MX Operating Manual
MX Operating Manual
MX
PUBLICATION:
17A-05-O
01
8/00
http://www.firealarmengineers.com
DOCUMENT CONTROL NUMBER
INTRODUCTION
1.1 KEY FUNCTION AND FEATURES
4
4
2.
OPERATING INSTRUCTIONS
2.1 OPERATORS INDICATORS
AND CONTROLS
2.1.1 GENERAL
2.1.2 OPERATOR DISPLAY
MODULE
2.1.3 OPERATOR CONTROL
MODULE
2.2 LCD DISPLAY
2.2.1 FIRE WINDOW
2.2.2 STATUS WINDOW
2.2.3 MAIN WINDOW
2.2.4 SOFTKEY WINDOW
2.3 NORMAL OPERATION
2.3.1 EVENT MONITORING
2.3.2 EVENT DISPLAY
2.4 OPERATION IN ALARM
2.4.1 SYSTEM RESPONSE
2.4.2 SOUNDER SILENCING
2.4.3 RESETTING THE CONTROLLER
2.4.4 MULTIPLE EVENTS
2.4.5 PRE-ALARM WARNINGS
2.5 OPERATION IN FAULT CONDITION
2.5.1 SYSTEM RESPONSE
2.5.2 OPERATOR ACTION
2.6 FIRE CONTROL KEYS
2.6.1 EVACUATE or FIRE ALARM
2.6.2 DAY/NIGHT MODE
2.6.3 TEST
2.7 AUXILIARY DISPLAY DEVICES
2.7.1 GENERAL
2.7.2 REPEATERS
2.7.3 PRINTERS
3.
CONTROLLER FUNCTIONS
3.1 ACCESS LEVELS
3.1.1 GENERAL
3.2 ENTERING PASSCODES/
FAST ACCESS CODES
3.3 VALID VALUES
3.4 MAIN MENU
3.5 ACTUAL STATUS
6
6
6
8
10
10
10
10
10
11
11
11
11
11
12
13
13
13
13
13
13
14
14
14
14
14
14
15
15
4.
3.6 ISOLATE/DE-ISOLATE
3.7 TIME/DATE
3.7.1 SET TIME/DATE
3.7.2 SUMMER/WINTER
3.8 EVENT LOG
3.8.1 VIEW EVENT LOG
3.8.2 PRINT EVENT LOG
3.9 VIEW/PRINT STATUS
3.9.1 VIEW/PRINT POINTS
ISOLATED
3.9.2 VIEW/PRINT POINTS
UNTESTED/FAILED
3.9.3 VIEW/PRINT POINT VALUES
3.9.4 VIEW FAULTS
3.10 SERVICE
3.10.1 WALK TEST
3.10.2 MAINTENANCE ENGINEER
18
19
19
20
20
20
20
21
21
21
22
22
22
23
ROUTINE CHECKS
4.1 GENERAL
4.2 DAILY CHECKS
4.3 WEEKLY CHECKS
25
25
25
25
21
15
15
15
16
16
17
17
PAGE 1 of 25
EQUIPMENT:
MX
PUBLICATION:
17A-05-O
01
8/00
http://www.firealarmengineers.com
Fig. 1
PAGE 3 of 25
MX
17A-05-O
01
8/00
http://www.firealarmengineers.com
1.
INTRODUCTION
1.1
PAGE 4 of 25
EQUIPMENT:
MX
PUBLICATION:
17A-05-O
01
8/00
http://www.firealarmengineers.com
PAGE 5 of 25
MX
17A-05-O
01
8/00
http://www.firealarmengineers.com
2.
OPERATING INSTRUCTIONS
2.1
OPERATORS INDICATORS
AND CONTROLS
2.1.1
GENERAL
Used to enter the number 1 or special
symbols
PAGE 6 of 25
SCROLL UP and SCROLL DOWN keys used to scroll through a display or log one
entry at a time. These keys will auto-repeat
if held down, ie, will scroll continuously.
EQUIPMENT:
MX
PUBLICATION:
17A-05-O
01
8/00
SOFTKEYS
SCROLL UP
SCROLL DOWN
FAST ACCESS
ALPHANUMERIC KEYPAD
http://www.firealarmengineers.com
Fig. 2
PAGE 7 of 25
MX
17A-05-O
01
8/00
http://www.firealarmengineers.com
2.1.3
CONTROLS
FUNCTION 1 - is configurable to
customer requirements.
FUNCTION 2 - is configurable to
customer requirements.
PANEL STATUS
SIGNALLING STATUS
SOUNDER STATUS
HARDWARE STATUS
PAGE 8 of 25
EQUIPMENT:
MX
PUBLICATION:
17A-05-O
01
8/00
ENABLE
KEYSWITCH
CONTROL
SWITCHES
http://www.firealarmengineers.com
Fig. 3
PAGE 9 of 25
MX
17A-05-O
01
8/00
http://www.firealarmengineers.com
2.2
LCD DISPLAY
Fire
19 characters x 8 lines
Main
19 characters x 14 lines
Status, and
19 characters x 5 lines
Softkeys
Fig. 4
2.2.1
FIRE WINDOW
2.2.2
STATUS WINDOW
2.2.3
MAIN WINDOW
SOFTKEY WINDOW
PAGE 10 of 25
EQUIPMENT:
MX
PUBLICATION:
17A-05-O
01
8/00
http://www.firealarmengineers.com
2.3
NORMAL OPERATION
2.3.2
EVENT DISPLAY
2.4
2.4.1
OPERATION IN ALARM
SYSTEM RESPONSE
EVENT MONITORING
Mains failure
Detection of a fire condition
Operation of EVACUATE/FIRE ALARM
key
Isolation
Test Mode
Warning
Information
PAGE 11 of 25
MX
17A-05-O
01
8/00
http://www.firealarmengineers.com
6) For a T2000 controller, the sounders and any
other configured outputs will be
activated. If the alarm is not accepted within
the programmed delay period by pressing
the SILENCE BUZZER key, all other
sounder outputs will be activated.
The message format is as follows:
Under FIRE:
The top line shows the Zone and Point number of the
device in alarm.
The second line shows the zone description (defined at
configuration).
The third line shows the point description (defined at
configuration)
i)
ii)
SOUNDER SILENCING
WARNING:
WHEN SEARCHING AN AREA FOR THE
SOURCE OF A FIRE ALARM SIGNAL,
WHERE A FIRE ALARM HAS BEEN
INITIATED BY A CARBON MONOXIDE
FIRE DETECTOR, IT MUST BE
REMEMBERED THAT A CARBON
MONOXIDE DETECTOR MAY GENERATE
AN ALARM BEFORE OTHER FIRE
INDICATORS (SUCH AS SMOKE) ARE
PRESENT.
THIS OCCURS MOST NOTABLY IN DEEP
SEATED FIRES IN DENSELY PACKED
MATERIALS, AREAS WHERE FIRES MAY
OCCUR IN CUPBOARDS AND
STOREROOMS REMOTE FROM
DETECTORS, AND WHERE SMOKE
IMPERVIOUS BARRIERS EXIST BETWEEN
THE SEAT OF THE FIRE AND THE
PAGE 12 of 25
EQUIPMENT:
MX
PUBLICATION:
17A-05-O
01
8/00
http://www.firealarmengineers.com
2.4.3
2.5
2.5.1
Note:
1) The controller cannot be reset until the
sounders have been silenced.
SYSTEM RESPONSE
MULTIPLE EVENTS
PRE-ALARM WARNINGS
2.5.2
OPERATOR ACTION
PAGE 13 of 25
MX
17A-05-O
01
8/00
http://www.firealarmengineers.com
The fault may be accepted without the cause of the fault
being removed. The fault will be placed in the Not
Cleared log. Uncleared faults may be viewed by selecting
the Not Clr (F4) key and scrolling the screens.
To accept a fault, proceed as follows:
a) Insert the Enable key and turn to the
Enable position.
b) Press the Menu (F1) key and select option
1 Accept Events, press the Accept (F3)
key to accept events, when all events have
been accepted the following will be
displayed:
Nothing to accept
2.6
SILENCE BUZZER
SILENCE/RESOUND
RESET
DAY MODE
EVACUATE (FIRE ALARM for Marine)
2.6.2
2.6.3
2.6.1
2.7
PAGE 14 of 25
DAY/NIGHT MODE
TEST
2.7.1
GENERAL
Repeaters
Printers
EQUIPMENT:
MX
PUBLICATION:
17A-05-O
01
8/00
http://www.firealarmengineers.com
2.7.2
REPEATERS
3.1
PRINTERS
3.
CONTROLLER FUNCTIONS
ACCESS LEVELS
3.1.1
GENERAL
Customer Operator (1 to 7)
Customer Manager (1 and 2)
PAGE 15 of 25
MX
17A-05-O
01
8/00
http://www.firealarmengineers.com
Fast
Access
Code
Lamp/Buzzer/LCD Test
Unrestored Events
Information Text
View Events (Scrolling)
MAIN MENU
Actual Status
20
(De-)isolate
30
Time/Date
Set time/Date
Summer/Winter
40
41
42
Event log
View Event Log
Print Event Log
50
51
52
View/print status
Points Isolated
Points Untested/Failed
Point Values
View Faults
60
61
62
63
64
Service
Walk Test
Maintenance engineer
Fire Alarm Cycle Count
Maintenance Request
Battery Test
Project Numbers
Software Versions
70
71
72
11
13
14
16
17
Table. 1
3.2
Customer
Manager
1
2
Enable
Key
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ENTERING PASSCODES/FAST
ACCESS CODES
PAGE 16 of 25
Customer Operator
3
4
5
3.3
VALID VALUES
1 - 99
1 - 240
1 - 250
0 - 15
1 - 24
1-8
1 - 96
1 - 15
1 - 15
1 - 14
1 - 10
1 - 10
EQUIPMENT:
MX
PUBLICATION:
17A-05-O
01
8/00
http://www.firealarmengineers.com
3.4
MAIN MENU
3.5
ACTUAL STATUS
PAGE 17 of 25
MX
17A-05-O
01
8/00
http://www.firealarmengineers.com
Actual Status IP can be in one of the following states:
Normal
Press 3 from the Main menu or press Fast Access key and
enter Fast Access Code 30. The following screen will be
displayed:
Fault
Active
PreAlarm
Resetting. or
Local Test
On
Off
Pulse 1
Pulse 2
3.6
ISOLATE/DE-ISOLATE
Point Complete
Point Input
Point Output
Zone/Sector Detectors
Zone/Sector MCP (Manual Call Point)
Zone/Sector Sounders
Zone/Sector Controls
Isolation Status
PAGE 18 of 25
EQUIPMENT:
MX
PUBLICATION:
17A-05-O
01
8/00
http://www.firealarmengineers.com
Successes:
Matches:
3.7.1
SET TIME/DATE
Use the >> key to move the cursor between options, enter
date and time values via the keypad or Softkey F3 (-) and
F4 (+).
Successes:
Matches:
3.7
Note:
1) When a value has been changed, F5 shows
Save, use this key when all editing has been
completed.
TIME/DATE
Press 4 from the Main menu or press Fast Access key and
enter Fast Access Code 40. The following type of screen will
be displayed:
PAGE 19 of 25
MX
17A-05-O
01
8/00
http://www.firealarmengineers.com
3.7.2
SUMMER/WINTER
The latest event is displayed, use the << and >> keys to
scroll through the log and the |<< to move to the back of
the log or the >>| key to move to the front of the log.
These screens cannot be changed, the information is
configured in MX CONSYS, use F5 to toggle between
Winter and Summer.
3.8
3.8.2
EVENT LOG
Press 5 from the Main menu or press Fast Access key and
enter Fast Access Code 50. The following type of screen
will be displayed:
PAGE 20 of 25
0
1
2
3
4
5
6
7
Information
Warning
Test Mode
Isolation
Fault
Supervisory
Pre-Alarm
Alarm
EQUIPMENT:
MX
PUBLICATION:
17A-05-O
01
8/00
http://www.firealarmengineers.com
3.9
3.9.2
VIEW/PRINT STATUS
Points Isolated
Points Untested/Failed
Point Values
View Faults (no print option)
Select option 6 from the Main menu or press the Fast Access
key and enter Fast Access Code 60, the following type of
screen will be displayed:
3.9.1
PAGE 21 of 25
MX
17A-05-O
01
8/00
http://www.firealarmengineers.com
3.9.4
VIEW FAULTS
3.10 SERVICE
Press 7 from the Main menu or press Fast Access key and
enter Fast Access Code 70. The following screen will be
displayed:
3.10.1.1 POINT
Press 1 to enter Point Input, an example of Point Input is
shown. Press F5 to start to initiate the Walk Test.
3.10.1
WALK TEST
Covered:
Excluded:
Press 1 from the Service menu or press Fast Access key and
enter Fast Access Code 71.
Activations:
Curr. Active:
PAGE 22 of 25
EQUIPMENT:
MX
PUBLICATION:
17A-05-O
01
8/00
http://www.firealarmengineers.com
3.10.1.2 ZONE/SECTOR
Covered:
Excluded:
Been Activ:
Been Clear:
Successfully:
Curr. Active:
MAINTENANCE/ENGINEER
Press 2 from the Service menu or press Fast Access key and
enter Fast Access Code 72. The following type of screen
will be displayed:
PAGE 23 of 25
MX
17A-05-O
01
8/00
http://www.firealarmengineers.com
3.10.2.3 BATTERY TEST
When selected, this option allows the state of the battery and
the charger current to be displayed.
Firmware
Local I/O
Each Loop
Each MPM
PAGE 24 of 25
EQUIPMENT:
MX
PUBLICATION:
17A-05-O
01
8/00
http://www.firealarmengineers.com
4.
ROUTINE CHECKS
4.1
GENERAL
4.2
DAILY CHECKS
Proceed as follows:
a) Ensure the front panel of the controller is
indicating a normal condition (ie, no alarm
or fault LEDs are lit and the LCD is
displaying the date and time).
JM/jm
30th August 2000
4.3
WEEKLY CHECKS
WARNING:
WARN ALL PERSONNEL THAT THE
SOUNDERS ARE ABOUT TO BE TESTED.
Proceed as follows:
a) If necessary, clean the front panel of the
controller with a suitable cleansing agent.
b) Set one device (either a callpoint or
detector) from one zone into alarm and
check that the system responds as follows:
PAGE 25 of 25