CTI Journal 29-1
CTI Journal 29-1
(ISSN: 0273-3250)
PUBLISHED SEMI-ANNUALLY
Copyright 2007 by The Cooling
Technology Institute, PO Box 73383,
Houston, TX 77273. Periodicals
postage paid at FORT WORTH, Texas.
MISSION STATEMENT
It is CTIs objective to: 1) Maintain and
expand a broad base membership of
individuals and organizations
interested in Evaporative Heat
Transfer Systems (EHTS), 2) Identify
and address emerging and evolving
issues concerning EHTS, 3) Encourage and support educational
programs in various formats to
enhance the capabilities and
competence of the industry to realize
the maximum benefit of EHTS, 4)
Encourge and support cooperative
research to improve EHTS Technology
and efficiency for the long-term
benefit of the environment, 5) Assure
acceptable minimum quality levels
and performance of EHTS and their
components by establishing standard
specifications, guidelines, and
certification programs, 6) Establish
standard testing and performance
analysis systems and prcedures for
EHTS, 7) Communicate with and
influence governmental entities
regarding the environmentally
responsible technologies, benefits,
and issues associated with EHTS, and
8) Encourage and support forums and
methods for exchanging technical
information on EHTS.
LETTERS/MANUSCRIPTS
Letters to the editor and manuscripts
for publication should be sent to: The
Cooling Technology Institute, PO Box
73383, Houston, TX 77273.
SUBSCRIPTIONS
The CTI Journal is published in
January and June. Complimentary
subscriptions mailed to individuals in
the USA. Library subscriptions $20/yr.
Subscriptions mailed to individuals
outside the USA are $30/yr.
CHANGE OF ADDRESS
Request must be received at
subscription office eight weeks before
effective date. Send both old and new
addresses for the change. You may
fax your change to 281.537.1721 or
email: [email protected].
PUBLICATION DISCLAIMER
CTI has compiled this publication
with care, but CTI has not Investigated, and CTI expressly disclaims
any duty to investigate, any product,
service process, procedure, design,
or the like that may be described
herein. The appearance of any
technical data, editorial material, or
advertisement in this publication
does not constitute endorsement,
warranty, or guarantee by CTI of any
product, service process, procedure,
design, or the like. CTI does not
warranty that the information in this
publication is free of errors, and CTI
does not necessarily agree with any
statement or opinion in this
publication. The entire risk of the use
of any information in this publication
is assumed by the user. Copyright
2007
by Journal,
the CTI Journal.
AllNo.
rights
CTI
Vol. 28,
1
reserved.
Contents
Feature Articles
8
14
28
38
48
62
Special Sections
70
72
86
Departments
02
04
06
Meeting Calendar
View From the Tower
Editors Corner
CTI Journal
The Official Publication of The Cooling Technology Institute
Vol. 28 No.1
Winter 2007
Journal Committee
Paul Lindahl, Editor-in-Chief
Art Brunn, Sr. Editor
Virginia Manser, Managing Editor/Adv. Manager
Donna Jones, Administrative Assistant
Graphics by Sarita Graphics
Board of Directors
Steve Chaloupka, President
Thomas Bugler, Vice President
Rich Altice, Secretary
Dennis (Denny) P. Shea, Treasurer
Robert (Bob) Giammaruti, Director
Richard (Rich) Harrison, Director
James Kanuth, Director
Ken Kozelski, Director
Terry Ogburn, Director
Mark Shaw, Director
Committee
Workshop
Annual
Conference
REDW
OOD
R
I
F
S
A
L
G
U
O
D
24 Hour Service on Your Lumber and Plywood Requirements
COMPLETE FABRICATION AND TREATING
SERVICE FROM OUR OPELOUSAS, LA PLANT
GAIENNIE
LUMBER
COMPANY
Member
Steven Chaloupka,
CTI President
Editors Corner
A Strategic Issues Task Force has existed in
CTI for several years , for the purpose of identifying and developing action plans to address
strategic issues affecting the companies and
members in our industry.
We have identified strategic issues in the past
by using a facilitated process involving a crosssection of stakeholders in our industry. This
year we conducted a process internally, and
have identified some issues for consideration
by the task force.
Respectfully,
Paul Lindahl, CTI Journal Editor
Abstract
Use of Air Cooled Condensing system, to condense turbine exhaust steam from the steam cycle
of combined cycle plants, coal fired plants and
various other plants using steam to generate electricity, has gained acceptance. However, as electricity generation is privatized, building plants at
The power industry today is largely decentralized
low cost has been the priority rather than the perand privatized. Building plants at low cost has beformance. This paper discusses the impact of vecome the priority. Low initial cost does not neceslocity consideration in the design of air cooled
sarily mean that it is also the low evaluated cost.
condensers. The velocity at design point and the
change in velocity affect the steam duct design
A 170 MW steam turbine (510 MW Combined
Ram Chandran
and the tube bundle design. As the ambient temCycle Plant) data is used as an example to illusperature varies, it affects and/ or limits the range of turbine opera- trate how one aspect of the design parameter can affect the design,
tion. This, in turn, can improve or adversely affect the plant electric performance and the cost of an Air Cooled Condenser.
power output. The velocity also has an effect on the condensate
temperature. The reheat of the condensate requires energy which
is redirected from generating capacity which is often ignored.
This paper will illustrate the effect of velocity on:
a.
b.
c.
d.
e.
f.
Duct design
Tube bundle design
Performance limitation
Control system capability
Range of condensate subcooling
Relative cost impact
Introduction
Use of Air Cooled Condensers as alternate cooling medium in the
steam cycle has become a reality. The Air Cooled Condenser market in
the last ten years has grown from $40 Million to $400 Million (Figure 1).
Design Data
The steam from the turbine exhaust is 1,100,000 lbs/h at 5.6 inches
HgA containing 3 percent moisture. This is to be condensed at an
ambient temperature of 105 Deg.F. Such design conditions are common for units to be located in many parts of the USA, Middle East
and some countries in Asia and South America. The Air Cooled
Condenser requires thirty six (36) cells or modules arranged in six
(6) A-Frame streets of six (6) modules in each street. It occupies a
plot area of 250 ft. x 280 ft., tube length of 36 ft. and costs per ft plot
area, $350.00.
At first look the initial material cost seems to be more as the duct
size is increased. It is also evident that the overall pressure drop
has decreased as the duct size is increased. There are two options
to consider:
1. Decrease cooling airflow and thus decrease fan power.
2. Decrease surface area required for condensing the steam
keeping the fan power constant.
Looking at the fan power consumption, the fan power has decreased
as the duct size is increased. This means that more power can be
sent to the grid generating additional revenue. Even at a capitalized
cost of $1,500/kW, the additional evaluated cost between Design 1
and 4 can be $1,357,500. The capitalized cost can vary from $1,500/
kW to $4,000/kW and the evaluated cost can vary between
$1,357,500 to $3,620,000.
The condensate subcooling has decreased requiring less heat input to heat up the condensate increasing the cycle efficiency. This
can be of the same order of magnitude as the capitalized cost. This
is discussed in the next section.
The high velocity limits the minimum pressure the turbine can
operate at. The turbine will not able to operate at its maximum efficiency if the backpressure is limited. The pressure
drop induced by high velocity results in excessive subcooling
of the condensate.
The loss due to the backpressure between Design 1 and 4
can be one (1) percent of the steam turbine output. In this
example it is 1.7 MW. Assuming that the plant operates at
minimum backpressure condition for fifty (50) percent of the
year, the loss can amount to $1,275,000 based on $1,500/kW.
In addition, the steam required to heat up the subcooled condensate can add another one (1) percent of the plant output
or $1,275,000 or $150,000/Deg.F.
11
Normally, single or two speed motors are used for the control of an
air cooled condenser. This may not be sufficient if the control is
limited by the backpressure. In such instances, Variable Frequency
Drives are required. This can increase the initial cost by $1,000,000.
Conclusions
Lower duct velocity results in
-
References
1.
12
13
There are two principal concepts that often confuse people who are not familiar with cooling towers and how they operate:
1)
DesJardins
The Art
Selecting the economic size for the tower is part art and part science. The science is knowing how all the components work together, and the art is picking the right box size. The science will
be discussed momentarily, but first lets discuss the box size.
One can have a great big tower with a little bit of power or a small
tower that uses a lot of power. The tower can be either a cross flow
or a counter flow tower, forced draft or induced draft. They all can
be designed to have the same capacity. That means they all will
cool the same amount of water through the same temperatures at
the same wet bulb. However, one may have a high fan power, or a
high pump head while the another takes more real estate or requires
more starters and controls or has better maintenance preferences.
Deciding which tower design is best for a given plant is usually
either an economic decision or a physical need decision, and sometimes compromises are needed.
The economics usually involve a life cycle analysis of the cost of
parasitic power for fans and pumps, the size of available real estate,
piping and electrical equipment costs, cost of the basin and its
supports, the cost of capital, whether or not the taxes are involved
for a new capital expense or a write off for repairs.
CTI Journal, Vol. 28, No. 1
15
Another factor is often dictated by the banks: how long will they
give you to pay back the loan? It used to be that banks would loan
money for seven years for a refinery or chemical plant and thirty
years for a power plant. It took three years to build a refinery and
five years to build a power plant. Therefore, the economic analysis
was based on power costs of three years for a refinery or chemical
plant and twenty-five years for a power plant, regardless of how
long the plant may operate. Since the power crisis of a few years
ago there have been reassessments of these types of projects by
the lenders, and they may consider long term payouts poor investments which raises the cost of capital.
The compromise comes when the economic analysis is for only a
few years, yet it is known that the plant may run for fifty years or
more. Perhaps there needs to be a consideration for the changes
that could be made after the initial plant payout period has elapsed.
Is it possible to add another cell or change the fan power to provide
more cooling that would increase plant output or efficiency? What
effect would these changes have on the tower or other equipment
in the plant? Remember, everything works as a system. Even
though capital resources may be limited, buying on a low first cost
may not always be the best answer.
Physical needs may also limit the design options. Perhaps the
expected water quality will be contaminated by oil or excessive dirt,
fouling particles, biological growth and other contaminants. These
potential problems may dictate splash fill rather than a more efficient film type fill, or less thermally efficient open flute film type
fills. Maybe larger nozzle openings or different drift eliminator
designs will be required. Easy, open access to the distribution
system available in a cross flow tower may be necessary if nozzle
plugging is expected and safety regulations do not allow entering a
tower when the plant is in operation.
High temperature PVC or other plastic components may allow higher hot water temperatures
Increased cost of water treating
Scaling in heat exchangers
Plant performance: It is suggested that running an overall
economic analysis of flow rate and temperatures would be
advisable.
Evaporation rates may increase because the discharge air
will hold more water per volume unit.
Most tower fill tests have been run by manufacturers at 38
C (100 F) hot water temperature. Several authors have documented that operation at hot water temperatures above 38
C (100 F) will likely result in design deficiencies if hot
water correction factors or revised rating theories are not
used. Since many power plants operate at hot water design
temperatures between 46 C (115 F) and 52 C (125 F), it
should be noted that necessary corrections from simplified
Merkel performance theory can be as high as 7% to 10% at
these conditions.
FRP (fiber reinforced plastic) structures may require special
design considerations.
Practical limits apply to each of the tower components. The discussion that follows will look at these limits and how changes in one
will affect all the others (and, sometimes the system in which the
tower is operating).
16
Water distribution at very low flow rates (less than 2.0 l/s/m2
or 3.0 gpm/ft2) are often a major cause of performance being
less than expected when laboratory testing was done at
higher flow rates. This also often occurs when a low flow
rate is used for design and the system is run with fewer than
the design number of pumps at low ambient temperatures
without taking cells out of service.
Using nozzles selected for very low flow rates requires careful consideration of possible variations in plant operations.
Although low flow rates will usually result in less pumping
costs, the overall affect on heat exchanger design should be
carefully considered. Low flow rates with high LMTD may
result in higher backpressure on the system and low water
velocities may lower the heat transfer coefficients to the
extent that larger heat exchangers are required.
Choosing the optimum design wet bulb
17
Tough duty: (Long range, close approach to a low wet bulb temperature)
Fill dimensions
Counter flow tower fill considerations:
Approach
The approach (cold water temperature minus the wet bulb temperature) has probably the most affect on tower performance. While
most manufacturers do not want to make selections based on designs with less than a 2.7C (5 F) approach because a small deviation in temperature can sometimes mean a large variation in percentage capacity, a tower will operate at lower approaches. However, this usually means very low flow rates per unit area of tower
and it may be difficult to guarantee the actual performance will
agree with predictions based on tests at higher flow rates.
A rough general rule is that the required tower size (and cost) varies
directly with the approach. As an example, a tower with an 4C
(8 F) approach will cost 25% more than a tower with a 4C (10 F)
approach. This larger tower might be in the form of a bigger box, or
the same box with a different fill, fan, fan stack height, and/or more
power, or a combination of all of these options.
Range
Changes in the Range (hot water temperature minus the cold water temperature) generally do not have as great of an effect on the
tower size as changes in the approach given a fixed heat load.
Altitude
The altitude or barometric pressure will definitely affect tower performance. The driving force for cooling water is related to the
difference in the vapor pressure of water at the film of the water
18
19
Water distribution:
rail) shipment.
Field erected towers are usually sized on 4 ft or 6 ft (or 2 meter)
structural spacing.
Cell size
Cell sizes for package and factory assembled towers are usually
based on practical shipping limitations for truck (and sometimes
20
21
accordingly. However, if louvers are not provided it is necessary to have wind baffles to prevent water from blowing
from the tower air inlets.
It is critical that multiple-cell counterflow towers be
checked to assure that the inlet air velocities to the interior cells are within practical limits: this is especially true
if there are transverse cell partitions, and failure to check
this design consideration has often been a major source of
poor tower performance.
Air inlets on both sides of a cross flow tower produces
desirable fan requirements because there will be twice the
amount of air flow for the same amount of pressure drop.
This is a major advantage of a cross flow tower.
Cross flow designs are often the best option for small package towers with propeller fans because counterflow designs
do not have room enough for large diameter fans to match
the required air flow. This is the main reason small packaged
counter flow towers are provided with blower fans.
For smaller applications in congested areas it is often desirable to orient the tower to provide the minimum noise pollution. Noise levels off the cased side of a tower will often be
6 to 12 dB less than the levels off the louver side.
FIGURE 1
Fans
22
23
If the fan is operating in the fan stall region it will be inefficient and performance will be erratic.
If fan changes are necessary they can be made with changes
to the pitch, fan speed, or number of blades or a more efficient fan blade design. Often it is possible to change to a
larger diameter fan with the knowledge that the driveshaft,
gear box, fan stack and mechanical equipment supports will
also have to change.
Making changes without considering the total consequence
is often undesirable.
Changing the hub disk seal diameter will change the velocity pressure, and it will affect the total efficiency. A hub disk
seal will reduce or prevent air recirculation at the center of
the fan.
Two speed fans can save considerable power expense. According to the fan laws the fan power decreases proportional to the speed cubed, and the noise level can be as
much as 13 dB less at half speed.
5 ft diameter inch
7.5%
7.0%
6.5%
28 ft diameter 1 inch
6.0%
40 ft diameter 2 inch
5.0%
Fan stacks
Fan stack designs are usually selected for economic reasons.
24
Extending the fan stack height not only costs more for the
taller stack, but it also may affect the structural design due
to higher wind load considerations.
Low height fan stacks ( 2 m / 6 ft high) on large fans (over 7
m (22 ft) diameter) are not recommended. The wind effects
on fan performance can be significant due to eddies formed
by the upwind edge of the stack. The minimum stack height
should be 3 m (10 ft.) for applications with large diameter
fans.
Straight-sided or truncated-cone type fan stacks may be
economical to build, however the reduction in fan efficiency
is usually quite significant maybe more than 15%.
Air rates
25
l/s/m
fpm
Gpm/ft
m/s
l/s/m 2
fpm
Gpm/ft 2
13.6
600
20
15
600
22
3.55
6.8
700
10
3.55
11
700
16
3.8
4.0
750
Pressure drops
Sometimes the ability to select a proper fan is limited by high static
pressure losses. Propeller fans usually do not perform well at total
static pressures above 250 Pa (1.0 inches wg) without an excessive
number of blades or high speed. High static pressures also can
result in noisy fans.
Inlet and discharge pressure losses by enclosures, louvers, screens
or obstructions must be accounted for.
Fan power
The output from fan curves is called fan horsepower or fan kW. It
is necessary to add drive losses created by gear boxes or belts and
bearings to obtain the brake horsepower or brake kW. Spiral bevel
gears, most commonly used in cooling towers, have an inherent
efficiency of 98%, and in addition a gear box will have a no load loss
due to friction and oil viscosity which brings the total drive loss to
a total of about 4% to 5%. Actual no load losses will vary from
about 0.5 kW for small gear boxes to 3.75 kW for very large boxes.
Motor efficiency
High efficiency motors are generally economical for cooling tower
fans. Since certified tower testing is based on readings of kW input
to the motors, it behooves the manufacturer to use the best motor
efficiency possible. On the other hand, owners and operators that
need to repair a motor should seriously consider new motors rather
then re-winding the old one to get the best efficiency.
26
Conclusion
Designing a cooling tower is partially art and mostly science.
The art is picking the best box size and the right combination of fill,
fan, and other components to give the most economical selection.
The most economical selection may be low first cost or low evaluated cost.
The science is adequately measuring the test data, developing a
theory that properly correlates the data and allows for application
of the data in a manner which does not produce distorted results.
Practical review of the results should show the laws of physics still
apply, i.e., similar fills should produce similar performance characteristics, and similar fans should have similar efficiencies. There is
no Black Magic.
Air and water distribution are all important. The best performance
is going to occur when the distribution is even over the full area of
the tower. This is difficult to achieve. Some water nozzles and
distributors are better than others, and sometimes a manufacturer
may claim performance capabilities based on testing with one type
of nozzle applies to their nozzle when this is really not the case.
Fan testing may have been done in ideal eased inlet stacks with
very close tip clearances. Actual field installations seldom have
extremely close tip clearances to allow for wind load deflections,
thermal expansion of the fan blades or the stack, possible slight
slumping of a stack over time, and construction assembly tolerances. The shape of the stack being used may not be the same as
the fan manufacturer used for its tests. Improper fan hub seal disks
may be used.
Air distribution can be affected by high inlet velocities, louver
spacing and angles, wind, partition location, obstructions and structural blockage, etc.
Static pressure losses for various components are the most difficult data to measure and predict. Different manufacturers may
show significant variations in the pressure drop across individual
components, but the total pressure drop will normally be quite
consistent.
These are just a few of the many considerations that create uncertainty. The object is not to hedge: it is to try the best possible to
predict something close to reality.
The important point to remember is that a cooling tower works as a
system, and changes to one part will usually affect others, and the
design of the tower can significantly affect the overall plant operation.
27
Abstract
For many years PVC film fills have been the most
popular choice of heat transfer media for use in
cooling towers. Throughout this history, design
features of these fills have continued to evolve
from the first cross-corrugated products through
vertically fluted fills to todays popular combination designs. Some of these features are not obvious to the casual observer and if not chosen correctly can adversely affect tower performance, product cost, lifespan, or ease of installation. This paper traces the history of these fill designs while
providing guidelines as to the proper fill selection.
Donald Zelek
History
Plastic film fills have been used in cooling towers for about 40
years. The first cross-fluted pack was patented in 1966. This was
followed shortly after by the first paper on cellular fill presented to
CTI by George Meek in the summer of 1967. During these early
years this new fill design was used primarily in smaller towers in the
US. During the 70s most large scale installations still favored
hanging sheets. It was not until the late 70s that the first large
scale new installation, AEPs Rockport facility, was designed around
film fill. It is interesting to note that the same fill is still in operation
in this tower after approximately 25 years of service. It was not
until the mid to late 80s that we began to see the first large scale
repacks with film fill such as AEPs Big Sandy and Gavin facilities.
Since these early products there has been considerable advancement in fill design. The early designers were looking at alternatives
to wood splash bars and heavy cement sheets. Early designers
such as Carl Munters realized that packs produced of cross-fluted
sheets provided much greater efficiency with much less weight.
Fouling concerns were primarily limited to scaling. However, over
the years operating conditions have changed and todays towers
have much greater demands applied to them. Economic issues
have forced tower sizes to be smaller raising airflows and water
loadings. Availability of water has been reduced which in many
cases has resulted in reduced water quality such as the use of
municipal waste water for cooling. These factors have all forced
film fills to change with these demands.
28
Figure 1
There are two main components to fouling. High total suspended
solids (TSS) which can be both water born and air born will create
the fouling load. But in addition to this a binding agent is also
needed in the form of high biological content or the presence of oils
or grease. These are the components that bind the TSS to the
packing and previous layers of TSS. To create an environment for
high fouling potential all three of these components will be present
in high concentrations.
This paper will not provide an in depth review of the aspects of
fouling. There have been several good papers presented at CTI on
this topic. Here, we will only be concerned with knowing how to
respond to this information. The guidelines presented for the selection of fills with respect to the fouling environment are based on
over 15 years of experience with fills in fouling environments in
waters serving steel mills, paper processors, petrochemical plants
and power plants using open bodies of water such as lakes
and rivers. Extensive research conducted by CTI member companies have also added to this knowledge base to provide the guidelines presented here. Selected important references are also included
in references list.
Cross-fluted fills have always been highly efficient. The cross
flutes with the numerous contact points within the packs allow for
good redistribution of water. The microstructure allows for turbuCTI Journal, Vol. 28, No. 1
24 x 1 1/8 deck
29
lent water flow. Microstructure is the small bumps and ridges formed
into each sheet and is present on most film fills. It can enhance the
products performance significantly. A fill with an aggressive microstructure will create a water film that is very turbulent and well
mixed as shown in Figure 2. This will help improve efficiency but
will also increase fouling potential. The angled flutes on crossfluted fills provide a path that moves the water at a relatively low
velocity through the fill. But all of these attributes also provide for
greater fouling potential. As a result cross-fluted fills should only
be used when good water chemistry and treatment is in place. As a
general rule TSS should not exceed 100ppm if there is good biological and scale control and there should be no oils or grease. The TSS
should be reduced to no more then 25ppm if the biological count is
high. Generally, this author is defining good biological control to
mean total aerobic bacteria not exceeding 10,000 colony forming
units per ml (CFU/ml). A high biological count is 100,000CFU/ml.
Fills with an offset flute design are more resistant to fouling. However, they should not be considered the most fouling resistant.
Offset fluted designs have fewer contact points and between them
the flutes are vertical or near vertical. The vertical flutes allow for a
faster water migration through the packing. This flushing action
keeps the fill cleaner. Fills of this type generally can withstand TSS
up to 200ppm provided there is good biological and scale control.
Oils and grease should not exceed 1ppm.
Vertically fluted film fills are the most tolerant to fouling. Unfortunately, the trade off is that they are also the least efficient. Water
moves through the vertical flutes unrestricted by any contact points.
Water film velocity is the greatest in these fills. The shearing action of the high velocity water film keeps these types of fill cleaner
in poor water conditions. However, it is important to note that one
can not assume that these types of fill are tolerant to all water
conditions. All film fills can foul when the correct conditions are
present.
This group can be further divided into two sub groups when looking at their potential for fouling. Vertically fluted fills with an aggressive microstructure can tolerate a TSS up to 500ppm with good
biological and scale control. With a poor biological control TSS
should not exceed 200ppm. Oils and grease should not exceed
5ppm.
Of the film fills, vertically fluted products with little or no microstructure are most resistant to fouling. The trade off is that these
fills will have the lowest thermal performance. They can operate in
TSS(ppm)w/high Bio
Cross-flute
Offset flute
<100 <25
<200 <50
<500 <200
<2000 <1000
Good
Good
Poor
Vertical flute
Vertical flute
microstructure no microstructure
None
<1
<5
<25
Fibers
None
None
None
None
Table 1
Figure 3
Figure 2
30
31
cross-fluted fill. Fill manufacturers have incorporated integral louvers and drift eliminators into their crossflow fills. These features
are required in most retrofits. However, the cross-fluted designs
have trouble managing the heavy water loadings. The angled flutes
force the water towards the louver face. As more water travels
down the drainage channel which separates the cross-fluted section from the integral louver, that passage way becomes flooded.
The excessive water in this channel will then block airflow through
the fill.
In most cases the tower can be engineered to correct or at least
minimize this problem. However, this requires an expert understanding of the tower in question and forces at work. Unfortunately, the solution may be different for each tower. These precise
modifications have made cross-fluted designs more difficult to use
and their performance somewhat unpredictable. In recent years the
trend has been to use herringbone designs for retrofits. With this
design there is no flute bias pushing the water towards the louver
face. The engineered zig-zag pattern keeps the water more evenly
distributed throughout the fill at higher air velocities.
Economic considerations
Once a flute type is determined, attention can be paid to economic
issues. The fill comprises approximately 20% of the cost of a new
tower. Items that can adversely affect fill costs are material gauge,
material type, installation labor, and freight.
In todays cost conscious world, thinner material gauges have become more common. In some cases this is not necessarily bad.
Advanced thermoforming techniques have been able to more evenly
distribute material during the forming process. As result it has
become common to use a mix of gauges throughout the same tower.
Typically the material on the top layer of the fill section will be of a
heavier gauge to better withstand the foot traffic of routine maintenance. Heavier material gauges on the bottom layer should also be
considered. This is particularly true with vertically fluted medias.
Many of these products have larger flute openings which do not
have the load bearing strength of the denser cross-fluted fills. The
point loads applied at the supports can be too great in some cases
for lighter material gauges.
It is difficult to apply a life span to a material gauge. There are
numerous examples at both ends of the spectrum of up to 25 years.
It is known that all plastics will break down with time. The molecular bonds break causing the plastic to become brittle. A heavier
gauge product will withstand this process for a longer period of
time and should be given consideration particularly when external
forces are expected such as regular foot traffic or ice loads.
At this point a note needs to be made on specifying material gauge.
This can become a confusing issue for those unfamiliar with PVC
fills because the cooling tower fill manufacturers do not necessarily use consistent notation when expressing the gauge of fill. In
some cases it could be expressed as an after-forming gauge and in
other cases it could be a before-forming gauge. During the forming
process the raw material is heated and passed over a tool which has
the shape of the product desired. When this occurs the raw material is stretched at certain points as shown in figure 4. This stretching process is not uniform and the ability of the manufacturing
process will dictate to what degree the final product is thinned out.
It should be noted that the CTI standard STD-136 specifies that the
material gauge shall be based on an average and a minimum
thickness after forming, as well as a raw material starting thickness
before forming.
32
Figure 4
A fills after-forming gauge will always be less than its before-forming gauge. It is important to know which gauge notation is being
specified. Do not be misled into thinking that a heavier gauge
product is being supplied. Statements like made of xx mil are
intentionally vague and could imply to mean either after-forming or
before-forming.
When purchasing any film fill, raw material type and quality must
also be considered. In the world today polyvinyl chloride (PVC) is
the most widely used material. Properties such as its low cost, ease
in forming and assembly, resistance to chemicals and degradation,
and self extinguishing characteristics makes this material the overwhelming material of choice. Other materials such as polypropylene, polystyrene, and cement boards are used but have drawbacks
such as weight, price, durability, and flammability. Options for
assembling other materials such as polypropylene are limited as
solvents are not effective on this material.
When specifying PVC it is important to insist that all raw materials
meet CTI Standard 136. Products that dont meet this standard are
likely to have problems such as a much lower heat deflection temperature. CTI standard 136 requires ASTM test D648 meet 160F.
Products not meeting this property would experience symptoms
such as shrinking at elevated temperatures. Cheaper materials may
also use a high level of less expensive flexible vinyls containing
plasticizers creating a finished product with poor beam strength or
little UV resistance. These inferior raw materials can not be noticed
by simple inspection in the field. Therefore, it is best to use raw
materials that have been QA tested to CTI standards.
Even what would appear to be small differences in fills such as part
size can influence the installed cost of the product. Bay size will
dictate to some degree the part size needed for a particular site.
However, even with the length fixed there are still many options
available. Most of the film fills today are supplied in assembled
blocks that range from as small as 4ft3 each to as large as 40ft 3 each.
There are numerous arguments as to which size is best. Several
points will be presented here but ultimately this is a site specific
issue.
As a general rule packs that are between 12ft3 and 20ft3 are less
expensive to manufacture then those that are much smaller or larger.
These parts are usually 2ft deep and between 6 and 10 ft in length.
These sizes are also typically favored by field personnel for their
ease in handling. However, poor water distribution would favor
shallower 12" deep packs. Each layer of fill is generally installed
90 to the previous one. This crossed pack design enables better
water distribution through the fill. There have been claims made
that the greater number of pack to packs interfaces created by
shallower packs will result in a greater potential for fouling. However, research shows that the water film velocity dictates the greatest potential for fouling and not the size of the opening at interface
of two packs.
CTI Journal, Vol. 28, No. 1
33
3.
4.
5.
6.
Figure 5
7.
Film fills are the best choice for many cooling towers. Their performance is unmatched. However, before any fill is chosen, a good
understanding of the water chemistry is required. This needs to
include both current conditions and anticipated conditions in the
future. Have a good understanding of the fill being offered and pay
attention to the details. Know where the product is being manufactured. This market is a mature one. Todays manufactures are
designing highly engineered products to meet very specific needs.
There are many options available and the one with the least expensive up front cost may not be the best in the long run. If unfamiliar
with the product, ask for drawings and samples and most importantly, ask questions.
8.
Conclusion
Figure 6
Duke, Jay. Allegheny Powers Experience with PVC Film
Fill in Cooling Towers. Paper presented at the American
Power Conference, Chicago, IL, 1994.
Meek, George. Cellular Cooling Tower Fill. Paper presented at the Cooling Tower Institute meeting, New York,
NY, 1967.
Mortensen, Kenneth. Low Clog Fill New Approaches.
Paper presented at the Cooling Tower Institute meeting,
Corpus Christi, TX, 2001.
The Munters Story, Published by Gullers Pictorial AB,
Stockholm, Sweden, 1983.
Whittemore, Michael and Tom Massy. Current Fouling
Problems of PVC Film Fills and Research into New Designs to Eliminate Fouling. Paper presented at the
American Power Conference, Chicago, IL, 1992.
Personal communications with Mr. Frank Michell November,
2005.
Appendix
References:
1.
2.
34
Cross-flute designs
35
36
37
Abstract
Reasons To Rebuild
The purpose of this paper is to detail the activities which took place
before and during the reconstruction of the (2) cooling towers of
Unit #3 during the months of October and November of 2005. The
paper identifies the activities and justification involved leading up
to this replacement as well as the procedures performed to actually
demolish and rebuild these (2) towers during a 5-week outage.
David Spacek
Figure 1
Background
The Westar Energy Company is the electric utility, which serves
the northeast, central, and east-central parts of Kansas. The Jeffrey Energy Center is a 2,300-Megawatt coal fired power plant,
which is part of the Westar Energy fleet and is located approximately 40 miles northwest of Topeka, Kansas. The plant consists
of three like size units (approximately 765 MW each) and burns
western coal from the Powder River Basin area of Wyoming. Each
is serviced by (2) round mechanical draft cooling towers.
The Cooling Towers, which serve Jeffrey Energy Center Unit #3,
were constructed and placed into service in 1983. There are two
towers and they are both round mechanical draft cross flow design.
Each tower is approximately 175 in diameter and approximately 40
feet tall. The airflow on each tower is supplied by eight mechanical
draft fans. The fans are all situated on a concrete deck on the top
and center of the tower and pull air through the fill sections in a
cross flow manner. The fans are really completely separate from the
heat transfer or fill section of the tower, which is located around the
perimeter of the concrete structure. Each tower is designed to flow
166,000 gallons per minute. The structural members in the heat
transfer section of the tower are treated Douglas Fir. The fill media
is a splash type in a parallel configuration.
38
Figure 2
with Douglas Fir and Stainless Steel hardware. The condition of
the wood had become suspect. During outage inspections it was
quite clear that significant erosion of the diagonal cross members
and girts had occurred. At almost every recent outage, drift eliminators had fallen out and in the course of putting them back in
place, it was clear the wood behind them had deteriorated. Also,
numerous perimeter louvers had fallen from the towers in the last
two years and in the course of reinstalling back in place, it was
clear that the wood had deteriorated on the inside fill area as well.
With the deterioration of the tower in general, the overall performance of the tower had decreased. There was also a need to bring
the towers at least back to the original design conditions.
39
The office trailer was easily connected with 220 VAC power. Also,
Internet and phone service was established via wireless Internet.
This worked very well. The construction crew spent the summer
assembling bents, installing clips on grids, and building walkways.
Having a building available to do some of the work insured no lost
production time due to the weather. On the past (4) towers, the
asbestos louvers were removed prior to the demo, but the louvers
on Unit #3 were not asbestos so this was not necessary.
Figure 3
They had also experienced some special occurrences during their
life. Those occurrences are listed below:
1. During the middle 1980s, there was a partial collapse of
one of the towers. This occurred during a shutdown of
Unit #3 in the middle of the winter. There was no heat load
on the tower during this time and the weather was cold
enough to freeze the water flowing over the tower and
cause the partial collapse.
2. A windstorm in the summer of 1994 collapsed about half
of the fan cylinders and also destroyed the fans and drive
shafts in those same cylinders.
3. About five years ago, it was determined that the hot water
basins on both towers were in very poor condition. During an outage in 2001 a plywood overlay of the basins was
done as a temporary repair until such time to reconstruct
the towers.
4. Some minor freeze damage occurred on one of the towers
in the spring of 2002. Some broken columns, girts, collapsed grid and fill, and some fallen louvers resulted from
water flowing over the tower with no heat load and an
unexpected cold spell caused the water to freeze.
5. Two partial collapses occurred on one of the towers during the winter of 2003. The tower was in service at the
time. The damage consisted of several broken columns
and the resulting collapsed girts, grid, and fill. Fortunately, the damaged areas were walled off and the remainder of the tower was able to operate normally.
6. A general increase of maintenance has occurred due to
some of the above mentioned problems as well as age of
the equipment.
Preparatory Work
Most of the construction materials arrived in the fall of 2004. There
were two reasons why the material arrived so early. Some consideration had been given to doing the reconstruction on the towers in
the spring of 2005. As illustrated by the items mentioned above,
the towers are in poor condition and if one of them did fail we
wanted to be prepared for an emergency replacement. Secondly,
the projection was for raw materials prices used to manufacture the
parts and pieces for the towers were going to climb because of oil
prices and we wanted to take advantage of the lower costs.
A small construction crew arrived on site in May of 2005. A work
area was established for them around the towers and also inside of
a seldom-used building at the plant. An office trailer and a crew
trailer were brought on site to be used by the construction crew.
40
Unit #3 was shut down the evening of October 7, 2005. At approximately midnight, the water flow to the towers was shut off. Immediately after the water was shut off, previously installed temporary
pumps were turned on to begin pumping out the cold water basin
into the normal drain system. As people arrived the next morning to
begin work, the water level was well below the basin floor level of
the cooling towers. The demolition could begin with minimum
water in the basins. After about two hours of preparation and set
up that morning, the demolition of the old towers began.
The demolition of the old towers was not a pretty sight. It was
done with a long pipe, which had hooks on the end of it. This pipe
was attached to a front-end loader. The front-end loader jabbed
this hooked pipe in the fill sections of the towers and with some
extra maneuvering brought both of them down with the debris falling into the basin. The demolition took approximately a day and a
half. This removal of the debris from the cold water basins had
taken approximately three days. The basins in both towers were
completely clean and dry. The old anchor castings were removed
and construction was ready to begin.
The (8) sets of mechanical equipment on top of the concrete structure was left intact. No replacement was performed.
Figure 4
Figure 5
CTI Journal, Vol. 28, No. 1
41
Figure 6
Figure 9
structed at the same time to insure the completion during the 5week outage, and different jobs were performed simultaneously.
The installation of the drift eliminators and walkways were some of
the last tasks to complete. The stairwells remained intact and reused on the new towers. These methods were refined over the last
four years during the reconstruction of four previous cooling towers at the Jeffrey Energy Center. Many lessons were learned during
those previous jobs and efficiencies of motions and methods were
achieved.
Figure 7
Figure 10
Figure 8
42
Figure 11
CTI Journal, Vol. 28, No. 1
43
44
45
the joints. Some minor repair of broken concrete around the coldwater basins and the access tunnels to the interiors of the towers
were also repaired. Lastly, six torsion tubes and the accompanying
support beams will be replaced on one of the towers. These torsion
tubes replacements will complete a project begun several years
ago. The torsion tubes currently in service in these six locations
are in poor condition and this replacement will insure reliable operation of those particular cells.
Figure 12
Figure 15
Conclusion
Figure 13
Figure 14
47
the registered design professional related to components that are not designed by the professional, such as cooling towers. The code requires
the professional to provide in the contract documents the design wind load pressure (psf) (kN/
m2).
Abstract:
Changes to national building code and the state
building code of Florida have given rise to special
requirements for cooling towers to be able to withstand hurricane forces.
This paper will review national and Florida state
building codes as they apply to cooling towers
with emphasis on what must be communicated to
specifying engineers, owners and building inspectors with the goal of getting unit acceptance at
the jobsite and also design of units that meet the
code.
Daniel S. Kelly
Introduction:
Cooling towers are an integral part of HVAC and industrial process
cooling systems. A heat load from a conditioned space or a manufacturing process is rejected into the atmosphere using a cooling
tower by evaporating a small percentage of the re-circulating water.
Because the atmosphere is the heat sink, cooling towers are usually installed exterior to the building allowing easy rejection of the
buildings cooling load to the atmosphere.
Building codes identify design dead, live, wind, snow, rain and
seismic loads for building or building components, such as cooling
towers. The minimum design criteria are described for the building
or component that is exposed to direct atmospheric conditions;
such as hurricane wind forces, when the failure of the component
could pose a loss of life hazard.
When an owner commissions design professionals to design and
construct his building, the owners expectations are not only a
finished building that is functional and aesthetically pleasing, but
one that meets all applicable building codes in order to obtain the
certificate of occupancy from the local authority. It is the responsibility of the registered design professionals to design, specify, purchase and install parts, materials, assemblies and systems, including components such as the cooling tower that meet or exceed the
minimum design criteria in the governing building code.
There are many different building codes published and adopted
across the country. IBC 2003 is currently adopted by 45 states and
Washington D.C. (see figure 1). ASCE 7 is referenced in IBC 2003
as the governing code when the provisions and exceptions allowing IBC 2003 to apply are not satisfied. Florida has its own state
code again based upon ASCE 7. Some states have adopted the IBC
2003 building code state wide, while others leave the codes up to
the local jurisdictions.
The registered design professional, usually the engineer of record,
specifies the details of the cooling tower in mechanical specifications. The IBC 2003 code explicitly identifies the responsibility of
48
Each section of the paper covering the three main wind load codes
discussed herein has the following parts:
Applicability: when and where it applies to cooling towers.
Application: how it applies to cooling towers.
Administration: Communication of the design parameters to the
manufacturer in order to be assured the cooling tower design meets
the code.
49
If the building meets all these criteria, then the cooling tower shall
be designed to meet the Design Pressure detailed in Section
1609.6.2.2.
II.
Application
Reading Chapter 1609.1 IBC 2003 and progressing through the code,
there are defining parameters to be determined useful in the interpretation and application of the code to cooling towers.
Basic wind speed is determined by Figure 1609 in IBC 2003. Figure
1609 is a series of maps with contour lines of constant wind speed.
One locates the jobsite on the maps and may interpolate linearly
between contours to determine the design basic wind speed for the
jobsite. Local jurisdictions may require wind speeds be employed
other than that defined in Figure 1609, particularly if the jobsite is
located in a special wind region, near mountainous terrain or near
gorges. Localized high wind velocities may occur in such regions.
When wind speeds are determined by local jurisdictions, Section
6.5.4 of ASCE 7 shall apply. Adjustments to the basic wind speed
by the local jurisdictions are based upon meteorological information. The registered design professional should investigate if local
high wind speeds apply.
Exposure Category reflects the characteristics of the ground surface irregularities. Variations in ground surface roughness due to
natural topography, vegetation and constructed features all contribute to the exposure category. The openness or amount of exposure the component (cooling tower) has to the impact of the wind
forces is accounted for in the exposure category.
Exposure A is not used in IBC 2003
Exposure B is the basic, catch all category. If the building does not
fall into Exposure C or D, then it shall have Exposure B. Exposure B
is characterized by urban and suburban areas with densely packed
obstructions having the size of single family dwellings or larger.
Exposure C is characterized by open terrain with scattered obstructions. Exposure C has a smooth natural topography and irregularities having height of 30 feet or less extending 1500 feet (457m) in all
directions from the building site. This category includes flat open
country, grasslands and shorelines in hurricane prone areas such
as the US Atlantic Ocean and the Gulf Coast where the figure 1609
basic wind speed exceeds 90 mph (39.6 m/s) and Hawaii, Puerto
Rico, Guam, Virgin Islands and American Samoa.
Exposure D is characterized by flat, unobstructed areas exposed to
wind flowing over open water (excluding hurricane prone areas) for
a distance of 1 mile (1.61 km). Shorelines include inland water ways,
the great lakes, the coastline of California, Oregon, Washington
and Alaska. Exposure D extends inland only 1500 feet (460m) or 10
times the building height, whichever is greater.
Importance Factor
The cooling tower is assigned a wind load importance factor, Iw .
Table 1604.5 provides guidance in selecting the importance factor
based upon the type of building and the occupancy. There are
three importance factor values; low hazard with Iw = 0.87 (or 0.77 in
hurricane prone areas), substantial hazard with Iw = 1.00 and essential facilities with I w = 1.15. The building category or nature of the
occupancy determines the appropriate importance factor.
All cooling towers installed on a building in comfort cooling applications should be assigned an importance factor of 1.00, unless
50
they meet more stringent requirements of Category III or IV buildings, where the importance factor should be 1.15. Cooling towers
installed on grade or otherwise installed on structural supports not
integral with the main windforce-resisting system of the building it
serves or on a Category II building may use 0.87 (or 0.77 in hurricane prone areas) or 1.0 importance factor as the design professional determines appropriate.
Category I buildings or other structures are those which pose a low
hazard to human life in the event of a failure, such as agricultural
facilities, temporary facilities and minor storage facilities.
Category II buildings and other structures are those that are not
listed in Category I, III or IV.
Category III and IV buildings and other structures are those which
pose a substantial hazard or designed as essential facilities, respectively. Examples of Category III and IV buildings are:
Where more than 300 people can congregate in one area
Non-adult educational structures with an occupant load
greater than 250
Adult educational structure with an occupant load greater
than 500
Jails and detention centers
Hospitals and health care facilities
Fire, rescue or police stations and emergency vehicle garages
Facilities used for emergency management/response.
Aviation towers, air traffic control centers
Water treatment, waste water facilities, water facilities required to maintain water pressure for fire suppression.
Buildings having critical national defense functions
Any other occupancy with an occupant load greater than
5000
51
Per Section 1609.6.2.2, the net design wind pressure is the sum of
the pressures applied normal to the cooling tower surface as shown
in Figure 1609.2.2. An additional sketch of a cooling tower with the
pressures acting toward and away from the cooling tower normal to
the surface is provided in Figure 2 in this paper.
II. Determine the design wind pressure for a data center installed at
grade in Atlanta, Georgia.
The Basic Wind Speed for Atlanta is 90mph.
Figure 1609
The net design wind pressure, pnet is determined using IBC 2003
Equation 16-35:
Table 1604.5
p net
III.
Administration
The Net Design Wind Pressure towards the 100 ft 2tower is 12.4.
Table 1609.6.2.1(2)
The Net Design Wind Pressure away from the 100 ft2 tower is 15.1.
Table 1609.6.2.1(2)
The Design Wind Pressure is therefore: (1.15) * (1.00) * (12.4 + 15.1)
= 31.6 psf.
Figure 1609
Table 1604.5
Section 1609.4
52
Section 1609.4
4.
II.
Application
53
Surface Roughness C is defined as open terrain with scattered obstructions having heights generally less than 30ft,
including flat open country, grasslands and all water surfaces in hurricane-prone regions.
Surface Roughness D is characterized by unobstructed areas and water surfaces outside hurricane-prone areas.
Exposure Categories
Exposure B applies when the ground surface roughness B condition prevails in the upwind direction for the greater of a distance of
at least 2630 feet or 10x the height of the building. If the building
mean roof height is less than or equal to 30 feet, then the upwind
distance consideration of the ground surface condition is reduced
to 1500 ft.
Exposure C is the catch all category in Section 6 ASCE 7. If the
building does not fall into Exposure B or D, then it shall have Exposure C.
Exposure D applies when the ground surface roughness D prevails
in the upwind direction for the greater of a distance of at least 5000
ft. or 10x the building height. Exposure D extends inland from shorelines (not in hurricane-prone areas) for the greater of 660 ft. from
the shoreline or 10x the building height.
Topographical Effects take into account increases in wind speeds
if the structure is located on top of a hill, ridge or escarpment. The
physical attributes of hill, ridge or escarpment are used to determine the topographical factor. Typically, this factor is equal to 1.0,
however the registered design professional should investigate if
there are topographical issues which need to be considered.
Enclosure Classifications are used in determining the internal pressure coefficients. All buildings or structures shall be defined as
enclosed, partially enclosed or open. An Open building is one having each wall at least 80% open. Partially Enclosed is where the
total area of openings in the windward wall exceeds the sum of the
open areas in the other walls and roof by 10% and the total area of
the windward wall openings exceeds 4 square feet or 1% of that
wall area with the percentage of the openings in the balance of the
building envelope not exceeding 20%. In a partially enclosed building, wind pressure can enter the building through an opening larger
than openings in the remaining walls, thus producing a positive
pressure inside the building. Buildings not meeting Open or Partially Enclosed criteria are defined as Enclosed.
Velocity Pressure, qz, evaluated at height z is calculated using
Section 6 ASCE 7 Equation 6-15
qz = 0.00256 * Kz * Kzt * Kd * V2 * I
where:
Kz = is the Velocity Pressure Coefficient, a factor on the nominal velocity pressure to account for the varying exposures from Section 6 ASCE 7 Table 6-3. The value depends
upon the height above ground and exposure category.
Kzt = is the Topographical Factor
Kd = is the Wind Directionality Factor, a factor accounting for
the structure type, such as component, chimney, tank,
sign, or trussed towers. This value is 0.85 for cooling towers.
V = Basic Wind Speed
55
I = Importance Factor
Note that qh is the velocity pressure using Section 6 ASCE 7 Equation 6-15 evaluated at height h. For purposes of components installed on a building roof that is more than 60 feet above grade,
height h and height z can be taken as equal, therefore qh = qz.
The Mean Roof Height is about 140 feet for a 10 story building.
The Basic Wind Speed, V, for Miami is 147mph.
Figure 6-1b
Table 6-4
Table 6-3
Table 6-1
Section 6.5.6.2
Exposure Category is C.
Section 6.5.6.3
Figure 6-5
Design Wind Load for Cooling Towers on buildings with mean roof
height greater than 60ft.
Figure 6-17
p = q * (GCp) qi * (GCpi)
where:
III.
Administration
Exposure Category is B.
Importance Factor
Examples:
I. Determine the design wind pressure for a cooling tower installed
on top of a 10 story commercial office building located in Miami,
Florida.
56
Figure 6-5
Figure 6-17
Figure 6-17
57
I.
Applicability
II.
Application
Exposure Category reflects the characteristics of the ground surface irregularities. Variations in ground surface roughness due to
natural topography, vegetation and constructed features all contribute to the exposure category. The openness or amount of exposure the component has to the brunt of the wind forces is accounted for in the exposure category.
Exposure A is characterized by large city centers with at least 50
percent of the buildings having height in excess of 70 feet. Exposure A is limited to areas for which this terrain prevails in an
upwind direction the greater of at least mile or 10 times the
building height.
Exposure B is the basic, catch all category. If the building does not
fall into Exposure C or D, then it shall have Exposure B. Exposure B
is characterized by urban and suburban areas with densely packed
obstructions having the size of single family dwellings or larger.
Exposure C is that area which lies within 1500 feet of a coastal
construction control line or 1500 feet of a high tide line, except
high velocity hurricane zones. Broward and Miami-Dade counties are high-velocity hurricane zones and shall be taken as Exposure C.
Exposure D is characterized by flat, unobstructed areas exposed to
wind flowing over open water (excluding hurricane prone areas) for
a distance of 1 mile (1.61 km). Shorelines include inland water ways,
the great lakes, the coastline of California, Oregon, Washington
and Alaska. Exposure D extends inland only 1500 feet (460m) or 10
times the building height, whichever is greater.
Importance Factor
The cooling tower is assigned a wind load importance factor, Iw .
Table 1604.5 provides guidance in selecting the importance factor
based upon the type of building and the occupancy. There are
three importance factor values; 0.87 (or 0.77 in hurricane prone
areas), 1.00 and 1.15. The building category or nature of the occupancy determines the appropriate importance factor.
All cooling towers installed in comfort cooling applications should
be assigned an importance factor of 1.00, unless they meet more
stringent requirements of Category III or IV buildings, where the
importance factor should be 1.15. Cooling towers installed on grade
or on structural supports not integral with the main windforceresisting system or on a Category II building may use 0.87 (or 0.77
in hurricane prone areas) or 1.0 importance factor as the design
professional determines appropriate.
Category I buildings or other structures are those which pose a low
hazard to human life in the event of a failure, such as agricultural
facilities, temporary facilities, minor storage facilities, and screen
enclosures.
Category II buildings and other structures are those that are not
listed in Category I, III or IV.
Category III and IV buildings and other structures are those which
pose a substantial hazard or designed as essential facilities, respectively. Examples of Category III and IV buildings are:
Where more than 300 people can congregate in one area
Non-adult educational structures with an occupant load
greater than 250
Adult educational structure with an occupant load greater
than 500
CTI Journal, Vol. 28, No. 1
59
The Net Design Wind Pressure away from the 100 ft2 tower is 22.5.
The design procedure is to determine the Basic Wind Speed, Importance Factor, Exposure Category and Height and Exposure Adjustment Coefficient specific to the site location. These parameters
are inputs used to determine the Design Wind Pressure.
III.
Administration
Figure 1609
Table 1604.5
Section 1609.4
The Net Design Wind Pressure towards the 100 ft 2 tower is 40.5.
Table 1609.6B
The Net Design Wind Pressure away from the 100 ft2 tower is 33.1.
Table 1609.6B
60
61
Abstract
Chemical Stress
River water containing about 100 ppm of calcium hardness and 0.8
1.2 ppm of PO4 was used as make-up water. Cycles of concentration were maintained at about 6.0. A neutral phosphate chemical
treatment program was in place, maintaining 18 20 ppm of total
inorganic phosphate (TIP) in the recirculating water.
63
Results
By reducing TIP concentrations, fouling reduction was achieved.
As shown in Figure 1, TIP was reduced through improved control
using the tagged dispersant polymer. The results are shown in
Figure 2. Heat exchanger efficiencies improved following adoption
of tagged polymer control.
Mechanical Stress
Mechanical stresses were moderate. Adequate flow was maintained through all exchangers and maximum skin temperatures were
only 130F (54C).
Operational Stress
Automation and good preventive maintenance minimized any operational stress.
Chemical Stress
The predominant stress at this facility was chemical. Elevated chlorides, sulfates and conductivity made the water very corrosive most
of the time, but inorganic phosphate concentrations were highly
variable, rendering the water scale-forming at other times.
Figure 1: The improvement in TIP control gained through
tagged polymer control is apparent. Online control based
strictly on the inert tracer material was an improvement over
conventional control using wet chemistry and manual
adjustment. Advancing to tagged polymer control, where
chemical adjustments are made based on the scale-forming
stress on the system, reduced TIP contribution even further.
Results
As shown in Figure 3, localized corrosion rates improved by 61%
after the change from the traditional, pyrophosphate-based treatment program to a PSO-based program. Figure 4 shows corrosion
coupons removed from the system before and after adopting the
PSO-based treatment program.
64
65
A fluorescent material, a bio-reporter, was introduced into the recirculating water. This material fluoresced at a wavelength detectable
by an online fluorometer. The bio-reporter reacted with an enzyme
dehydrogenase produced by respiring organisms. The reacted form of the bio-reporter was also detectable by the online
fluorometer. By monitoring the concentrations of both the reacted
and un-reacted forms of the bio-reporter, and the rates at which
they changed, an accurate, continuous picture of the bio-activity
in the system emerged.6
Results
As can be seen in Figure 5, bio-populations were high every Monday morning, the result of bringing chillers offline over the weekend and then bringing them back online during the work week.
Figure 6 shows the dynamic bio-conditions found in the system on
a Monday and how the bio-control program reacted. As the biopopulation increased, the oxidant pump ran for longer periods of
time, injecting more biocide into the system. When the inflexion
point was reached, the biocide pump ran less frequently and for
shorter periods of time. Biocide use was minimized and bio-populations were quickly brought under control. Because the bio-reporter reacted with all dehydrogenase in the system, changes reflected total system bio-activity, not just that associated with planktonic bacteria. Overall bio-control, both planktonic and sessile,
improved as a result.
Mechanical Stress
Mechanical stress on the system was low. The system was welldesigned and sized properly for the application.
Operational Stress
During the summer months, the cooling system was not needed
over the weekends. Operators shut down some of the chillers
during those times, bringing them back online when the heat load
on the building warranted it. Because no water flowed through the
chillers during this time, biocides could not act on the bio-population in the offline equipment.5
Chemical stress
Using ORP control to dose oxidizing biocides was effective, but
not optimal. Biocide usage was higher than necessary to achieve
good microbial results.
67
Conclusions
(Endnotes)
68
Don't forget to
reserve your
space.
48 exhibit spaces
available at
$1200/space.
69
Agency Name
Address
Contact Person
Website / Email
Telephone
Fax
A,B
Kenneth Hennon
www.cleanair.com
[email protected]
800.208.6162
865.938.7569
A, B
Ronald Rayner
[email protected]
61 2 9789 5900
61 2 9789 5922
A,B
Thomas E. Weast
www.cttai.com
[email protected]
913.681.0027
913.681.0039
A, B
Thomas Wheelock
www.mchale.org
[email protected]
865.588.2654
425.557.8377
* Type A license is for the use of mercury in glass thermometers typically used for smaller towers.
Type B license is for the use of remote data acquisition devices which can accommodate multiple measurement locations required by larger towers.
70
Agency Name
Address
Contact Person
Website / Email
Telephone
Fax
Kenneth Hennon
www.cleanair.com
[email protected]
800.208.6162
865.938.7569
Thomas Wheelock
www.mchale.org
[email protected]
865.588.2654
425.557.8377
71
ACT-80R
ACT-100R
ACT-125R
ACT-150R
ACT-175R
ACT-200R
ACT-225R
ACT-250R
ACT-300R
ACT-70RU
ACT-80RU
ACT-100RU
ACT-125RU
ACT-150RU
ACT-175RU
ACT-200RU
ACT-225RU
ACT-250RU
Footnotes:
1 . Certification includes tower construction materials indicated by the
suffixes -B, -E, and S which are added to basic model numbers above.
-B is for FRP casing, FRP basin and HDG mainframe and
hardware.
-E is for FRP casing, FRP basin and stainless steel main
frame and hardware
-S is for stainless steel casing, basin, mainframe and hard
ware.
2 . Certification includes use of side, end, or bottom water inlet configuration.
3 . Certification includes units with optional gear drive in place of standard belt drive.
4 . Certification includes use of optional handrail and/or ladder cage.
5 . Multiple cell models of the single cell models above are also available
but not listed.
FXT-16
FXT-16-CM
FXT-20
FXT-20-EM
FXT-38
FXT-42
FXT-47
FXT-47-HM
FXT-74-FM
FXT-74
FXT-87
FXT-95
FXT-160-HM
FXT-160
FXT-175
FXT-192
FXT-11
FXT-11-CM
FXT-11-DM
FXT-26-CM
FXT-26
FXT-30
FXT-33
FXT-58-EM
FXT-58-FM
FXT-58
FXT-68
FXT-115-GM
FXT-115
FXT-130
FXT-136
FXT-216-JM
FXT-216
FXT-240
FXT-257
FXT
Construction Options
Multiple Cells
Non-Standard Motor Size
Not CTI Certified
Suffix
(Note 1)
CTI
Certified
Capacity Adjustment
Required
None
M
X
Yes
Note 3
No
No, Note 2
Yes, Note 3
Note 4
Notes:
1. Typically no suffix is used for an accessory or modification that does not affect
capacity.
72
2. Multiple cell models of the single cell models above are also available but not
individually listed (e.g. two cells of an FXT-115 is marketed as an FXT-230).
3. Units with non-standard motor sizes are certified only if they are listed in the
Data of Record and sold at the revised capacity listed in the rating table.
4. This suffix is affixed to model numbers of units that are not CTI Certified, due
either to application or product accessories or modifications to the tower (e.g.
FXT-11X).
FXV-L431-HM FXV-L441-JM
FXV-L431
FXV-L441
FXV-431
FXV-441
FXV-431-LM
FXV-441-MM
FXV-LQ640-KM
FXV-LQ640
FXV-Q640-MM
FXV-Q640
FXV-Q640-OM
FXV-LQ660-KM
FXV-LQ660
FXV-Q660-MM
FXV-Q660
FXV-Q660-OM
FXV-L422-GM
FXV-L432-HM
FXV-L442-JM
FXV-L641-KM
FXV-L661-KM
FXV-L422
FXV-422
FXV-422-KM
FXV-L432
FXV-432
FXV-432-LM
FXV-L442
FXV-442
FXV-442-MM
FXV-L641
FXV-641-MM
FXV-641
FXV-641-OM
FXV-L661
FXV-661-MM
FXV-661
FXV-661-OM
FXV-L423-GM
FXV-L423
FXV-423
FXV-423-KM
FXV-L433-HM FXV-L443-JM
FXV-L433
FXV-L443
FXV-433
FXV-443
FXV-433-LM
FXV-443-MM
FXV-LQ641-KM
FXV-LQ641-LM
FXV-LQ641
FXV-Q641-NM
FXV-Q641
FXV-LQ661-KM
FXV-LQ661-LM
FXV-LQ661
FXV-Q661-NM
FXV-Q661
FXV-L424-GM
FXV-L424-HM
FXV-L424
FXV-424
FXV-L434-HM
FXV-L434-JM
FXV-L434
FXV-434
FXV-L444-JM
FXV-L444-KM
FXV-L444
FXV-444
FXV-L642-KM
FXV-L642
FXV-642-MM
FXV-642
FXV-642-OM
FXV-L662-KM
FXV-L662
FXV-662-MM
FXV-662
FXV-662-OM
FXV-LQ440-JM
FXV-LQ440
FXV-Q440
FXV-Q440-MM
FXV-LT642-KM
FXV-LT642
FXV-T642-MM
FXV-T642
FXV-T642-OM
FXV-LT662-KM
FXV-LT662
FXV-T662-MM
FXV-T662
FXV-T662-OM
FXV-LQ441-JM
FXV-LQ441-KM
FXV-LQ441
FXV-Q441
FXV-L643-KM
FXV-L643
FXV-643-MM
FXV-643
FXV-643-OM
FXV-L663-KM
FXV-L663
FXV-663-MM
FXV-663
FXV-663-OM
FXV-L644-KM
FXV-L644-LM
FXV-L644
FXV-644-NM
FXV-644
FXV-L664-KM
FXV-L664-LM
FXV-L664
FXV-664-NM
FXV-664
FXV-288-2TM
FXV-288-2TN
FXV-288-2TO
FXV-288-2TP
FXV-288-2TQ
FXV-288-2TR
FXV-364-31N
FXV-364-31O
FXV-364-31P
FXV-364-31Q
FXV-364-31R
FXV-364-31S
FXV-364-2TN
FXV-364-2TO
FXV-364-2TP
FXV-364-2TQ
FXV-364-2TR
FXV-364-2TS
FXV-288-41M
FXV-288-41N
FXV-288-41O
FXV-288-41P
FXV-288-41Q
FXV-288-41R
FXV-288-1QM
FXV-288-1QN
FXV-288-1QO
FXV-288-1QP
FXV-288-1QQ
FXV-288-1QR
FXV-364-41N
FXV-364-41O
FXV-364-41P
FXV-364-41Q
FXV-364-41R
FXV-364-41S
FXV-364-1QN
FXV-364-1QO
FXV-364-1QP
FXV-364-1QQ
FXV-364-1QR
FXV-364-1QS
Suffix
(Note 1)
A
S
Q
none
X
Note 6
VF1-036-21J
VF1-036-21K
VF1-036-21L
VF1-036-22J
VF1-036-22K
VF1-036-22L
VF1-036-31J
VF1-036-31K
VF1-036-31L
VF1-036-32J
VF1-036-32K
VF1-036-32L
VF1-036-41J
VF1-036-41K
VF1-036-41L
VF1-036-42J
VF1-036-42K
VF1-036-42L
VF1-036-51J
VF1-036-51K
VF1-036-51L
VF1-048-21L
VF1-048-21M
VF1-048-22L
VF1-048-22M
VF1-048-31M
VF1-048-31N
VF1-048-32M
VF1-048-32N
VF1-048-41M
VF1-048-41N
VF1-048-42M
VF1-048-42N
VF1-048-51M
VF1-048-51N
VF1-072-21M
VF1-072-21N
VF1-072-21O
VF1-072-22M
VF1-072-22N
VF1-072-22O
VF1-072-31M
VF1-072-31N
VF1-072-31O
VF1-072-32M
VF1-072-32N
VF1-072-32O
VF1-072-41M
VF1-072-41N
VF1-072-41O
VF1-072-51N
VF1-072-51O
VF1-096-12N
VF1-096-12O
VF1-096-12P
VF1-096-21O
VF1-096-21P
VF1-096-21Q
VF1-096-22O
VF1-096-22P
VF1-096-22Q
VF1-096-31O
VF1-096-31P
VF1-096-31Q
VF1-096-32O
VF1-096-32P
VF1-096-32Q
VF1-096-41O
VF1-096-41P
VF1-096-41Q
VF1-096-42O
VF1-096-42P
VF1-096-42Q
VF1-096-51P
VF1-096-51Q
VF1-192-12N
VF1-192-12O
VF1-192-12P
VF1-192-21O
VF1-192-21P
VF1-192-21Q
VF1-192-22O
VF1-192-22P
VF1-192-22Q
VF1-192-31O
VF1-192-31P
VF1-192-31Q
VF1-192-32O
VF1-192-32P
VF1-192-32Q
VF1-192-41O
VF1-192-41P
VF1-192-41Q
VF1-192-42O
VF1-192-42P
VF1-192-42Q
VF1-192-51P
VF1-192-51Q
VF1-144N-21P
VF1-144N-21Q
VF1-144N-21R
VF1-144N-22P
VF1-144N-22Q
VF1-144N-22R
VF1-144N-31P
VF1-144N-31Q
VF1-144N-31R
VF1-144N-32P
VF1-144N-32Q
VF1-144N-32R
VF1-144N-41P
VF1-144N-41Q
VF1-144N-41R
VF1-144N-51P
VF1-144N-51Q
VF1-144N-51R
VF1-288N-21P
VF1-288N-21Q
VF1-288N-21R
VF1-288N-22P
VF1-288N-22Q
VF1-288N-22R
VF1-288N-31P
VF1-288N-31Q
VF1-288N-31R
VF1-288N-32P
VF1-288N-32Q
VF1-288N-32R
VF1-288N-41P
VF1-288N-41Q
VF1-288N-41R
VF1-288N-51P
VF1-288N-51Q
VF1-288N-51R
VF1-144-12P
VF1-144-12Q
VF1-144-12R
VF1-144-21P
VF1-144-21Q
VF1-144-21R
VF1-144-22P
VF1-144-22Q
VF1-144-22R
VF1-144-31P
VF1-144-31Q
VF1-144-31R
VF1-144-32P
VF1-144-32Q
VF1-144-32R
VF1-144-41P
VF1-144-41Q
VF1-144-41R
VF1-144-42P
VF1-144-42Q
VF1-144-42R
VF1-144-51P
VF1-144-51Q
VF1-144-51R
VF1-288-51P
VF1-216-21N
VF1-216-21O
VF1-216-21P
VF1-216-22N
VF1-216-22O
VF1-216-22P
VF1-216-31N
VF1-216-31O
VF1-216-31P
VF1-216-41O
VF1-216-41P
VF1-216-41Q
VF1-216-51O
VF1-216-51P
VF1-216-51Q
VF1-288-11P
VF1-288-11Q
VF1-288-11R
VF1-288-12P
VF1-288-12Q
VF1-288-12R
VF1-288-21P
VF1-288-21Q
VF1-288-21R
VF1-288-22P
VF1-288-22Q
VF1-288-22R
VF1-288-31P
VF1-288-31Q
VF1-288-31R
VF1-288-32P
VF1-288-32Q
VF1-288-32R
VF1-288-41P
VF1-288-41Q
VF1-288-41R
VF1-288-42P
VF1-288-42Q
VF1-288-42R
VF1-288-51Q
VF1-288-51R
VF1-432-21N
VF1-432-21O
VF1-432-21P
VF1-432-22N
VF1-432-22O
VF1-432-22P
VF1-432-31N
VF1-432-31O
VF1-432-31P
VF1-432-41O
VF1-432-41P
VF1-432-41Q
VF1-432-51O
VF1-432-51P
VF1-432-51Q
CTI
Capacity Adjustment
Certified
Required
Yes
Yes
Yes
Yes
No
Note 6
Note
Note
Note
Note
Note
Note
2
2
3
4
5
6
Notes:
1.
2.
3.
4.
5.
6.
Typically no suffix is used for an accessory or modification that does not affect capacity.
Construction does not affect thermal capacity, but does increase Process Fluid Pressure
Drop as noted in BAC Selection Software.
Low Sound fans on models with Two Air Inlet Side and Two Coils incur a capacity
reduction of 2% relative to the same model with a standard fan.
Internal Access Package on the models with One Air Inlet Side and One Coil incur a
capacity reduction of ~1.8%, depending on the model and operating conditions. Refer
to BAC Selection Software to determine the effect on a specific model at a specific operating condition.
This suffix is affixed to model numbers of units that are not CTI Certified, due either to
application or product accessories or modifications to the tower.
The CTI thermal performance certification applies only to units with water as the process fluid.
73
VFL-036-12K
VFL-036-12L
VFL-036-12M
VFL-036-21J
VFL-036-21K
VFL-036-21L
VFL-036-21M
VFL-036-22J
VFL-036-22K
VFL-036-22L
VFL-036-22M
VFL-036-31K
VFL-036-31L
VFL-036-31M
VFL-036-32K
VFL-036-32L
VFL-036-32M
VFL-036-41K
VFL-036-41L
VFL-036-41M
VFL-036-42K
VFL-036-42L
VFL-036-42M
VFL-048-12K
VFL-048-12L
VFL-048-12M
VFL-048-21K
VFL-048-21L
VFL-048-21M
VFL-048-22K
VFL-048-22L
VFL-048-22M
VFL-048-31K
VFL-048-31L
VFL-048-31M
VFL-048-32K
VFL-048-32L
VFL-048-32M
VFL-048-41L
VFL-048-41M
VFL-048-42L
VFL-048-42M
VFL-072-21M
VFL-072-21N
VFL-072-21O
VFL-072-21P
VFL-072-22M
VFL-072-22N
VFL-072-22O
VFL-072-22P
VFL-072-31N
VFL-072-31O
VFL-072-31P
VFL-072-32N
VFL-072-32O
VFL-072-32P
VFL-072-41N
VFL-072-41O
VFL-072-41P
VFL-072-42N
VFL-072-42O
VFL-072-42P
VFL-096-21N
VFL-096-21O
VFL-096-21P
VFL-096-22N
VFL-096-22O
VFL-096-22P
VFL-096-31N
VFL-096-31O
VFL-096-31P
VFL-096-32N
VFL-096-32O
VFL-096-32P
VFL-096-41N
VFL-096-41O
VFL-096-41P
VFL-096-42N
VFL-096-42O
VFL-096-42P
VFL-096-51N
VFL-096-51O
VFL-096-51P
VFL-096-52N
VFL-096-52O
VFL-096-52P
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Note 2
No
Note 2
Note 3
Note 4 & 5
Notes:
1. Typically no suffix is used for an accessory or modification that does not affect
capacity.
2. Construction does not affect thermal capacity, but does increase Process Fluid Pressure Drop as noted in Selection Software.
3. ASME Code construction per se does not affect capacity or pressure drop, but often
Heavy Duty Coil construction is specified as well which does affect pressure drop.
4. This suffix is affixed to model numbers of units that are not CTI Certified, due either
to application or product accessories or modifications.
5. The CTI thermal performance certification applies only to units with water as the
process fluid.
VT0-32-H
VT0-41-J
VT0-41-KM
VT0-78-JM
VT0-78-K
VT0-88-L
VT0-132-L
VT0-145-M
VT0-155-N
VT0-155-OM
VT0-24-EM
VT0-24-FM
VT0-24-G
VT0-28-H
VT0-52-HM
VT0-52-J
VT0-57-K
VT0-102-KM
VT0-102-L
VT0-102-MM
VT0-166-LM
VT0-166-MM
VT0-166-N
VT0-176-O
VT0-65-J
VT0-75-K
VT0-75-LM
VT0-107-KM
VT0-107-L
VT0-116-M
Footnotes:
1. Towers which include the suffix D added to the models above (e.g. VT0-12-ED)
are furnished with capacity control dampers and the certified capacity is 98.5% of
the published value.
2. Towers which include the suffix X added to the models above (e.g. VT0-19-GX)
are not CTI Certified due either to application, product accessories or modification.
74
VT1-N301-MM
VT1-N301-NM
VT1-N301-OM
VT1-N301-PM
VT1-N301-Q
VT1-N301-RM
VT1-N301-SM
VT1-275-LM
VT1-275-MM
VT1-275-NM
VT1-275-OM
VT1-275-P
VT1-275-QM
VT1-275-RM
VT1-416-LM
VT1-416-MM
VT1-416-NM
VT1-416-O
VT1-416-PM
VT1-N220-KM
VT1-N220-LM
VT1-N220-MM
VT1-N220-NM
VT1-N220-O
VT1-N240-P
VT1-N240-QM
VT1-N325-MM
VT1-N325-NM
VT1-N325-OM
VT1-N325-P
VT1-N346-Q
VT1-N346-RM
VT1-N346-SM
VT1-307-LM
VT1-307-MM
VT1-307-NM
VT1-307-O
VT1-340-P
VT1-340-QM
VT1-340-RM
VT1-478-LM
VT1-478-MM
VT1-478-N
VT1-507-O
VT1-507-PM
VT1-507-QM
VT1-N255-KM
VT1-N255-LM
VT1-N255-MM
VT1-N255-NM
VT1-N255-OM
VT1-N255-P
VT1-N270-Q
VT1-N370-MM
VT1-N370-NM
VT1-N370-OM
VT1-N370-PM
VT1-N370-Q
VT1-N395-R
VT1-N395-SM
VT1-375-LM
VT1-375-MM
VT1-375-NM
VT1-375-OM
VT1-375-P
VT1-400-Q
VT1-415-R
VT1-415-SM
VT1-560-LM
VT1-560-MM
VT1-560-NM
VT1-560-O
VT1-600-P
VT1-600-QM
Footnotes:
1 . Multiple cell models of the single cell models above are also available
but not listed.
2 . Towers which include the suffix D added to the models above (e.g.
VT1-307-OD) are furnished with capacity control dampers and the
certified capacity is 98.5% of the published value.
3 . Towers which include the suffix X added to the models above (e.g.
VT1-N301-QX) are not CTI Certified due either to application,
product accessories or modification.
VTL-051-G
VTL-059-H
VTL-066-J
VTL-072-K
VTL-103-JM
VTL-103-K
VTL-116-L
VTL-126-M
VTL-227-LM
VTL-227-MM
VTL-227-NM
VTL-227-O
VTL-027-EM
VTL-027-F
VTL-030-G
VTL-034-H
VTL-079-GM
VTL-079-HM
VTL-079-JM
VTL-079-K
VTL-137-JM
VTL-137-KM
VTL-137-LM
VTL-137-M
VTL-245-MM
VTL-245-NM
VTL-245-OM
VTL-245-P
VTL-039-EM
VTL-039-FM
VTL-039-GM
VTL-039-H
VTL-082-HM
VTL-082-JM
VTL-082-K
VTL-092-L
VTL-152-LM
VTL-152-M
VTL-152-NM
VTL-152-OM
VTL-272-MM
VTL-272-NM
VTL-272-OM
VTL-272-P
VTL-045-FM
VTL-045-GM
VTL-045-H
VTL-045-JM
VTL-095-HM
VTL-095-JM
VTL-095-K
VTL-095-LM
VTL-095-MM
VTL-171-L
VTL-185-M
VTL-198-N
VTL-209-O
Footnotes:
1 . Towers which include the suffix D added to the models above (e.g.
VTL-126-MD) are furnished with capacity control dampers and the
certified capacity is 98.5% of the published value.
2 . Towers which include the suffix X added to the models above (e.g.
VTL-079-GMX) are not CTI Certified due either to application,
product accessories or modification.
15162-HM
15162
15177
15201
15219
15200-JM
15200
15227
15250
15214-JM
15214
15245
15270
15282
15296-KM
15296
15325
15350
15368
15310-KM
15310
15340
15365
15385
15425
Suffix
Note 1
none
none
Q
WQ
M
none
X
CTI
Capacity Adjustment
Certified
Required
Yes
Yes
Yes
Yes
Note 4
Yes
No
No
No
Note 2
Note 3
Yes, Note 4
No
Note 5
Note:
1 . Typically no suffix is used for an accessory or modification that does
not affect capacity.
2 . Low sound fans on Series 1500 Cooling Towers incur a capacity
reduction of 3% relative to the same unit with a standard fan.
3 . Whisper Quiet low sound fans on Series 1500 Cooling Towers use a
high solidity fan running at reduced speed and incur a capacity reduction of 3 % relative to the same unit with a standard fan.
4 . Units with non-standard motor sizes are certified only if they are
listed in the Data of Record and sold at the revised capacity listed in
the rating table.
5 . This suffix is affixed to model numbers of units that are not CTI
Certified, due either to application or product accessories or modifications.
3412A-JM
3412A-KM
3412A-LM
3412A-MM
3412A
3436A
3333A-JM
3333A-KM
3333A-LM
3333A
3358A
3379A
3455A-KM
3455A-LM
3455A-MM
3455A
3482A
3527A
S3-D240JL
S3-D240L
S3-D272L
S3-D299L
S3-D412JL
S3-D412KL
S3-D412LL
S3-D412ML
S3-D412L
S3-D436L
S3-D333JL
S3-D333KL
S3-D333LL
S3-D333L
S3-D358L
S3-D379L
S3-D455KL
S3-D455LL
S3-D455ML
S3-D455L
S3-D482L
S3-D527L
3872A-OM
3872A-PM
3872A
3923A
3970A
European Models
S3-D473KL S3-D728NL
S3-D473LL S3-D728OL
S3-D473ML S3-D728L
S3-D473L
S3-D781L
S3-D501L
S3-D828L
S3-D552LL
S3-D552ML
S3-D552NL
S3-D552L
S3-D604L
S3-D648L
S3-D672L
S3-D872OL
S3-D872PL
S3-D872L
S3-D923L
S3-D970L
3985A-PM
3985A-QM
3985A
31056A
31132A-PM
31132A-QM
31132A-RM
31132A
3583A-MM
3583A
3618A
3676A
3725A
31213A-QM
31213A-RM
31213A
31301A
S3-D985PL
S3-D985QL
S3-D985L
S3-D1056L
S3-D1132PL
S3-D1132QL
S3-D1132RL
S3-D1132L
S3-D583ML
S3-D583L
S3-D618L
S3-D676L
S3-D725L
S3-D1213QL
S3-D1213RL
S3-D1213L
S3-D1301L
Suffix
Note 1
CTI
Certified
Capacity Adjustment
Required
L
P
none
Z
E
G
Q
M
V
none
X
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Note 4
Yes
Yes
No
No
No
No
No
Yes, Note 2
No
Yes, Note 3
Yes, Note 4
Yes, Note 5
See Note 6
Note 7
Notes:
1 . Typically no suffix is used for an accessory or modification that does
not affect capacity.
2 . Two sets of drift eliminators incur a capacity reduction of 2% relative to the standard unit.
3 . Low Sound Fans on Series 3000A Cooling Towers incur a capacity
reduction of 3% relative to the same unit with a standard fan.
4 . Units with non-standard motor sizes are certified only if they are
listed in the Data of Record and sold at the revised capacity listed in
the rating table.
5 . Velocity Recovery Fan Stacks increase the capacity of a tower model
by 3 to 6%, depending upon the model and the operating conditions.
Refer to BAC Selection Software to determine the effect on a particular model at a specific operating condition.
6 . Models beginning with the prefix S3 (European models) utilize low
sound fans as standard, and a different fan guard from the North
American models. Therefore they incur a capacity reduction of 5%
(3% for low sound fans plus 2% for fan guard) compared to the North
American models.
7 . This suffix is affixed to model numbers of units that are not CTI
Certified, due either to application or product accessories or modifications.
75
Evapco, Inc.
AT Line of CTI Certified Cooling Towers
CTI Certification Validation Number 99-13-01
July 15, 2006 (Revision 6)
TM105319
TM175319
TM110319
TM115319
TM205319
TM275319
TM210319
TM215319
TM305319
TM375319
TM310319
TM315319
TM405319
TM475319
TM410319
TM415319
TM505319
TM575319
TM510319
TM515319
TM605319
TM675319
TM610319
TM615319
TM105419
TM175419
TM110419
TM115419
TM205419
TM275419
TM210419
TM215419
TM305419
TM375419
TM310419
TM315419
TM405419
TM475419
TM410419
TM415419
TM505419
TM575419
TM510419
TM515419
TM605419
TM675419
TM610419
TM615419
TM105312
TM175312
TM110312
TM115312
TM205312
TM275312
TM210312
TM215312
TM305312
TM375312
TM310312
TM315312
TM405312
TM475312
TM410312
TM415312
TM505312
TM575312
TM510312
TM515312
TM605312
TM675312
TM610312
TM615312
TM105412
TM175412
TM110412
TM115412
TM205412
TM275412
TM210412
TM215412
TM305412
TM375412
TM310412
TM315412
TM405412
TM475412
TM410412
TM415412
TM505412
TM575412
TM510412
TM515412
TM605412
TM675412
TM610412
TM615412
Evapco, Inc.
AT Line of CTI Certified Cooling Towers
CTI Certification Validation Number 99-13-01
July 15, 2006 (Revision 6)
19-28
19-38
19-48
19-58
19-68
19-78
19-88
19-98
19-59
19-69
19-79
19-89
19-99
19-111
19-211
19-311
19-411
19-511
19-611
19-711
19-811
19-911
19-412
19-512
19-612
19-712
19-812
19-912
29-024
29-124
29-224
29-324
29-424
29-524
29-624
19-114 29-724
19-214 29-824
19-314 29-924
19-414
19-514 29-228
19-614 29-328
19-714 29-428
19-814 29-528
19-914 29-628
29-728
29-318 29-828
29-418 29-928
29-518
29-618 39-336
29-718 39-436
29-818 39-536
29-918 39-636
39-736
29-121 39-836
29-221 39-936
29-321
29-421 39-242
29-521 39-342
29-621 39-442
29-721 39-542
29-821 39-642
29-921 39-742
39-842
39-942
112-012
112-112
112-212
112-312
112-412
112-512
112-612
112-712
112-812
112-912
212-024
212-124
212-224
212-324
212-424
212-524
212-624
212-724
212-824
212-924
312-036
312-136
312-236
312-336
312-436
312-536
312-636
312-736
312-836
312-936
212-128
212-228
212-328
212-428
212-528
212-628
212-728
212-828
112-018 212-928
112-118
112-218 212-036
112-318 212-136
112-418 212-236
112-518 212-336
112-618 212-436
112-718 212-536
112-818 212-636
112-918 212-736
212-836
112-520 212-936
112-620
112-720 224-018
112-820 224-118
112-920 224-218
224-318
224-418
224-518
224-618
224-718
224-818
224-918
312-042
312-142
312-242
312-342
312-442
312-542
312-642
312-742
312-842
312-942
112-314
112-414
112-514
112-614
112-714
112-814
112-914
312-054
312-154
312-254
312-354
312-454
312-554
312-654
312-754
312-854
312-954
312-260
312-360
312-460
312-560
312-660
312-760
312-860
312-960
424-024
424-124
424-224
424-324
424-424
424-524
424-624
424-724
424-824
424-924
114-0124
114-0224
114-0324
114-0424
114-0524
114-0624
114-0724
114-0824
114-0924
114-1024
114-1124
424-028 114-1224
424-128
424-228 214-0148
424-328 214-0248
424-428 214-0348
424-528 214-0448
424-628 214-0548
424-728 214-0648
424-828 214-0748
424-928 214-0848
214-0948
424-036 214-1048
424-136 214-1148
424-236
424-336 314-0172
424-436 314-0272
424-536 314-0372
424-636 314-0472
424-736 314-0572
424-836 314-0672
424-936 314-0772
314-0872
314-0972
314-1072
314-1172
314-1272
76
28-521
28-621
28-721
28-821
28-921
28-524
28-624
28-724
28-824
28-924
38-236
38-336
38-436
38-536
38-636
38-736
38-836
38-936
38-442
38-542
38-642
38-742
38-842
38-942
28-428
28-528
28-628
28-728
28-828
28-928
110-112
110-212
110-312
110-412
110-512
110-612
110-712
110-812
110-912
210-124
210-224
210-324
210-424
210-524
210-624
210-724
210-824
210-924
310-136
310-236
310-336
310-436
310-536
310-636
310-736
310-836
310-936
220-112
220-212
220-312
220-412
220-512
220-612
220-712
220-812
220-912
420-124
420-224
420-324
420-424
420-524
420-624
420-724
420-824
420-924
110-118
110-218
110-318
110-418
110-518
110-618
110-718
110-818
110-918
210-136
210-236
210-336
210-436
210-536
210-636
210-736
210-836
210-936
310-154
310-254
310-354
310-454
310-554
310-654
310-754
310-854
310-954
220-118
220-218
220-318
220-418
220-518
220-618
220-718
220-818
220-918
420-136
420-236
420-336
420-436
420-536
420-636
420-736
420-836
420-936
28-518
28-618
28-718
28-818
28-918
228-0124
228-0224
228-0324
228-0424
228-0524
228-0624
228-0724
228-0824
228-0924
428-0148
428-0248
428-0348
428-0448
428-0548
428-0648
428-0748
428-0848
428-0948
428-1048
428-1148
428-1248
217-412
217-512
217-612
217-712
217-812
217-912
217-214
217-314
217-414
217-514
217-614
217-714
217-814
217-914
224-018 224-720
224-118 224-820
224-218 224-920
224-318
224-418
224-518
224-618
224-718
224-818
224-918
Evapco, Inc.
AT Line of CTI Certified Cooling Towers
CTI Certification Validation Number 99-13-01
July 15, 200 6 (Revision 6)
AT Line UBT Models
8-56B
8-66B
8-76B
8-86B
8-96B
8-29B
8-39B
8-49B
8-59B
8-69B
8-79B
8-89B
8-99B
8-012B
8-112B
8-212B
8-312B
8-412B
8-512B
8-612B
8-712B
8-812B
8-912B
8-324B
8-424B
8-524B
8-624B
8-724B
8-824B
8-924B
12-212B
12-312B
12-412B
12-512B
12-612B
12-712B
12-812B
12-912B
12-324B
12-424B
12-524B
12-624B
12-724B
12-824B
12-924B
12-454B
12-554B
12-654B
12-754B
12-854B
12-954B
24-524B
24-624B
24-724B
24-824B
24-924B
8-318B
8-418B
8-518B
8-618B
8-718B
8-818B
8-918B
8-536B
8-636B
8-736B
8-836B
8-936B
12-218B
12-318B
12-418B
12-518B
12-618B
12-718B
12-818B
12-918B
12-136B
12-236B
12-336B
12-436B
12-536B
12-636B
12-736B
12-836B
12-936B
24-218B
24-318B
24-418B
24-518B
24-618B
24-718B
24-818B
24-918B
24-336B
24-436B
24-536B
24-636B
24-736B
24-836B
24-936B
Evapco, Inc.
ESWA Line of CTI Certified Closed Circuit Coolers
CTI Certification Validation Number 06-13-05
November 10, 2006 (Revision 2)
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
77-23H
77-23I
77-23J
77-24H
77-24I
77-24J
77-25H
77-25I
77-25J
77-26H
77-26I
77-26J
ESWA 102-23H
ESWA 102-23I
ESWA 102-24H
ESWA 102-24I
ESWA 102-25H
ESWA 102-25I
ESWA 102-26H
ESWA 102-26I
ESWA 153-23H
ESWA 153-23I
ESWA 153-23J
ESWA 153-24H
ESWA 153-24I
ESWA 153-24J
ESWA 153-25H
ESWA 153-25I
ESWA 153-25J
ESWA 153-26H
ESWA 153-26I
ESWA 153-26J
ESWA 72-23H
ESWA 72-23I
ESWA 72-23J
ESWA 72-24H
ESWA 72-24I
ESWA 72-24J
ESWA 72-25H
ESWA 72-25I
ESWA 72-25J
ESWA 72-26H
ESWA 72-26I
ESWA 72-26J
ESWA 96-23H
ESWA 96-23I
ESWA 96-24H
ESWA 96-24I
ESWA 96-25H
ESWA 96-25I
ESWA 96-26H
ESWA 96-26I
ESWA 142-23H
ESWA 142-23I
ESWA 142-23J
ESWA 142-24H
ESWA 142-24I
ESWA 142-24J
ESWA 142-25H
ESWA 142-25I
ESWA 142-25J
ESWA 142-26H
ESWA 142-26I
ESWA 142-26J
ESWA 144-23I
ESWA 144-23J
ESWA 144-23K
ESWA 144-24I
ESWA 144-24J
ESWA 144-24K
ESWA 144-25I
ESWA 144-25J
ESWA 144-25K
ESWA 144-26I
ESWA 144-26J
ESWA 144-26K
ESWA 216-23J
ESWA 216-23K
ESWA 216-23L
ESWA 216-23M
ESWA 216-24J
ESWA 216-24K
ESWA 216-24L
ESWA 216-24M
ESWA 216-25J
ESWA 216-25K
ESWA 216-25L
ESWA 216-25M
ESWA 216-26J
ESWA 216-26K
ESWA 216-26L
ESWA 216-26M
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
77-33H
77-33I
77-33J
77-33K
77-34H
77-34I
77-34J
77-34K
77-35H
77-35I
77-35J
77-35K
77-36H
77-36I
77-36J
77-36K
ESWA 102-33H
ESWA 102-33I
ESWA 102-33J
ESWA 102-33K
ESWA 102-34H
ESWA 102-34I
ESWA 102-34J
ESWA 102-34K
ESWA 102-35H
ESWA 102-35I
ESWA 102-35J
ESWA 102-35K
ESWA 102-36H
ESWA 102-36I
ESWA 102-36J
ESWA 102-36K
ESWA 153-33H
ESWA 153-33I
ESWA 153-33J
ESWA 153-34H
ESWA 153-34I
ESWA 153-34J
ESWA 153-35H
ESWA 153-35I
ESWA 153-35J
ESWA 153-36H
ESWA 153-36I
ESWA 153-36J
ESWA 72-33H
ESWA 72-33I
ESWA 72-33J
ESWA 72-33K
ESWA 72-34H
ESWA 72-34I
ESWA 72-34J
ESWA 72-34K
ESWA 72-35H
ESWA 72-35I
ESWA 72-35J
ESWA 72-35K
ESWA 72-36H
ESWA 72-36I
ESWA 72-36J
ESWA 72-36K
ESWA 96-33H
ESWA 96-33I
ESWA 96-33J
ESWA 96-33K
ESWA 96-34H
ESWA 96-34I
ESWA 96-34J
ESWA 96-34K
ESWA 96-35H
ESWA 96-35I
ESWA 96-35J
ESWA 96-35K
ESWA 96-36H
ESWA 96-36I
ESWA 96-36J
ESWA 96-36K
ESWA 142-33H
ESWA 142-33I
ESWA 142-33J
ESWA 142-33K
ESWA 142-34H
ESWA 142-34I
ESWA 142-34J
ESWA 142-34K
ESWA 142-35H
ESWA 142-35I
ESWA 142-35J
ESWA 142-35K
ESWA 142-36H
ESWA 142-36I
ESWA 142-36J
ESWA 142-36K
ESWA 144-33I
ESWA 144-33J
ESWA 144-33K
ESWA 144-34I
ESWA 144-34J
ESWA 144-34K
ESWA 144-34L
ESWA 144-35I
ESWA 144-35J
ESWA 144-35K
ESWA 144-35L
ESWA 144-36I
ESWA 144-36J
ESWA 144-36K
ESWA 144-36L
ESWA 216-33K
ESWA 216-33L
ESWA 216-33M
ESWA 216-34K
ESWA 216-34L
ESWA 216-34M
ESWA 216-34N
ESWA 216-35K
ESWA 216-35L
ESWA 216-35M
ESWA 216-35N
ESWA 216-36K
ESWA 216-36L
ESWA 216-36M
ESWA 216-36N
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
77-43I
77-43J
77-43K
77-44I
77-44J
77-44K
77-45I
77-45J
77-45K
77-46I
77-46J
77-46K
ESWA 102-43I
ESWA 102-43J
ESWA 102-43K
ESWA 102-44I
ESWA 102-44J
ESWA 102-44K
ESWA 102-45I
ESWA 102-45J
ESWA 102-45K
ESWA 102-46I
ESWA 102-46J
ESWA 102-46K
ESWA 153-43I
ESWA 153-43J
ESWA 153-43K
ESWA 153-44I
ESWA 153-44J
ESWA 153-44K
ESWA 153-45I
ESWA 153-45J
ESWA 153-45K
ESWA 153-46I
ESWA 153-46J
ESWA 153-46K
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA
ESWA 96-43I
ESWA 96-43J
ESWA 96-43K
ESWA 96-44I
ESWA 96-44J
ESWA 96-44K
ESWA 96-45I
ESWA 96-45J
ESWA 96-45K
ESWA 96-46I
ESWA 96-46J
ESWA 96-46K
ESWA 142-43I
ESWA 142-43J
ESWA 142-43K
ESWA 142-44I
ESWA 142-44J
ESWA 142-44K
ESWA 142-45I
ESWA 142-45J
ESWA 142-45K
ESWA 142-46I
ESWA 142-46J
ESWA 142-46K
ESWA 144-43J
ESWA 144-43K
ESWA 144-44J
ESWA 144-44K
ESWA 144-44L
ESWA 144-44M
ESWA 144-45J
ESWA 144-45K
ESWA 144-45L
ESWA 144-45M
ESWA 144-46J
ESWA 144-46K
ESWA 144-46L
ESWA 144-46M
ESWA 216-43K
ESWA 216-43L
ESWA 216-43M
ESWA 216-44K
ESWA 216-44L
ESWA 216-44M
ESWA 216-44N
ESWA 216-44O
ESWA 216-45K
ESWA 216-45L
ESWA 216-45M
ESWA 216-45N
ESWA 216-45O
ESWA 216-46K
ESWA 216-46L
ESWA 216-46M
ESWA 216-46N
ESWA 216-46O
ESWA 216-46P
ESWA 216-46S
72-43I
72-43J
72-43K
72-44I
72-44J
72-44K
72-45I
72-45J
72-45K
72-46I
72-46J
72-46K
Footnotes:
1. Certification includes units with optional High Flow Header Connections for better process fluid distribution at higher flows.
2. Certification includes units with optional gear drive in place of standard belt drive.
3. Certification includes use of optional external platforms/ladders for access.
4. Certification includes an optional supplier for fans on standard models and two optional low sound fan types one of which requires a 3.5% reduction in thermal capacity.
5. Certification includes an optional stainless steel coil section which requires a slight reduction in thermal capacity. See selection data for capacity of stainless steel coil units versus
standard units.
77
Evapco, Inc.
LPT Line of CTI Certified Cooling Towers
CTI Certification Validation Number 05-13-04
January 3, 2005 (Revision 0)
LPT Series Basic Models
LPT
LPT
LPT
LPT
LPT
LPT
316
326
336
346
356
366
LPT
LPT
LPT
LPT
LPT
LPT
LPT
LPT
LPT
516
526
536
546
556
566
576
586
596
LPT
LPT
LPT
LPT
LPT
LPT
519
529
539
549
559
569
LPT
LPT
LPT
LPT
LPT
LPT
LPT
5112
5212
5312
5412
5512
5612
5712
LPT
LPT
LPT
LPT
LPT
LPT
LPT
819
829
839
849
859
869
879
LPT
LPT
LPT
LPT
LPT
LPT
LPT
LPT
8112
8212
8312
8412
8512
8612
8712
8812
Footnotes:
1
2.
Evapco, Inc.
LSTB Line of CTI Certified Cooling Towers
CTI Certification Validation Number 05-13-03
January 3, 2005 (Revision 0)
LSTB Series Basic Models
LSTB
LSTB
LSTB
LSTB
LSTB
5112
5212
5312
5412
5512
LSTB
LSTB
LSTB
LSTB
LSTB
8P112
8P212
8P312
8P412
8P512
LSTB
LSTB
LSTB
LSTB
LSTB
8P124
8P224
8P324
8P424
8P524
LSTB
LSTB
LSTB
LSTB
LSTB
LSTB
10112
10212
10312
10412
10512
10612
LSTB
LSTB
LSTB
LSTB
LSTB
10124
10224
10324
10424
10524
LSTB 5118 LSTB 8P118 LSTB 8P136 LSTB 10118 LSTB 10136
LSTB 5218 LSTB 8P218 LSTB 8P236 LSTB 10218 LSTB 10236
LSTB 5318 LSTB 8P318 LSTB 8P336 LSTB 10318 LSTB 10336
LSTB 5418 LSTB 8P418 LSTB 8P436 LSTB 10418 LSTB 10436
LSTB 5518 LSTB 8P518 LSTB 8P536 LSTB 10518 LSTB 10536
LSTB 5618 LSTB 8P618
LSTB 10618 LSTB 10636
LSTB 5718
LSTB 10718
Footnotes:
1 . The following suffixes (I, D, H, F, L, U, LI, LD, LH and LF) are to be
added to the basic numeric model designations listed above to indicate
the tower configuration options that are also included in the CTI Certification.
I
= Intake sound attenuation
D
= Discharge sound attenuation
H
= Tapered Discharge Hood
F
= Full sound attenuation
L
= One motor size smaller
U
= Two motor sizes smaller
LI
= Intake sound attenuation + One motor size smaller
78
GHRFG Series
GHRGS Series
GHRSS Series
GHRFS Series
GHRFG-303115
GHRFG-303102
GHRFG-404103
GHRFG-404105
GHRFG-505103
GHRFG-505105
GHRFG-5555105
GHRFG-5555175
GHRFG-606105
GHRFG-606175
GHRFG-707175
GHRFG-707110
GHRFG-708175
GHRFG-708110
GHRFG-708115
GHRFG-709175
GHRFG-709110
GHRFG-709115
GHRFG-808175
GHRFG-808110
GHRFG-808115
GHRFG-809175
GHRFG-809110
GHRFG-809115
GHRFG-810110
GHRFG-810115
GHRFG-810120
GHRFG-811115
GHRFG-811120
GHRFG-812115
GHRFG-812120
GHRFG-812125
GHRGS-303115
GHRGS-303102
GHRGS-404103
GHRGS-404105
GHRGS-505103
GHRGS-505105
GHRGS-5555105
GHRGS-5555175
GHRGS-606105
GHRGS-606175
GHRGS-707175
GHRGS-707110
GHRGS-708175
GHRGS-708110
GHRGS-708115
GHRGS-709175
GHRGS-709110
GHRGS-709115
GHRGS-808175
GHRGS-808110
GHRGS-808115
GHRGS-809175
GHRGS-809110
GHRGS-809115
GHRGS-810110
GHRGS-810115
GHRGS-810120
GHRGS-811115
GHRGS-811120
GHRGS-812115
GHRGS-812120
GHRGS-812125
GHRSS-303115
GHRSS-303102
GHRSS-404103
GHRSS-404105
GHRSS-505103
GHRSS-505105
GHRSS-5555105
GHRSS-5555175
GHRSS-606105
GHRSS-606175
GHRSS-707175
GHRSS-707110
GHRSS-708175
GHRSS-708110
GHRSS-708115
GHRSS-709175
GHRSS-709110
GHRSS-709115
GHRSS-808175
GHRSS-808110
GHRSS-808115
GHRSS-809175
GHRSS-809110
GHRSS-809115
GHRSS-810110
GHRSS-810115
GHRSS-810120
GHRSS-811115
GHRSS-811120
GHRSS-812115
GHRSS-812120
GHRSS-812125
GHRFS-303115
GHRFS-303102
GHRFS-404103
GHRFS-404105
GHRFS-505103
GHRFS-505105
GHRFS-5555105
GHRFS-5555175
GHRFS-606105
GHRFS-606175
GHRFS-707175
GHRFS-707110
GHRFS-708175
GHRFS-708110
GHRFS-708115
GHRFS-709175
GHRFS-709110
GHRFS-709115
GHRFS-808175
GHRFS-808110
GHRFS-808115
GHRFS-809175
GHRFS-809110
GHRFS-809115
GHRFS-810110
GHRFS-810115
GHRFS-810120
GHRFS-811115
GHRFS-811120
GHRFS-812115
GHRFS-812120
GHRFS-812125
GHRFG-714275
GHRFG-714210
GHRFG-816275
GHRFG-816210
GHRFG-816215
GHRGS-714275
GHRGS-714210
GHRGS-816275
GHRGS-816210
GHRGS-816215
GHRSS-714275
GHRSS-714210
GHRSS-816275
GHRSS-816210
GHRSS-81621
GHRFS-714275
GHRFS-714210
GHRFS-816275
GHRFS-816210
GHRFS-816215
GHRFG-1414475
GHRFG-1414410
GHRFG-1616475
GHRFG-1616410
GHRFG-1616415
GHRGS-1414475
GHRGS-1414410
GHRGS-1616475
GHRGS-1616410
GHRGS-1616415
GHRSS-1414475
GHRSS-1414410
GHRSS-1616475
GHRSS-1616410
GHRSS-1616415
GHRFS-1414475
GHRFS-1414410
GHRFS-1616475
GHRFS-1616410
GHRFS-1616415
HRFG-707175
HRFG-707110
HRFG-808175
HRFG-808110
HRFG-808115
HRFG-714275
HRFG-714210
HRFG-1414475
HRFG-1414410
HRFG-404103
HRFG-404105
HRFG-708175
HRFG-708110
HRFG-708115
HRFG-809175
HRFG-809110
HRFG-809115
HRFG-816275
HRFG-816210
HRFG-816215
HRFG-1616475
HRFG-1616410
HRFG-1616415
HRFG-505103
HRFG-505105
HRFG-709175
HRFG-709110
HRFG-709115
HRFG-810110
HRFG-810115
HRFG-810120
HRFG-606105
HRFG-606175
HRFG-811115
HRFG-811120
HRFG-812115
HRFG-812120
HRFG-812125
Standard Fan
Extended Stack
TFW-80
TFW-100
TFW-125
TFW-150
TFW-175
TFW-200
TFW-225
TFW-250
TFW-80S
TFW-100S
TFW-125S
TFW-150S
TFW-175S
TFW-200S
TFW-225S
TFW-250S
TFW-70UL
TFW-80UL
TFW-100UL
TFW-125UL
TFW-150UL
TFW-175UL
TFW-200UL
TFW-225UL
TFW-300
TFW-300S
TFW-250UL
Footnotes:
1. Certification includes tower construction materials indicated by the suffixes -B, E, and -S which are added to basic model numbers above.
-B is for FRP casing, FRP basin and HDG mainframe and hardware.
-E is for FRP casing, FRP basin and stainless steel mainframe and hardware
-S is for stainless steel casing, basin, mainframe and hardware.
2. The basic model numbers above are for 50hz fan motor and the suffix /F is added for
60hz motor applications. For example, TFW-100S-B is for 50hz motor, TFW-100SB/F is for 60hz motor.
3. Certification includes use of side, end, or bottom water inlet configuration.
4. Certification includes units with optional gear drive in place of standard belt drive.
5. Certification includes use of optional handrail and/or ladder cage.
6. Multiple cell models of the single cell models above are also available but not
listed.
806-080-1-3
806-100-1-5
806-110-1-7.5
806-112-1-5
806-125-1-10
806-115-1-5
806-130-1-7.5
806-136-1-7.5
806-145-1-10
806-155-1-15
809-140-1-7.5
809-156-1-10
809-170-1-10
809-190-1-15
809-180-1-10
809-206-1-15
809-217-1-15
809-234-1-20
IMC
IMC
IMC
IMC
IMC
IMC
IMC
IMC
IMC
IMC
IMC
IMC
IMC
IMC
IMC
IMC
IMC
812-205-1-15
812-200-1-10
812-245-1-20
812-246-1-15
812-260-1-20
812-247-1-10
812-273-1-15
812-280-1-15
812-297-1-20
812-317-1-25
809-310-2-10
809-300-2-7.5
809-340-2-10
809-380-2-15
809-360-2-10
809-447-2-20
809-467-2-20
IMC
IMC
IMC
IMC
IMC
IMC
IMC
IMC
1212-265-1-15
1212-290-1-20
1212-305-1-25
1212-325-1-30
1212-345-1-20
1212-360-1-25
1212-438-1-25
1212-457-1-30
IMC
IMC
IMC
IMC
IMC
IMC
IMC
IMC
IMC
1218-840-2-20
1218-910-2-25
1218-960-2-30
1218-1085-2-25
1218-1150-2-30
1218-1255-2-40
1218-1250-2-30
1218-1342-2-40
1218-1427-2-50
IMC
IMC
IMC
IMC
IMC
IMC
IMC
1212-580-2-20
1212-610-2-25
1212-685-2-20
1212-720-2-25
1212-760-2-30
1212-870-2-25
1212-927-2-30
IMC
IMC
IMC
IMC
IMC
IMC
1218-1370-3-25
1218-1445-3-30
1218-1730-3-30
1218-1885-3-40
1218-2000-3-40
1218-2127-3-50
IMC
IMC
IMC
IMC
IMC
IMC
IMC
812-440-2-20
812-405-2-10
812-430-2-10
812-520-2-20
812-590-2-20
812-600-2-20
812-632-2-25
IMC
IMC
IMC
IMC
IMC
IMC
IMC
IMC
1218-460-1-25
1218-485-1-30
1218-545-1-25
1218-580-1-30
1218-630-1-40
1218-627-1-30
1218-677-1-40
1218-717-1-50
IMC
IMC
IMC
IMC
IMC
IMC
IMC
1218-1750-4-25
1218-1955-4-20
1218-2100-4-25
1218-2215-4-30
1218-2410-4-40
1218-2587-4-40
1218-2750-4-50
EX Seriesa
EC Seriesb
(SI - Metric Units) (IP - English Units)
Low Noise Fans
Low Noise Fans
EX-80KLb
EX-100KLb
EC-65
EC-80
EX-80KLSb
EX-100KLSb
EC-65L
EC-80L
EX-112.5KLSb
EX-125KLSb
EC-90L
EC-100L
EX-150KLSb
EX-175KLSb
EC-120L
EC-140L
EX-125KLb
EC-100
EX-150KLb
EX-175KLb
EC-120
EC-140
EX-200KLb
EC-160
EX-225KLb
EX-250KLb
EC-180
EC-200
MEX-300
MEX-350
EX-200KLSb
EC-160L
MEX-250KLS
MEX-300KLS
EC-200L
EC-240L
EC-240
EC-280
MEX-350KLS
EC-280L
MEX-400
EC-320
MEX-400KLS
EC-320L
MEX-500
EC-400
EC Seriesb
(IP - English Units)
Standard Fans
LC-150
LC-175
LC-200
LC-225
LC-250
Multiple cell models of the single cell models above are also available but
not listed.
MCRI-L SERIES
Standard Low Noise
(IP- English Units)
MCR-80L
MCR-100L
MCR-125L
MCR-150L
MCR-175L
MCR-200L
MCR-250L
MCR-300L
MCR-350L
MCR-400L
MCR-450L
MCR-500L
MCR-600L
MCR-700L
MCRI-80L
MCRI-100L
MCRI-125L
MCRI-150L
MCRI-175L
MCRI-200L
MCRI-250L
MCRI-300L
MCRI-350L
MCRI-400L
MCRI-450L
MCRI-500L
MCRI-600L
MCRI-700L
MCR-80SL
MCR-100SL
MCR-125SL
MCR-150SL
MCR-175SL
MCR-200SL
MCR-250SL
MCR-300SL
MCR-350SL
MCR-400SL
MCR-450SL
MCR-500SL
MCR-600SL
MCR-700SL
MCRI-80SL
MCRI-100SL
MCRI-125SL
MCRI-150SL
MCRI-175SL
MCRI-200SL
MCRI-250SL
MCRI-300SL
MCRI-350SL
MCRI-400SL
MCRI-450SL
MCRI-500SL
MCRI-600SL
MCRI-700SL
Footnotes:
1.
Model numbers listed above are for standard construction of FRP (Fiberglass Reinforced Plastic) casing and HDG (Hot Dipped Galvanized) steel structure. Certified
models with optional SS (Stainless Steel) casing and structure are also available but
not listed.
For FRP casing with SS structure add the suffix -S, for example MCR-80L-S.
For SS casing with SS structure add the suffix -SC, for example MCRI-700SL-SC.
2.
Certification includes units with optional gear drive in place of standard belt drive.
79
MXRI-L SERIES
Standard Low Noise
(IP- English Units)
MXR-SL SERIES
Super Low Noise
(SI- Metric Units)
MXRI-SL SERIES
Super Low Noise
(SI- English Units)
MXR-80L
MXR-100L
MXR-125L
MXR-150L
MXR-175L
MXR-200L
MXR-225L
MXR-250L
MXR-300L
MXR-350L
MXR-400L
MXR-500L
MXR-600L
MXR-700L
MXRI-80L
MXRI-100L
MXRI-125L
MXRI-150L
MXRI-175L
MXRI-200L
MXRI-225L
MXRI-250L
MXRI-300L
MXRI-350L
MXRI-400L
MXRI-500L
MXRI-600L
MXRI-700L
MXR-80SL
MXR-100SL
MXR-125SL
MXR-150SL
MXR-175SL
MXR-200SL
MXR-225SL
MXR-250SL
MXR-300SL
MXR-350SL
MXR-400SL
MXR-500SL
MXR-600SL
MXR-700SL
MXRI-80SL
MXRI-100SL
MXRI-125SL
MXRI-150SL
MXRI-175SL
MXRI-200SL
MXRI-225SL
MXRI-250SL
MXRI-300SL
MXRI-350SL
MXRI-400SL
MXRI-500SL
MXRI-600SL
MXRI-700SL
Footnotes:
1. Model numbers listed above are for standard construction of FRP (Fiberglass Reinforced Plastic) casing and HDG (Hot Dipped Galvanized) steel structure. Certified models with
optional SS (Stainless Steel) casing and structure are also available but not listed.
For FRP casing with SS structure add the suffix -S, for example MXR-80L-S.
For SS casing with SS structure add the suffix -SC, for example MXRI-700SL-SC.
2. Certification includes units with optional gear drive in place of standard belt drive.
3. Multiple cell models of the single cell models above are also available but not listed.
Polacel, b. v.
CR Series Line of CTI Certified Cooling Towers
CTI Certification Validation Number 04-25-01
July 16, 2004 (Revision 0)
CMDR Models
80
CMDR12 135-DL-60
CMDR12 135-DM-60
CMDR12 135-DH-60
CMDR12 135-DL-90
CMDR12 135-DM-90
CMDR12 135-DH-90
CMDR12 135-DL-120
CMDR12 135-DM-120
CMDR12 135-DH-120
CMDR12 300-DL-60
CMDR12 300-DM-60
CMDR12 300-DH-60
CMDR12 300-DL-90
CMDR12 300-DM-90
CMDR12 300-DH-90
CMDR12 300-DL-120
CMDR12 300-DM-120
CMDR12 300-DH-120
CMDR19 135-DL-90
CMDR19 135-DM-90
CMDR19 135-DH-90
CMDR19 135-DL-120
CMDR19 135-DM-120
CMDR19 135-DH-120
CMDR19 135-DL-150
CMDR19 135-DM-150
CMDR19 135-DH-150
CMDR19 300-DL-90
CMDR19 300-DM-90
CMDR19 300-DH-90
CMDR19 300-DL-120
CMDR19 300-DM-120
CMDR19 300-DH-120
CMDR19 300-DL-150
CMDR19 300-DM-150
CMDR19 300-DH-150
CMDR12 160-DL-60
CMDR12 160-DM-60
CMDR12 160-DH-60
CMDR12 160-DL-90
CMDR12 160-DM-90
CMDR12 160-DH-90
CMDR12 160-DL-120
CMDR12 160-DM-120
CMDR12 160-DH-120
CMDR12 380-DL-60
CMDR12 380-DM-60
CMDR12 380-DH-60
CMDR12 380-DL-90
CMDR12 380-DM-90
CMDR12 380-DH-90
CMDR12 380-DL-120
CMDR12 380-DM-120
CMDR12 380-DH-120
CMDR19 160-DL-90
CMDR19 160-DM-90
CMDR19 160-DH-90
CMDR19 160-DL-120
CMDR19 160-DM-120
CMDR19 160-DH-120
CMDR19 160-DL-150
CMDR19 160-DM-150
CMDR19 160-DH-150
CMDR19 380-DL-90
CMDR19 380-DM-90
CMDR19 380-DH-90
CMDR19 380-DL-120
CMDR19 380-DM-120
CMDR19 380-DH-120
CMDR19 380-DL-150
CMDR19 380-DM-150
CMDR19 380-DH-150
CMDR12 180-DL-60
CMDR12 180-DM-60
CMDR12 180-DH-60
CMDR12 180-DL-90
CMDR12 180-DM-90
CMDR12 180-DH-90
CMDR12 180-DL-120
CMDR12 180-DM-120
CMDR12 180-DH-120
CMDR12 460-DL-60
CMDR12 460-DM-60
CMDR12 460-DH-60
CMDR12 460-DL-90
CMDR12 460-DM-90
CMDR12 460-DH-90
CMDR12 460-DL-120
CMDR12 460-DM-120
CMDR12 460-DH-120
CMDR19 180-DL-90
CMDR19 180-DM-90
CMDR19 180-DH-90
CMDR19 180-DL-120
CMDR19 180-DM-120
CMDR19 180-DH-120
CMDR19 180-DL-150
CMDR19 180-DM-150
CMDR19 180-DH-150
CMDR19 460-DL-90
CMDR19 460-DM-90
CMDR19 460-DH-90
CMDR19 460-DL-120
CMDR19 460-DM-120
CMDR19 460-DH-120
CMDR19 460-DL-150
CMDR19 460-DM-150
CMDR19 460-DH-150
CMDR12 210-DL-60
CMDR12 210-DM-60
CMDR12 210-DH-60
CMDR12 210-DL-90
CMDR12 210-DM-90
CMDR12 210-DH-90
CMDR12 210-DL-120
CMDR12 210-DM-120
CMDR12 210-DH-120
CMDR12 540-DL-60
CMDR12 540-DM-60
CMDR12 540-DH-60
CMDR12 540-DL-90
CMDR12 540-DM-90
CMDR12 540-DH-90
CMDR12 540-DL-120
CMDR12 540-DM-120
CMDR12 540-DH-120
CMDR19 210-DL-90
CMDR19 210-DM-90
CMDR19 210-DH-90
CMDR19 210-DL-120
CMDR19 210-DM-120
CMDR19 210-DH-120
CMDR19 210-DL-150
CMDR19 210-DM-150
CMDR19 210-DH-150
CMDR19 540-DL-90
CMDR19 540-DM-90
CMDR19 540-DH-90
CMDR19 540-DL-120
CMDR19 540-DM-120
CMDR19 540-DH-120
CMDR19 540-DL-150
CMDR19 540-DM-150
CMDR19 540-DH-150
CMDR12 240-DL-60
CMDR12 240-DM-60
CMDR12 240-DH-60
CMDR12 240-DL-90
CMDR12 240-DM-90
CMDR12 240-DH-90
CMDR12 240-DL-120
CMDR12 240-DM-120
CMDR12 240-DH-120
CMDR12 630-DL-60
CMDR12 630-DM-60
CMDR12 630-DH-60
CMDR12 630-DL-90
CMDR12 630-DM-90
CMDR12 630-DH-90
CMDR12 630-DL-120
CMDR12 630-DM-120
CMDR12 630-DH-120
CMDR19 240-DL-90
CMDR19 240-DM-90
CMDR19 240-DH-90
CMDR19 240-DL-120
CMDR19 240-DM-120
CMDR19 240-DH-120
CMDR19 240-DL-150
CMDR19 240-DM-150
CMDR19 240-DH-150
CMDR19 630-DL-90
CMDR19 630-DM-90
CMDR19 630-DH-90
CMDR19 630-DL-120
CMDR19 630-DM-120
CMDR19 630-DH-120
CMDR19 630-DL-150
CMDR19 630-DM-150
CMDR19 630-DH-150
Polacel, b. v.
CR Series Line of CTI Certified Cooling Towers
CTI Certification Validation Number 04-25-01
July 16, 2004 (Revision 0)
CMC Models
CMC1-DL-60
CMC1-DL-90
CMC1-DM-60
CMC1-DM-90
CMC1-DH-60
CMC1-DH-90
CMC9-DL-60
CMC9-DL-90
CMC9-DM-60
CMC9-DM-90
CMC9-DH-60
CMC9-DH-90
CMC2.9-DL-60
CMC2.9-DL-90
CMC2.9-DM-60
CMC2.9-DM-90
CMC2.9-DH-60
CMC2.9-DH-90
CMC3.9-DL-60
CMC3.9-DL-90
CMC3.9-DM-60
CMC3.9-DM-90
CMC3.9-DH-60
CMC3.9-DH-90
CMC2-DL-60
CMC2-DL-90
CMC2-DM-60
CMC2-DM-90
CMC2-DH-60
CMC2-DH-90
CMC12-DL-60
CMC12-DL-90
CMC12-DM-60
CMC12-DM-90
CMC12-DH-60
CMC12-DH-90
CMC2.12-DL-60
CMC2.12-DL-90
CMC2.12-DM-60
CMC2.12-DM-90
CMC2.12-DH-60
CMC2.12-DH-90
CMC3.12-DL-60
CMC3.12-DL-90
CMC3.12-DM-60
CMC3.12-DM-90
CMC3.12-DH-60
CMC3.12-DH-90
CMC4-DL-60
CMC4-DL-90
CMC4-DM-60
CMC4-DM-90
CMC4-DH-60
CMC4-DH-90
CMC16-DL-60
CMC16-DL-90
CMC16-DM-60
CMC16-DM-90
CMC16-DH-60
CMC16-DH-90
CMC2.16-DL-60
CMC2.16-DL-90
CMC2.16-DM-60
CMC2.16-DM-90
CMC2.16-DH-60
CMC2.16-DH-90
CMC3.16-DL-60
CMC3.16-DL-90
CMC3.16-DM-60
CMC3.16-DM-90
CMC3.16-DH-60
CMC3.16-DH-90
CMC6-DL-60
CMC6-DL-90
CMC6-DM-60
CMC6-DM-90
CMC6-DH-60
CMC6-DH-90
Footnotes for CMDR and CMC models.
1.
2.
3.
The basic model numbers above are for 50 hz fan motors and the suffix U is added for 60 hz fan motor applications. For example, CMDR19 630-DH150 is for 50 hz and CMDR19 630-DH-150U is for 60 hz.
The suffix -PS1 through -PS10 is added to the basic model numbers to indicate the nozzle size required for the application flow rate.
The cold water basin configuration is indicated by either suffix /2 for no cold water basin, the suffix /3 for a GRP basin with HDGS sub-frame, or the suffix
/4 for a GRP basin only.
Polacel b. v.
XR Series Line of CTI Certified Cooling Towers
CTI Certification Validation Number 04-25-02
July 16, 2004 (Revision 0)
XE Models
XE 2.120-VL
XE 2.120-L
XE 2.120-M
XE 2.120-H
XL Models
XL 2.320-VVL-235_60
XL 2.320-VL-235_60
XL 2.320-L-235_60
XL 2.320-M-235_60
XT 2.240-VL-135
XT 2.240-L-135
XT 2.240-M-135
XT Models
XT 2.480-VL-135
XT 2.480-L-135
XT 2.480-M-135
XT 2.720-VL-135
XT 2.720-L-135
XT 2.720-M-135
XL 2.320-VVL-235_90
XL 2.320-VL-235_90
XL 2.320-L-235_90
XL 2.320-M-235_90
XT 2.240-VL-185
XT 2.240-L-185
XT 2.240-M-185
XT 2.480-VL-185
XT 2.480-L-185
XT 2.480-M-185
XT 2.720-VL-185
XT 2.720-L-185
XT 2.720-M-185
XL 4.440-VVL-235_90
XL 4.440-VL-235_90
XL 4.440-L-235_90
XL 4.440-M-235_90
XT 2.240-VL-235
XT 2.240-L-235
XT 2.240-M-235
XT 2.480-VL-235
XT 2.480-L-235
XT 2.480-M-235
XT 2.720-VL-235
XT 2.720-L-235
XT 2.720-M-235
XL 4.520-VVL-235_90
XL 4.520-VL-235_90
XL 4.520-L-235_90
XL 4.520-M-235_90
Footnotes for XR Series models.
1 .The basic model numbers above are for 50 hz fan motors and the suffix U is added for 60 hz fan motor applications. For example, XE 2.120-VL is for 50
hz and XE 2.120-VLU is for 60 hz.
2 .The cold water basin configuration is indicated by either suffix /2 for no cold water basin, the suffix /3 for a GRP basin with HDGS sub-frame, or the suffix
/4 for a GRP basin only.
81
FWS-127-5.5
FWS-127-7.5
FWS-127-11
FWS-169-7.5
FWS-169-11
FWS-169-15
Footnotes:
1 . Suffixes -GI, -SS, -AS, -AG are added to the basic model numbers listed
above to indicate the tower construction materials or options:
-GI for FRP casing, FRP basin and HDG structural members and hardware.
-SS for FRP casing, FRP basin and stainless steel structural members and
hardware.
-AS for stainless steel casing, basin, structural members and hardware.
-AG for HDG casing, basin, structural members and hardware.
2 . Suffixes /E and /L are added to the basic model numbers to indicate
optional parts:
/E is for additional drift eliminator installed to the basic models (reduces
capacity ~2%).
/L is for additional louver installed in front of air inlet face.
3 . Certification includes units with optional gear drive in place of standard
belt drive.
4 . Certification includes units with motor mounted outside air stream in
place of inside air stream.
5 . Certification includes use of optional handrail and/or optional caged
ladders.
6 . Multiple cell models of the single cell models above are also available
but not listed.
FRS-100-4
FRS-150-5.5
FRS-100-5.5 FRS-150-7.5
FRS-100-7.5 FRS-150-11
FRS-250-11
FRS-350-15
FRS-250-15
FRS-350-18.5
FRS-250-18.5 FRS-350-22
Footnotes:
1 . Suffixes -GI, -SS, -AS, -AG are added to the basic model numbers listed
above to indicate the tower construction materials or options:
-GI for FRP casing, FRP basin and HDG structural members and hardware.
-SS for FRP casing, FRP basin and stainless steel structural members and
hardware.
-AS for stainless steel casing, basin, structural members and hardware.
-AG for HDG casing, basin, structural members and hardware.
2 . Suffix /E is added to the basic model numbers to indicate optional parts:
/E is for additional drift eliminator installed to the basic models (reduces
capacity ~2%).
3 . Certification includes units with optional gear drive in place of standard
belt drive.
4 . Certification includes use of optional handrail and/or optional caged
ladders.
FWS-127-5.5
FWS-127-7.5
FWS-127-11
FWS-169-7.5
FWS-169-11
FWS-169-15
Footnotes:
1 . Suffixes -GI, -SS, -AS, -AG are added to the basic model numbers listed
above to indicate the tower construction materials or options:
-GI for FRP casing, FRP basin and HDG structural members and hardware.
-SS for FRP casing, FRP basin and stainless steel structural members and
hardware.
-AS for stainless steel casing, basin, structural members and hardware.
-AG for HDG casing, basin, structural members and hardware.
2 . Suffixes /E and /L are added to the basic model numbers to indicate
optional parts:
/E is for additional drift eliminator installed to the basic models (reduces
capacity ~2%).
/L is for additional louver installed in front of air inlet face.
3 . Certification includes units with optional gear drive in place of standard
belt drive.
4 . Certification includes use of optional handrail and/or optional caged
ladders.
5 . Multiple cell models of the single cell models above are also available
but not listed.
FXS-300
FXS-350
FXS-400
FXS-450
FXS-500
FXS-550
Footnotes:
1 . Suffixes -GI, -SS, -AS, -AG are added to the basic model numbers listed
above to indicate the tower construction materials or options:
-GI for FRP casing, FRP basin and HDG structural members and hardware.
-SS for FRP casing, FRP basin and stainless steel structural members and
hardware.
-AS for stainless steel casing, basin, structural members and hardware.
-AG for HDG casing, basin, structural members and hardware.
2 . Certification includes units with optional gear drive in place of standard
belt drive.
3 . Certification includes use of optional handrail and/or optional caged
ladders.
82
AV63001
AV63011
AV63021
AV63031
AV63041
AV65001
AV65011
AV65021
AV65031
AV65041
AV65051
AV62001
AV62011
AV62021
AV62031
AV62041
AV62051
AV64001
AV64011
AV64021
AV64031
AV64041
AV64051
AV66001
AV66011
AV66021
AV66031
AV66041
AV67001
AV67011
AV67021
AV67031
AV67041
Multiple cell models of the single cell models above are also available but not listed.
MCW901731K1
MHF703C061
MHF703C062
MHF703C081
MHF703C082
MHF703C084
MHF703C101
MHF703C102
MHF703C121
MHF703C122
MHF703C124
MHF704D061
MHF704D062
MHF704D081
MHF704D082
MHF704D084
MHF704D101
MHF704D102
MHF704D121
MHF704D122
MHF704D124
MHF705F061
MHF705F062
MHF705F081
MHF705F082
MHF705F084
MHF705F101
MHF705F102
MHF705F121
MHF705F122
MHF705F124
MHF706E061
MHF706E062
MHF706E081
MHF706E082
MHF706E084
MHF706E101
MHF706E102
MHF706E121
MHF706E122
MHF706E124
MHF707H061
MHF707H062
MHF707H081
MHF707H082
MHF707H084
MHF707H101
MHF707H102
MHF707H121
MHF707H122
MHF707H124
MHF702C061
MHF702C062
MHF702C081
MHF702C082
MHF702C101
MHF702C102
MHF702C121
MHF702C122
MHF703D061
MHF703D062
MHF703D081
MHF703D082
MHF703D084
MHF703D101
MHF703D102
MHF703D121
MHF703D122
MHF703D124
MHF704E061
MHF704E062
MHF704E081
MHF704E082
MHF704E084
MHF704E101
MHF704E102
MHF704E121
MHF704E122
MHF704E124
MHF705H061
MHF705H062
MHF705H081
MHF705H082
MHF705H084
MHF705H101
MHF705H102
MHF705H121
MHF705H122
MHF705H124
MHF706H061
MHF706H062
MHF706H081
MHF706H082
MHF706H084
MHF706H101
MHF706H102
MHF706H121
MHF706H122
MHF706H124
MHF707J061
MHF707J062
MHF707J081
MHF707J082
MHF707J084
MHF707J101
MHF707J102
MHF707J121
MHF707J122
MHF707J124
MHF702D061
MHF702D062
MHF702D081
MHF702D082
MHF702D101
MHF702D102
MHF702D121
MHF702D122
MHF703E061
MHF703E062
MHF703E081
MHF703E082
MHF703E084
MHF703E101
MHF703E102
MHF703E121
MHF703E122
MHF703E124
MHF704G061
MHF704G062
MHF704G081
MHF704G082
MHF704G084
MHF704G101
MHF704G102
MHF704G121
MHF704G122
MHF704G124
MHF705J061
MHF705J062
MHF705J081
MHF705J082
MHF705J084
MHF705J101
MHF705J102
MHF705J121
MHF705J122
MHF705J124
MHF706J061
MHF706J062
MHF706J081
MHF706J082
MHF706J084
MHF706J101
MHF706J102
MHF706J121
MHF706J122
MHF706J124
MHF707L061
MHF707L062
MHF707L081
MHF707L082
MHF707L084
MHF707L101
MHF707L102
MHF707L121
MHF707L122
MHF707L124
MHF704H061
MHF704H062
MHF704H081
MHF704H082
MHF704H084
MHF704H101
MHF704H102
MHF704H121
MHF704H122
MHF704H124
MHF705K061
MHF705K062
MHF705K081
MHF705K082
MHF705K084
MHF705K101
MHF705K102
MHF705K121
MHF705K122
MHF705K124
MHF706L061
MHF706L062
MHF706L081
MHF706L082
MHF706L084
MHF706L101
MHF706L102
MHF706L121
MHF706L122
MHF706L124
MHF707M061
MHF707M062
MHF707M081
MHF707M082
MHF707M084
MHF707M101
MHF707M102
MHF707M121
MHF707M122
MHF707M124
MHF706M061
MHF706M062
MHF706M081
MHF706M082
MHF706M084
MHF706M101
MHF706M102
MHF706M121
MHF706M122
MHF706M124
MHF707N061
MHF707N062
MHF707N081
MHF707N082
MHF707N084
MHF707N101
MHF707N102
MHF707N121
MHF707N122
MHF707N124
MCW901732L1
MCW901732M1
MCW901738N1
MCW901736L1
MCW901736M1
MCW901737N1
MCW901748P1
MCW901748Q1
MCW901746N1
MCW901756Q1
MCW901747N1
MCW901747P1
MCW901757Q1
MCW901757R1
MCW901758R1
Multiple cell models of the single cell models above are also available but not listed.
MHF706N061
MHF706N062
MHF706N081
MHF706N082
MHF706N084
MHF706N101
MHF706N102
MHF706N121
MHF706N122
MHF706N124
MCP301216L
MCP301216M
MCP301217L
MCP301217M
NC
Steel
Models
Box
Size
8301
8302
8303
8304
8305
8306
8307
8309
8310
8311
8312
8321
8322
8323
8324
NC
8325
Fiberglass 8326
Models
8327
8328
8329
8330
8331
8332
Standard Models
Low Noise Designator
Not Applicable
See Low Noise Configuration Options and Low Noise Designator Definitions in the Table Below
Low Noise Configuration Option
Low Noise Designator CTI Certified (Note 1)
Standard Models
No Designator
Yes
Low Noise Fan No Attenuation
L
Yes
Low Noise Fan w/ 2 ft. Inlet Attenuation
K
Yes
Low Noise Fan w/ 4 ft. Inlet Attenuation
M
Yes
Low Noise Fan w/ 2 ft. Outlet Attenuation
N
Yes
Low Noise Fan w/ 4 ft. Outlet Attenuation
P
Yes
Low Noise Fan w/ 2 ft. Inlet & 2 ft. Outlet attenuation
Q
Yes
Low Noise Fan w/ 4 ft. Inlet & 2 ft. Outlet attenuation
R
Yes
Low Noise Fan w/ 2 ft. Inlet & 4 ft. Outlet attenuation
S
Yes
Low Noise Fan with 4 ft. Inlet & 4 ft. Outlet attenuation
T
Yes
Ultra Low Noise Fan No Attenuation
C
Yes
Ultra Low Noise Fan w/ 2 ft. Inlet Attenuation
U
Yes
Ultra Low Noise Fan w/ 4 ft. Inlet Attenuation
V
Yes
Footnotes:
1. Capacity adjustments are required for all non-standard model configurations. See selection
software at www.spxcooling.com or www.marleyct.com for specific capacity of each configuration.
2. Multiple cell models of the single cell models above are also available but not listed.
3. Sample Model Number NC8305DM2 where
NC8305 = Box Size
D = Motor Power/Stack Designator
M = Low Noise Option Designator
2 = Number of Cells
83
22121
22122
22123
23121
23122
23123
23124
22221
22222
22223
22224
22225
24121
24122
24123
24124
24125
24126
24127
23221
23222
23223
23224
23225
24221
24222
24223
24224
24225
TTXE-021975
TTXE-031975
TTXE-041975
TTXE-061975
TTXE-081975
TTXE-101975
Footnotes:
1 . Models listed above are for single cells with a base inlet height of 6ft.
2 . Multiple cell models of the single cell models above are also available
but not listed.
3 . Models with inlet heights more or less than 6-ft are also available but
not listed.
4 . Multiple cell models of the single cell models and/or models with air
inlet heights more or less than 6-ft require capacity correction per
the TTXE correction table submitted with the CTI Certification
application.
TCI-1108-5-1
TCI-1108-7.5-1
TCI-1108-10-1
TCI-1108-15-1
TCI-1108-20-1
TCI-1110-10-1
TCI-1110-15-1
TCI-1110-20-1
TCI-1110-25-1
TCI-1112-15-1
TCI-1112-20-1
TCI-1112-25-1
TCI-1112-30-1
TCI-1114-20-1
TCI-1114-25-1
TCI-1114-30-1
TCI-1114-40-1
TCI-1116-25-1
TCI-1116-30-1
TCI-1116-40-1
TCI-1116-50-1
TCI-1118-30-1
TCI-1118-40-1
TCI-1118-50-1
TCI-1118-60-1
2 Cell Models
TCI-0812-5-2
TCI-0812-7.5-2
TCI-0812-10-2
TCI-0812-15-2
TCI-0816-5-2
TCI-0816-7.5-2
TCI-0816-10-2
TCI-0816-15-2
TCI-0820-10-2
TCI-0820-15-2
TCI-0820-20-2
TCI-0820-25-2
TCI-0824-10-2
TCI-0824-15-2
TCI-0824-20-2
TCI-0824-25-2
TCI-0828-15-2
TCI-0828-20-2
TCI-0828-25-2
TCI-0828-30-2
TCI-1116-5-2
TCI-1116-7.5-2
TCI-1116-10-2
TCI-1116-15-2
TCI-1116-20-2
TCI-1120-10-2
TCI-1120-15-2
TCI-1120-20-2
TCI-1120-25-2
TCI-1124-15-2
TCI-1124-20-2
TCI-1124-25-2
TCI-1124-30-2
TCI-1128-20-2
TCI-1128-25-2
TCI-1128-30-2
TCI-1128-40-2
3 Cell Models
TCI-1130-10-3
TCI-1130-15-3
TCI-1130-20-3
TCI-1130-25-3
TCI-1136-15-3
TCI-1136-20-3
TCI-1136-25-3
TCI-1136-30-3
TCI-1142-20-3
TCI-1142-25-3
TCI-1142-30-3
TCI-1142-40-3
TCI-1148-25-3
TCI-1148-30-3
TCI-1148-40-3
TCI-1148-50-3
TCI-1132-25-2
TCI-1132-30-2
TCI-1132-40-2
TCI-1132-50-2
TCI-1136-30-2
TCI-1136-40-2
TCI-1136-50-2
TCI-1136-60-2
Footnotes:
1. Series TCI towers are supplied with stainless steel basins and are available with either stainless steel or galvanized panels and structure.
2. Series TCI towers are offered with either gear or belt drives.
3. Fixed or variable orifice nozzles are available with all Series TCI towers.
4. Premium efficient motors are supplied on all Series TCI towers.
84
Box
Size
Standard Models
Low Noise Designator
Not Applicable
Standard Fan
Extended Stack
JNT-80
JNT-100
JNT-80S
JNT-100S
JNT-70UL
JNT-80UL
JNT-125
JNT-150
JNT-125S
JNT-150S
JNT-100UL
JNT-125UL
JNT-175
JNT-200
JNT-175S
JNT-200S
JNT-150UL
JNT-175UL
JNT-225
JNT-250
JNT-225S
JNT-250S
JNT-200UL
JNT-225UL
JNT-300
JNT-300S
JNT-250UL
Footnotes:
1. Certification includes tower construction materials indicated by the suffixes -B, -E,
and -S which are added to basic model numbers above.
-B is for FRP casing, FRP basin and HDG mainframe and hardware.
-E is for FRP casing, FRP basin and stainless steel mainframe and hardware
-S is for stainless steel casing, basin, mainframe and hardware.
2. The basic model numbers above are for 50hz fan motor and the suffix /F is added for
60hz motor applications. For example, JNT-100S-B is for 50hz motor, JNT-100S-B/
F is for 60hz motor.
3. Certification includes use of side, end, or bottom water inlet configuration.
4. Certification includes units with optional gear drive in place of standard belt drive.
5. Certification includes use of optional handrail and/or ladder cage.
6. Multiple cell models of the single cell models above are also available but not
listed.
85
86
87
Index of Advertisers
Advance Cooling Towers ...................... 25
Aggreko Cooling Tower Services ......... 44, 45
AHR Expo ............................................... 71
AirFlo Cooling Technologies .................. 39
Amarillo Gear Company ......................... IBC
American Cooling Tower, Inc. ............... 13, 67
Amcot Cooling Tower Corporation ........ 35
AMSA, Inc. ............................................. 15, 55
Bailsco Blades and Casting, Inc............ 36
Baltimore Aircoil Company ..................... OBC
BASF ...................................................... 51
Bedford Reinforced Plastics ................. 27
BIC Magazine .......................................... 6
Brentwood Indistries, Inc. ..................... 57
ChemTreat, Inc. ...................................... 11
ClearAir .................................................. 47
CTI Certified Towers .............................. 72 - 85
CTI Licensed Agencies .......................... 70
CTI Table Top Exhibits ............................ 69
CTI ToolKit ............................................... 86
Cooling Tower Resources, Inc. ............. 49
CTL Group .............................................. 61
Dynamic Fabricators .............................. 7
Electric Power ........................................ 27
Fibergrate Composite Structures .......... 63
Gaiennie Lumber Company ................... 2
Howden Cooling Fans ........................... 5
Hudson Products Corporation ............... 23
Industrial Cooling Tower ........................ 12, IFC
KIMCO ..................................................... 65
McHale & Associates, Inc. .................... 59
Midwest Towers, Inc. ............................ 43
Multi-Wing ............................................... 37
Myron L Company .................................. 4
Neri .......................................................... 41
Paharpur Cooling Towers Ltd. .............. 33
Paltech Cooling Towers ......................... 21
Rexnord .................................................. 3
C.E. Shepherd Company ....................... 19
SPIG ........................................................ 17
Spraying Services, Inc. .......................... 31
SPX Cooling Technologies ..................... 53
Strongwell .............................................. 9
Tower Performance ............................... 88
WQA-Aquatech ..................................... 68
88