RC Chapter 8
RC Chapter 8
8.2) Starting with the column in Problem 8.1, perform enough additional calculations to determine the effects of
increasing fC from 5000 to 8000 psi on column capacity at both high and low axial loads. Assuming that a
8.3) Plot the design strength curve relating Pn and Mn for the column of Problem 8.1. Design and detail the tie
steel required by the ACI Code. Is the column a good choice to resist a load Pu = 540 kips applied with an
eccentricity e = 4.44 in.?
8.4) The short column shown in Fig. P8.4 will be subjected to an eccentric load causing uniaxial bending about
the Y axis. Material strengths are fy = 60ksi and fC= 4 ksi.
FIGURE P8.4
8.5) The column shown in Fig. P8.5 is subjected to axial load and bending moment, causing bending about an
axis parallel to that of the rows of bars. What moment Mn would cause the column to fail if the axial load Pn applied
simultaneously was 1250 kips? Material strengths are fC= 4000 psi and fy = 60 ksi.
FIGURE P8.5
8.6) What is the strength Mn of the column of Problem 8.5 if it was loaded in pure bending (axial force = 0) about
one principal axis?
8.7) Construct the interaction diagram relating Pn to Mn for the building column shown in Fig. P8.7. Bending will
be about the axis a-a. Calculate specific coordinates for concentric loading (e = 0), for Pb, and at least three other
points, well chosen, on the curve. Material strengths are f C= 8000 psi and fy = 60,000 psi.
FIGURE P8.7
8.8) A short rectangular reinforced concrete column shown in Fig. P8.8 is to be a part of a long-span rigid frame
and will be subjected to high bending moments combined with relatively low axial loads, causing bending about
the strong axis. Because of the high eccentricity, steel is placed unsymmetrically as shown, with three No. 14 (No.
43) bars near the tension face and two No. 11 (No. 36) bars near the compression face. Material strengths are f C=
FIGURE P8.8
8.9) The square column shown in Fig. P8.9 must be designed for a factored axial load of 130 kips. Material
strengths are fC = 4000 psi and fy = 60,000 psi.
(a) Select the longitudinal and transverse reinforcement for an eccentricity Ey = 2.7 in.
FIGURE P8.9
8.10) The square column shown in Fig. P8.1 0 is a comer column subject to axial load and biaxial ending.
Material strengths are fy = 60,000 psi and fC= 4000 psi.
(a) Find the unique combination of Pn, Mnx, and Mny,, that will produce incipient failure with the neutral axis located
as in the figure. The compressive zone is shown shaded. Note that the actual neutral axis is shown, not the
FIGURE P8.10
8.11) For the axial load Pn found in Problem 8.10, and for the same column, with the same eccentricity ratio ey/ex,
find the values of Mnx and Mny that would produce incipient failure, using the load contour method. Compare with
the results of Problem 8.10. Take = 1.30, and use the graphs in Appendix A, as appropriate.
8.12) For the eccentricities ex and eY found in Problem 8.10, find the value of axial load Pn that would produce
incipient failure, using the reciprocal load (Bresler) method. Use the graphs in Appendix A, as appropriate.
Compare with the results of Problems 8.10 and 8.11.
8.13) A 20 in. square lower-story interior building column must be designed for maximum and minimum factored
axial loads Pu of 880 and 551 kips, respectively. For both values of Pu , the column will be subjected to
simultaneous factored bending moments Mu of 295 and 24 ft-kips about the Y and X axes, respectively (Fig.
P8.13). Material strengths are f y = 60,000 psi and f C= 4000 psi. Using equal reinforcement on all sides, design the
longitudinal and transverse reinforcement for this column.
FIGURE P8.13
8.14) A 16 in. square lower-story comer column in the building described in Problem 8.13 will be subjected to
maximum and minimum factored axial loads Pu of 209 and 130 kips, respectively. For both values of Pu, the
columns must be designed for simultaneous factored bending moments Mu of 110 and 104 ft-kips about the Y and
X axes, respectively. Using equal reinforcement on all sides, design the longitudinal and transverse reinforcement
for this column.