Application Setting Philosophy: A Philosophy For Distance Element Fault Detector Settings

This document discusses the philosophy for setting distance element fault detectors. It explains that phase current for a three-phase fault is higher than for a phase-to-phase fault. The setting can be 50% of the phase current for a three-phase fault to detect a phase-to-phase fault. Alternatively, it can be set to the phase-to-phase current for a three-phase fault, which will also detect a phase-to-phase fault since the currents are the same. Safety margins are ensured in both cases.

Uploaded by

طه محمد
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
88 views2 pages

Application Setting Philosophy: A Philosophy For Distance Element Fault Detector Settings

This document discusses the philosophy for setting distance element fault detectors. It explains that phase current for a three-phase fault is higher than for a phase-to-phase fault. The setting can be 50% of the phase current for a three-phase fault to detect a phase-to-phase fault. Alternatively, it can be set to the phase-to-phase current for a three-phase fault, which will also detect a phase-to-phase fault since the currents are the same. Safety margins are ensured in both cases.

Uploaded by

طه محمد
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Application Setting Philosophy

A Philosophy for
Distance Element Fault Detector Settings
For the purposes of this discussion, the B phase current will be used since a comparison of threephase and phase-to-phase bolted faults will be made.
From component theory, we know

I B = I 0 + a 2 I 1 + aI 2

(1)

where
a = 1120
For a three-phase fault, I0 = I2 = 0 and the positive sequence current can be determined by

I1 =

E1
Z1

(2)

where
E1 = positive sequence source voltage
Z1 = sum of positive sequence source and line impedances
Applying (1), we get

I B = a 2 I1

(3)

Substituting (2), we get

IB = a2

E1
Z1

(4)

For a phase-to-phase fault, I0 = 0 and I1 = -I2. The positive sequence current can be determined by

E1
2 Z1

(5)

I B = a 2 I 1 - aI 2

(6)

I1 =
Applying (1), we get

Rearranging (6) and substituting (5), we get

IB =

a 2 - a E1

2
Z1

SEL Application Setting Philosophy Fault Detectors

(7)

Page 1 of 2

Comparing (4) and (7), we see that the difference in phase current for the two fault conditions is

a2 - a
a2 - a
. If we only look at magnitudes, a 2 applies a factor of 1 where
applies
2
2
3
3
. Therefore, we see that the phase current for a phase-to-phase fault is
times
a factor of
2
2
a 2 versus

the phase current for a three-phase fault at the same location.


Knowing the relationship between the phase current for a three-phase and phase-to-phase fault
allows fault detector settings to be determined by using the three-phase fault current magnitude.
If the fault detector operates on phase current, the setting can be safely set at 50% of the phase
current for a three-phase fault. Such a setting provides a pick up value that is equal to 58% of the
phase current for a phase-to-phase fault.
If the fault detector operates on phase-to-phase current, the setting can be safely set at the phase
current for a three-phase fault. Such a setting provides a pick up value that is equal to 58% of the
phase-to-phase current for either fault condition. The safety margin is automatic since the phaseto-phase current is 3 times the phase current during a three-phase fault and the phase-to-phase
current is 2 times the phase current for a phase-to-phase fault. The result is that a phase-to-phase
fault detector will see the same current for a three-phase or phase-to-phase fault, as shown below.
Assume I f is the phase current for a three-phase fault.
Then the phase-to-phase current for a three-phase fault is

I BC = 3 I f
And the phase-to-phase current for a phase-to-phase fault is

I BC =

3
If 2 = 3 If
2

SEL Application Setting Philosophy Fault Detectors

Page 2 of 2