Rex521 Tobene
Rex521 Tobene
Buyers Guide
Feeder Protection Relay REX 521
1MRS752177-MBG
Issued: 20.11.2001
Status: Updated
Version: E/22.06.2004
Data subject to change without notice
4
Feeder Protection Relay REX 521
1MRS752177-MBG
5
Feeder Protection Relay REX 521
1MRS752177-MBG
7
Feeder Protection Relay REX 521
1MRS752177-MBG
Applications Several standard configurations are available The H03 standard configuration is designed
for the protection relay. Refer to the REX 521 to be used in single busbar systems using one
Technical Reference Manual, Standard Con- circuit-breaker for selective non-directional
figurations (see References on page 27) short-circuit protection, non-directional time-
for more detailed information. overcurrent protection, directional earth fault
protection and automatic reclosing with syn-
The B01 standard configuration is designed cro- and voltage-check functionality.
to be used in single busbar systems using one
circuit-breaker for selective short-circuit, The H04 standard configuration is designed
time overcurrent and earth fault protection of to be used in single busbar systems using one
radial isolated neutral networks, solidly circuit-breaker for selective non-directional
earthed networks, resistant earthed networks short-circuit protection, non-directional time-
and resonant earthed networks. overcurrent protection, directional and non-
directional earth fault protection and auto-
The B02 standard configuration is designed matic reclosing.
to be used in single busbar systems using one
circuit-breaker for selective short-circuit pro- The H05 standard configuration is designed
tection, time-overcurrent protection, earth to be used in single busbar systems using one
fault protection and automatic reclosing. The circuit-breaker for selective non-directional
configuration can be used in different types of short-circuit protection, non-directional time-
networks such as radial isolated neutral net- overcurrent protection, non-directional earth
works, solidly earthed networks, resistant fault protection, overvoltage protection, und-
earthed networks and resonant earthed net- ervoltage protection, residual overvoltage
works. protection and thermal overload protection
for devices.
The M01 standard configuration is designed
to be used in single busbar systems using one The H06 standard configuration is designed
circuit-breaker for selective short-circuit, to be used in single busbar systems using one
time overcurrent and directional earth fault circuit-breaker for selective non-directional
protection of radial isolated neutral networks, short-circuit protection, non-directional time-
solidly earthed networks, resistant earthed overcurrent protection, overvoltage protec-
networks and resonant earthed networks. tion, undervoltage protection, residual over-
voltage protection, underfrequency protection
The M02 standard configuration is designed and overfrequency protection.
to be used in single busbar systems using one
circuit-breaker for selective short-circuit pro- The H07 standard configuration is designed
tection, time-overcurrent protection, direc- for protection of large or medium-size three-
tional earth fault protection and automatic phase AC motors in circuit-breaker controlled
reclosing. The configuration can be used in motor drives. Due to the large number of pro-
different types of networks such as of radial tective functions integrated, the relay pro-
isolated neutral networks, solidly earthed net- vides a complete protection against motor
works, resistant earthed networks and reso- damage caused by electrical faults. The H07
nant earthed networks. configuration can also be applied to other
objects needing thermal overload protection,
The H01 standard configuration is designed such as power transformers. It can also be
to be used in single busbar systems using one used in applications requiring overcurrent
circuit-breaker for selective directional and protection, under or overvoltage protection
non-directional short-circuit protection, and/or directional or non-directional earth
directional time-overcurrent protection, fault protection.
directional earth fault protection and auto-
matic reclosing with syncro- and voltage- The H08 standard configuration is designed
check functionality. to be used in single busbar systems using one
circuit-breaker for selective non-directional
The H02 standard configuration is designed short-circuit protection, non-directional time-
to be used in single busbar systems using one overcurrent protection, non-directional earth
circuit-breaker for selective directional and fault protection, overvoltage protection, und-
non-directional short-circuit protection, ervoltage protection, residual overvoltage
directional and non-directional time-overcur- protection and thermal overload protection
rent protection, directional earth fault protec- for devices. The protection is based on phase-
tion and automatic reclosing.
8
Feeder Protection Relay REX 521
1MRS752177-MBG
9
Feeder Protection Relay REX 521
1MRS752177-MBG
Design The protection relay is based on a multipro- and informs the user via indication messages.
cessor environment. The human-machine Modern technology is applied both in hard-
interface (HMI)1 including an LCD display ware and software solutions.
with different views makes the local use easy
The protection relay is part of the ABB Sub-
1. HMI is referred to as MMI in the relay and in the station Automation system and extends the
Relay Setting Tool.
functionality and flexibility of the concept
further.
10
Feeder Protection Relay REX 521
1MRS752177-MBG
REX521xMxxx
REX521xBxxx
REX521xHxxx
REX521xSxxx
Transformer modules (MIM) 1 1 1 1
Transformers
Current transformers 1/5 A 4 4 4 1
Current transformers 0.2/1 A 1 1 1
Voltage transformers 100 V 1 4 1
Sensor channels
Current sensor inputs 3
Voltage sensor inputs 3
Main CPU modules 1 1 1 1
2 x 16 character display
Digital inputs 9
IRF outputs 1
11
Feeder Protection Relay REX 521
1MRS752177-MBG
Design, software Functionality is available as part of the stan- Functions available for use in the different
dard configurations B01, B02, M01, M02, standard configurations are listed below.
H01, H02, H03, H04, H05, H06, H07 and
H08.
H01 1
H08 6
M01
M02
B01
B02
H02
H03
H04
H05
H06
H07
Standard configurations
IEEE
Function
FB name device
blocks
number
Protection functions
3I> NOC3Low 51 x x x x x x x x x x x
3I>> NOC3High 50/51 x x x x x x x x x x x
3I>>> NOC3Inst 50/51 x x x x x x x x x x
Io> NEF1Low 51N x x x2 x x x
Io>> NEF1High 50N/51N x x x 2 x x x
Io>>> NEF1Inst 50N x x x2 x x
Io>->3 DEF2Low 67N/51N x x x x x x x
Io>>->3 DEF2High 67N x x x x x x x
Io>>>->3 DEF2Inst 67N x x x x x x
3I>-> DOC6Low 67 x x4 x
3I>>-> DOC6High 67 x x4
3U> OV3Low 59 x x x x
3U>> OV3High 59 x x x x
3U< UV3Low 27 x x x x
3U<< UV3High 27 x x x x
3I2f> Inrush3 68 x x x x x x x x x x
Iub> CUB3Low 46 x x x x x x x x
3Ith> TOL3Cab 49F x x x x x x x x
O->I AR5Func 79 x x x x x x
Uo> ROV1Low 59N x x x
Uo>> ROV1High 59N x x x
Uo>>> ROV1Inst 59N x x x
f1 Freq1St1 81U/81O x x x x
f2 Freq1St2 81U/81O x
SYNC1 SCVCSt1 25 x x
Is2t n< MotStart 48, 14, 66 x
3I() PREV3 46R x
I2> NPS3Low 46 x
I2>> NPS3High 46 x
3I< NUC3St1 37 x
FUSEF FuseFail 60 x
3Ithdev> Tol3Dev 49M x x x
U1<U1U2> PSV3St1 27, 47, 59 x
12
Feeder Protection Relay REX 521
1MRS752177-MBG
H01 1
H08 6
M01
M02
B01
B02
H02
H03
H04
H05
H06
H07
Standard configurations
IEEE
Function
FB name device
blocks
number
Control functions
I<->O CB1 COCB1 x x x x x x x x x x x x
I<->O IND1 COIND1 x x x x x x x x x x x x
I<->O IND2 COIND2 x x x x x x x x x x x x
I<->O IND3 COIND3 x5
I<->O POS COLOCAT x x x x x x x x x x x x
ALARM1-8 MMIALAR1-8 x x x x x x x x x x x x
Measurement functions
3I MECU3A x x x x x x x x x x x x
Io MECU1A x x x x x x x x x x x x
Uo MEVO1A x x x x x x x x x x
DREC MEDREC x x x x x x x x x x x x
3U MEVO3A x x x x x x x x
3U_B MEVO3B x
f MEFR1 x x x x x x x x
PQE MEPE7 x x x x x x x x
AI1 MEAI1 x
Condition monitoring functions
CB wear CMBWEAR1 x x x x x x x x x x x x
TCS1 CMTCS1 x x x x x x x x x x x x
MCS 3I CMCU3 x x x x x x x x x x x x
MCS 3U CMVO3 x x x x x x x x
TIME1 CMTIME1 x
Power quality monitoring functions
PQ 3Inf PQCU3H x x x x x x x x x x x x
PQ 3Unf PQVO3H x x x x x x x x
Standard functions
SWGRP x x x x x x x x x x x x
1
H01 available only with sensor version of REX 521
2
Configured fixedly to the I0 (1/5 A) channel or Ios if selected
3Can be used as Io>, Io>> and Io>>> or Uo>, Uo>> and Uo>>> function block with
some limitations
4
3I>-> and 3I>>-> cannot be set to operate as 3I>, 3I>> or 3I>>>
5
Motor status indication
6
Available only as VT version. VTs are used to measure phase-to-earth voltages,
calculated phase-to-phase voltages are shown by 3U_B
Note! Calculated Uo (Uos) used in Sensor versions of H01 and H03 configurations.
Calculated Io (Ios) also available in H01-H05, H08 configurations
13
Feeder Protection Relay REX 521
1MRS752177-MBG
Technical data
Table 1: Energizing inputs
Rated frequency 50.0/60.0 Hz
Current inputs rated current 0,2 A/1 A/5 A
Thermal withstand continuously 1.5 A/4 A/20 A
capability for 1 s 20 A/100 A/500 A
dynamic current withstand, half-wave value 50 A/250 A/1250 A
input impedance <750 m/<100m/
<20 m
Voltage inputs rated voltage 100 V/110 V/115
V/120 V (parametri-
zation)
voltage withstand, continuous 2 x Un (240 V)
burden at rated voltage <0.5 VA
Sensor inputs voltage range RMS 9.4 V RMS
voltage range peak 12 V
input impedance >4.7 M
input capacitance <1 nF
14
Feeder Protection Relay REX 521
1MRS752177-MBG
15
Feeder Protection Relay REX 521
1MRS752177-MBG
16
Feeder Protection Relay REX 521
1MRS752177-MBG
17
Feeder Protection Relay REX 521
1MRS752177-MBG
18
Feeder Protection Relay REX 521
1MRS752177-MBG
19
Feeder Protection Relay REX 521
1MRS752177-MBG
L1 L3
A
0 -
+
Q0
N
*) - I
X4.1
+
ACFail Mains 1
X1.1
2
TempAlarm -
L1 L3
P1 S1 5
IRF 4
S2 3
P2 8
7
S1
SO1 6
12 1A
CT4
S2 11 5A I0 10
10 11
9
8
1A
5A CT3 IL3
7 SO2 9
6 1A
CT2 12
5 5A IL2
13
4
3
2
1A
5A
CT1 IL1
1 PO1
14
15
PO2
17
18 +
PO3
X4.2
4
3
2 **)
HSPO1
X4.2 TCS1 1 +
5 DI1
- 6
7 X3.2
DI2 SERIAL BUS
8 DI3
9
10 X3.3
DI4 SERIAL BUS
11 DI5
12
13
14 DI6
15 DI7
16
17
18 DI8
X3.1
1
DI9
2
9 DATA A
RS-485
DATA B
10
*) Power flow direction
Block_Basic_a
20
Feeder Protection Relay REX 521
1MRS752177-MBG
L1 L3
A
0 -
+
Q0
N
*) - I
da dn X4.1
+
ACFail Mains 1
X1.1
2
TempAlarm -
L1 L3
P1 S1 5
IRF 4
S2 3
18
P2 100V
VT1 U0 8
16 7
S1 15 0,2A
CT5
14 1A I0B
13
SO1 6
12 1A
CT4
S2 11 5A I0 10
10 11
9
8
1A
5A CT3 IL3
7 SO2 9
6 1A
CT2 12
5 5A IL2
13
4
3
2
1A
5A
CT1 IL1
1 PO1
14
15
PO2
17
18 +
PO3
X4.2
4
3
2
**)
HSPO1
X4.2 TCS1 1 +
5 DI1
- 6
7 X3.2
DI2 SERIAL BUS
8 DI3
9
10 X3.3
DI4 SERIAL BUS
11 DI5
12
13
14 DI6
15 DI7
16
17
18 DI8
X3.1
1
DI9
2
9 DATA A
RS-485
DATA B
10
Block_Medium_a
21
Feeder Protection Relay REX 521
1MRS752177-MBG
L1 L3
A
0 -
+
Q0
N
n
*) - I
a
da dn X4.1
+
ACFail Mains 1
X1.1
27 VT4 U31**) 2
100V TempAlarm -
25
L1 L3 24 VT3
P1 S1 100V U23 5
22 IRF 4
21 VT2
100V U12
S2 19 3
P2 18
100V
VT1 U0 8
16 7
S1 15 0,2A
CT5
14 1A I0B
13
SO1 6
12 1A
CT4
S2 11 5A I0 10
10 11
9
8
1A
5A CT3 IL3
7 SO2 9
6 1A
CT2 12
5 5A IL2
13
4
3
2
1A
5A
CT1 IL1
1 PO1
14
15
PO2
17
18 +
PO3
X4.2
4
3
***)
2
HSPO1
X4.2 TCS1 1 +
5 DI1
- 6
7 X3.2
DI2 SERIAL BUS
8 DI3
9
10 X3.3
DI4 SERIAL BUS
11 DI5
12
13
14 DI6
15 DI7
16
17
18 DI8
X3.1
1
DI9
2
9 DATA A
RS-485
10 DATA B
22
Feeder Protection Relay REX 521
1MRS752177-MBG
L1 L3
A
0 -
+
Q0
N
n
*) - I
a
da dn X4.1
+
ACFail Mains 1
X1.1
27 VT4 U3 2
100V TempAlarm -
25
L1 L3 24 VT3
P1 S1 100V U2 5
22 IRF 4
21 VT2
100V U1
S2 19 3
P2 18
100V
VT1 U0 8
16 7
S1 15 0,2A
CT5
14 1A I0B
13
SO1 6
12 1A
CT4
S2 11 5A I0 10
10 11
9
8
1A
5A CT3 IL3
7 SO2 9
6 1A
CT2 12
5 5A IL2
13
4
3
2
1A
5A
CT1 IL1
1 PO1
14
15
PO2
17
18 +
PO3
X4.2
4
3
2
**)
HSPO1
X4.2 TCS1 1 +
5 DI1
- 6
7 X3.2
DI2 SERIAL BUS
8 DI3
9
10 X3.3
DI4 SERIAL BUS
11 DI5
12
13
14 DI6
15 DI7
16
17
18 DI8
X3.1
1
DI9
2
9 DATA A
RS-485
10 DATA B
23
Feeder Protection Relay REX 521
1MRS752177-MBG
X4.1
+
ACFail Mains 1
X1.1
27 2
TempAlarm -
25
24
5
22 IRF 4
21
19 3
18 VT1
100V U0 *) 8
16 7
15 0,2A
CT5
14 1A I0B
13
SO1 6
12 1A
CT4
11 5A I0 10
10 11
9
8
7 SO2 9
6 12
5 13
4
3
2
1 PO1
14
Sensor VD3 15
Voltage input, U3 X2.1
DIFF
Sensor RS3
Current input, IL3 X2.4 PO3
DIFF
Sensor RS2
Current input, IL2 X2.5
DIFF
HSPO1
X4.2 TCS1 1
5 DI1
6
7 X3.2
DI2 SERIAL BUS
8 DI3
9
10 X3.3
DI4 SERIAL BUS
11 DI5
12
13
14 DI6
15 DI7
16
17
18 DI8
X3.1
1
DI9
2
9 DATA A
Block_HighSensor_a
RS-485
DATA B
10
24
Feeder Protection Relay REX 521
1MRS752177-MBG
Ordering informa- When ordering REX 521 protection relays, Each protection relay has a specific order
tion specify the following: number that identifies the protection relay
type as well as the hardware and the software
order number as described in the figure below. The order
number is labelled on the marking strip on the
quantity
front panel of the relay delivered, for exam-
additional language ple, Order No: REX521EMHPSM01E.
REX521EMHPSM01E XX
Configuration revision
Configuration name: B01, B02, M01, M02, H01, H02, H03, H04, H05, H06, H07, H08
Rear communication: S=SPA/IEC/Modbus/DNP 3.0 L=SPA/IEC/Modbus/DNP 3.0/LON
Optical connectors for rear communication: P = plastic-fibre, G = glass-fibre
Power supply: H = PS_87H, L = PS_87L
Type of hardware: B = Basic, M = Medium, H = High, S = High sensor
Revision OrderNo_b
Accessories
Semi-flush mounting kit 1MRS050254
Wall mounting kit 1MRS050240
Rack mounting kits:
Enclosure size (x 19): Mounting kit order number:
1/2 + 1/3 1MRS050241 and 1MRS050238
1/3 1MRS050258
1/ + 1/3 1MRS050241 and 1MRS050377
1/3 + 1/3 + 1/4 1MRS050241 (2 pcs) and 1MRS050381
1/4 + 1/4 + 1/3 1MRS050241 (2 pcs) and 1MRS050382
1/3 + 1/4 1MRS050609 and 1MRS050241
Connection cable for front
panel connector 1MKC950001-1
25
Feeder Protection Relay REX 521
1MRS752177-MBG
26
References Manuals for REX 521