Tutorial 2
Tutorial 2
QUESTION 1
In the two-bus system shown in Figure Q1, bus 1 is a slack bus with
V1 1.00
per unit. A load of 100 MW and 50 Mvar is taken from bus 2. The
line impedance is
Figure Q1
P2 (0)
and
J ( 0)
Q2 (0)
J 1 ( 0)
at bus 2.
and
J 2 ( 0)
for
V2
2
c) Obtain the voltage magnitude
and phase angle
of bus 2 that are
produced by the first iteration of the Newton-Raphson method.
I 12
QUESTION 2
For the system shown in Figure Q2, the line impedances are as indicated in
per unit on 100 MVA base.
Figure Q2
a) Define type of buses for the power system in Figure Q2 and list out
known as well as unknown parameters for each bus.
b) Using Gauss-Seidel method, find bus voltages
angles
2, 3
V2 ,
V3
and phase
2, 3
V2 ,
Raphson method.
d) State ONE (1) advantage and disadvantage between Gauss Seidel
and Newton Raphson method to determine unknown parameters in
power system.
QUESTION 3
For a three bus power system assume bus 1 is the swing with a per unit
voltage of 1.0
j0.5, and bus 3 is a PV bus with 1.0 per unit generation and a 1.0 voltage
setpoint. The per unit line impedances are j0.1 between buses 1 and 2,
j0.4 between buses 1 and 3, and j0.2 between buses 2 and 3. Using a flat
start, use the NewtonRaphson approach to determine the first iteration
phasor voltages at buses 2 and 3.
QUESTION 4
In the power system network shown in Figure Q4, bus 1 is a slack bus with
V 1=1.0 0
S2
= 280 MW +j60
Mvar. The line impedance on a base of 100 MVA is Z = 0.02 + j0.04 per
unit.
Figure Q4
a) Using Gauss-Seidel method, determine
of
V 2 ( 0 )=1.0+ j0.0
b) Determine S1 and the real and reactive power loss in the line.
QUESTION 5
In the two-bus system shown in Figure Q5, bus 1 is a slack bus with
V 1=1.0 0
pu. A
load of 150 MW and 50 Mvar is taken from bus 2. The line admittance is
y 12=10 73.74
voltage magnitude and phase angle of bus 2. Start with an initial estimate of
pu and 2=0 . Perform one iteration.
Figure Q5
V 2 =1.0