Automation Server (Mar 2014)
Automation Server (Mar 2014)
Automation Server
Communications hub
Capable of coordinating traffic from above and
below its location, the Automation Server can
deliver data directly to you or to other servers
throughout the site. The Automation Server can run
multiple control programs, manage local I/O,
alarms, and users, handle scheduling and logging,
and communicate using a variety of protocols.
Because of this, most parts of the system function
autonomously and continue to run as a whole even
if communication fails or individual servers or
devices go offline.
A SmartStruxure solution server is the core of the Two USB host ports
system and performs key functionality, such as One USB device port
control logic, trend logging, and alarm supervision.
The Automation Server software is pre-loaded on The USB device port allows you to upgrade
Schneider Electric supplied hardware that supports and interact with the Automation Server using
communication and connectivity to the I/O and field the Device Administrator.
busses. The distributed intelligence of the WorkStation/WebStation interface
Automation Servers ensures fault tolerance in the
Through any client, the user experience is similar
system and provides a fully featured user interface
regardless of which SmartStruxure solution server
through WorkStation and WebStation.
the user is logged on to. The user can log directly
on to an Automation Server to engineer,
Features commission, supervise, and monitor the
The Automation Server is a powerful device that Automation Server as well as its attached I/O
can act as a standalone server and also control I/O modules and field bus devices. See the
modules and monitor and manage field bus WorkStation and WebStation datasheets for
2014 Schneider Electric. All rights reserved.
The Automation Server supports the use of Web The Automation Server communicates using the
Services based on open standards, such as SOAP networking standards. This makes installations
and REST, to consume data into the SmartStruxure easy, management simple, and transactions
solution. Use incoming third-party data secure.
(temperature forecast, energy cost) over the Web to
determine site modes, scheduling, and Supported protocols
programming.
IP addressing (IPv6 ready)
TCP communications
Specifications
Electrical
DC input supply power .........................................................................................................................7 W
DC input supply voltage ..................................................................................................................24 VDC
Environment
Ambient temperature, operating .............................................................................0 to 50 C (32 to 122 F)
Ambient temperature, storage .........................................................................-20 to +70 C (-4 to +158 F)
Maximum humidity...............................................................................................95 % RH non-condensing
2014 Schneider Electric. All rights reserved.
Material
Plastic rating................................................................................................................................UL94-5VB
Enclosure....................................................................................................................Eco Friendly ABS/PC
Enclosure rating...................................................................................................................................IP 20
Mechanical
Dimensions including terminal base ..............................90 W x 114 H x 64 D mm (3.6 W x 4.5 H x 2.5 D in.)
Terminals
LNS
LNS version..................................................................................................................................OpenLNS
Installed on WorkStation PC
LonMark
Resource files version ........................................................................................................................ 13.20
CPU
Frequency ....................................................................................................................................160 MHz
SDRAM ..........................................................................................................................................128 MB
Flash memory .....................................................................................................................................4 GB
Part numbers
Automation Server .......................................................................................................SXWAUTSVR10001
TB-AS-W1, Terminal Base for Automation Server
(Required for each Automation Server) ........................................................................SXWTBASW110001
Add-on options
SW-EWS-1, EcoStruxure Web Services (run-time) option
2014 Schneider Electric. All rights reserved.
Internal configuration The I/O bus in the terminal base provides the
Automation Server with power and an address.
All connectors of the Automation Server except for
the Ethernet connector refers to signal ground as The address value in the I/O bus is increased by
shown in the figure below. one for each terminal base. The I/O bus also
enables RS-485 communication between the I/O
module and the Automation Server.
Regulatory Notices
Federal Communications Commission CE - Compliance to European Union (EU)
FCC Rules and Regulations CFR 47, Part 15, Class B 2004/108/EC Electromagnetic Compatibility Directive
This device complies with part 15 of the FCC Rules. Operation is subject to the following This equipment complies with the rules, of the Official Journal of the European Union, for
two conditions: (1) This device may not cause harmful interference. (2) This device must governing the Self Declaration of the CE Marking for the European Union as specified in
accept any interference received, including interference that may cause undesired the above directive(s) per the provisions of the following standards: IEC/EN 61326-1
operation. Product Standard, IEC/EN 61010-1 Safety Standard.
Industry Canada
ICES-003 WEEE - Directive of the European Union (EU)
This is a Class B digital device that meets all requirements of the Canadian Interference This equipment and its packaging carry the waste of electrical and electronic equipment
Causing Equipment Regulations. (WEEE) label, in compliance with European Union (EU) Directive 2002/96/EC, governing
the disposal and recycling of electrical and electronic equipment in the European
community.
C-Tick (Australian Communications Authority (ACA))
AS/NZS 3548
This equipment carries the C-Tick label and complies with EMC and radio UL 916 Listed products for the Unites States and Canada, Open Class Energy
communications regulations of the Australian Communications Authority (ACA), governing Management Equipment.
the Australian and New Zealand (AS/NZS) communities.
2014 Schneider Electric. All rights reserved.