SLAB Cuplock With H20-01

This document contains load calculations and structural analyses for formwork designs for concrete slabs of varying thicknesses (280mm, 400mm, and 800mm). It includes design assumptions about load parameters, load computations, analysis of secondary and primary beam requirements, and conclusions about using H20 timber beams in configurations that meet permissible load criteria. The maximum bay sizes determined to be suitable for each slab thickness are also stated.

Uploaded by

Manu Mohan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
939 views7 pages

SLAB Cuplock With H20-01

This document contains load calculations and structural analyses for formwork designs for concrete slabs of varying thicknesses (280mm, 400mm, and 800mm). It includes design assumptions about load parameters, load computations, analysis of secondary and primary beam requirements, and conclusions about using H20 timber beams in configurations that meet permissible load criteria. The maximum bay sizes determined to be suitable for each slab thickness are also stated.

Uploaded by

Manu Mohan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

STATICAL CALCULATION

Project:
Subject:

Client:
Project No.

Rev

280 mm Thick SLAB

Date:

08-DEC-16

CUPLOCK Formwork System for 280 mm Thick Slab


Load Computations
Design assumptions
3

26 kN/m
2
1.5 kN/m

Weight of Fresh Concrete:


Live Load:

0.5 kN/m

Formwork Weight:

Loading Data
Load Computation
3)

Load

Concrete (KN/m

Slab

26

Thickness
(m)
0.28

Live Load
2)
(KN/m

Formwork
Weight

1.5

Element Data
H20 Timber
H = 200 mm
W = 80 mm
2
EI = 500 KN-m
Permissible Shear = 11 KN
Permissible Moment = 5 KN-m

Load acting on secondary beam = 4.4 Kn/m


Analysis Results
Check on H20 Secondary Beam spaced @ 488 mm C.C.
Max. Shear = 4.15 KN < 11 KN OK
Max. Moment = 1.27-m < 5.0 kN.m. OK
Deflection = 0.1 mm < L/500
Check on Two H20 Primary Beam spaced @ 1600mm C/C.
Max. Shear = 9.88 KN < 22.0 KN OK
Max. Moment = -3.54 KN-m < 10.00 KN-m OK
Deflection = 0.10 mm < L/300
U head Load = 19.77KN < 33 KN OK

USE MAX BAY SIZE 1.8*1.6 M2

(KN/m

0.5

2)

Computed
Load
2

(KN/m )

9.28

STATICAL CALCULATION
Project:
Subject:

Client:
Project No.

Rev

400 mm Thick SLAB

Date:

08-DEC-16

CUPLOCK Formwork System for 400 mm Thick Slab


Load Computations
Design assumptions
3

26 kN/m
2
1.5 kN/m

Weight of Fresh Concrete:


Live Load:

0.5 kN/m

Formwork Weight:

Loading Data
Load Computation
3)

Load

Concrete (KN/m

Slab

Thickness
(m)

26

0.4

Live Load
2)
(KN/m

Formwork
Weight

1.5

Element Data
H20 Timber Beam
H = 200 mm
W = 80 mm
2
EI = 500 KN-m
Permissible Shear = 11 KN
Permissible Moment = 5 KN-m

Load acting on secondary beam = 5.8 Kn/m


Analysis Results
Check on H20 Secondary Beam spaced @ 488 mm C.C.
Max. Shear = 4.28KN < 11 KN OK
Max. Moment = -0.93-m < 5.0 kN.m. OK
Deflection = 0.1 mm < L/500
Check on TWO H20 Primary Beam spaced @ 1300mm C/C.
Max. Shear = 11.16 KN < 22.0 KN OK
Max. Moment = -3.99 KN-m < 10.00 KN-m OK
Deflection = 0.10 mm < L/300
U head Load = 22.31 KN < 33.0 KN OK

USE MAX BAY SIZE 1.8*1.3 M2

(KN/m

0.5

2)

Computed
Load
2

(KN/m )

12.4

STATICAL CALCULATION
Project:
Subject:

Rev

800 mm Thick beam

Client:
Project No.
Date:

08-DEC-16

CUPLOCK Formwork System for 800 mm Thick Slab


Load Computations
Design assumptions
Weight of Fresh Concrete:

26 kN/m

Live Load:

1.5 kN/m

Formwork Weight:

0.5 kN/m

3
2
2

Loading Data
Load Computation
3)

Load

Concrete (KN/m

Slab

Thickness
(m)

26

0.8

Live Load
2)
(KN/m

Formwork
Weight

1.5

Element Data
H20 Timber Beam
H = 200 mm
W = 80 mm
2
EI = 500 KN-m
Permissible Shear = 11 KN
Permissible Moment = 5 KN-m

Load acting on secondary beam = 8.00 Kn/m


Analysis Results
Check on H20 Secondary Beam spaced @ 350 mm C.C.
Max. Shear = 6.40 KN < 11 KN OK
Max. Moment = 1.10-m < 5.0 kN.m. OK
Deflection = 0.1 mm < L/500
Check on TWO H20 Primary Beam spaced @ 1600mm C/C.
Max. Shear = 12.27 KN <22.0 KN OK
Max. Moment = 4.39 KN-m < 10.00 KN-m OK
Deflection = 0.10 mm < L/500
U head Load = 24.54 KN < 33.0 KN OK

USE MAX BAY SIZE 1.8*1.6 M2

(KN/m

0.5

2)

Computed
Load
2

(KN/m )

22.8

SECONDARY BEAM DESIGN


SLAB THICKNESS 280mm

SLAB THICKNESS 400mm

TRANSFERING BEAM WITH 800 mm DEPTH

PRIMARY BEAM DESIGN


H20 BEAM AS PRIMARY for 280mm thick slab

Hence use 2 H20beams for safe.


H20 BEAM AS PRIMARY FOR 400mm thick slab

Hence use 2 H20beams for safe.


H20 BEAM AS PRIMARY FOR TRANSFERING BEAM

Hence use 2 H20beams for safe.