Motor Protection
Motor Protection
of the motor, since precise information of the thermal state of the motor is
required during
heating and cooling. It is set as a multiple of T1 and should be set to the nearest
value above
the motor cooling time constant.
Short circuit protection (50/51)
Faults between phases seldom occur because of the relatively large amount of
insulation
between phase windings. As the stator windings are completely enclosed in
earthed metal,
most faults will involve earth, which would then operate the earth fault
protection. However, a
fast operating overcurrent element is often employed to protect against phase
faults
occurring at the motor terminals; such as terminal flashovers.
The short circuit protection included within the P24x relays consists of an
adjustable current
threshold and a definite time setting.
In order to avoid tripping during start-up as a result of asymmetric CT saturation,
this
element as a minimum operating time of 100ms for currents in the range I> to
1.2I>.
The definite time characteristic is shown below in Figure 3.
Characteristics
Standard Inverse
Very Inverse
Extremely Inverse
0.02
1.0
2.0
0.14
13.5
80.0
the current to flow in the outer section of the rotor conductors; commonly known
as the 'skin
effect'. Since the current is occupying a smaller section of the rotor, the apparent
impedance
presented to it is increased, therefore the I 2R heating is greatly increased. As the
motor
accelerates during starting the slip begins to decrease and the current is able to
occupy
more of the rotor conductor. The apparent impedance therefore reduces along
with the
heating effect. The motor is therefore able to tolerate starting current for the
starting time, but
not locked rotor current.
Undervoltage protection function (27)
Undervoltage conditions may occur on a power system as a result of increased
loading, fault
conditions or incorrect regulation. Transient voltage dips may allow successful
motor reacceleration.
However, sustained undervoltage conditions will result in motor stalling. Time
delayed undervoltage protection is therefore commonly applied.
The undervoltage protection included within the P24x relays consists of two
independent
phase to phase measuring stages.
Two stages are included to provide both alarm and trip stages, where required.
The voltage threshold setting for the undervoltage protection should be set at
some value
below the voltage excursions which may be expected under normal system
operating
conditions.