The HLINKCC is a dataline communications link

which allows access to the Complete Control


System dataline for global programming, monitoring
and control.
The HLINKCC also synchronizes and sets the clocks
in all Lighting Control Panels on the dataline, and
provides a contact closure to annunciate failed field
panels or relays.
Multiple HLINKCCs may be used on a single dataline
to provide multiple operator stations or communications
portals to other building control systems.

Features
Industry standard RS232 serial communications port
for connection to PC or modem
300/1200/2400/4800/9600/19200 auto baud
LED status indicators for Power, On Line and
Dataline activity
System synchronization clock with automatic
adjustments for Daylight Savings and Leap Year
Alarm contacts with LED indication to annunciate
failed field devices or the HLINKCC itself
Random dataline access with bus arbitration
supports multiple HLINKCCs on a dataline
Before starting, read the enclosed installation and
setup instructions. If you have any questions, call
our Service Team at: 888-852-2778.

Santa Clara, CA 95050

2001 The Watt Stopper, Inc.

Installation Instructions

HLINKCC
Dataline Communications Link
for Complete Control Networks Setup

HLINKCC Dataline Communications Link for Complete Control Networks Setup

Figure 1 HLINKCC Connections

DATALINE
COMPUTER
POWER

RED

BLACK

Connecting HLINKCC
Connect the dataline to the DATALINE
terminals on the back of the HLINKCC
as shown to the right. Connect red to the
left terminal, black to the center terminal
and shield to the right terminal.
Connect an optional external device
(2A 28VDC maximum) to the ALARM
terminals, located on the back of the unit
between the COMPUTER and POWER
connectors.
Plug the included 12 volt power supply
into a 120VAC 60Hz outlet and connect
the cable to the POWER connector as
shown below right. The LINK FAIL LED
on the front of the HLINKCC will flash for
10 seconds while the unit performs
internal diagnostics.
Connect the unit to a PC or modem,
using HCABLE-C to connect to a PC or
HCABLE-M to connect to a modem
(cables available separately).

SHIELD

ALARM

HLINKCC Dataline Communications Link for Complete Control Networks Setup

Figure 2 HLINKCC Typical Wiring PC Direct Connection

HDPS1CC
DATALINE
POWER
SUPPLY
TO FIELD PANELS

HDLW2P DATALINE WIRE

115 VAC

HLINKCC

HCABLE-C

TO EXTERNAL ALARM DEVICE


CONTACTS RATED 2A 28VDC
POWER
TRANSFORMER

Figure 3 HLINKCC Typical Wiring Remote Connection Via Modem

HDPS1CC
DATALINE
POWER
SUPPLY
TO FIELD PANELS
REMOTE LOCATION PC
HDLW2P DATALINE WIRE

115 VAC

HLINKCC

HCABLE-M
HMODEM

HMODEM

TO EXTERNAL ALARM DEVICE


CONTACTS RATED 2A 28VDC
POWER
TRANSFORMER

PHONE
LINE

POWER
TRANSFORMER

PHONE
LINE

POWER
TRANSFORMER

HLINKCC Dataline Communications Link for Complete Control Networks Setup

For emergency service and support,


call our Service Team at: 888-852-2778.

Normal Operation

Troubleshooting

NOTE: Upon powering up, the LINK


FAIL indicator will flash for 10 seconds
while the HLINKCC performs internal
diagnostics.

No communications connection
with HLINKCC

Indicator

Function

POWER LED

On

ON LINE LED

On if PC or modem
is connected and
HSOFT-CM1 or
WinControl software is
in the Connect mode.

DATALINE LED Normally On.


Blinks when there is
activity on the dataline.
LINK FAIL LED Normally Off.
Flashes when an
HLINKCC hardware
failure, shorted
dataline or nonprogrammed clock is
detected.

Check the POWER indicator. If it is off,


check the power supply.
Refer to the HSOFT-CM1 or WinControl
Software Users Manual for the proper
PC or modem configuration. Check the
cable connection from the PC or modem
to HLINKCC.
HLINKCC is on-line, but will not
communicate with LCPs
If the DATALINE LED is off, check the
dataline connections and polarity.
Confirm that the dataline power supply
(HDPS1CC) is operational.
Use the lighting control softwares Test
routine to identify panels on the dataline.

FIELD FAIL LED Normally Off.


Flashes when a relay
failure or loss of
Lighting Control Panel
(LCP) program is
detected.
ALARM RESET Push to open the
button
alarm contacts and
turn off the external
device.
(The FAIL indicator will
continue to flash until
reset by the operator.)

Panel Division 888-852-2778