Power Analysis
Power Analysis
Homework 6
Problem 2. Given the impedance diagram of a simple system as shown in Figure 1, draw the admittance diagram
for the system and develop the 4 x 4 bus admittance matrix Ybus by inspection.
Y11
Y21
Ybus =
Y31
Y41
2.
Y12
Y22
Y32
Y42
1
Y13
Y23
Y33
Y43
Y14
Y24
,
Y34
Y44
Y23 = Y32 =
y23
Y34 = Y43 =
y34 .
Plugging in the values from the admittance diagram, the admittance matrix becomes
8.5
2.5
5.0
0
2.5 8.75
5.0
0
S.
Ybus = j
5.0
5.0
22.5 12.5
0
0
12.5 12.5
Problem 3. A load L consuming 1 p.u. of active power and 0.5 p.u. of reactive power is connected to a generator
G1 through a short transmission line with Z 0 = 0.02 + j0.06 p.u. Also, there is a capacitor connected to the load
bus with admittance Ycap = j0.25 p.u. The generator voltage is voltage VG1 = 10.
Solution
a) The one line diagram is shown in Figure 3.
1<0
Bus 1
Bus 2
j0.25
G1
5 + j15
.
5 j14.57
S = 1+j0.5
c) The power flow equations can now be written for each bus.
Bus 1:
P1 = V12 G11 + V1 V2 [G12 cos(1 2 ) + B12 sin(1 2 )] = 5 + V2 [5 cos(2 ) 15 sin(2 )]
Q1 = V12 B11 + V1 V2 [G12 sin(1 2 ) B12 cos(1 2 )] = 15 + V2 [5 sin(2 ) 15 cos(2 )]
Bus 2:
P2 = V22 G22 + V2 V1 [G21 cos(2 1 ) + B21 sin(2 1 )] = 5V22 + V2 [5 cos(2 ) + 15 sin(2 )] = 1
Q2 = V22 B22 + V2 V1 [G21 sin(2 1 ) B21 cos(2 1 )] = 14.75V22 + V2 [5 sin(2 ) 15 cos(2 )] = 0.5
Problem 4. Use PowerWorld Simulator to modify the Example 6.9 in textbook by inserting a second line between
bus 2 and bus 5. Give the new line a circuit identifier of 2 to distinguish it from the existing line. The line parameters
of the added line should be identical to those of the existing line 2-5. Determine/explain the new lines effect on V2 ,
the line loadings, and on the total real power losses. Please print a copy of your modified PowerWorld schematic and
turn it in.
Solution The results of adding a new line between bus 2 and bus 5 are given in Table 1.
Table 1: Effects of Line Addition
Bus Voltage V2 [p.u.]
Total real power losses [MW]
Branch b/w bus 1-5 (% loading)
Branch b/w bus 2-4 (% loading)
Branch b/w bus 2-5 (% loading)
Branch b/w bus 3-4 (% loading)
Branch b/w bus 4-5 (% loading)