Project Client Date 11-11-2016 Report Ref TLC-055-TR 23 Contractor Device Earth Pits

The document reports the results of earth resistance measurements tests conducted on earth pits and lightning protection pits at a facility. It provides the measured earth resistance values of 23 individual pits and their combined grid values. It also lists the testing equipment used, including an Earth Resistance Kit, and notes that all test results were found to be satisfactory.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
48 views2 pages

Project Client Date 11-11-2016 Report Ref TLC-055-TR 23 Contractor Device Earth Pits

The document reports the results of earth resistance measurements tests conducted on earth pits and lightning protection pits at a facility. It provides the measured earth resistance values of 23 individual pits and their combined grid values. It also lists the testing equipment used, including an Earth Resistance Kit, and notes that all test results were found to be satisfactory.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Project

Date 11-11-2016
Client
Report ref TLC-055-TR 23
Contractor Device EARTH PITS

TEST SHEET FOR EARTH PIT RESISTANCE MEASUREMENT TEST

1. EARTH RESISTANCE MEASUREMENT:

EARTH RESISTANCE EARTH RESISTANCE


VALUES VALUES
S.NO DESCRIPTION
INDIVIUDAL VALUE COMBINED VALUE
(PIT) (GRID)
1 EARTH PIT 1 2.96 0.12
2 EARTH PIT 2 3.45 0.8
3 EARTH PIT 3 2.45 1.61
4 EARTH PIT 4 3.35 0.44
5 EARTH PIT 5 3.24 0.74
6 EARTH PIT LIGHTNING 1 15 0.35
7 EARTH PIT LIGHTNING 2 3.27 0.70
8 EARTH PIT LIGHTNING 3 3.30 0.47
9 EARTH PIT LIGHTNING 4 3.40 0.59
10 EARTH PIT LIGHTNING 5 3.46 0.94
11 EARTH PIT LIGHTNING 6 2.95 0.98
12 EARTH PIT LIGHTNING 7 2.48 0.98
13 EARTH PIT LIGHTNING 8 2.18 0.36
14 EARTH PIT LIGHTNING 9 2.38 0.08
15 EARTH PIT LIGHTNING 10 1.93 0.36
16 EARTH PIT LIGHTNING 11 2.82 0.49
17 EARTH PIT LIGHTNING 12 3.40 0.64
18 STN TX NEUTRAL EARTH 1 4.22 --
19 STN TX NEUTRAL EARTH 2 4.36 --
20 TX 1 NEUTRAL EARTH 1 3.67 0.03
21 TX 1 NEUTRAL EARTH 2 3.42 0.09
22 TX 2 NEUTRAL EARTH 1 2.42 0.27
23 TX 2 NEUTRAL EARTH 2 3.45 0.06

2. Testing Equipment Details


TESTED BY WITNESSED/APPROVED BY

Sign Sign

Name : Name

Date: Date

Page 1 of 2
Project

Date 11-11-2016
Client
Report ref TLC-055-TR 23
Contractor Device EARTH PITS

Serial
Equipment Name Make Model Calibration Valid Up to
Number
Earth Resistance Kit Kyoritsu 4105A W8149124 2-04-2017

3. Remarks/Observations: All the test results found satisfactory.

TESTED BY WITNESSED/APPROVED BY

Sign Sign

Name : Name

Date: Date

Page 2 of 2