Measurement of Level in A Tank Using Capacitive Type Level Probe
Measurement of Level in A Tank Using Capacitive Type Level Probe
Pre-requisite:
Before performing this experiment, student must have knowledge about
1. Working of a typical Capacitor
2. Types of Capacitors
3. Effect of various factors that affect the output of a capacitor
e.g. temperature, dielectric constant of
insulator used, distance between the plates, are of the plates used, etc.
Level measurements
In industry, liquids such as water, chemicals, and solvents are used in various
processes. The amount of such liquid stored can be found by measuring level of the
liquid in a container or vessel. The level affects not only the quantity delivered but also
pressure and rate of flow in and out of the container.
Level sensors detect the level of substances like liquids, slurries, granular materials,
and powders. The substance to be measured can be inside a container or can be in its
natural form (e.g. a river or a lake). The level measurement can be either continuous or
point values.
Continuous level sensors measure the level to determine the exact amount of
substance in a continuous manner.
Point-level sensors indicate whether the substance is above or below the sensing
point. This is essential to avoid overflow or emptying of tanks and to protect pumps from
dry run.
Temperature
Pressure or vacuum
Chemistry
Agitation (action)
Vibration
Mechanical shock
Price
Accuracy
Response rate
Ease of calibration
Direct methods
Indirect methods
Dip Stick
Resistance Tapes
Sight Glass
Floats
Ultrasonic
Radar
Load cell
Capacitance
Conductivity
Capacitance level sensors are used for wide variety of solids, aqueous and organic
liquids, and slurries. The technique is frequently referred as RF as radio frequency
signals applied to the capacitance circuit. The sensors can be designed to sense
material with dielectric constants as low as 1.1 (coke and fly ash) and as high as 88
(water) or more. Sludges and slurries such as dehydrated cake and sewage slurry
(dielectric constant approx. 50) and liquid chemicals such as quicklime (dielectric
constant approx. 90) can also be sensed. Dual-probe capacitance level sensors can
also be used to sense the interface between two immiscible liquids with substantially
different dielectric constants.
Since capacitance level sensors are electronic devices, phase modulation and the use
of higher frequencies makes the sensor suitable for applications in which dielectric
constants are similar.
Working Principle:
The principle of capacitive level measurement is based on change of capacitance. An
insulated electrode acts as one plate of capacitor and the tank wall (or reference
electrode in a non-metallic vessel) acts as the other plate. The capacitance depends on
the fluid level. An empty tank has a lower capacitance while a filled tank has a higher
capacitance.
A simple capacitor consists of two electrode plate separated by a small thickness of an
insulator such as solid, liquid, gas, or vacuum. This insulator is also called as dielectric.
Value of C depends on dielectric used, area of the plate and also distance between the
plates.
Where:
C = capacitance in picofarads (pF)
E = a constant known as the absolute permittivity of free space
K = relative dielectric constant of the insulating material
A = effective area of the conductors
d = distance between the conductors
This change in capacitance can be measured using AC bridge.
Measurement:
Measurement is made by applying an RF signal between the conductive probe and the
vessel wall.
The RF signal results in a very low current flow through the dielectric process material in
the tank from the probe to the vessel wall. When the level in the tank drops, the
dielectric constant drops causing a drop in the capacitance reading and a minute drop
in current flow.
This change is detected by the level switch's internal circuitry and translated into a
change in the relay state of the level switch in case of point level detection.
In the case of continuous level detectors, the output is not a relay state, but a scaled
analog signal.
Level Measurement can be divided into three categories:
Non-contact measurement
Non-conducting material:
For measuring level of non conducting liquids, bare probe arrangement is used as liquid
resistance is sufficiently high to make it dielectric. Since the electrode and tank are fixed
in place, the distance (d) is constant, capacitance is directly proportional to the level of
the material acting as dielectric.
Conducting Material:
In conducting liquids, the probe plates are insulated using thin coating of glass or plastic
to avoid short circuiting. The conductive material acts as the ground plate of the
capacitor.
Proximity measurements (Non-contact type measurements):
In Proximity level measurement is the area of the capacitance plates is fixed, but
distance between plates varies.
Proximity level measurement does not produce a linear output and are used when the
level varies by several inches.
Advantages of Capacitive level measurement:
1. Relatively inexpensive
2. Versatile
3. Reliable
4. Requires minimal maintenance
5. Contains no moving parts
6. Easy to install and can be adapted easily for different size of vessels
7. Good range of measurement, from few cm to about 100 m
8. Rugged
9. Simple to use
10. Easy to clean
Guided-wave technology sends the radar pulse down a probe that extends into the tank contents,
either liquid or solid. Typically, theyre mounted from the tank top hanging down. The pulse hits
the surface and is reflected back up the probe to the sensor, where the transit time is translated
into a distance. This is very similar to through-air radar, which accomplishes the same action
without the probe.
This technology gives a very precise continuous reading, is energy efficient (a consideration for
potential battery-powered wireless connectivity), and can operate in difficult situations where
other approaches fail.
The probe concentrates the energy pulse much as speaking through a tube concentrates the
sound. This is particularly useful under certain conditions where a through-air pulse is less
reliable:
Turbulent liquids;
Problematic solids.
A unit can only measure as far as the probe extends. There is no theoretical
limit, but there are practical issues when they get very long.
Sticky material can build up on a probe. Various designs can see through this
to a point, but eventually it will interfere with an accurate reading.
In some cases, probes have been bent to read around corners. This is tricky,
though, and you should consult with your provider as to practicality.
The probe does not have to be the full length of the tank unless you need
readings all the way to the bottom. If the process only needs readings in the
upper half of the tank, thats all the length you need.
Operating pressuresUltrasonic devices are not intended for extreme pressure limits;
maximum working pressures should not exceed 30 psig.
GWR is based on the principle of time domain reflectometry (TDR). With TDR, a low-energy
electromagnetic pulse is guided along a probe. When the pulse reaches the surface of the medium
being measured, the pulse energy is reflected up the probe to circuitry that then calculates the
fluid level based on the time difference between the pulse being sent and the reflected pulse
received. The sensor can output the analyzed level as a continuous measurement reading via an
analog output, or it can convert the values into freely positionable switching output signals.
Unlike older technologies, GWR offers measurement readings that are independent of the
chemical or physical properties of the process media with which it is in contact. Additionally,
GWR performs equally well in liquids and solids.
GWR is suitable for a variety of level measurement applications including those that involve:
Agitated surfacesBoiling surfaces, dust, foam, and vapor do not affect device
performance. GWR also works with recirculating fluids, propeller mixers, and aeration
tanks.
Fine powders and sticky fluidsGWR works with vacuum tanks filled with used
cooking oil as well as tanks holding paint, latex, animal fat, soybean oil, sawdust, carbon
black, titanium tetrachloride, salt, and grain.
One of the most common misconceptions about GWR is how product build-up on the probe
affects the level measurements. One would think that if you have a mass of product stuck to the
probe, or a coating of product over the probe's entire length, that the signal would misidentify the
true liquid surface (Figure 3). This is not the case. The GWR radar signal has a very large
detection area360 and extending out several feetaround the probe. When the
electromagnetic pulse comes in to contact with a mass of product on the probe, the signal is
returned and analyzed to see whether it reflects the true liquid level (Figure 4). Because the true
liquid level always has a larger return signal than the return signal generated from the smaller
mass sticking to the probe, the sensor can easily identify the liquid surface. Algorithms
developed over the last decade have made this contacting form of level measurement an
excellent choice for even the stickiest of fluid-level applications.
Figure 3. Sticky product covered over a 2 in. length of 1/4 in. o.d. rod probe
Figure 4. Sound energy pulse advances outward from the probe surface
Comparison Points
The chart in Figure 5 compares some important comparison points between ultrasonic and GWR
transmitters:
Figure 5. A comparison between ultrasonic and GWR transmitters
Ultrasonic transmitters
Sound waves
Noncontact measurement
Contact measurement
Operating Limits
Mounting
Top-mounted
Top-mounted
Environmental and Application Conditions
Overall Performance
Acceptable
Performance is based on strength of the
reflected sound wave or echo
Exceptional
Performs well independent of process
conditions