Altivar 11
Variable speed drives
for asynchronous motors,
$79//////(8
Users manual
ATV11.book Page 13 Mercredi, 22. mai 2002 10:33 10
ENGLISH
The ItH parameter (Motor thermal protection).
The preset speeds SP2-SP3-SP4.
The speed reference if it is other than 0 - 5 V (0 -10V or 0 -20mA or 4 -20mA).
Factory configuration
The Altivar 11 is factory-configured for the most common operating conditions:
Logic inputs:
- LI1, LI2 (2 directions of operation): 2-wire control on transition, LI1 = forward, LI2 = reverse.
- LI3, LI4: 4 preset speeds (speed 1 = speed reference or LSP, speed 2 = 10 Hz,
speed 3 = 25 Hz, speed 4 = 50 Hz).
Analog input AI1: speed reference (0 + 5 V).
Relay R1: the contact opens in the event of a fault (or drive off)
DO output: analog output, image of the motor frequency.
If the factory configuration is not suitable, the FUn menu can be used to modify the functions and the I/O
assignments.
Dimensions
ATV 11H a b c G H
2 4 mm mm mm mm mm mm
U05// E, U ranges 72 142 6125 601 1311 2 x 5
=
U09// U range
U09// E range 72 142 6138 601 1201 2 x 5
U12// E range
H
U18M/ E range
U18M/ U range 72 147 138 601 1311 2 x 5
= G = = G =
=
ATV 11P a b c G H
mm mm mm mm mm mm
all ratings 72 142 101 601 1311 2 x 5
13
ATV11.book Page 14 Mercredi, 22. mai 2002 10:33 10
When IP20 protection is adequate, it is recommended that the protective cover on the top
50 mm
of the drive is removed, as shown below.
ATV 11P////// drives can be mounted on (or in) a steel or aluminium machine frame, observing the following
conditions:
Maximum ambient temperature: 40 C
Vertical mounting at 10
The drive must be fixed at the centre of a support (frame) which is a minimum of 10 mm thick and with a square
cooling area (S) of 0.12 m2 minimum for steel and 0.09 m2 for aluminium, exposed to the open air.
Support area for the drive (min 142 x 72) machined on the frame with a surface smoothness of 100 m max and
a roughness of 3.2 m max.
Mill the tapped holes lightly in order to remove any burrs.
Coat the whole support surface of the drive with thermal contact grease (or equivalent).
10 m
m S
Minimum
machined
area
60 mm
72 mm
9HULI\WKHWKHUPDOVWDWHRIWKHGULYHE\FKHFNLQJSDUDPHWHUW+G683PHQXWRFRQILUPWKDWWKH
GULYHKDVEHHQPRXQWHGFRUUHFWO\
14
ATV11.book Page 15 Mercredi, 22. mai 2002 10:33 10
Power Terminals
ENGLISH
To motor To motor
To braking To braking
module module
+ 15V
+ 5V
AI 1
LI 1
LI 2
LI 3
LI 4
DO
RC
RA
0V
15
ATV11.book Page 16 Mercredi, 22. mai 2002 10:33 10
ATV11////F1/
L1
ATV11////M2/
L1
L2
(2)
ATV11////M3/
L1
L2
L3
(1)
+15 V
RA
RC
LI1
LI2
LI3
LI4
PA / +
PC / -
+5V
AI1
DO
0V
W
U
W1
U1
V1
(3)
+
a
M Reference
potentiometer
PA
PB
(1) Fault relay contacts, for remote indication of the drive status.
(2) Internal + 15 V. If an external source is used (+ 24 V max.), connect the 0 V of the source to the 0V terminal,
and do not use the + 15 V terminal on the drive.
(3) Galvanometer or low level relay.
Note: Fit interference suppressors to all inductive circuits near the drive or coupled to the same circuit (relays,
contactors, solenoid valves, etc)
16
ATV11.book Page 17 Mercredi, 22. mai 2002 10:33 10
Exits a menu or
parameter, or aborts the Altivar 11
ENT
Save the selection:
ENGLISH
Example:
Parameter Value or assignment
The display flashes when a
value is stored.
1 flash
(save)
(Next parameter)
Normal display, with no fault present and no startup:
- rdY: Drive ready
- 43.0: Display of the parameter selected in the SUP menu (default selection: frequency reference).
- dcb: DC injection braking in progress
- nSt: Freewheel stop
If there is a fault, it is shown with a flashing display.
17
ATV11.book Page 18 Mercredi, 22. mai 2002 10:33 10
ESC
Menu: Motor control
drC
ESC
Menu: Application functions Fun Menus
ESC
The parameters in clear boxes can only be modified when the drive is stopped and locked.
Parameters in shaded boxes can be modified with the drive operating or stopped.
18
ATV11.book Page 19 Mercredi, 22. mai 2002 10:33 10
The parameters in clear boxes can only be modified when the drive is stopped and locked.
Parameters in shaded boxes can be modified with the drive operating or stopped.
Drive performance can be optimised by entering the values marked on the motor rating plate
ENGLISH
Code Description Adjustment range Factory setting
5N3 Nominal motor voltage marked on the rating plate. 100 to 500 V Acc. to rating
&R3 Nominal motor frequency marked on the rating plate. 40 to 200 Hz 50 / 60Hz dep. on
bFr
3T! Frequency loop stability 0 to 100% when 20
stopped
1 to 100% when
operating
Value too high: lengthening of response time
Value too low: overspeed, possible instability.
&,' Frequency loop gain 0 to 100% when 20
stopped
1 to 100% when
operating
Value too high: overspeed, instability.
Value too low: lengthening of response time
5&R IR compensation 0 to 200% 50
Used to optimise the torque at very low speed, or to
adapt to special cases (example: for motors connected
in parallel, lower UFr).
N#R Nominal motor current marked on the rating plate 0.25 to 1.5 In (1) Acc. to rating
#,) Limiting current 0.5 to 1.5 In (1) 1.5 In
N3, Nominal motor slip 0 to 10.0 Hz Acc. to rating
Calculate using the formula: nSL = parameter FrS x (1 - Nn/Ns)
Nn = nominal motor speed marked on the rating plate
Ns = motor synchronous speed
3,0 Slip compensation 0 to 150% (of nSL) 100
Used to adjust the slip compensation around the value set by the nominal motor slip nSL, or to adapt
to special cases (example: for motors connected in parallel, lower SLP).
#/3 Nominal motor cosine marked on the rating plate 0.50 to 1.00 Acc. to rating
19
ATV11.book Page 20 Mercredi, 22. mai 2002 10:33 10
ESC ESC
FCS Reminder of the configuration
ENT
The parameters in clear boxes can only be modified when the drive is stopped and locked.
Parameters in shaded boxes can be modified with the drive operating or stopped.
(1) The preset speeds can also be accessed in the 1st level adjustment parameters.
20
ATV11.book Page 21 Mercredi, 22. mai 2002 10:33 10
ENGLISH
- : function inactive
-9%3 : This function automatically increases the deceleration time, if this
has been set at too low a value for the inertia of the load, thus avoiding the
overvoltage fault.
!D# Automatic DC injection
!#T Operating mode YES
-N/ : function inactive
-9%3 : DC injection on stopping, duration adjustable via tdC, when
operation is no longer controlled and the motor speed is zero. The value
of this current can be adjusted via SdC.
-#T : Continuous DC injection on stopping, when operation is no longer
controlled and the motor speed is zero. The value of this current can be
adjusted via SdC.
In 3-wire control the injection is only active when LI1 is at 1.
tdC is only accessible if ACt = YES, SdC if ACt = YES or Ct.
TD# Injection time on stopping, adjustable from 0.1 to 30.0 s 0.5
3D# Injection current, adjustable from 0 to 1.2 In (In = nominal drive current) 0.7 In
3&T Switching frequency
!#T Frequency range LF
-,&R : random frequency around 2 or 4 kHz according to SFr
-,& : fixed frequency of 2 or 4 kHz according to SFr
-(& : fixed frequency of 8, 12 or 16 kHz according to SFr
3&R Switching frequency: 4
- : 2 kHz (if ACt = LF or LFr) (if ACt = LF or LFr)
- : 4 kHz (if ACt = LF or LFr) 12
- : 8 kHz (if ACt = HF) (if ACt = HF)
- : 12 kHz (if ACt = HF)
- : 16 kHz (if ACt = HF)
When SFr = 2 kHz, the frequency automatically changes to 4 kHz at high
speed.
When SFt = HF, the selected frequency automatically changes to the
lower frequency if the thermal state of the drive is too high. It automatically
returns to the SFr frequency as soon as the thermal state permits.
21
ATV11.book Page 22 Mercredi, 22. mai 2002 10:33 10
22
ATV11.book Page 23 Mercredi, 22. mai 2002 10:33 10
ENT
SUP FrH
ESC
Value Frequency reference
ESC ENT
ESC
tHd
ESC
ENGLISH
Value
Drive thermal state
ENT
When the drive is running, the value displayed is that of one of the monitoring parameters. The default value
which is displayed is the motor reference (parameter FrH).
While the value of the required new monitoring parameter is being displayed, the "ENT" key must be pressed
a second time to confirm the change of monitoring parameter and to store it. From then on the value of this
parameter will be displayed during operation (even after the drive has been switched off).
If the new choice is not confirmed by pressing the "ENT" key for a second time, the drive will return to the
previous parameter after it has been switched off.
The following parameters can be accessed, with the drive stopped or running.
Code Parameter Unit
&R( Display of the frequency reference (factory configuration) Hz
R&R Display of the output frequency applied to the motor Hz
,#R Display of the motor current A
5,N Display of the line voltage V
T(R Display of the motor thermal state: 100% corresponds to the nominal thermal state. %
Above 118%, the drive trips on an OLF fault (motor overload). It can be reset below 100%.
T(D Display of the drive thermal state: 100% corresponds to the nominal thermal state. %
Above 118%, the drive trips on an OHF fault (drive overheating). It can be reset below 80%.
23
ATV11.book Page 24 Mercredi, 22. mai 2002 10:33 10
Faults displayed
The cause of the fault must be removed before resetting.
Faults SOF, OHF, OLF, OSF, ObF, and PHF can be reset via a logic input if this function has been configured.
Faults OHF, OLF, OSF, ObF, and PHF can be reset via the automatic restart function, if this function has been
configured. All faults can be reset by switching the drive off then on again.
Fault Remedy
/#& Ramp too short, check the settings.
overcurrent Inertia or load too high, check the size of the motor/drive/load.
Mechanical locking, check the state of the mechanism.
3#& Check the cables connecting the drive to the motor, and the insulation of the motor.
motor short-circuit,
insulation fault
)N&
ENGLISH
24