Earthing and Testing
Earthing and Testing
Chapter 5
Earthing
Earthing means connection of the neutral point of a supply system or the non-current
carrying parts of electrical apparatus such as metallic frame work, metallic covering of
cables, metal covers of switches, metal casing of portable apparatus, frame of every
generator and motor etc. to the general mass of earth in such a manner that at all times
an immediate discharge of electrical energy takes place without danger.
Earth Electrodes Resistance
If we were to place an electrode in the earth and then measure the resistance between
the electrode and points at increasing larger distance from it, we would notice that the
resistance increased with distance until a point was reached (usually around 2.5m)
beyond which no increase in resistance was seen.
R(ohm)
1.5m 3m
6m
Distance(m)
Fig.1
The value of this electrode resistance will depend on the length and cross-sectional
area of the electrode and the type of the soil.
Typical Value of Soil Resistivity in Ohms
Garden Soil
5 to 50
Clay
10 to 100
Sand
250 to 500
Rock
1000 to 10,000
Earth-fault-loop path
Fig. 2 shows the path taken by an earth-fault current. This system has a direct
connection of the supply transformer to earth and a direct connection of the installation
metalwork to earth.
________________________________________________________________________________69
Earthing and Testing
__________________________________________________________Electrical Installation
Supply Transformer
CPC
The total sum impedance of the individual parts of the path is known as the loop
impedance, Zs. This is made up of :
Ze which is the impedance external to the consumers intake terminals and
include the supply transformer secondary winding, the phase conductor and
the metallic return path (general mass of earth) back to the supply
transformer earthing arrangement.
The value of Zb depends on the type of supply system.
R1. Which is the resistance of the phase conductor from the supply intake
position to the final circuit load.
R2. Which is the resistance of the circuit protective conductor (CPC).
The total earth-loop impedance is thus:
and
Zs = Ze + (R1 + R2)Ohms
If = Vs / ZS
Where If is the fault current and VS is the nominal voltage to earth (usually 220 V).
The loop impedance Ze external to the installation may be measured in existing
installations using a phase-to-earth loop impedance tester. However, when a building is
noly at the drawing board stage, we have three methods available to assess the value of
Ze:
(I) determine it from details (if available) of the supply transformer, the main distribution
cable and the proposed service cable: or
(II) measure it from the supply intake position of an adjacent building having service cable
of similar size and length to that proposed; or
(III) use maximum likely values issued by the supply authority. Having established ZS, the
resistance of the phase conductor (R1) plus the resistance of the CPC (R2), i.e. R1+R2
calculated for the type of conductor used (normally copper or aluminum).
(I)
(II)
Testing of Installation
________________________________________________________________________________70
Earthing and Testing
__________________________________________________________Electrical Installation
The tests to be performed before a new installation or an addition to an existing
installation is connected to the supply mains are as follows:
1. Insulation Resistance
The insulation resistance between the wiring and earth with all fuses
(breakers) and lamps in and all switches ON
1.2. The insulation resistance between the conductors with all lamps out
and all switches ON
2. Testing of polarity of non-linked single pole switches.
3. Testing of earth continuity path.
4. Testing of earth-electrode resistance.
1. Insulation Resistance
The aim of this test is to know whether the wires or cables used in the wiring are
sufficiently insulated to avoid leakage current. Test is performed by a DC source not
less than twice of working voltage but not exceeding 500 V. A 500 V tester, known as
Megger is used for this purpose.
Since installation circuits are wired in parallel, one can see that for a very large
Installations an insulation resistance test at the intake position may show a low value,
which isnt actually due to bad insulation. In order to overcome this problem, EELPA
regulation (SECTION E-2) permits such installation to be broken down into smaller
units of not less than 50 outlets.
Testing of Insulation Resistance Between the Wiring and the Earth.
a)
b)
c)
d)
e)
Final
Circuits
Insulation
Resistance
Tester
All Switches
Closed
DB
________________________________________________________________________________71
Earthing and Testing
__________________________________________________________Electrical Installation
Fig. 1. Insulation Resistance to Earth
The line terminal of the megger (marked as L) is connected to the point where
the conductors have been shorted at the main switch and the E terminal is connected to
the earth. Now the handle of the tester is turned so that it begins to slip and the reading
on the dial gives the insulation resistance between the wiring and earth.
The insulation resistance to earth measured should not be less than 1 Mega
220v
)
ohm. Very small leakage current (IL =
1 M
Testing of Insulation Resistance Between Conductors
The objective of this test is to ensure that the insulation is sound between the
conductors so that there may not be an appreciable leakage between them.
In this test the circuit diagram remains the same as in Fig.1 except that all the lamps
and all metallic connections between the two wires of the installation are removed
from the holders.
With the supply isolated, all protective devices in place, and all single pole switches in
ON position; the terminals of the megger are connected between poles (i.e. R to S, R
to T, S to T, and each pole in turn to N). The reading should not be less than 1 Mega
ohm.
Final Circuit
Insulation
Resistance
Tester
DB
All switches closed
________________________________________________________________________________72
Earthing and Testing
__________________________________________________________Electrical Installation
P
Lamp Holder
SW
Test Lamp
(Light)
________________________________________________________________________________73
Earthing and Testing