Protecting Transmission Lines Terminated Into Transformers: Elmo Price and Roger Hedding, ABB Inc
Protecting Transmission Lines Terminated Into Transformers: Elmo Price and Roger Hedding, ABB Inc
I. INTRODUCTION
276
A. Transformer impedance
Transformer impedances are of importance when
applying distance protection or any function that
computes impedance. Transformer impedances are
provided by the manufacturer in percent on the MVA
base of the measured (tested) windings. The measured
impedance values are generally accurate to within about
1%. The impedance of course needs to be converted to
the same base ohms on which the transmission line ohms
are expressed and appropriately incorporated into
protection settings.
kVL
RCL
RVL
kVL
RCL
RVL
VL
kVH
ZG1
+j30
1:e
ZG2
Positive
mZL1
(1-m)ZL1
ZR1
mZL2
Negative
VH2
n
ZR2
ZG0
ZT
(1-m)ZL0
mZL0
mZL0
Zero
ZR0
(1-m)ZL0
ZR0
IL0
ZT
ZR2
x
VH2
VL2
(1-m)ZL2
x
Negative
(1-m)ZL2
mZL2
IL2
VH0
VL0
IL0 =0
IH0
ZG0
VH0
VL0 =0
Zero
Zero
ZT
ZG0
ITL0
VL0
Zero
ZT
VL2
n
-j30
ZR1
IL2
1:e
(1-m)ZL1
VH1
VL1
ZG2
VH1
ZG0
mZL1
VL1
ZT
ZT
IL1
RELAY R
IL1
Positive
RELAY R
ZT
RVH
VH
IH
RELAY G
ZG1
RELAY G
RVH
VH
IH
IL
RCH
IL
VL
RCH
kVH
mZL0
ITH0 =0
VH0
(1-m)ZL0
ZR0
VL0
ZTL0 ZTH0
mZL0
ITL0
ITH0
ITM0
ZTM0 VH0
(1-m)ZL0
ZR0
VR0
n
Figure 3. Sequence network models of line with non phase shifting ANSI
transformer connections showing alternate zero sequence circuits for Wyewye and Wye-wye-delta transformations. High voltage (line) side is in
phase with low voltage side. In this example the delta winding is not
loaded and is provided as a grounding source only.
VH0
n
277
3) Wye-wye connection
The zero sequence circuit for this connection is figure
3(c). There is no phase shift between high and low voltage
windings. Zero sequence quantities can be measured on the
source G side that can represent somewhat accurately the
quantities present on the line side of the transformer. There
will be a difference in per unit voltages VL0 and VH0 due to
the transformer impedance voltage drop, but this is
effectively measured by distance units. This voltage drop
has no effect on current differential protection.
B. Phase shift
Figure 2 shows that there is a voltage and current angle
phase shift across a delta-wye or wye-delta connected
transformer. The high voltage (line side in this figure)
quantities lead the low voltage (source G) quantities by 30
for both connections. This is based on ANSI standard
connections. The effect of this phase shift needs to be
accounted for to insure correct voltage and current
measurement and protection operation.
C. Turns ratio including effect of tap-changer
The transformers turns ratio including the effect of the
tap changer needs to be considered for both line distance
and differential protection when the transformer is in the
line protection zone. The turns ratio needs to be known for
proper application. The tap changer changes the
transformer turns ratio and this affects both impedance and
current differential measurement.
For distance relaying, the line and transformer
impedances must sometimes be combined and this needs to
be done so very carefully. The line impedance in ohms that
is connected to the high voltage winding, for example, can
be easily calculated on another of the transformers
windings base simply by multiplying the impedance by the
square of the actual turns ratio at the tap position of
interest. The transformer impedance, however, is the
leakage impedance between two windings and when
expressed on a particular winding base cannot be totally
reflected across the transformer except at the transformer
tap position (ratio) at which that specific impedance was
measured by test. Therefore, the actual tested impedance at
the tap position of interest must be used. This information
is generally provided on the transformers nameplate or
with test data provided by the transformers manufacturer.
For line differential protection the range of the tap
changer must be considered when setting the minimum
differential pickup level. The application of modern
protection schemes to dynamically follow tap changer
position greatly improves sensitivity to internal faults of
differential schemes.
4) Wye-delta-wye connection
The zero sequence circuit for this connection is figure
3(d). There is no phase shift between high and low voltage
winding quantities. There is, however, a delta winding that
provides a ground current path. Zero sequence quantities
can be measured on the source G side of the transformer
although they will be different than those on the line side.
There will be a difference in per unit voltages VL0 and VH0
due to the transformer impedance voltage drop, but this is
effectively measured by distance units. There will also be a
difference in per unit currents IL0 and IH0 due to the
transformer ground current, ITM0, through the transformer
ground impedance ZTM0. This will affect both line distance
and differential measurement.
E. Transformer energizing inrush current
When a power transformer is energized, high
magnetizing current flows for several cycles in the
transformer winding that is energized and no magnetizing
current flows in other windings. This is a differential
current within the transformer referred to as inrush current
and is characterized by a high peak current with
considerable harmonic content, particularly 2nd and 5th.
Generally, transformer differential protection provides
harmonic restraint to prevent undesired operations upon
energization. When energizing a transformer terminated
line the effects of inrush current need to be addressed.
Line differential protection must still address the
differential current produced by transformer energization.
Also, the effect of the magnetizing inrush current on
overcurrent and distance unit operations should be of
concern.
Transformer magnetizing current at energization is, in
the worst case of high residual flux, limited by the
energized windings air core reactance, i.e. the winding coil
reactance without the iron core. Air core reactance is a
function of the transformer design and can be smaller than
the transformers leakage reactance between the windings
that is used for through-fault short circuit calculations.
Given that this it is possible, settings for direct trip phase
overcurrent functions based on transformer leakage
impedance may be exceeded upon transformer
energization. Considerable ground current may also exist
due to unbalanced phase magnetizing inrush current. This
will be particularly true for cases where ground overcurrent
units that are part of line protection are set low to look into
278
Z SEC
kVL
kVH
RVH
Z PRI
A. Using VH and IL
RCL
(1)
VH 0 VR0
Z L0
I TH 0
(2)
V H 0 V R 0 I TH 0
Z L0 K T Z L0
I TL 0
I TL 0
(3)
KT 1
Z G 0 Z TL 0
Z TM 0
Z L 0 K T Z L 0
Figure 4. Instrument transformer connections VH and IL
279
(4)
(5)
d)
1) General Considerations
This is generally the more practical connection when
both line side vts and cts cannot be used. It is more
convenient with both VL and IL to compute and use the
primary impedances on the low voltage (VL) base. The
impedance reach is measured from the low or bus side
voltage transformer providing VL and the impedance setting
must include the transformer impedance ZT. Transformer
impedances are calculated very accurately; therefore the
zone-1 reach is set at 0.99 ZT + .9ZL. The ZT multiplier .99
is used to allow for almost 1% positive error in the ZT
measurement (i.e. actual impedance is ZT/0.99, but ZT is
measured).
280
80
% Underreach
70
40
30
20
0
0
V L 0 V R 0 Z TL 0 I TL 0 ( Z TH 0 Z L 0 ) I TH 0
(6)
VL 0 VR 0
Z ' L 0 Z TL 0 K T Z TH 0 Z L 0
I TL 0
(7)
0.5
1.5
d)
50
10
60
1) General Considerations
Using these connections the impedance reach is
measured from the low or bus side voltage transformer
providing VL and the impedance setting must include the
transformer impedance ZT.
281
The
RCH
Z SEC
kVH
kVL
RVL
Z PRI
(8)
d)
V L 0 V R 0 Z TL 0 I TL 0 ( Z TH 0 Z L 0 ) I TH 0 (9)
VL 0 VR 0
Z
Z ' L 0 TL 0 Z TH 0 Z L 0
I TH 0
KT
(10)
282
b)
Using VL and IL
283
D. Inrush current
When a power transformer is energized, high current
flows for several cycles in the transformer winding that is
energized and no inrush current flows in other windings. If
low side cts are used, then a transformer energized from the
line (high voltage) side will have inrush current flowing on
the high side but not the low side. This results in a
differential current and relay operation. A way around this
is to desensitize the relay by setting the minimum
differential operating current above this inrush differential
284
3.
4.
5.
6.
7.
*Impedance backup
Bus G
ZT
CT1
Bus R
CT2
ZL
*
87T
Transformer Differential
Scheme
87L/21
Line Current
Differential
Scheme
VI. CONCLUSIONS
When protecting transmission lines terminated into
transformers it is preferred to use line side instrument
transformers so that line protection can be implemented
independent of the effects of a transformer within the line
protection zone. When the transformer is within the
protection zone, it should always have its own differential
protection. Two methods for protecting the combined line
and transformer zone were reviewed, line distance and line
differential. Line differential would be the simpler and
more reliable of the two schemes if simultaneous tripping
of all terminal breakers is required on internal faults. A
summary of the issues with each application follows.
A. Line Step-distance
Following are the more significant issues using stepdistance when the transformer is within the protected zone:
1. The secondary impedance base for relay settings
must be computed with the transformer ratio when
the cts and vts are not on same side of transformer.
2. When the transformer is in the protection zone the
effect of load tap-changing on impedance settings
needs to be considered. The minimum secondary
285
Connection
VH
IH
VH
IL
R= RCL/(RT*RVH)
Z1 = .9ZL
Z2 = 1.2 ZL
VL
IH
R= RCH*RT/RVL
Z1 = .99ZT + .9ZL
Z2 = .99ZT + 1.2ZL
VL
Effect of tap-changer
Effect of transformer turns ratio
Effect of I0 infeed
Effect of transformer inrush
IL
R= RCL/RVL
Z1 = .99ZT + .9ZL
Z2 = .99ZT + 1.2ZL
Setting
Z1 = .9ZL
Z2 = 1.2 ZL
VII. APPENDIX
ZSEC = R*ZPRI
R= RCH/RVH
Effect of tap-changer
Effect of transformer turns ratio
Effect of transformer phase shift
Effect of transformer inrush
I0 filtering or correction
Effect of tap-changer
Effect of transformer turns ratio
Effect of transformer phase shift
Effect of transformer inrush
I0 filtering or correction at remote terminal
286
REFERENCES
[1]
No issues
[2]
[3]
[4]
IL
VH or VL
BIOGRAPHIES
Elmo Price is currently a Regional Technical Manager
for the Substation Automation and Protection Division of
ABB. He received his BSEE degree in 1970 from Lamar
University in Beaumont, Texas and his MSEE degree in
Power Systems Engineering in 1978 from the University of
Pittsburgh. He began his career with Westinghouse in
1970, which was consolidated into ABB in 1988. He has
worked in many power engineering and management
assignments. He has two patents and has authored or
coauthored numerous papers primarily focusing on
protection application.
Elmo is a registered professional engineer and a member
of the IEEE and the Power System Relay Committee and
serves on the Line Protection Subcommittee.
IL
VH or VL
287