Protection Relay of Generator Test
Protection Relay of Generator Test
Document Class
HK1
D
C
For Commissioning
Revised as commen
B
A
Revised as comment
For approval
Rev.
Description
Agustus
03 , 2016
Date
Hasni
Rahman
Tirda
Yoga
Prepare
d
Checke
d
Reviewe
d
Approve
d
OWNER`
S
DWG.NO
DWG. NO.
DATE OF ISSUED
Agustus 03, 2016
REVISION NO.
REV
Commissioning Procedure
HK-
Page 2 of 6
TABLE OF CONTENTS
1.
2.
3.
4.
5.
6.
7.
8.
9.
COVER...............................................................................................................
SCOPE.................................................................................................................
OBJECTIVE........................................................................................................
REFERENCE.......................................................................................................
TEST INSTRUMENT.........................................................................................
RISK AND SAFETY PRECAUTION.................................................................
VISUAL CHECK.................................................................................................
SYNCHRONIZING RELAY TEST PROCEDURE...........................................
ATTACHMENT..................................................................................................
1
3
3
3
3
3
3
4
4
Commissioning Procedure
HK-
Page 3 of 6
1. Title
Protection Relay of Generator Test
2. Scope
Protection relay test for generator. Consisting of functions as follows, over
current, under and over voltage, under and over frequency loss of field reverse power.
3. Objective
This test is to assure the relay can trip or give alarm to the system when
something happend on generator operation.
4. Reference
- Manual instruction of substation test set ISA T-3000
- Manual instructur of generator relay siemens 7UM62
5. Test instrument
- Substation test set ISA T-3000
- Power supply 3 phase 0~400V
6. Risk and safety precaution
-
7. Check visual
-
REV
Commissioning Procedure
HK-
8. Test procedure
Page 4 of 6
Point A = K2
Set the angle to 90o or 270o
Set the current to 5A
Increasing the voltage from zero until the relay trips
Put red cable of current of T-3000 on terminal relay #
Put black cable of current of T-3000 on terminal relay #
Put red cable of voltage of T-3000 on terminal relay #
Put block cable of voltage of T-3000 on terminal relay #
Install stop cable to rip contact of relay
PLTU Kendari Unit 3 (110 MW) Project
Protection Relay of Generator Test
REV
Commissioning Procedure
HK-
Point B = K1
Set the current to 5A
Set the angle to 270o
Decreasing the voltage from 90V to zero until the relay trips
Page 5 of 6
Forward test :
I = In = 5A : = 0o press ON + TIME, the relay should out trip
Reverse test :
I = In = 5A : = 1800 press ON+TIME, the relay should trip
REV
Commissioning Procedure
HK-
Page 6 of 6
Put red and block cables of voltage of T-3000 on voltage terminal of relay
Install stop cable to trip contact of the relay
Power on T-3000 and press ON+TIME button
Adjust voltage close to setting value (from zero to 120V)
Relay will trip and calculate the time
Record the result
Do same thing for under voltage