MSDB J Type Vertical 45 Way Data Sheet
MSDB J Type Vertical 45 Way Data Sheet
Features
Multi-tier outgoing fuse ways provide increased space for cabling
Factory options include;
Left or Right hand incoming supply
4 core incoming / outgoing cable kit
N/E bar located at top or bottom of enclosure to suit top or bottom entry options
M12 fixings for incoming connections and internal busbar links
Pre-drilled removable gland plate fitted with closed cell foam sealing gasket
Removable double doors to facilitate fitment in shallow riser cupboards
Accept up to 300mm2 3 or 4 core aluminium or copper conductors
Optional glanding kit for different cable types e.g. copper screened, aluminium or steel wire armoured
Page 1 of 3
Enclosure specification
Construction
Oven-cured epoxy powder coated finish with a minimum
thickness of 50 microns
Standard colour Admiralty grey to BS 381c, shade No 632
Two stage padlockable double doors enabling independent
access to outgoing 100A fuse ways or Distribution Network
Operator (DNO) access to incoming J type fuses.
Quick release spring loaded hinge pins permit rapid door
removal for improved access
Overall 250mm depth enables installation in confined spaces
Two external M12 earth studs
J type fuse holders......................................... Glass reinforced
Polybutylene Terepthalate (PBT)
J type fuse base......................... Glass reinforced polyamide 6
Performance data
Incoming supply.....................................................630A max
Internal equipment
Operator protection IP2XB (all screens, shrouds and fuse
handles in place)
Frequency..................................................................50-60Hz
Equipped with BS 7657 100A rated SP outgoing ways (BS
88 30 x 57mm cylindrical cartridge fuses, not supplied)
Serrated cable bores in 100A outgoing ways accept up to
35mm2 solid or stranded conductors
Operator protection
Neutral and earth bars fitted with twin hexagon drive M8
cable pinching screws per terminal
Termination kit for 4 core cable with 95mm2 to 300mm2
mechanical shear-off connectors specifiable at point of order
Above terminals will accept solid aluminium or stranded
copper conductors, Waveform or SWA type cables
(additional kit required for each SWA termination)
BS 88 J type slotted tag fuses with 92mm fixing centres
fitted on incoming phases
Fully rated neutral and earth bars
Technical datasheet
Short circuit withstand strength................. 18kA for 1second
All shrouds and fuse handles in place........................ IP2XB
Recommended N/E bar terminal torque....................... 3.5Nm
Conformity to standards
Third party tested to BS EN 60439-1
(Form 4 compliant)
Complies with draft ENA technical specifications for MSDBs
IP rating according to BS EN 60529
Incoming fuses.................................................... BS 88 J type
Outgoing fuse ways to BS 7657:1993
Page 2 of 3
Technical datasheet
Dimensions (mm)
Configuration
45 way 1J
Fixing centres
X
749
235
967
1150
911
397
900
769
www.lucyswitchgear.com