Installation Instructions: Netcontroller Ii
Installation Instructions: Netcontroller Ii
30-3001-994
Rev C.1
NetController II
Mounting
Screw
Andover Continuum
Power Supply Connector
I/O Bus
Connector
Third-Party
Power Supply Connector
Mounting
Screw
Cover
Mounting
Screw
BOTTOM PANEL
Cover Tab
Cover Tab
3. Connect the Ethernet and Communication Port connections based on your requirements. (See the Ethernet and
Comm Port Connections section of this document.)
4. Connect the power supply connector of the controller to an
Andover Continuum power supply or third-party UL Listed UL
294 or UL 603 power limited power supply. Access the PC
board and connect the battery. (See the DC Power and Battery
Backup Connections section.)
5. Apply power to the controller and I/O modules.
6. Configure the controller using the controllers embedded WebServer pages and CyberStation. For more information, refer to
the Related Documentation section at the end of this document.
Mounting Instructions
DIN RAIL
2
PANEL
1
Physical Dimensions
222.3 mm
8.75
152.4 mm
6.00
63.5 mm
2.50
Wiring Rules
These modules are intended for installation
within the UL Listed enclosure 3P-UL-ENCL
for UL 294 and UL 1076.
For reliable operation, follow these wiring guidelines:
Never lay wires across the surface of a printed circuit board.
Use shielded wire.
Terminate the shield of the wires at one end of the run
only preferably at the end where your I/O module is located.
When stripping wire, be careful not to drop small pieces of wire
inside the cabinet.
Dont run your wiring in the same conduit with
AC power.
Dont run your wiring in the same conduit with your
output wiring.
module damage.
Continuum
Power Supply
I/O
NetController II
I/O
24VDC
Battery
Supply
2-Conductor
Shielded Power Cable
from Power Supply
Third-Party
DC Power Supply
2-Conductor
Shielded
Power Cable
BAT
( )
NetController II
2-Conductor Shielded
data cable from
NetController
12VDC, 7AH
Battery
( )
( )
(+)
(+)
12VDC, 7AH
Battery
I/O
I/O
I/O
I/O
I/O
!
Use care when attaching power
wiring to these connectors.
They are not to be used as a strain relief.
The connectors cannot withstand
excessive bending or flexing.
+ 12 to 28VDC
VDC Return
AC POWER
24 VAC
20 VA
50/60 HZ
L
DC POWER
12 - 28 VDC
10 W
90
50
Warning
Ribbon Cable
Connectors
Receptacle
_
+
Battery
The NetController II can directly connect to the I/O modules without using cables through a system of built-in plugs and jacks. All I/O modules
include two complementary module connectors. Creating a system is as
simple as physically plugging the modules together. (See the Horizontal
and Vertical Connection illustrations below).
LON Interfaces
The NetController II supports two types of Local Operating Network (LON) bus media:
RS-485 (ACC-LON) Default setting
Horizontal Connection
I/O Bus Connector
Power Supply
I/O Bus
Connector
5
4
3
2
1
PIN
5
4
24 VDC Return
3
2
Shield
Comm B
Comm A
Power Supply
I/O
Power Supply
Net
Controller II
NetController II
Vertical Connnection
5
4
3
2
1
I/O
I/O
Function
+24 VDC
NetController II
NetController II
I/O
I/O
Port
COMM2
COMM1
Ethernet
COMM3
COMM4
Ethernet Cable w/
RJ-45 Connector
Connector Interface
Ethernet
Comm1
RS-232
ETHERNET
RS-485 (3-pin)
Service Port cable (Wireless Adapter or RoamIO2)
Comm2
Comm3
Service Port
RS-232
(Optional) Modem (RJ-11)
Comm4
RS-422 (L-Bus) or
Wireless Adapter or RoamIO2
(COMM1 and COMM2)
RS-485 (5-pin)
COMM 4*
RS-422 Connector
1
COMM 1 & 3*
COMM 3*
RJ-11 Modem Connector
(Optional)
RS-232 Connectors
RX+ (IN+)
TXD
DSR
RD
Ground
RTS
DCD
CTS
DTR
RX- (IN-)
Shield
TIP
TX+ (OUT+)
RING
TX- (OUT-)
COMM 4*
COMM 1*
RS-485 Connector
+
Shield
COMM 2*
RS-485 Connector
+
Shield
RS-485 Connector
(Jumpers convert
RS-422 to RS-485)
+
Shield
Earth Ground
+
* The Ethernet connector has been
evaluated by UL for UL294/UL1076.
All other communication connectors
have been evaluated by UL for
supplemental use.
Specifications
Dimensions
8.75 W x 6.00 L x 2.5 H (222.3 x 152.4 x 63.5 mm)
Weight
1.5 lbs. (0.68 kg)
Enclosure Type
UL open class, flammability rating of UL94-5V, IP 10
Mounting
DIN rail or wall mount using attached fasteners. Andover
Continuum UL Listed enclosure model 3P-UL-ENCL is available
for UL 294 and UL 1076.
Operating Environment
Temperature: 32o to 122o F (0o to 50o C)
Humidity: 10 to 90% RH, non-condensing
Input Power
Andover Continuum Power Supplies:
PS 120/240 AC 85 (not evaluated by UL)
PS 120/240 AC 85-U (AC 85-U can only be used for UL 294)
Third Party Power Supply:
1228VDC @ 10W
24VAC @ 20VA, 50/60 Hz.
Internal Battery
NiMH, 3.6 VDC, 800 mAh
Real Time Clock
Battery-backed by UPS and internal battery.
Comm. Error Checking
International Standard CRC 16.
Ethernet LAN Interface
10/100 Ethernet: Ethernet cable with RJ-45 connector.
Serial Comm. Interface
Four programmable ports, software configurable as printer, modem,
wireless adapter, ROAM I/O, or third-party system. Infinet can be
configured on Ports 1 and 2.
Comm1: RS-232, RS-485, Service Port
Comm2: Service Port, RS-485
Comm3: RS-232, (optional) Modem (RJ-11 connector)
Comm4: RS-422 (L-Bus) or RS-485
Serial Comm. Speed
Comm1: Baud rates up to 38.4 K for RS-232 mode.
Comm3: Baud rates up to 38.4 K when configured for RS-232 or
internal modem.
Infinet Bus Length
4,000 ft (1,220m) standard for Infinet using approved shielded, twisted
pair, low capacitance cable. InfiLink module allows extensions to longer
distances.
I/O Bus
ACC-LON communications. Choice of bus media, RS-485 or
FTT-10A.
RS-485 Bus
Comm. Speed: 39K baud
Bus Length:
2,000 ft. (610m)
Bus Media:
Shielded, twisted pair cable. 120 ohm termination
required at both ends of the ACC-LON network
(when modules are mounted remotely).
FTT-10A Bus
Comm Speed: 78K baud
Bus Length:
Up to 8858 ft. (2700m) bus topology
Up to 1640 ft. (500m) free topology. Repeater required
for longer distances.
Bus Media:
Refer to Echelon FTT-10A free topology documentation
Connections
Power: 5-position plug-in connector on left side of module for
direct connection to Continuum power supply module.
3-position connector on left side of module for connection to a
third-party power supply module.
I/O Bus: 5-position plug-in connector on right side of module for
direct connection of up to 32 I/O modules.
Ethernet: RJ-45 connector for 10/100 Ethernet.
Printer: RJ-45
Modem: RJ-11 Connector
Status Indicator LEDs
System: Power, CPU, Error
Comm1: TD, RD, DCD, DTR
Comm2: TD, RD
Comm3/Modem: TD, RD, DCD, DTR, MODEM
Comm4: TD, RD
I/O Bus: Status
Ethernet: ACT/LINK, 10/100 Mbps
Push Button Switches
Clear Memory: RESET/Clear Memory
Reset IP Address: (On PC board) Resets Network address settings in
flash memory and restores all non-volatile settings to
factory defaults.
Regulatory Notices
Federal Communications Commission
FCC Rules and Regulations CFR 47, Part 15, Class A
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference.
(2) This device must accept any interference received, including interference that may cause undesired operation.
Complies with FCC Part 68 Rules (when optional modem is installed).
FCC Registration Number: AU7NMOIBMT5656R REN Number: 0.1B
Caution: The user that changes or makes modifications not expressly approved by Schneider Electric for compliance could void the users authority to operate the equipment.
Industry Canada
ICES-003
This is a Class A digital device that meets all requirements of the Canadian Interference Causing Equipment Regulations.
UL 916 Listed product for the United States and Canada, Access Control Equipment
UL 294 (Access Control System Unit Subassemblies for the United States) and UL 1076 (Proprietary
Burglar Alarm System Unit Subassemblies for the United States) and C22.2 No. 205-M1983 (Signal
Equpment for Canada)
Note: Refer to the UL Listed Access Control Propietary Burglar Alarm System installation manual (the UL 294 Access Control and UL
1076 Proprietary Burglar Alarm Systems Reference 30-3001-504) for specific wiring, operation, and compatibility information.
Related Documentation
The following related documentation provides more information on Andover Continuum products. These
documents are neither required nor evaluated by Underwriters Laboratories (UL) for UL Listings.
Document
Document Number
30-3001-995
30-3001-996
30-3001-1000
Schneider Electric
One High Street
North Andover, MA 01845
(978) 975-9600
Fax: (978) 975-9782
http://www.schneider-electric.com/buildings