Permitted load capacity at safety factor 3 at extraction
Concrete C25 kN
Solid brick kN

Express hanger SVH-E1


Express hanger SVH-E2

1.0
1.0

0.5
0.5

Use and installation

Hole must be drilled with a 8 mm


drill, drilling depth minimum 30
mm. Drive in the Express hanger
with the Mounting tool SVH-T.
The installation depth always
turns out to be the right.

The short and stiff wire ends grip


effectively into the sides of the
hole resulting in a safe and
strong fixing.

Mounting of wires. Cover plate


hides the hole.

Express hanger SVH can also be


used for installation of Fixing strip
TRB and TGB.

When the fixing strip is turned


into position it self-locks. Can
also be locked with screw, rivet
or lashing wire for extra security.

At a visible installation, hide the


hole with a cover plate. Delivered
together with SVH-E1.

150

Mounting close to the ceiling with


Securing spring SVH-L.

Securing spring SVH-L


Stainless steel AISI304.
For installation of armatures close to ceiling.

Securing spring SVH-L


*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Part. No. C*

Number/
package

Weight kg
100 pcs

781872 3

25

0.20

Use and installation

For installation of armatures close


to the ceiling. Maximum loading
per securing spring is 4 kg.

Mounting tool SVH-T


Electro-galvanized.
For installation of Express hanger SVH.

Mounting tool SVH-T


*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Part. No. C*

Number/
package

Weight kg
100 pcs

781873 0

10

1.8

Use and installation

For installation of Express


hanger SVH. The installation
depth will always turn out to be
the right.

151

Fixing strip TGB


Pre-galvanized.
For pendant installation and clamping.
Cold-rolled and galvanized sheet metal, perforated for easy installations.
For fixing tools as Express hanger SVH or Low density anchor TLF with Angled bracket TLF-F12.

Fixing strip TGB 11x0.7


*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Part. No. C*

Number/
Package

Weight kg
100 pcs

781874 7

1 (25m)

105

Use and installation

Can be mounted with Express


hanger SVH.

Can be mounted with Low


density anchor TLF and
Angled bracket TLF-F12.

Can easily be mounted with other suitable fixing tools.

Fixing strip TRB


Stainless steel AISI304.
For pendant installation and clamping.
Stainless steel band AISI304 for qualified installations in all type of environments.
Express hanger SVH or Low density anchor TLF with Angled bracket TLF-F12 can be used as fixing tools.

Fixing strip TRB 11x0.7


*EAN-code=732167+Part.no+C (control figure)

WEF-0001

Part. No. C*

Number/
package

Weight kg
100 pcs

781875 4

1 (10m)

42

Use and installation

Can be mounted with Express


hanger SVH.

152

Can be mounted with Low


density anchor TLF and
Angled bracket TLF-F12.

Can easily be installed with other suitable fixing tools.

Frame installations

153

Installation examples

Water pipes, gas and sprinkler


installations mounted on Uprofile fixed with Profile clamp 42
under the ladder.

Hydraulic and pneumatic pipes


are easily placed on cable
ladders.

Installation of neon light fittings


can easily be made with Wall
bracket 11/25 or 11/75.

A Wire tray can easily be


mounted along a cable ladder
with accessories from the Wire
tray program.

One or more cable ladders can


be mounted with Vertical piece
2F, Profile clamp 41 and T-bolt.

At heavy loadings several cable


ladders can be mounted with
Vertical piece 20, Profile clamp
41 and T-bolt.

Cable ladders mounted on


Vertical piece 2F and Support
bracket 3.

Cable ladders mounted on


Vertical piece 20 and cantilever
arms.

Installation of neon light fittings


can easily be made with Wall
bracket 11/25 or 11/75.

Cable ladders mounted with Wall


bracket 11/25 or 11/75.

Floor installations

Other installation examples

3
5

6
8

The Support bracket/joint for


Wibe cable trays may very well
be used as a mounting plate.

154

Tilted protective roofs can easily


be mounted with a Cantilever
arm 50F placed upside down.

Use Cantilever arm 50/700-1000


as support when cable ladders
have to pass columns etc.

7
9

Installations under ventilation


pipes and ducts:
1. Ventilating pipe
2. Vertical piece 2F
3. Angle bracket 5L
4. T-bolt
5. P/F-rail 24/20, 24/34
or 24/48
6. Ceiling bracket 5
7. Support bracket 3
8. Cable ladder

Installation examples

155

Installation examples

156

Installation examples

157

Installation examples

158

Installation examples

159

Installation examples

160

Management system - Quality and Environment

Wibe has a third-party certified management system for


quality and environment in accordance with ISO 9001:2000
and ISO 14001:2004

AB WIBE
Box 401, SE-792 27 MORA, Sweden
Telephone +46 250 280 00, Telefax +46 250 188 55
e-mail: [email protected], www.wibe.se

You might also like