Sample Leak Testing Report For Ast Tank

The document summarizes the results of a leak test performed on the bottom and annular welds of an above ground storage tank. The test involved cleaning and preparing the welds, applying a foamy liquid and vacuum box, and observing for bubbles under 300 bar of vacuum pressure for 10 minutes. No bubbles were observed, indicating no leaks. Both the bottom plate and annular plate welds met acceptance criteria and were found to be in acceptable condition as of the date of inspection.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
43% found this document useful (7 votes)
12K views1 page

Sample Leak Testing Report For Ast Tank

The document summarizes the results of a leak test performed on the bottom and annular welds of an above ground storage tank. The test involved cleaning and preparing the welds, applying a foamy liquid and vacuum box, and observing for bubbles under 300 bar of vacuum pressure for 10 minutes. No bubbles were observed, indicating no leaks. Both the bottom plate and annular plate welds met acceptance criteria and were found to be in acceptable condition as of the date of inspection.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 1

REPORT No.

LEAK TESTING REPORT FOR ABOVE


GROUND STORAGE TANK; (PMS)

LOGO

Project: INTEGRITY ASSESSMENT OF PMS TANK

Quality Control Form:

Client:
AREAS OF INSPECTION: TANK BOTTOM AND ANNULAR WELD JOINTS

Report
Date:

CODE FOR INSPECTION: API653 AND API650

MATERIAL: CARBON STEEL

PROCEDURE:
1. PROPERLY CLEAN AND PREPARE ALL WELDMENTS.
2. APPLY LEAN QUANTITY OF FOAMY LIQUID & SET VACUUM BOX
DIRECTLY ON WELDMENT TO BE TESTED, AND THEN APPLY
COMPRESSED AIR.
3. THE PRESSURE BUILD UP, WILL SEAL THE WELDMENT SURFACE AND
ALLOW VACUUM OF MAXIMUM OF 300 BAR TO EXIST WITHIN THE
BOX FOR 10 MINS.
4. FINALLY, CAREFULLY AND PATIENTLY OBSERVE INSIDE THE VACUUM
BOX THROUGH THE GLASS FOR ANY CONTINOUS BUBBLE. WHICH
CAN BE INDICATIVE OF A LEAK ALONG ANY WELDMENT UNDER TEST
Area: TANK BOTTOM & ANNULAR
PLATE
Material: A283 GRADE C;

Category: NA
Welding process: NOT REQUIRED

Prepared edge

State of Examination
X
Surface Preparation

Size: NOT REQUIRED

As weld

Brushing

After PWHT
Repair
As weld

ACCEPTANCE
CRITERIA

FOAMY LIQUID

Thickness (Average): 9.5mm & 5.5mm

Other
X

CONSUMABLES

GAMMATEC

Base Metal

Grinding

EQUIPMENT

TEST PRESSURE; 300BAR (4.4Psi)


VACUUM BOX DIMENSIONS: 70cm
x25cmX8cm

Other

LIGHTING IN TANK

API653

100LUX

Temperature

AMBIENT

TEST RESULT
CML

JUDGMENT

BOTTOM
PLATE

ANNULAR PLATE

TOP SIDE

TOP SIDE

INTERNAL

INTERNAL &
EXTERNAL

DEFECTS

Accept

Reject

NIL

OK

NIL

OK

Date of
Inspection

Remarks

OK AS OF DATE
OF INSPECTION
OK AS OF DATE
OF INSPECTION

REPORT SUMMARY FOR PMS TANK 31;


NO BUBBLE WAS OBSERVED DURING THE VACUUM BOX TEST. THE TANK BOTTOM STEEL PLATE AND
ANNULAR PLATE WELDMENTS MEET THE ACCEPTABLE CRITERIA OF API653 & API650 AS AT THIS DAY OF
PROJECT
SUPERVISORS

REVIEWED BY

1.
2.

API INSPECTOR &


ENGINEER

APPROVED BY

CLIENT