Specifications of Solar Power System

The document specifies the requirements for a solar power system to provide power for a gas chromatograph. The key specifications are: 1) The system produces 48V DC at a continuous load of 10A and 110V AC. It includes 4000W solar modules, a charge controller, 24 batteries of 100-110AH at 12V DC, and a 2.5KVA inverter. 2) The solar modules are monocrystalline cells in an aluminum frame rated 245-260Wp each. 3) The system must power the gas chromatograph continuously and be warranted to produce at least 80% of peak power output after 15 years.

Uploaded by

Naqash Ahmed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
258 views

Specifications of Solar Power System

The document specifies the requirements for a solar power system to provide power for a gas chromatograph. The key specifications are: 1) The system produces 48V DC at a continuous load of 10A and 110V AC. It includes 4000W solar modules, a charge controller, 24 batteries of 100-110AH at 12V DC, and a 2.5KVA inverter. 2) The solar modules are monocrystalline cells in an aluminum frame rated 245-260Wp each. 3) The system must power the gas chromatograph continuously and be warranted to produce at least 80% of peak power output after 15 years.

Uploaded by

Naqash Ahmed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 3

Specifications of SOLAR POWER SYSTEM

Department

MEASUREMENT
DEPARTMENT

Section

Gas Quality

Description
Spec #

SOLAR POWER SYSTEM FOR GAS CHROMATOGRAPHY


Meas. KT/SPSFGC/09-2012 (28-09-2012)

The Complete Solar Power System with nominal standard 48 Volts D.C, capable for
the continuous load of 10 Amps at 110 VAC for the operation of Gas Chromatograph
System.
The System comprising (A) Solar modules of capacity 4000 Watts, (B) Charge
Controller suitable for required Solar Modules and Battery Bank (C) Re-chargeable
GEL type Battery bank of 24 numbers of 100 to 110 AH at 12 VDC (D) Inverter of
capacity 2.5 KVA, 110/220 VAC user switchable and (E) All accessories including
cables, Junction Box, fixtures, fittings etc.
(A) Solar Module:
Modules should be framed photovoltaic Panels, Monocrystalline cells encapsulated
in toughened, low Iron, impact resistant, moisture proof glass laminate mounted in
anodized aluminum frame. The module shall be designed to withstand blowing
sand and dust with no damage to glass in presence of sand materials up to 1mm
in diameter, driven by a sustained 65 km ph winds with gusts to 112 kmph.
Modules shall be adequately protected from damage from temporary localized
shadowing i.e. having by pass diodes and blocking diodes to protect reverse
current during night hours. Solar cells be textured and anti reflective coating be
applied to increase conversion efficiency and low light irradiance

Nominal volt configuration


Solar Module System Power capacity
Module (s) Type
Each Solar module Capacity
Module Efficiency
Cell Efficiency
Max Power Voltage
Max Power Current
Open Circuit Voltage
Short Circuit Current
Operating Temperature
Panel output
Safety approval
D must conform

48 V DC standard
4000 Watts
Monocrystalline
245 to 260 Wp
14.35-15.24 c (%)
17.3-18 c (%)
50 Vm (V)
5.1 Im (A)
59.55 Voc (V)
5.5 Isc (A)
-10 Deg C to 85 deg C.
via junction box with 4 by-pass diodes
(Class 1, division 2, groups C &

To IEC 61215, safety 11 conformity to


CE, IEC 61730 and UL1703)
Specifications of SOLAR POWER SYSTEM
Department

MEASUREMENT
DEPARTMENT

Description
Spec #

SOLAR POWER SYSTEM FOR GAS CHROMATOGRAPHY


Meas. KT/SPSFGC/09-2012 (28-09-2012)

Warranty

Accessories
surface with

Section

Gas Quality

Limited peak power output warranty


Min 80 % of the prim after 15 years as per
International Warranty certificate.
Limited warranty for defect in material
Workmanship for 2 years as per
International Warranty Certificate.
All fittings and fixture for mounting on
Complete fixture stand etc with provision of
panels
Direction and adjustment.

General Requirement
(A) Manufacturers Authorization letter to quote their module and that they will
undertake rectification/replacement as per their International Warranty.
(B) The manufacturer of modules is ISO 9001 certified.
(C) Manufacturers / Suppliers should submit lists of clients with names and
addresses and performance satisfactory certificates from them, in Pakistan
and abroad for 5 previous years.
(D)The Solar Module being quoted by firms must submit a test report by one
of the laboratories given below:
1. Fraunhofer ISE, Heidenhofstr . 2D-79110 Freiburg, Germany
(www.ise.fhg.de)
2. NREL- National Renewable Energy Laboratory, 1617 Cole Blvd.
Golden, Co 80401-3393, USA (www.nrel.gov)
3. Arizona State University photovoltaic Testing Laboratory PTL
7349E, Unity Avenue, MESA, Arizona, 85212 USA
4. Post and Telecommunications Industry Products Quality Survillance and
Inspection Center (PTPIC), No 28 Xinjiekov-Wai 1000 88 Beijing
(www.ptpic.com.cn)
5. European Solar Installation Renewable Energies Unit Institute
for Environmental and Sustainability via E, Ferm 1 Ispra (VA) 21020, Italy
(www.ia,es.jre.it)
6. Tu V Rheinland Product Safety Gmbh, AmGracien Stein D 51105 Cologne,
Germany
(www.de.tuv.com)