Electrical Drawings Checklist Updated
Electrical Drawings Checklist Updated
Case ID:
Electrical Contractor Name :
Date
2nd Submission
3rd Submission
|P age 1
Part 1
1.
Set up of Drawing
1.1. Case Related Comments:
1.2. Drawing Title to be mentioned.
1.3. No space for ADDC stamp.
1.4. Type of Project to be mentioned.
1.5. Minimum size of the drawing sheet A1 or A0 required.
1.6. Scale of the drawing to be mentioned.
1.7. Electrical room location and cable entry approval to be shown.
1.8. Single Line Diagram, load schedule, lighting layout, power layout, site plan
drawing sheet to be submitted.
1.9. Owner name should be written.
1.10. Main Contractor name & stamp to be mentioned.
1.11. Consultant name & stamp should be mentioned.
1.12. Electrical Contractor name & stamp to be mentioned.
1.13. Sector & Plot number should be shown.
1.14. Drawing Sheet Number to be marked.
1.15. Legend should be added.
1.16. Legend and layout are not matching.
1.17. All layouts must be clear.
1.18. Grid marking required
1.19. Electrical layouts must match with approved architectural drawings
1.20. Meter schedule to be provided
1.21. Light and Power Layouts to be colored according to phase color (red, yellow,
blue) and ALL other drawings to be in BLACK color.
1.22. Drawings or attachments missing.
1.23. Discuss project before re-submitting, for appt. call 800ADDC
|P age 2
Part 2
2.
MDB shall be installed on dry, well-ventilated area and not very closed to
window or door.
2.11.
2.13.
acceptable.
2.14.
2.15.
Cable route for the outgoing cables to be within the plot limit.
2.16.
Route of the cables / bus bar riser to be shown and shall be through
common area and away from gas line, water pipe, AC duct .
2.17.
|P age 3
2.18.
be shown.
2.19.
2.20.
2.21.
2.22.
2.23.
2.24.
2.25.
2.26.
Bus bar Riser rating must be same as rating of feeding circuit breaker.
2.27.
electrical room.
2.28.
2.29.
2.30.
circuit breakers (such as CBs, MCBs, MCCBs, ACBs, RCDs, RCBOs) and
shall not be contain fusses of any kind.
2.31.
2.32.
2.33.
2.34.
2.35.
2.37.
separate duct.
2.39.
Distance and voltage drop calculations must be provided for all cables (in
volts).
|P age 4
2.40.
The maximum voltage drop from the connection point to the area of final
Circuit breaker rating shall be match with load and cable size.
2.42.
In case of feeding different blocks from one LV panel each block must
2.44.
2.45.
requirement.
2.46.
GRP meter, cabinet shall be from approved ADDC type with shutter door
2.48.
2.49.
requirement
2.51.
For supplying of 500A rating and above at least two independent earth
|P age 5
Part 3
3.
mentioned.
3.11.
3.12.
3.13.
3.14.
3.15.
3.16.
3.17.
For group of villas, location of SMDB electric room shall be close to the
villa.
3.18.
Separate earth pit is required if SMDB is more than 30 meter far away
|P age 6
Part 4
4.
they serve. It should not be under staircase, bedroom, kitchen and bath wall.
4.11.
Breaker rating for lighting 6-15A for radial circuit 20A, for rings sockets
30A and for water heater window AC and other power points 20A, cooker
30A, to be used.
4.14.
4.15.
4.16.
4.18.
Under floor trunking shall be purpose made metallic trunking for under
RSB.
|P age 7
4.20.
4.21.
4.22.
4.23.
Calculation of cooker load shall be 3000 watt PLUS the largest ring or
actual rating.
4.24.
4.25.
All sockets outlets and flexible outlets shall be with isolating switch.
4.26.
Circuit supplying a kitchen must not be to used supply any other area.
4.27.
4.28.
4.29.
RSB.
4.31.
position.
4.32.
4.33.
|P age 8
Part 5
5.
5.11.
5.12.
5.13.
5.14.
panel
5.15.
5.16.
5.17.
5.18.
Three phase Sockets for cleaning cradle shall not be looped together.
5.19.
from MDB.
|P age 9
5.20.
5.22.
5.23.
Breaker capacity and size of cable shall be match with chiller load.
5.24.
5.25.
5.26.
5.28.
reactor.
5.29.
Data sheet shall be submitted with highlight the model number to prove
power factor between 0.9 lagging and unity for residential villas.
| P a g e 10
Part 6
6.
All single phase motor above 1 H.P and three phase motors above 3H.P
6.12.
6.13.
6.14.
system.
6.15.
Length and voltage drop for pole lights circuit/ boundary lights circuit to
be shown.
6.16.
6.17.
| P a g e 11
Part 7
7.
7.11.
Outside socket outlets must be provided with integrate RCD (30 mA)
protection.
7.12.
7.13.
7.14.
7.15.
7.16.
Single phase socket outlets shall be blue in color and three phase socket
outlet.
7.18.
7.19.
| P a g e 12
7.20.
7.21.
Labeling along PV d.c cables shall be provided to indicate the polarity and
| P a g e 13