Danfoss vlt3000 PDF
Danfoss vlt3000 PDF
Product Manual
Software version: 3.0 and 3.11
This product manual applies to all VLT 3000 frequency converters with software
version 3.0 and 3.11:
* Version 3.0 covers VLT 3002-3022, 200/400/500 V and VLT 3032-3052, 400/500 V.
* Version 3.11 covers VLT 3032-3052, 230 V, and VLT 3060-3250, 380/500 V.
Where version 3.11 deviates from version 3.0 this is described.
The size and voltage of the frequency converter will be identified automatically on
start-up.
Warning:
Touching the electrical parts, even when the mains supply
has been switched off, can cause serious injury or death.
When using VLT types 3002-3052: Wait 4 minutes
When using VLT types 3060-3250: Wait 14 minutes
These rules concern 1. When repairs are undertaken, the mains 4. The leakage currents to ground are
your safety supply to the VLT must be disconnected. higher than 3 mA.
2. The Stop/Reset key on the frequency 5. The factory setting does not incorpor-
converters keyboard does not ate protection against motor overload.
disconnect the power supply and may For this function parameter 315 is set
therefore not be used as a safety at data value trip [2] or data value
switch. warning [1].
Warning against 1. The motor can be stopped using di- 3. A stopped motor can start if a fault
improper start gital commands, bus commands, occurs in the frequency converters
references or local stop, while the electronics or after a temporary
frequency converter is connected to overload, mains fault or faulty motor
the mains. If personal safety requires connection.
elimination of any possibility of unin-
tended start, these stops will not be
sufficient.
The Electronic Thermal Relay (ETR) in UL listed VLT's provides class 20 motor
overload protection in accordence with NEC in single motor applications, when
parameter 315 is set for "TRIP" and parameter 107 is set for nominal motor
rated (nameplate) current. Effective from software version 1.10.
Quick setup
Product description
Introduction .......................................... 8
Technology ........................................... 9
Sizing ................................................... 12
Product range ....................................... 14
Technical data ...................................... 23
Dimensions ........................................... 28
Description of terminals ........................ 31
Connection examples ........................... 32
Installation
Operational instructions
Galvanic isolation -
Earth leakage current ........................... 128
Extreme running conditions .................. 129
du/dt and peak voltage on motor .......... 130
Acoustic noise ...................................... 130
Thermal motor protection ..................... 130
Derating ................................................ 131
EMC testresults .................................... 134
Vibration and shock .............................. 137
Air humidity .......................................... 137
Efficiency .............................................. 138
Mains supply
interference / harmonics ....................... 139
Power factor ......................................... 139
Service
Fault messages ................................... 140
Electrostatic discharge (ESD) ............... 141
Fault location ........................................ 142
Accessories
External mounting
of display .............................................. 146
Connection of brake resistors ............... 146
Connection of option cards ................... 146
Mounting of bonding plate for
UL approval .......................................... 148
Mounting of fan option .......................... 148
Factory settings
Index
For first-time Danfoss If you have not used a Danfoss VLT be- Pay attention to the safety rules on page
VLT users fore, Quick setup will be a help, and also 2 before start-up.
Installation and Operational instructions.
For experienced Danfoss If you already have experience with the For more information see the other sec-
VLT users Danfoss VLT, you will find the Quick tions, of which EMC-correct installation
setup section most useful. and Special conditions will be particularly
useful.
Available The following chart shows what literature Note that there can be deviations be-
documentation is available on the VLT 3000 Series. tween different countries.
All
Option
users
Data sheet
PROFIBUS RFI - LC Brake
MD.30.AX.02
manual module resistor
MG.10.AX.YY MI.65.FX.YY MI.65.BX.YY
PROFIBUS Clamp
data sheet module
MD.10.AX.YY MI.65.IX.YY
Brake
module
MI.62.GX.YY
LC
module
X = Revision of edition MI.65.FX.YY
YY = Language version
Programming keys When the supply voltage is connected, the Use the key to switch to DATA MODE.
Data
MODE.
Note: All settings are based on factory settings, but the following must
be selected: 103, 104 and 105.
Screen for control cables, is mounted under terminal clamp according to
instructions on p. 57.
The following settings are also used for specialised motors and parallel coupled motors, or variable torque
application or when a brake module is mounted
Item Parameter Description Settings Display
1 100 Load For normal applications with constant torque:
Select: Constant torque compensated CTWITHCOMP
For centrifugal pumps and fans:
Select: VT medium VT MODE-MED
For centrifugal pumps and fans with heavy start:
Select: VT Medium CT Start VT MED W/CT
For synchronous motors, parallel coupled motors or specialised motors
Select: Constant torque CTMODE
2 300 Brake option If brake option/module is used:
Select: Applied APPLIED
3 Start frequency converter This is by applying 24 V D.C. to terminals 18 and 27 from
terminal 12 or by using external 24 V D.C. voltage.
The following settings are used for local operation and start
Item Parameter Description Settings Display
1 003 Operation mode Select: Local LOCAL
2 004 Local reference Set required output frequency using the "+" or "" keys.
Control principle A frequency converter rectifies the a.c. The variable voltage and frequency
voltage to D.C. voltage and then converts supplying the motor make possible infinite
this D.C. voltage to A.C. voltage with speed control of standard three-phase
variable amplitude and frequency. asynchronous motors.
VLT 3000 Series frequency converters The features are obtained through a
use an inverter control system known as special switching pattern: the switching
the Voltage Vector Control (VVC) intervals are very short, which means high
developed by Danfoss. switching frequency, and the six semi-
The VVC principle is superior to the conductors of the inverter section are
traditional PWM (Pulse Width Modulation) alternately held inactive, in pairs, through-
principle used in most modern frequency out a 60 sine period. The current wave
converters in the following ways: form of the motor current closely resembles
Full-rated motor voltage at rated motor that obtained on mains operation. The
frequency switching pause in 60 of the sine period
Near perfect resemblance to the also means that full-rated motor voltage
sinusoidal mains supply can be obtained and inverter switching
Extremely low switching losses, resulting losses are reduced by about one third.
in high converter efficiency
The figures below show the switching The full-rated motor voltage and the
pattern and the maximum motor voltage in perfect current wave form mean that the
relation to the mains voltage according to Danfoss VLT 3000 Series allows full mo-
the VVC principle and the traditional PWM tor performance without any derating
principle, respectively. just like running the motor on the mains.
Motor voltage and simplified switching pattern with the Danfoss VVC principle
1,00
U-V U-W W-U
U
0,50
0,00
0 60 120 180 240 300 360
-0,50
V W
-1.00
Motor voltage and switching pattern with the traditional PWM principle
1,00
0,866
U-V V-W W-U
U
0,50
0,00
0 60 120 180 240 300 360
-0,50
V W
-1.00
Switching pattern for phase U Single-phase voltage Phase-phase voltage for motor
The VLT 3000 Series is delivered with a These components built-in as standard
number of standard components which give you the following advantages:
you would normally have to buy separately Save space and reduce costs
such as motor coils, mains reactor DC link Simplify the installation as the
coil and galvanic insulation (PELV). VLT 3000 will meet most demands.
Factory programmed Depending on the type of load, the It is possible to choose between 3 U/f
U/f characteristics VLT 3000 Series has dynamic adapting or characteristics for VT operation, offering
factory programmed U/f characteristics the choice of optimising the start torque or
(motor voltage/frequency) giving the reducing the noise level or power losses
correct magnetisation of the motor, thus from the motor. A new parameter (106)
ensuring optimum dynamic, accuracy or called Automatic motor tuning optimizes
efficiency. the motor parameters at constant load
torque.
Constant torque CT
(Parameter 100)
Quadratic torque VT
(Parameter 100)
1: VT low
2: VT medium
3: VT high
Control accuracy Slip-compensated 0.5% 5-50 Hz: VLT 3011-3052(10-90% load change)
(depending on motor size) 10-50 Hz: VLT 3004-3008
1.0% 5-50 Hz: VLT 3004-3052 (10-140% load change)
PID (closed loop) 0.1% 5-50 Hz: (140 - +140% load change)
Open loop (digital) 0.01% 0.5-120 Hz
(frequency stability)
0.5-500 Hz
0.05% Frequency resolution (digital)
Programmable The digital technique used in the VLT It is easy for the user to program the
control inputs and 3000 Series makes it possible to program required functions on the keyboard of the
signal outputs the different control inputs and signal VLT 3000 Series or via the terminals or
in 4 setups outputs, and to select 4 different user- the RS 485 interface.
defined setups.
Protected against mains The VLT 3000 Series is protected against Rated motor voltage and full torque can be
disturbance transients arising on the mains, e.g. when maintained down to 10% undervoltage on
you switch in power factor phase correction the supply mains.
capacitors or when the supply is subject to
lightning strikes.
Low disturbance on As the VLT 3000 Series has coils in the This gives a good power factor, thus
the mains intermediate circuit built-in as standard the reducing the harmonic load on the mains
harmonic generation is low. supply.
Effective radio The VLT 3000 Series can be delivered with Some VLT types have a mains filter as
frequency interference an RFI filter complying with EN 55011. standard in compliance with grade 1, class A.
suppression (EMC) Filters are available as options or modules.
Long motor cables As standard the VLT 3000 Series is cable between motor and frequency
delivered with built-in motor coils. This converter without any additional coils.
means that it is possible to install a long
Advanced Current measurement in all three motor The effective monitoring of the three supply
VLT protection phases gives perfect protection of the VLT phases means that the VLT 3000 Series
3000 series in the event of short circuits or stops in the event of a missing phase. In
earth faults on the motor terminals. this way overloading of the inverter and the
capacitors of the intermediate circuit, which
The continuous monitoring of the three would reduce the lifetime of the frequency
motor phases makes switching on the converter drastically, can be avoided.
motor cables possible e.g. by opening/
closing a contactor. The VLT 3000 Series has built-in thermal
protection of the unit as standard. The
function turns off the inverter on thermal
overload.
Advanced The VLT 3000 Series has a built-in electro- The thermal motor protection is compar-
motor protection nic thermal motor protection. able with thermal relay in the motor cables.
The frequency converter calculates the To achieve optimum protection against
motor temperature on the basis of voltage, overheating of the motor when covered or
current, frequency and time. blocked, or in case the ventilation should
Therefore it is superior to the traditional fail, it is possible to build in a thermistor
bi-metallic protection where the altered and connect this to the frequency con-
cooling conditions due to the speed control verter thermistor input (terminal 16, see
are not taken into consideration. page 102).
: Intermittent operation
: In continuous operation some specifications might change
Mains: 380/400/415 V
Typical shaft Constant output Constant output
VLT type output current IVLT,N power at 415 V
CT [kW] VT CT [A] VT CT [kVA] VT
Mains: 440/460/500 V
Typical shaft Constant output Constant output
VLT type output current IVLT,N power at 500 V
CT [kW] VT CT [A] VT CT [kVA] VT
Remote box
175H1788
IP 00 IP 54 IP 21 option IP 21 option
with fan without fan
175H7040/7008 175H1007/7007
RFI option RFI module RFI-LC module LC motor filter *) LC module Brake module Clamp module
175U0253 175U0252 175H6198/6199 175H5147
*) Made for Danfoss A/S by the firm Platthaus
200 / 220 / 230 V 380 / 400 / 415 V 440 / 460 / 500 V
VLT VLT VLT
Description kW Code no. Description kW Code no. Description kW Code no.
type type type
IP 00 1,1 175H4131 IP 00 1,1 175H7238 IP 00 1,1 175H1729
IP 00 with brake 1,1 175H4132 IP 00 with brake 1,1 175H7239 IP 00 with brake 1,1 175H1730
3002 IP 21 (as option) 1,1 175H1007 3002 IP 21 as option) 1,1 175H1007 3002 IP 21 (as option) 1,1 175H1007
IP 54 1,1 175H4133 IP 54 1,1 175H7240 IP 54 1,1 175H1731
IP 54 with brake 1,1 175H4134 IP 54 with brake 1,1 175H7241 IP 54 with brake 1,1 175H1732
IP 00 1,5 175H4135 IP 00 1,5 175H7242 IP 00 1,5 175H1733
IP 00 with brake 1,5 175H4136 IP 00 with brake 1,5 175H7243 IP 00 with brake 1,5 175H1734
3003 IP 21 (as option) 1,5 175H1007 3003 IP 21 (as option) 1,5 175H1007 3003 IP 21 (as option) 1,5 175H1007
IP 54 1,5 175H4137 IP 54 1,5 175H7244 IP 54 1,5 175H1735
IP 54 with brake 1,5 175H4138 IP 54 with brake 1,5 175H7245 IP 54 with brake 1,5 175H1736
IP 00 2,2 175H4139 IP 00 2,2 175H7246 IP 00 2,2 175H1737
IP 00 with brake 2,2 175H4140 IP 00 with brake 2,2 175H7247 IP 00 with brake 2,2 175H1738
3004 IP 21 (as option) 2,2 175H7040 3004 IP 21 (as option) 2,2 175H1007 3004 IP 21 (as option) 2,2 175H1007
IP 54 2,2 175H4141 IP 54 2,2 175H7248 IP 54 2,2 175H1739
IP 54 with brake 2,2 175H4142 IP 54 with brake 2,2 175H7249 IP 54 with brake 2,2 175H1740
IP 00 4,0 175H7264 IP 00 4,0 175H1741
IP 00 with brake 4,0 175H7265 IP 00 with brake 4,0 175H1742
3006 IP 21 (as option) 4,0 175H7040 3006 IP 21 (as option) 4,0 175H1007
IP 54 4,0 175H7266 IP 54 4,0 175H1743
IP 54 with brake 4,0 175H7267 IP 54 with brake 4,0 175H1744
IP 00 5,5 175H7268 IP 00 5,5 175H1745
IP 00 with brake 5,5 175H7269 IP 00 with brake 5,5 175H1746
3008 IP 21 (as option) 5,5 175H1007 3008 IP 21 (as option) 5,5 175H1007
IP 54 5,5 175H7270 IP 54 5,5 175H1747
IP 54 with brake 5,5 175H7271 IP 54 with brake 5,5 175H1748
All code numbers: 175XXXXX. CT: Constant torque / VT: Variable torque (quadratic load)
1) Can only be mounted in units with brake function. 2) The RFI filter option (175H7038) may be beneficial. 3) Only bottom can be used. 4 ) Forced cooling
needed.
"-" Cannot be delivered.
VLT type 3006 - 3022, 200/230 V / VLT type 3011 - 3052, 380/415 V / VLT type 3011 - 3052, 440/500 V
Remote box
175H1788
VLT type 3032 - 3052, 220/440 V, VLT type 3060 - 3250, 380/440/500 V
Remote box
175H1788
NEMA 1/12 NEMA 12 NEMA 1/12 NEMA 12 NEMA 1/12 Base Brake module Optional
IP 21/54 IP 54 IP 21/54 IP 54 IP 21/54 IP 20 NEMA 12 base for VLT
including RFI mounted without base RFI mounted only wall RFI filter IP 54 3100-3150
base with filter, (option) with filter mounting mounting cabinet/
including base without base RFI filter
(option)
220/230/240 V Fuses
VLT 3032 - 3052
Description kW Code no. Description Amp Bussmann 3100 3125 3150 3200 3250
type
name 3060 3075
IP 21 22 175L4500
3032
IP 54 22 175L4503 Input fuse 150 T-Tron JJS 175L3490
380/440/500 V
VLT Description 3060 3075 3100 3125 3150 3200 3250
Description kW Code no.
type
Brake module IP 54 175L3030 175L3031
IP 21 45 175L3000
3060 RFI module IP20 175L3657 175L3658 175L3659 175L3660
IP 54 45 175L3007
RFI module IP54 175L3661 175L3662 175L3663 175L3664
IP 21 55 175L3001
3075
IP 54 55 175L3008 Mounting cabinet IP54 with main switch 175L3038(175A) 175L3040(200A) 175L3042(400A)
IP 21 75 175L3002 Mounting cabinet IP54 with main switch 175L3039(200A) 175L3041(400A) 175L3043(600A)
3100
IP 54 75 175L3009 Mounting cabinet IP54 without main switch 175L3653 175L3654 175L3655
IP 21 90 175L3003 Base for floor installation for VLT - 175L3047 Included
3125
IP 54 90 175L3010
Base for RFi/mounting cabinet IP54 - 175L3048 Included
IP 21 110 175L3004 PROFIBUS option 175H4754
3150
IP 54 110 175L3011
Modbus Plus option Contact Danfoss
IP 21 132 175L3005
3200 PC software ( GB 175H2850) ( D 175H2876) ( DK 175H2877)
IP 54 132 175L3012
Remote box 175H1788
IP 21 160 175L3006
3250
IP 54 160 175L3013 Terminal adapter kit 175L3640 175L3641 175L3642
Function diagram for VLT type 3011 - 3052 380/500 V, VLT type 3006 - 3022 200/230 V
Function diagram for VLT type 3032 - 3052, 220/240 V, VLT type 3060 - 3075 (380/500 V)
According to international VDE and UL/CSA requirements VLT type 3002 3003 3004 3006 3008 3011 3016 3022 3032 3042 3052
Constant torque (CT):
Output current IVLT,N [A] 5.4 7.8 10.5 19.0 25.0 32.0 46.0 61.0 80.0 104.0 130.0
IVLT,MAX [A] (60 s) 6.7 12.5 17.0 30.0 40.0 51.2 73.6 97.6 120.0 156.0 195.0
Output SVLT,N [kVA] 2.1 3.1 4.2 7.6 10.0 12.7 18.3 24.3 31.9 41.4 51.8
SVLT,MAX [kVA] (60 s) 2.7 4.9 6.7 12.0 15.9 20.4 29.2 38.9 47.8 62.1 77.7
Typical shaft output PVLT,N [kW] 1.1 1.5 2.2 4.0 5.5 7.5 11.0 15.0 22.0 30.0 37.0
Quadratic torque (VT):
Output current IVLT,N [A] 5.4 7.8 10.5 25.0 32.0 46.0 61.0 88.0 104.0 130.0 154.0
Output SVLT,N [kVA] 1.9 2.9 4.0 10.0 12.7 18.3 24.3 35.1 41.4 51.8 61.3
Typical shaft output PVLT,N [kW] 1.1 1.5 2.2 5.5 7.5 11,0 15,0 22.0 33.0 37.0 45.0
Max. cable cross-section [mm2] 2.5 2.5 2.5 16.0 16.0 16.0 35.0 50.0 70.0 70.0 70.0
Max. motor cable length [m] 300, with screened cables: 150 m 300
Output voltage UM [%] 0-100, of mains voltage max. 230 V
Output frequency fM [Hz] 0-120 or 0-500; programmable
Rated motor voltage UM,N [V] 200/220/230
Rated motor frequency fM,N [Hz] 50/60/87/100
Thermal protection during operation Integrated thermal motor protection (electronic);
thermistor to DIN 44081
Switching on output Unlimited (frequent switching on output may result
in fault message)
Ramp times [s] 0.1 - 3600
VLT type 3002 3003 3004 3006 3008 3011 3016 3022 3032 3042 3052
Max. input current const. load IL,N [A] 6.8 9.1 13.3 17.5 22.2 26.4 41.7 52.2 78.0 102.0 128.0
quad. load IL,N [A] 6.8 9.1 13.3 23.1 29.6 42.0 56.8 72.3 102.0 128.0 152.0
Max. cable cross-section [mm2] 2.5 2.5 2.5 16.0 16.0 16.0 35.0 50.0 120.0 120.0 120.0
Max. pre-fuses1) [A] 16.0 16.0 25.0 40.0 50.0 60.0 80.0 125.0 150.0 150.0 150.0
+10%
Supply voltage (VDE 0160) [V] 3 x 200/220/230 10% 3 x 220/230/240-15%
Supply frequency [Hz] 50/60
Power factor / cos. 1 0.9/1.0
Efficiency 0.96 at 100% load
Switching on input times/min. times/min. 2
VLT type 3002 3003 3004 3006 3008 3011 3016 3022 3032 3042 3052
IP 00 7.4 7.4 7.4 - - - - - - - -
IP 20 - - - 24.0 26.0 32.0 49.0 51.0 - - -
Weight (kg)
IP 21 8.0 8.0 8.0 - - - - - 143.0 145.0 147.0
IP 54 11.0 11.0 11.0 34.0 37.0 48.0 63.0 65.0 143.0 145.0 147.0
Power loss CT [W] 60.0 100.0 130.0 270.0 425.0 399.0 615.0 935.0 760.0 910.0 1110
at max. load VT [W] 60.0 100.0 130.0 425.0 580.0 651.0 929.0 1350 950.0 1110 1290
VLT type 3002-04: IP 00 / IP 21 / IP 54
Enclosure
VLT type 3006-22: IP 20 / IP 54
VLT type 3032-52: NEMA 1 / 2, IP 21 / 54
Vibration test [g] 0.7
Relative humidity [%] VDE 0160 5.2.1.2.
[C] VLT 3002-3004: -10 +40, operation at full load2)
VLT 3006-3052: -10 +45/40(CT/VT) at full load2)
Ambient temperature (to VDE 0160)
[C] VLT 3002-3004: -30/25 +65/70, in storage/transport
VLT 3006-3052: -25 +65/70, in storage/transport
Frequency converter protection Protection against earthing and short-circuiting
Emission EN 55011, EN 55014
EMC standards
EN 50082-2, IEC 1000-4-2, IEC 1000-4-3, IEC 1000-4-4,
(See section EMC test results)
Immunity IEC 1000-4-5 VDE 0160, ENV 50140, ENV 50141
1) VLT 3022: Only semi-conductor fuses; VLT 3032-3052: Bussman rapid type JJS built-in (see list)
2) In the range -10 to 0C, the equipment can start and run; however, the display values and certain operating characteristics will not fulfil the
specifications.
Acc. to international VDE and UL/CSA requirements VLT type 3002 3003 3004 3006 3008 3011 3016 3022 3032 3042 3052
Constant torque (CT):
Output current IVLT,N [A] 2.8 4.1 5.6 10.0 13.0 16.0 24.0 32.0 44.0 61.0 73.0
IVLT,MAX [A] (60 s) 3.5 6.5 9.0 16.0 20.8 25.6 38.4 51.2 70.4 97.6 117.0
Output SVLT,N [kVA] 2.0 2.9 4.0 7.2 9.3 11.5 17.2 23.0 31.6 44.0 52.5
SVLT,MAX [kVA] (60 s) 2.5 4.6 6.4 11.5 15.0 18.4 27.6 36.8 50.5 70.2 84.1
Typical shaft output PVLT,N [kW] 1.1 1.5 2.2 4.0 5.5 7.5 11.0 15.0 22.0 30.0 37.0
Quadratic torque (VT):
Output current IVLT,N [A] 2.8 4.1 5.6 13.0 16.0 24.0 32.0 44.0 61.0 73.0 88.0
Output SVLT,N [kVA] 2.0 2.9 4.0 9.3 11.5 17.2 23.0 31.6 44.0 52.5 63.3
Typical shaft output PVLT,N [kW] 1.1 1.5 2.2 5.5 7.5 11.0 15.0 22.0 30.0 37.0 45.0
Max. cable cross-section [mm2] 2.5 2.5 2.5 2.5 2.5 16.0 16.0 16.0 35.0 35.0 50.0
Max. motor cable length [m] 300, with screened cables: 150 m
Output voltage UM [%] 0-100, of mains voltage
Output frequency fM [Hz] 0-120 or 0-500; programmable
Rated motor voltage UM,N [V] 380/400/415
Rated motor frequency fM,N [Hz] 50/60/87/100
Integrated thermal motor protection (electronic);
Thermal protection during operation
thermistor to DIN 44081
Switching on output Unlimited (frequent switching on output may result in fault message)
Ramp times [s] 0.1 - 3600
VLT type 3002 3003 3004 3006 3008 3011 3016 3022 3032 3042 3052
Max. input current const. load IL,N [A] 2.8 4.8 7.0 10.0 13.0 13.8 21.8 30.7 41.9 55.6 66.5
quad. load. IL,N [A] 2.8 4.8 7.0 13.0 17.0 22.0 31.0 41.5 57.5 66.5 80.0
Max. cable cross-section [mm2] 2.5 2.5 2.5 2.5 2.5 16.0 16.0 16.0 35.0 35.0 50.0
Max. pre-fuses [A] 16.0 16.0 16.0 25.0 25.0 50.0 63.0 63.0 80.0 1001) 1251)
Supply voltage [V] 3 x 380/400/415 10% (VDE 0160)
Supply frequency [Hz] 50/60 Hz
Power factor / cos. 1 0.9/1.0
Efficiency 0,96 at 100% load
Switching on input times/min. 2
VLT type 3002 3003 3004 3006 3008 3011 3016 3022 3032 3042 3052
IP 00 7.4 7.4 7.4 12.0 14.0 - - - - - -
Weight (kg) IP 20 - - - - - 24.0 26.0 32.0 49.0 54.0 54.0
IP 21 8.0 8.0 8.0 13.0 15.0 - - - - - -
IP 54 11.0 11.0 11.0 14.0 15.0 34.0 37.0 48.0 63.0 69.0 69.0
Power loss CT [W] 60 100 130 195 200 270 425 580 880 1390 1875
at max. load VT [W] 60 100 130 280 300 425 580 880 1390 1875 2155
Enclosure VLT type 3002-08: IP 00 / IP 21 / IP 54
VLT type 3011-52: IP 20 / IP 54
Vibration test [g] 0.7
Relative humidity [%] VDE 0160 5.2.1.2.
[C] -10 +40 -10 +45/40 (CT/VT)
Ambient temperature operation at full load2) at full load2)
(to VDE 0160) [C] -25 +65/70, -25 +65/70,
in storage/transport in storage/transport
EMC standards Emission EN 55011, EN 55014, EN 61000-3-2
(See section EMC test results) Immunity EN 50082-2, IEC 1000-4-2, IEC 1000-4-3, IEC 1000-4-4,
IEC 1000-4-5, VDE 0160, ENV 50140, ENV 50141
According to international VDE and UL/CSA requirements VLT type 3060 3075 3100 3125 3150 3200 3250
Constant torque (CT):
Output current IVLT,N [A] 86 105 139 168 205 243 302
IVLT,MAX [A] (60s) 129 158 209 252 308 365 453
Output SVLT,N [kVA] 61.8 73 96 116 142 168 209
SVLT,MAX (60s) 89 109 144 175 213 253 314
Typical shaft output PVLT,N [kW] 45 55 75 90 110 132 160
Quadratic torque (VT):
Output current IVLT,N [A] 105 139 168 205 243 302 368
IVLT,MAX [A] (60s) 116 153 185 226 267 332 405
Output SVLT,N [kVA] 73 96 116 142 168 209 255
Typical shaft output PVLT,N [kW] 55 75 90 110 132 160 200
Max. cable cross-section [mm2] 70 70 150 150 150 2x95 2x95
Max. motor cable length [m] 300
Output voltage UM [%] 0-100 of mains voltage
Output frequency fM [Hz] 0-120 or 0-500, programmable
Rated motor voltage UM,N [V] 380/400/415/440/460/500
Rated motor frequency fM,N [Hz] 50/60/87/100
Thermal protection during operation Integrated thermal motor protection (electronic);
thermistor to DIN 44081
Switching on output Unlimited (frequent switching on output may result in fault message)
Ramp times [s] 0.1 - 3600
VLT Type 3060 3075 3100 3125 3150 3200 3250
Input current IL,N [A] 84.6 103.3 138.4 167.2 201.7 241.9 307.6
IL,MAX (60s) [A] 129.0 158.0 209.0 252.0 308.0 365.0 453.0
Quadratic load IL,N [A] 103.3 138.4 167.2 201.7 241.9 293.3 366.3
IL,MAX (60s) [A] 116.0 153.0 185.0 226.0 267.0 332.0 405.0
Max. cable cross-section [mm2] 120.0 120.0 2 x 120 2 x 120 2 x 120 2 x 240 2 x 240
Pre-fuses1) [A] 150.0 150.0 250.0 250.0 300.0 450.0 500.0
Supply voltage (VDE 0160) [V] 3 x 380/400/415/440/460/500 10%
Supply frequency [Hz] 50/60
Power factor / cos. 1 0.9/1.0
Efficiency 0,96 at 100% load
Switching on input times/min. 1
VLT type 3060 3075 3100 3125 3150 3200 3250
IP 21 147 147 211 211 220 306 306
Weight (kg)
IP 54 147 147 211 211 220 306 306
Front 423 529 713 910 1091 1503 1812
Power loss at max. load CT [W]
Heat sink 859 1074 1447 1847 2216 3051 3679
Front 529 713 910 1091 1503 1812 2209
Power loss at max. load VT [W]
Heat sink 1074 1447 1847 2216 3051 3679 4485
Enclosure IP 21 / IP 54 NEMA 1/12
Vibration test [g] 0.7
Relative humidity [%] VDE 0160 5.2.1.2.
Ambient temperature [C] -10 +40 operation at full load (VT) -10 +45 (CT)2)
(to VDE 0160) [C] -30/25 +65/70 in storage/transport
Frequency converter protection Protection against earthing and short-circuiting
EMC standards Emission EN 55011, EN 55014
(See section EMC test results) Immunity EN 50082-2, IEC 1000-4-2, IEC 1000-4-3, IEC 1000-4-4,
IEC 1000-4-5, VDE 0160
Acc. to international VDE and UL/CSA requirementsVLT type 3002 3003 3004 3006 3008 3011 3016 3022 3032 3042 3052
Constant torque (CT):
Output current IVLT,N [A] 2.6 3.4 4.8 8.2 11.1 14.5 21.7 27.9 41.4 54.0 65.0
IVLT,MAX [A] (60s) 3.4 5.5 7.7 13.1 17.6 23.2 34.7 44.6 67.2 86.4 104.0
Output SVLT,N [kVA] 2.3 2.9 4.1 7.1 9.6 12.6 18.8 24.2 36.0 46.8 56.3
SVLT,MAX [kVA] (60s) 2.9 4.7 6.7 11.3 15.2 20.1 30.1 38.6 58.2 7.8 90.1
Typical shaft output PVLT,N [kW] 1.1 1.5 2.2 4.0 5.5 7.5 11.0 15.0 22.0 30.0 37.0
Quadratic torque (VT):
Output current IVLT,N [A] 2.6 3.4 4.8 8.2 11.1 21.7 27.9 41.4 54.0 65.0 78.0
Output SVLT,N [kVA] 1.6 2.9 4.1 7.1 9.6 18.8 24.2 35.9 46.8 56.3 67.5
Typical shaft output PVLT,N [kW] 1.1 1.5 2.2 4.0 5.5 11.0 15.0 22.0 30.0 37.0 45.0
Max. cable cross-section [mm2] 2.5 2.5 2.5 2.5 2.5 16.0 16.0 16.0 35.0 35.0 50.0
Max. motor cable length [m] 300, with screened cables: 150 m (3011-3052 in VT: 150 m and 40 m)
Output voltage UM [%] 0-100, of mains voltage
Output frequency fM [Hz] 0-120 eller 0-500, programmable
Rated motor voltage UM,N [V] 440/460/500
Rated motor frequency fM,N [Hz] 50/60/87/100
Thermal protection during operation Integrated thermal motor protection (electronic); thermistor to DIN 44081
Switching on output Unlimited (frequent switching on output may result in fault message)
Ramp times [s] 0.1 3600
VLT type 3002 3003 3004 3006 3008 3011 3016 3022 3032 3042 3052
Max. const. load. [A] 2.6 3.4 4.8 8.2 11.1 12.6 20.1 26.8 37.3 50.2 61.3
input current quadratic load [A] 2.6 3.4 4.8 8.2 11.1 19.6 26.0 34.8 48.6 60.3 72.0
Max. cable cross-section [mm2] 2.5 2.5 2.5 2.5 2.5 16.0 16.0 16.0 35.0 35.0 50.0
Max. pre-fuses [A] 16.0 16.0 16.0 25.0 25.0 30.0 40.0 50.0 60.0 100.01) 125.01)
Supply voltage (VDE 0160) [V] 3 x 440/460/500 10% (VDE 0160)
Supply frequency [Hz] 50/60
Power factor / cos. 1 0.9/1.0
Efficiency 0.96 at 100% load
Switching on input times/min. 2
VLT type 3002 3003 3004 3006 3008 3011 3016 3022 3032 3042 3052
IP 00 7.4 7.4 7.4 12 14 - - - - - -
IP 20 - - - - - 25 26 31 49 54 54
Weight (kg)
IP 21 8.0 8.0 8.0 13 15 - - - - - -
IP 54 11 11 11 14 15 34 37 48 63 69 69
CT [W] 60 100 130 160 200 174 287 580 958 1125 1467
Power loss at max. load
VT [W] 60 100 130 160 200 281 369 880 1133 1440 1888
VLT type 3002-08: IP 00 / IP 21 / IP 54 VLT type 3011-52: IP 20 /IP54
Enclosure
VLT type 3042-52: IP 20 / IP 54
Vibration test [g] 0.7
Relative humidity [%] VDE 0160 5.2.1.2.
[C] -10 +40 -10 +45/40(CT/VT)
Ambient temperature at full load2) at full load2)
(to VDE 0160) [C] -25 +65/70 -25 +65/70
in storage/transport in storage/transport
Frequency converter protection Protection against earthing and short-circuiting
Emission EN 55011, EN 55014
EMC standards
Immunity EN 50082-2, IEC 1000-4-2, IEC 1000-4-3, IEC 1000-4-4,
(See section EMC test results)
IEC 1000-4-5, VDE 0160, ENV 50140, ENV 50141
1) Semi-conductor fuses.
2) In the range -10 to 0C, the equipment can start and run; however, the display values and certain operating characteristics will not fulfil the specifications.
According to international VDE and UL/CSA requirements VLT type 3060 3075 3100 3125 3150 3200 3250
Constant torque (CT):
Output current IVLT,N [A] 77 96 124 156 180 240 302
IVLT,MAX [A](60s) 116 144 186 234 270 360 453
Output SVLT,N [kVA] 67 83 107 135 156 208 262
SVLT,MAX (60s) [kVA] 100 125 161 203 234 312 392
Typical shaft output PVLT,N [kW] 55 75 90 110 132 160 200
Quadratic torque (VT):
Output current IVLT,N [A] 96 124 156 180 240 302 361
IVLT,MAX [A](60s) 106 136 172 198 264 332 397
Output SVLT,N [kVA] 83 107 135 156 208 262 313
Typical shaft output PVLT,N [kW] 75 90 110 132 160 200 250
Max. cable cross-section [mm2] 70 70 150 150 150 2 x 95 2 x 95
Max. motor cable length [m] 300
Output voltage UM [%] 0-100 of mains voltage
Output frequency fM [Hz] 0-120 or 0-500; programmable
Rated motor voltage UM,N [V] 380/400/415/440/460/500
Rated motor frequency fM,N [Hz] 50/60/87/100
Thermal protection during operation Integrated thermal motor protection (electronic); thermistor
to DIN 44081
Switching on output Unlimited (frequent switching on output may result in fault message)
Ramp times [s] 0.1 - 3600
VLT type 3060 3075 3100 3125 3150 3200 3250
Input current IL,N [A] 75.8 94.4 123.4 155.3 177.1 238.9 307.6
IL,MAX (60s)[A] 113.7 141.6 185.1 233.0 265.7 358.4 461.4
Quadratic load IL,N [A] 94.4 123.4 155.3 177.1 238.9 307.6 359.3
IL,MAX (60s)[A] 106.0 136.0 172.0 198.0 264.0 332.0 397.0
Max. cable cross-section [mm2] 120.0 120.0 2 x 120 2 x 120 2 x 120 2 x 240 2 x 240
Max. pre-fuses1) [A] 150.0 150.0 250.0 250.0 300.0 450.0 500.0
Supply voltage (VDE 0160) [V] 3 x 380/400/415/440/460/500 10%
Supply frequency [Hz] 50/60
Power factor / cos. 1 0.9/1.0
Efficiency 0.96 at 100% load
Switching on input times/min. 1
VLT type 3060 3075 3100 3125 3150 3200 3250
IP 21 147 147 211 211 220 306 306
Weight (kg)
IP 54 147 147 211 211 220 306 306
Front 423 529 713 910 1091 1503 1812
Power loss at max. load CT [W]
Heat sink 859 1074 1447 1847 2216 3051 3679
Front 529 713 910 1091 1503 1812 2209
Power loss at max. load VT [W]
Heat sink 1074 1447 1847 2216 3051 3679 4485
Enclosure IP 21 / IP 54, NEMA 1/12
Vibration test [g] 0.7
Relative humidity [%] VDE 0160 5.2.1.2.
Ambient temperature [C] -10 +40 at full load2) (VT) -10 +45 (CT)2)
(to VDE 0160) [C] -30/25 +65/70 in storage/transport
Frequency converter protection Jord- og kortslutningssikker
EMC standards Emission EN 55011, EN 55014
(See section EMC test results) Immunitet EN 50082-2, IEC 1000-4-2, IEC 1000-4-3, IEC 1000-4-4,
IEC 1000-4-5 VDE 0160
IP 00
220 volt
VLT type 3002-3004 With brake
A (mm) 300 440
B (mm) 281 281
C (mm) 178 178
D (mm) 55 55
a (mm) 191 330
b (mm) 258 258
above/below (mm) 150 150
left/right (mm) 0 0
IP 20
220 volt
VLT type 3006-3008 3011 3016-3022
A (mm) 660 780 950
B (mm) 242 242 308
C (mm) 260 260 296
a (mm) 640 760 930
b (mm) 200 200 270
above/below (mm) 200 200 200
left/right (mm) 0 0 0
IP 21
220 volt
VLT type 3002-03 With brake 3004 With brake RFI module
Options Brake module
A (mm) 360 500 390 530
B (mm) 281 281 281 281 A (mm) 115
C (mm) 178 178 178 178 B (mm) 281
D (mm) 85 85 85 85 C (mm) 178
a (mm) 191 330 191 330 D (mm) -
b (mm) 258 258 258 258 a (mm) 57.5
above/below (mm) 150 150 150 150 b (mm) 258
left/right (mm) 0 0 0 0 above/below (mm) 150
left/right (mm) 0
380 / 500 volt
VLT type 3002-04 With brake 3006 With brake 3008 With brake
A (mm) 360 500 500 610 530 640
B (mm) 281 281 281 281 281 281
C (mm) 178 178 178 178 178 178
D (mm) 85 85 85 85 85 85
a (mm) 191 330 330 440 330 440
b (mm) 258 258 258 258 258 258
above/below (mm) 150 150 150 150 150 150
left/right (mm) 0 0 0 0 0 0
IP 54
220 volt
VLT type 3002-04 With brake 3006-11 3016-22
A (mm) 530 530 810 940
B (mm) 281 281 355 400
C (mm) 178 178 280 280
D (mm) 85 85 70 70
a (mm) 330 330 560 690
b (mm) 258 258 330 375
above/below (mm) 150 150 150 150
left/right (mm) 0 0 0 0
IP 21 / IP 54
Control:
Controls
Terminal 29 / par. 405 Jogging Freeze jogging Freeze reference Digital reference Ramp selection
= Factory setting.
*) Must be with break contact function (NCL), since the function is activated at 0 V on the input.
**) Choose the thermistor function if terminal 50 (10 V D.C.) and terminal 16 (parameter 400) are connected.
***) Terminal 19 is pulse start revers if terminal 18 is set to pulse start
Connection examples
The following shows 8 different connection examples with relevant programming suggestions
Example 1:
Connection examples
Example 2:
Example 3:
Example 4:
Example 5:
Example 6:
Example 7:
Activation of
PID regulator 101 closed loop
Example 7:
Activation of
PID regulator 101 closed loop
The VLT 3000 Series can be installed with flanges side by side
VLT 3060-3250 VLT 3060-3150 is supplied with a mount- VLT 3060-3075 is only for wall
ing console placed behind the VLT. This installation.
console also serves as an air channel for VLT 3100-3150 is supplied for wall
the cooling ribs, and on operation the installation as standard.
console must be mounted on the VLT.
The console does not have to be disman-
tled for installation, but it can be removed
temporarily by loosening the connecting
bolts from the inside of the VLT.
Remember to attach the console again.
Otherwise there is great danger of cut-out
due to overheating.
The 4 drop-shaped holes in the mounting
console make it possible to attach the
fixing bolts to the wall or in the panel
before suspension of the VLT.
The fixing bolts will be accessible through
the top and bottom of the console to
facilitate tightening.
The bases for VLT and options have been previous versions of VLT 3100-3250
updated to match VLT 3100-3250 with units, but never use the previous base
the removable plate in the bottom. Note design for the VLT units with the remov-
that the ventilation slots have been re- able base plate.
placed with two apertures in the sides.
When a base is also used for the mounting
console and RFI in IP 54 enclosure, Base seen from side:
remember to match up the ventilation
apertures.
The new base design can be used with
Base:
A [mm] 76 100
a [mm] 23 10
A [mm] 79 102
a [mm] 23 10
Cable access: VLT types 3002-3008, 400/500 V, and It is recommended that the cables be lead
VLT 3002-3004, 200 V, with IP 54 en- through the base, but the sides can also
closure have a plastic base with holes be used.
marked for cable unions.
The plate in the right-hand side of the
Note that for the above VLTs for 200 V VLT enclosure can be removed, and the
and 500 V (UL-approved) a metallic hole can be used for cable lead-through if
bonding plate is included in the plastic an extra enclosure or an IP 54 RFI module
base. The metal plate is used to terminate is required. If one of these modules is to
cable conductor or armouring. See the be used, the right-hand side of the VLT
information on p. 148 concerning connec- enclosure may not be bored for other
tion of the bonding plate when IP 00 VLTs cables.
are converted to IP 21 enclosure with UL
approval. The VLT enclosure is made of steel. To
avoid metal flakes flying into the VLTs
The cable unions mechanically support the electronics, cable holes should not be
cables for IP 21/54 enclosure. For the bored until the unit has been vertically
IP 00 version, the cables must be relieved installed.
by other means (cable stirrups). The
cables end in removable plugs. The drawing below shows the VLT types
3060-3250 seen from the bottom with the
VLT 3011-3052, 400/500 V, and VLT removable base plate.
3006-3022, 200 V, have a metal base with
cut-outs for cable lead-through.
Cooling To enable the VLT to get rid of the See the dimensioning tables.
cooling air, there must be a free air space The following applies to VLT types 3002-
both above and below the VLT. The 3052:
minimum spacing requirements depend
on the VLT type and enclosure.
Model 3002-3052
Enclosure grade A
IP 00 100 mm
IP 21 100 mm
IP 20 200 mm
IP 54 150 mm
Model A B
3100-3150 230 130
3200-3250 260 130
Heat emission from The tables on pp. 25-29 show the output
the VLT 3000 loss P2(W) from the VLT 3000. The
maximum cooling air temperature tIN,MAX is
40 C at 100% load (of rated value).
1. Add up the values of P for all the 3. Calculate the necessary quantity of air
VLTs to be installed in the same panel. in m3/h =
The highest cooling air temperature (tIN)
Px 3.1
occurring must be lower than tIN,MAX Insert t in Kelvin
(40 C). t
The day/night average must be 5 C
lower (VDE 160). The outlet from the fan must be located
above the highest mounted frequency
The outlet temperature of the cooling air converter.
may not exceed: tOUT,MAX (45 C). Remember to take pressure drops over
2. Calculate the permitted temperature filters into account and that the pressure
difference between the cooling air decreases as the filters are choked.
temperature (tIN) and the cooling air
outlet temperature (tOUT): t = 45 C-tIN
Warning The VLTs voltage is dangerous when it is Incorrect installation of the motor or VLT
connected to the mains supply and for up can damage equipment and cause
to 14 minutes after disconnection of the serious injury or death. Therefore comply
VLT. Electrical installation may therefore with the instructions in this manual, as
only be carried out by an authorized techni- well as local and national safety regula-
cian. tions.
Note:
It is the responsibility of the user or
technician to ensure correct earthing and
protection according to current local and
national standards.
Pre-fuses For VLT types 3002-3052, external pre- For VLT types 3032-3052, 230 V, and
fuses must be installed in the current VLT types 3060-3250, pre-fuses are
supply to the frequency converter. included in the VLTs mains connection.
The technical data section on pp. 23-27
states correct size and dimensioning.
High voltage test A high voltage test can be performed by The resistors is placed between +D.C. bus
short-circuiting terminals U, V, W, L1, L2, to the chassis and -D.C. bus to the chas-
L3, and impressing 2.5 kW D.C. for 1 sis, for a few seconds.
second between this short circuit and the
chassis.
After the high voltage test, the filter con-
densers should be discharged using a
resistor of e.g. 100 ohm, 1/4 W- 1/2 W.
*) Note: With the above fuses, VLT types 3060-3075 have a short-circuiting capacity of
100,000 A.
*) Note: With the above fuses, VLT types 3100-3150 have a short-circuiting capacity of
100,000 A.
*) Note: With the above fuses, VLT types 3100-3150 have a short-circuiting capacity of
100,000 A.
What is CE-labelling? The purpose of CE-labelling is to avoid relevant EU directives. The CE-label says
technical obstacles to trade within EFTA nothing about the quality or specifications
and the EU. The EU has introduced the of a product. Three EU directives relate to
CE-label as a simple way of showing frequency converters:
whether a product complies with the
Danfoss VLT CE-labelling is a positive feature when The CE-label also applies to the EMC
frequency converter used for it original purpose, i.e. to facilitate directive on the condition that the EMC-
and CE-labelling trade within the EU and EFTA. correct installation and filtering in-
structions in the manual have been
followed. On this basis a conformity
However, CE-labelling may cover many declaration is issued in accordance with
different specifications. This means that it the EMC directive.
has to be checked what a given CE-label
specifically covers.
To help ensure that your installation is
EMC-correct, the manual provides de-
The specifications covered can in fact be tailed instructions for installation. Further-
widely different. That is why the CE-label more, we specify which norms that are
can give installers a false feeling of secu- complied with by our products.
rity when using a frequency converter as a
component in a system or an appliance.
We offer the filters that meet the specifica-
tions and can gladly provide other types of
We CE-label our VLT frequency convert- assistance that can help you obtain the
ers in accordance with the low-voltage best possible EMC result.
directive. This means that as long as the
frequency converter is installed correctly,
we guarantee that it complies with the
low-voltage directive. We issue a declara-
tion of conformity confirming that our CE-
label complies with the low-voltage direc-
tive.
Compliance with EMC In support of our claim that the VLT In most cases the VLT frequency con-
directive 89/336/EEC frequency converter complies with the verter is used by professionals of the trade
protection requirements for emission and as a complex component forming part of a
immunity under EMC directive 89/336/ larger appliance, system or installation. It
EEC, a Technical Construction File (TCF) must be noted that the responsibility for
has been prepared for each model. Such the final EMC properties of the appliance,
a file defines the EMC requirements and system or installation rests with the fitter.
the measurements made in accordance As an aid to the fitter, Danfoss has pre-
with harmonised EMC standards in a pared EMC installation guidelines for the
Power Drive System (PDS) that consists of Power Drive System. The standards and
a VLT frequency converter, a control testing levels stated for the Power Drive
cable and the controls (control box), motor System are complied with, provided that
cable and motor plus any options added. the EMC-correct installation guidelines are
The Technical Construction File is pre- applied.
pared on this basis in cooperation with an
authorised EMC laboratory (Competent
Body).
Earthing The following basic issues need to be for example, has a lower HF impedance
considered when installing a frequency than a round conductor for the same
converter, so as to obtain electromagnetic conductor square value.
compatibility (EMC). If more than one appliance is installed in
cabinets, the cabinet rear plate, which
Safety earthing: must be made of metal, should be used as
a common earth reference plate. The
Please note: The frequency converter has
metal cabinets of the different appliances
a high leakage current and must be
are mounted on the cabinet rear plate
earthed appropriately for safety reasons.
using the lowest possible HF impedance.
Apply local safety regulations.
This avoids having different HF voltages
for the individual appliances and avoids
High-frequency earthing: the risk of radio interference currents
Keep the earth wire connections as short running in connection cables that may be
as possible. used between the appliances.
In order to obtain a low HF impedance,
Connect the different earth systems at the use the fastening bolts of the appliances
lowest possible conductor impedance. as HF connection to the rear plate. It is
The lowest possible conductor impedance necessary to remove insulating paint or
is obtained by keeping the conductor as similar from the fastening points.
short as possible and by using the great-
est possible surface area. A flat conductor,
The control cable and the filtered mains necessary distance depends on the sensi-
Cables tivity of the installation and the signal
cable should be installed separately from
the motor and brake cables to prevent cables, and that therefore no precise
interference coupling. Normally, a distance values can be stated.
of 20 cm will be sufficient, but it is recom-
mended to keep the greatest possible If cable clamps are used, sensitive signal
distance wherever possible, especially cables are not to be placed in the same
where cables are installed in parallel over a cable clamps as the motor cable or brake
substantial distance. (Seperation should cable.
increase in proportion).
If signal cables are to cross power cables,
With respect to sensitive signal cables, this should be done at an angle of 90
such as telephone cables and data cables, degrees.
the greatest possible distance is recom-
mended with a minimum of 1 m per 5 m of Remember that all noisy in- or outgoing
power cable (mains, motor and brake cables to/from a cabinet should be
cable). It must be pointed out that the screened or filtered.
Screened cables The screen must be a low HF-impedance Screen armour intended for mechanical
screem. This is ensured by using a braided protection, for example, is not suitable for
screen of cobber, aluminium or iron. an EMC-correct installation.
Radio interference Electrical interference from the cable The screen reduces the radiated inter-
in general network, cable-borne interference, 150 ference, but increases the low frequency
kHz-30 MHz, and airborne interference interference on the mains. With a mains
from the drive system, 30 MHz-1 GHz, is filter, the interference level on the mains
for frequencies under approx. 50 MHz will be reduced to around the same level
produced in particular by the inverter, the for both screened and unscreened cables.
motor cable and the motor system.
The motor cable screen must be con-
As the sketch below shows, capacitive nected to the VLTs enclosure as well as
currents in the motor cable together with the motor enclosure. The best way to do
high du/dt from the motor voltage will this is to use screen clamps to avoid unr
produce interference. ravelled screen ends. These increase the
screen impedance at higher frequencies,
Use of screened motor cable increases which reduces the screen effect and
the leakage current I, (see fig. below). This increases the interference current (I4).
is because screened cables have higher
capacitance to earth than unscreened When screened cable is used for
cables. If the leakage current is not fil- PROFIBUS, control cable, signal interface
tered, it will cause greater interference on and brake, the screen must be mounted on
the mains in the radio leakage range under the enclosure at both ends. In certain
approx. 5 MHz. Since the leakage current situations, however, it will be necessary to
I1 is carried back to units through the break the screen to avoid current loops.
screen (I4), in principle this will give only a
small electromagnetic field from the
screened motor cable, according to the
figure below.
In cases where the screen must be placed must be installed when using unscreened
on a mounting panel for the VLT fre- cables.
quency converter, the mounting panel In order the reduce the interference level
must be of metal because the screen from the system overall (unit + installation)
currents must be led back to the unit. It is as far as possible, it is important to make
also important to ensure good electrical motor and brake cables as short as
contact from the mounting screws through possible.
the mounting curve to the VLT frequency
Cables with a sensitive signal level may
converter.
not be led together with motor and brake
With regard to installation, it is generally cables.
less complicated to use unscreened
Radio interference higher than 50 MHz
cables than screened cables. To observe
(airborne) will be particularly affected by
the EN55011-1A requirements to radiated
the control electronics.
interference (30MHz-1GHz) a motor filter
Motor cable In order to comply with the EMC specifi- screen should basically not be broken and
cations concerning emission and immu- not be earthed in the process. If it be-
nity, the motor cable must be screened comes necessary to break the screen to
unless otherwise stated for the mains filter install a motor isolator or motor relays, the
in question. It is important to keep the screen should be continued at the lowest
motor cable as short as possible so as to possible HF impedance.
reduce the interference level and the
leakage currents to a minimum.
Using filters 175H7083 and 175H7084, the
VLT 3002-3008 complies with EN55011-
The motor cable screen should be con- 1A using an unscreened motor cable. In
nected to the metal cabinet of the fre- addition to reducing the mains interfer-
quency converter and to the metal casing ence, the filters also reduce the interfer-
of the motor. Screen connections should ence radiating from the unscreened motor
be made using as large a surface as cable. As far as the motor cable is con-
possible. (See the instructions for installa- cerned, only interference above 30MHz is
tion, pp. 57-59, item D). The motor cable reduced (see EN55011-1A).
Brake cables If a brake module is used, the cable to the special union. In the case of VLT 3060 -
brake resistor must be screened. In the VLT 3250, where the brake module is a
case of VLT 3002 - VLT 3008, connect the separate module in its own casing, it is
screen to the conductive rear plate, on possible to use special unions or to
which the VLT frequency converter has terminate the screen in the conventional
been mounted. If VLT 3011 - VLT 3052 are way. All sizes of unit require the screen to
used, mount the screen by means of a be connected to the brake resistor
casing.
Control cables Control cables should be screened. The In connection with very long control cables
screen should be connected using a and analogue signals, 50 Hz ripple loops
clamp to the VLT frequency converter may occur in rare cases, depending on the
base (see the instructions for installation, installation. This is because of interference
pp. 57-59, item C). Normally, the screen coupling from the mains supply cables. In
should also be connected to the base of this connection it can be necessary to
the controlling appliance (follow the break the screen or possible insert a 100 nF
instructions for use of the appliance in condenser between screen and base.
question).
Cable for serial The cable for serial communication should With regard to cable specifications and
communication be screened. instructions for installation in general,
The screen should be installed using a reference is made to the PROFIBUS
clamp on the VLT frequency converter product manual.
(see the instructions for installation, pp. 57-
59, item B).
Equalising currents Efforts should be made to avoid possible trolling appliance. They can be avoided by
equalising currents that may occur when making a tight fit with the cabinet base
the control cable screen is connected to rear plate, thereby ensuring that any
the base (earthed) at both ends. Equalising equalising currents will run via the base
currents occur because of voltage differ- rear plates and their joints, not via the
ences between the VLT frequency cable screens.
converter base and the base of the con-
VLT 3002-3008
VLT 3011-3052
VLT 3060-3250
VLT 3100-3150
VLT 3200-3250
Fwd.
Rev. Power kW
Note: For safety reasons the key can only Power HP
be activated when the frequency converter Energy kWh
is set for local operation (parameter 003), Motor voltage V
and the functions and must be se- D.C. voltage V
Jog Fwd.
Rev.
time.
Different modes, The display will give you different infor- See the list of status, reset and alarm mes-
different information mation, depending on the mode and the sages on page 122.
operation setting.
See the list of parameters on pages
151-152.
DISPLAY MODE
SELECTED DISPLAY READ-OUT, including unit
PARAMETER MODE
DATA MODE
ALARM MODE
ALARM
RESET MODE TRIPPED
REASON FOR ALARM OVERVOLTAGE
General Initialization is used to return to a known behaving strangely and cannot be reset in
initial status (factory setting). the normal way.
This requirement arises on change of
software version, if so many of the para- Fundamentally, initialization takes place in
meters have been changed that the two ways:
situation is no longer clear, or if the VLT is
Manual initialization (Press the keys MENU + DATA + JOG Reset of operation data (para. 600) and
simultaneously with mains connection until fault memory (para. 602)
init eeprom is shown in the third line).
Initialization of all other parameters as de-
This method is used on: scribed under initialization via parameter
604
Replacement of software version.
Standard
(RS 485) 500 Address
501 Baud Rate
Time out The software automatically leaves DATA Local reference (parameter 004) is not left
MODE after 20 seconds if no operation is automatically after 20 seconds.
recorded.
By pressing once, it is possible to
Data
Menu build-up The frequency converter has a menu sys- Parameter grouping
tem with several parameters to be used to 0.. Operation and display 000-099
optimise your motor operation. 1.. Load and motor 100-199
The parameters are divided into 7 groups 2.. References and limits 200-299
(group 0 - group 6). 3.. Functions and timers 300-399
4.. Inputs and outputs 400-499
5.. Serial data interface 500-599
There are also groups for different options.
They are described in guidelines for each 6.. Service and diagnosis 600-699
option.
Parameter The parameter number is made up of three Within each group the parameters are
numbering digits. numbered, starting with 0.
The digit on the left indicates the group. For example, in group 1..: 100, 101, 102....
Travelling through After the first power-up you will find the Changing a parameter number
the menu frequency converter in DISPLAY MODE. You can enter the parameters of the
selected group with the key followed
Menu
Changing group by + or .
If you want to travel through the menu, use
the key followed by the keys + or
Menu + increases and decreases the
(see page 61). parameter number.
Data value of a When you have chosen a parameter and The data value can be a digit or a text.
parameter want to change its data value, press the
key followed by the + or key.
Data
Changing a data value: When you have pressed the digit to the
Data A new data value is stored on leaving
digit right will be active and be shown flashing. DATA MODE, or automatically after 20
The other digits can be activated one by seconds.
one by pressing one, two or three times.
Data Please note: You have to press to stop
Stop
Reset
The activated digit can be changed by the motor before changing the data values
pressing + or . of some parameters (see factory settings).
Changing a data value: If the data value of the chosen parameter Please note: You have to press to stop
Stop
Reset
text is a text, the display shows the selected the motor before changing the data values
text.This can be changed by pressing Data of some parameters (see factory settings).
and then + or . All options are then
shown one by one. The text shown in the
display will be stored at the same moment
you leave DATA MODE.
Leaving DATA mode You are storing the data value by pressing
Menu. Now you have activated the para-
meter number and can travel through the
group of parameters again using + and .
Operation and display In this group you will find parameters Note: The choice between the 12 different
Group 0.. concerning the display read-out, local display read-outs mentioned on page 60 is
operation and setup handling. not an element of this group.
Note:
The drive should be started / stopped
repeatedly to ensure stability.
Introduction The brake control for the electromechani- The motor current monitoring features a
cal brake features functions which among function which automatically activates the
other things improve positioning. brake when the motor current drops to or
below the programmed minimum value.
Brake control The brake control features an optimized It is possible to override motor current
relay function with a short reaction time, to monitoring during start-up. How long it is
control the electromechanical brake. to be inactive depends on the delay
The brake must be active (without voltage) setting.
while the unit is running idle. Relay 01/04
can be programmed so that the motor To achieve high dynamics, start compen-
brake is released automatically when the sation is deselected in parameter 100.
programmed motor frequency is exceeded.
It is possible to set separate ramp-up The parameters for brake control are
(start) and ramp-down (stop), cut-out and described below:
cut-in frequencies.
Para. 100 Data value [6]
Para. 230-231-
232-233 See drawing below
Para. 409/410 Data value [16][17]
Start/Stop
Frequency/Current
Relay
References and limits The VLT frequency converter distin- programmed in group 4...
Group 2.. guishes between different types of refer- Unused references are set at 0, or
ences. switched out (parameters 205-208, 412-
Note that the analogue reference type is 413).
Analogue reference
(parameter 411) 1. Linear between min. and max. Data [0]
2 . Proportional to reference with min.
and max. limitation. Data [1]
3. Proportional to reference with reversing.
Data [2]
Functions and timers, This group includes a parameter called This function tells the frequency converter
Group 3.. flying start. how to handle a motor with a rotating
shaft.
: Flying start
: Normal start
: Dont care
Inputs and outputs Group 4.. is used to program other The analogue output signals and the
Group 4.. configurations of the terminals than the relays can be used for different types of
default configuration. indication.
See the configuration of the digital input See parameters 407 and 408.
signals on page 32.
Serial data interface The serial bus communicates using RS stop bit (logically 1). There is no parity
Group 5.. 485 (terminals 68 and 69). It is possible to check. Set the baud rate (speed of trans-
read and set the parameters of the VLT mission) in parameter 501 and the ad-
frequency converter, and to give it refer- dress of each unit in parameter 500.
ence and control commands. The serial port
can be used by up to 31 VLT Telegram format / protocol
frequency converters per master without us- The communication protocol for the VLT
ing a repeater. If 3 repeaters are used, 3000 Series consists of a 22-byte telegram
up to 99 VLT frequency converters can be using ASCII characters. These characters
connec-ted to one master. make it possible to operate, set and read
parameters, and to receive status feed-
It is important to connect and terminate the back from the VLT
serial bus with the correct impedance to frequency converter.
avoid any reflections which may disturb the Communication takes place in the following
cables data transmission. way: The master sends a telegram to a
VLT frequency converter. Then the master
This adjustment can take place by setting awaits a reply from that frequency con-
the 03.1 and 03.2 switches in the on posi- verter before sending a new message.
tion (see p. 148) in the last VLT frequency The reply to the master is a copy of the
converter connected to the serial BUS. telegram sent by the master, now
containing any updated data values and
Communication takes place by means of a the status of the VLT frequency converter.
protocol specified by Danfoss.
The data format consists of 10 bits: one
start bit (logically 0), eight data bits, and one
Continued...
MG.30.A7.02 - VLT is a registered Danfoss trademark 73
Group description
Byte 19 =2
Serial data interface, Control words, bytes 5-8 in the telegram According to the data format, 1 byte
group 5.. (continued) The control word is used to send control consists of 8 data bits, but in the control
commands from a master (e.g. a PC) to word only the 4 least significant bits of
the VLT frequency converter. each byte are used, so that ASCII charac-
ters from A to 0 can be used. The table
below shows the significance of the indi-
vidual bits of the control word:
Control word
Byte 8 Byte 7 Byte 6 Byte 5
N S S N N D J J N R H Q F O O O
O E E O O A O O O A O U R F F F
L L T G G M L I E F F F
F E E F F A F P D C E
U C C U U 2 1 U K W 3 2 1
C T T C C N C S R H
T T T O O O T T A S E / / /
T S S T T T F F T O M T E
I E E I I F F I P P O L O O O
0 O T T O O V O P N N N
N - - N N A / / N / P
U U L O R P 3 2 1
ASCII / P
/ P / / I O O / S S A O
D N N T S M S
1 R 2 1 C S R A I P S.
E A L / E R B
V T O S T L
E C W V E E
R H A T
S - D L
I U O I
N P W D
G N
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
@ 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
A 0 0 0 1 0 0 0 1 0 0 0 1 0 0 0 1
B 0 0 1 0 0 0 1 0 0 0 1 0 0 0 1 0
C 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1
D 0 1 0 0 0 1 0 0 0 1 0 0 0 1 0 0
E 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1
F 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0
G 0 1 1 1 0 1 1 1 0 1 1 1 0 1 1 1
H 1 0 0 0 1 0 0 0 1 0 0 0 1 0 0 0
I 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1
J 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0
K 1 0 1 1 1 0 1 1 1 0 1 1 1 0 1 1
L 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0
M 1 1 0 1 1 1 0 1 1 1 0 1 1 1 0 1
N 1 1 1 0 1 1 1 0 1 1 1 0 1 1 1 0
O 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
P X X X X X X X X X X X X X X X X
X = Dont care, if P is used in a group of 4 bits, current status is retained. Only the groups with the characters in P are
activated. Bit 10 = 0 signifies no change from current status.
Serial data interface, The function of bit 04 can be redefined to nect the control word if it is not to be used
group 5.. D.C. brake in parameter 514. Otherwise in connection with updating or reading of
(continued) the function is as described above. Note: In parameters.
parameter 504/505 it is selected how bit 04 Bit 11, No function/slow down:
is connected (gates) with the equivalent Used to reduce the speed reference with
function on the digital inputs. the value in parameter 513. Bit 11 = 0
means no change of reference, bit 11 = 1
Bit 05, Hold/ramp possible:
means that the reference is reduced. The
Ordinary ramp stop which uses the ramp
function of bit 11 and 12 can be rede-fined
time in parameter 215/216. Bit 05 = 0
to selection of digital reference in param-
means stop, bit 05 = 1 means that the
eter 515, according to the following table:
frequency converter can start if the other
start conditions are fulfilled.
Bit 06, Ramp stop/start: Digital reference/ Bit 14 Bit 13
parameter
Ordinary ramp stop which uses the ramp
1/205 0 0
time in parameter 215/216. Bit 06 = 0
2/206 0 1
means stop, bit 06 = 1 means that the
3/207 1 0
frequency converter can start if the other
4/208 1 1
start conditions are fulfilled. Note: In para-
meter 506 it is selected how bit 06 is con-
Note: In parameter 510 it is selected how
nected (gates) with the equivalent function
bit 11/12 is connected (gates) with the
on the digital inputs.
equivalent function on the digital inputs.
Bit 07, No function/reset:
Reset of trip. Bit 07 = 0 means no reset, Bit 12, no function/catch up:
bit 07 = 1 means reset of a trip. Note: In Used to increase a speed reference with
parameter 508 it is selected how bit 07 is the value in parameter 513. Bit 12 = 0
connected (gates) with the equivalent gives no chance of reference, bit 12 = 1
function on the digital inputs. increases the reference. If both slow-down
and catch-up are activated (bit 11 and 12 =
Bit 08, JOG 1 OFF/ON:
1), slow-down has highest priority,
Activation of preprogrammed speed in
i.e. the speed reference is reduced. The
parameter 511 (Bus JOG 1). JOG 1 is only
function of bit 11 and 12 can be redifined to
possible when bit 04 = 0 and bit 00-03
selection of digital reference, see
= 1.
description of bit 11 above.
Bit 09, JOG 2 OFF/ON:
Activation of preprogrammed speed in Bit 13/14, selection of setup:
parameter 512 (Bus JOG 2). JOG 2 is only Bit 13 and 14 are used to select between
possible when bit 04 = 0 and bit 00-03 = four menu setups according to the follow-
1. If both JOG 1 and JOG 2 are activated ing table:
(bit 08 and 09 = 1), JOG has highest prio- Setup Bit 14 Bit 13
rity, i.e. the speed programmed in parame- 1 0 0
ter 511 is used. 2 0 1
3 1 0
Bit 10, Data not valid/valid: 4 1 1
Used to tell the VLT frequency converter The function is only possible when multi
whether the control word must be used or setup is selected in parameter 001.
ignored. Bit 10 = 0 means that the control
word is ignored. Bit 10 = 1 means that the Note: In parameter 509 it is selected how
control word is used. This function is rel- bit 13/14 are connected (gates) with the
evant because the control word is always equivalent function on the digital
contained in the telegram, no matter which inputs.
telegram type is used (see byte 4 in tel-
egram format), i.e. it is possible to discon-
Serial data interface, Bit 15, No function/reversing: bit 15 only means reversing when bus,
group 5.. (continued) Reversing of the motors speed direction. logical or or logical and (logical and, how-
Bit 15 = 0 means no reversing, ever, only with terminal 19) is selected.
bit 15 = 1 means reversing.
Note that as starting point reversing is
selected to digital in parameter 507,
Example:
The following code word can be used to
give the VLT frequency converter the
start command:
Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
0/1 0 0 0 0 0 1 0 0 0 1 1 1 1 1 1 1
ASCII @ D G O
Status word, bytes 5-8 in the telegram located in bytes 5-8 of the response
The status word is used to inform the mas- telegram from the VLT frequency
ter (e.g. a PC) of the VLT frequency con- converter to the master.
verters status. The status word is The table below shows the significance of
the individual bits of the status word:
Status word
Byte 8 Byte 7 Byte 6 Byte 5
T C V V N O L N N S O O N N V C
I U O L O U O O O T N N O O L O
M R L T T T C T A T T N
E R T O A W R 3 2 F T
R E A O R F L O A T / / A E N R
S N G K U N R o O U N O O
T E / N O O N P F F L A T L
O S N P P R I O F F T B
K O O T I E E E N S / L R N
R
/ K K A N A R F G S 3 2 T E E O
O / / L G T A / / I R D A T
V O O L / I T O W B I / D
E V V S R O I N A L P E Y R
R E E , U N O R E N / E
R R N N R N / A R A
R
L A N A / E I S B E D
0 I L L U I N B F N T L A Y
M I I T N G U G A E D /
ASCII / I M M O G E S R D Y R
T I I / T E
T T S F C A
1 R
T E O N D
A Q N O Y
R U T T
T E R
N O P
C L O
Y
S
L S
I I
M B
I L
T E
S
O
K
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
@ 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
A 0 0 0 1 0 0 0 1 0 0 0 1 0 0 0 1
B 0 0 1 0 0 0 1 0 0 0 1 0 0 0 1 0
C 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1
D 0 1 0 0 0 1 0 0 0 1 0 0 0 1 0 0
E 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1
F 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0
G 0 1 1 1 0 1 1 1 0 1 1 1 0 1 1 1
H 1 0 0 0 1 0 0 0 1 0 0 0 1 0 0 0
I 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1
J 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0
K 1 0 1 1 1 0 1 1 1 0 1 1 1 0 1 1
L 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0
M 1 1 0 1 1 1 0 1 1 1 0 1 1 1 0 1
N 1 1 1 0 1 1 1 0 1 1 1 0 1 1 1 0
O 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Serial data interface, Bit 00, Control not ready/ready: Bit 08, Speed in ref./speed = ref.:
group 5.. (continued) Bit 00 = 0 means that the control words Bit 08 = 0 means that the motors cur-rent
bit 00, 01 or 02 = 0 (OFF1, OFF2 or speed is different from the set speed
OFF3), or the VLT frequency converter reference. This can e.g. be the case while
has tripped. Bit 00 = 1 means that the the speed is ramped up/down on start/stop.
VLT frequency converter is ready to Bit 08 = 1 means that the motors current
operate when it receives the necessary speed is equal to the set speed reference.
start signals.
Bit 09, Local control/bus control:
Big 01, VLT not ready/ready: Bit 09 = 0 means that the VLT frequen-
Same significance as bit 00. cy converter has stopped with the help of
the stop key on the operating panel, or
Bit 02, Free-wheeling/possible: local or local with external free-wheeling
Bit 02 = 0 means that the control words stop has been selected in parameter 003.
bit 00, 02 or 03 = 0 (OFF1, OFF2 or Bit 09 = 1 means that it is possible to
OFF3 or Free-wheeling), or the VLT control the VLT frequency converter via
frequency converter has tripped. Bit 02 = the serial port.
1 means that the control words bit 00,
01, 02 and 03 = 1, and the VLT fre- Bit 10, Out of range/frequency OK:
quency converter has not tripped. Bit 10 = 0 means that the output frequen-
cy is outside the limits set in parameter 210
Bit 03, No fault/trip: (Warning: Low frequency) and parameter
Bit 03 = 0 means that the VLT frequency 211 (Warning: High frequency). Bit 10 = 1
converter is not in a fault status. Bit 03 = means that the output frequency is within
1 means that the VLT frequency con- the aforementioned limits.
verter has tripped and it requires a reset
signal before it can run. Bit 11, Not running/running:
Bit 11 = 0 means that the motor is not
Bit 04, ON2/OFF2: running. Bit 11 = 1 means that the VLT
Bit 04 = 0 means that the control words frequency converter has a start signal or
bit 01 = 1. the output frequency is greater than 0.5 Hz.
Bit 04 = 1 means that the control words
bit 01 = 0. Bit 12, VLT OK/stalls, auto start:
Bit 12 = 0 means that there is no tem-
Bit 05, ON3/OFF3: porary overload of the inverter. Bit 12 = 1
Bit 05 = 0 means that the control words means that the inverter has stopped due to
bit 02 = 1. overload, but the VLT frequency con-
Bit 05 = 1 means that the control words verter has not tripped and it will continue
bit 02 = 0. when the overload disappears.
Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
0/1 0 0 0 0 1 0 1 1 1 0 0 0 0 1 1 1
ASCII @ K H G
Serial data interface, Response telegram from VLT frequency converter to master (PC or PLC)
group 5.. Function Byte no. ASCII character Decimal value
(continued) Start byte 1 < 60
2 0 48
Address
3 1 49
Control character 4 U 85
5 G 71
6 H 72
Control/status word
7 K 75
8 @ 64
9 0 48
10 5 53
Parameter no.
11 1 49
12 6 54
Sign 13 + 43
14 0 48
15 0 48
Data value 16 0 48
17 8 56
18 0 48
Comma 19 0 48
20 0 48
Check sum
21 7 55
Stop byte 22 > 62
Description of choices:
Remote control is selected for control via
the control terminals or serial port (RS485).
Note:
For both local selections, speed can be
controlled on parameter 004.
= Factory setting. Text in ( ) = Display text.
The figures in [ ] are used in bus communication.
Description of choices:
Preprogrammed contains the factory-set
data and can be used as data source if
the other setups are to be brought to a
known status. The language is always
English.
It is not possible to change data once this
setup has been chosen.
Setup 1-4 is 4 individual setups which can
be used as required. These can be pro-
grammed freely, irrespective of which
setup the VLT is running in.
Setup = Parameter 001 is the preset value
normally used. This function can be
deselected for access to program during
operation in other setups than the VLT is
currently running in.
Note:
The start conditions (terminals 18 and
27) must be present together with a
speed reference (possibly digital ref.
parameter 205-208) so that current limit
control can be used.
Warning:
If the aforementioned conditions exist
when the unit is switched on, the motor
can rotate for up to 5 sec. even though
the current limit setting is 0.
109 Value: You can set the motor voltage below the
Start voltage 0.0 - (UM,N + 10%) field weakening point independently of the
(Start voltage) motor current. Use this parameter to com-
pensate too low starting torque.
If several motors are operating in parallel
the start voltage must normally be raised.
Warning: If the use of start voltage is
overdone it can lead to magnetic
saturation and motor overheating and
the frequency converter may trip out.
Therefore take care when using the
start voltage.
222 Value:
Frequency bypass 4 0 - fRANGE fRANGE
(Freq 4 bypass)
223 Value:
Frequency bypass 0 - 100% 0
band width
(Bypass B. width)
312 Value: Sets the max. time allowed for auto restart
Max. auto restart time 0 - 10 sec. 5 sec. before a final trip, if selected in para. 309.
(Auto restart t)
317 Value:
Relay OFF-delay 0.00 - 10.00 sec. 0.00
(Relay off dela)
= Factory setting. Text in ( ) = Display text.
The figures in [ ] are used in bus communication.
100 MG.30.A7.02 - VLT is a registered Danfoss trademark
Parameter description 4.. Inputs and outputs
ALARM
TRIP
MOTOR TRIP
Reversing
NB:
If the start command (logic 1) is given to
terminals 18 and 19 simultaneously, the
motor is stopped.
No operation:
As para. 402.
Ramp selection:
Different ramp times can be selected using
terminal 29:
Terminal 33 Terminal 32
No reference-
change 0 0
Increase reference 0 1
Reduce reference 1 0
Reduce reference 1 1
Terminal 16, 17 or 29 = 1.
Terminal 32 Terminal 33
Freeze reference (sum) 0 0
Increase reference 0 1
Reduce reference 1 0
Reduce reference 1 1
Index 13/14:
Decimal value between 0 and 1023, where
0 corresponds to 0% and 1023 to 100% of
the selected input signal, e.g. 0-10 V.
Index 15:
Decimal value to be converted to a 16-bit
binary code. Each bit represents a warning
according to the table below. When a
warning is given, the equivalent bit has the
value 1.
Bit Warning
0 Current limit
1 No motor
2 Reference fault
3 Motor overloaded
4 Inverter overloaded
5 Frequency warning low
6 Frequency warning high
7 Current warning low
8 Current warning high
9 EEPROM fault
10 24 V fault
11 Over current
12 Voltage warning high
13 Voltage warning low
14 Overvoltage
15 Undervoltage
Index 16:
Decimal value to be converted to a 16-bit
binary code. Each bit represents a control
command according to the table on p. 75.
When a control command is activated, the
equivalent bit has the value 1.
Index 17:
Decimal value to be converted to a 16-bit
binary code. Each bit represents a status
report according to the table on p. 77.
When a status report is activated, the
equivalent bit has the value 1.
601 0 1 2 3 4 - - 19 Function:
Data log Digital input [0] (Index 000.00-019.06)
(Data log) Control word [1] Logging of data for the last few seconds of
Status word [2] operation.
Reference % [3] Description of choises:
Frequency out [4] Digital inputs stated in hex code (0-FF).
Phase current [5] Control word stated in hex code (0-FFFF)
D.C. voltage [6] for bus operation RS 485, see p. 75.
Status word stated in hex code (0-FFFF)
for bus operation RS 485, see p. 77.
Reference states the control signal as a
percentage (0-100%).
Frequency out states the units output
frequency in Hz (0.0-999.9).
Phase current is the units output current in
A (0.0-999.0).
D.C. voltage states the intermediate circuit
voltage in [VDC] (0-999).
602 0 1 2 3 4 - - 7 Function:
Fault memory Fault code [0] (Index 000.00-007.02)
(Alarm memory) Time [1] Storage of data on trip.
Value [2] Description of choices:
Fault code indicates the reason for a trip by
a figure code between 1 and 15:
Fault code Alarm
1 Inverter fault
2 Overvoltage
3 Undervoltage
4 Over-current
5 Earth fault
6 Excess temperature
7 Inverter overloaded
8 Motor overloaded
9 Current limit
10 Trip locked
11 Control card or option card fault
13 Auto-optimization fault
14 DC suppley fault
15 Thermistor input activated, see
parameter 400/terminal 16
650 Function:
VLT type Used to indicate which unit the control card
(VLT type) is placed in, in cases where the control card
cannot decide for itself, or to select voltage
range in multi-voltage units if the factory
setting deviates from what is required.
Description of choices:
The parameter is used to select the correct
VLT type/size/voltage for VLT types 3060-
3250 and VLT types 3575-3800, which are
multi-voltage units. If the factory-set voltage
does not correspond to the voltage in the
application for which the unit is used, the
following procedure is used.
Status messages Status messages appear in the third line of Ramp operation (RAMPING):
the display, see example below: Remote control has been selected in
parameter 003, and the output frequency
50.0 Hz changes according to the set ramp times.
FREQUENCY
START LOCAL Freeze reference (FREEZE.):
Remote control has been selected in
LOCAL STOP (ENAB STP LOC): parameter 003, freeze reference in
Local or local with external stop has parameter 400, 401 or 405, and the
been selected in parameter 003, and stop respective input (16, 17 or 29) has been
has been activated on the keyboard. activated.
Jogging (JOGGING):
Remote control has been selected in
parameter 003, jogging in parameter 405,
and there is 24 V to terminal 29.
Warnings Warnings appear in the third line of the detects that no motor is connected to the
display, see the example below: VLT frequency converters output.
Frequency warning low
Voltage low (LO FREQ WARN):
The output frequency is lower than the
(VOLTAGE LOW) value in parameter 210.
Overvoltage (OVERVOLTAGE):
The intermediate circuit voltage is above
the inverters overvoltage limit, see table
p. 124. The inverter has stopped, and after
the time in parameter 311 there will be a
trip.
Voltage limits:
3x200/230 V 3x380/415 V 3x440/500 V VLT 3060-3250
VLT 3000 Series [VDC] [VDC] [VDC] [VDC]
Undervoltage 210 400 460 470
Voltage warning low 235 440 510 480
Voltage warning high 370 665 800 790
(Brake option used,
parameter 300) (395) (705) (845) (820)
Overvoltage 410 730 880 850
The voltages stated are the VLTs intermediate circuit voltage, the equivalent mains
voltage is the intermediate circuit voltage divided by 2.
Reset messages Reset messages appear in the second line Trip (TRIP):
of the display, and alarm messages appear The VLT frequency converter has cut out,
in the third line of the display, see example and manual reset is required. Manual reset
below: can be the reset key on the keyboard, a
digital input (terminal 16, 17 or 27) or bit 07
ALARM in the control word (RS485).
TRIP
UNDERVOLTAGE Trip locked (TRIP LOCK):
The VLT frequency converter has cut out
Automatic restart (AUTO START): and can only be reset after the mains
When automatic reset is selected as voltage is switched off. After the mains
reset function, the message states that the voltage is cut back in, manual reset is
VLT frequency converter is trying to required.
restart automatically after cutting out. The Alarm messages
restart time depends on parameter 312.
EXCEPT fault::
EXCEPT
XXXX ERROR
PC=XXXX
TESTING
CONTROL CARD
FAULT_XXXX
The reason for the fault message is a fault
on the control card or possible option card.
Contact Danfoss.
Galvanic isolation The galvanic isolation of the VLT isolation of the signal UDC indicating
(PELV) frequency converter is tested according to the DC link voltage
VDE 0106/0160 (PELV). 2. Gate drivers controlling the IGBT's
(trigger transformers)
Galvanic isolation is present when 3. Current transducers
voltage-flashover between two current (Hall effect current transformers)
circuits is prevented when exposed to a pre-
determined test voltage. Components, as well as the assembled fre-
quency converter, are tested
Galvanic isolation of the VLT frequency- according to VDE 0106/0160. Selected
converter control circuits is achieved by components, e.g. signal transformers,
using signal and power isolation trans- are tested with 3 kV a.c. for 1 second,
formers and leakage paths with a minimum and the assembled frequency converter
width of 10.4 mm. is tested with 2.5 kV d.c and 2.4 kV a.c.
The galvanic isolation can be shown in three On request, Danfoss will provide a test
locations (see drawing below), namely: certificate to confirm that the galvanic
1. Power supply (SMPS) incl. signal isolation is in accordance with
VDE 0106/0160.
Earth leakage current The earth leakage current is primarily Never operate on ELCBs where
caused by the capacitance between con- local regulations do not permit it due to pos-
ductor and the screen of the motor cable. sible DC component in the leakage
When an RFI filter is used this contributes current.
an additional leakage current, as the filter
circuit is connected to earth through Any ELCB relays used must be:
capacitors. Suitable to protect equipment with a
This size of the leakage current to ground direct current element in the earth
depends on the following: current (3-phase bridge rectifier)
Length of motor cable Suitable for power-up with pulsing,
Switching frequency short discharge.
With/without RFI filter Suitable for high discharge current.
Motor earthed on site or not
Motor cable with/without screen
du/dt and When a transistor in the inverter is acti- low du/dt ratio value even with very short
peak voltage vated, the voltage applied to the motor will motor cable.
on motor rise by a du/dt ratio determined by Note:
the motor cable (type, cross-section, When using very small motors without
length, screened/unscreened) phase coil insulation it is recommended to
Inductors mount a clamp filter or an LC-filter in
series after the VLT.
The self-inductance will cause an over- Clamp filter, code no. 175H5147 (fits all
shoot UPEAK in the motor voltage before it units in the VLT types 3002 - 3052).
stabilizes at a level determined by the volt-
age in the intermediate circuit. Typical values for the du/dt ratio and the
Both the du/dt ratio and the peak voltage peak voltage UPEAK measured on the ter-
UPEAK influence the lifetime of the motor. Too minals of the frequency converter between
high values will primarily affect motors with- two phases (30 m screened motor cable):
out phase coil insulation.
With short (few metres) motor cable, the VLT type 3002 - 3052:
du/dt ratio will be very high but the peak du/dt 200 - 300 V/s
voltage very low. At long (100 metres) UPEAK 800 - 1100 V
motor cable du/dt will decrease and UPEAK
will increase. VLT type 3060 - 3250:
To ensure a reasonable lifetime of the du/dt 2000 - 2100 V/s
motor, the VLT 3000 Series has as UPEAK 900 - 950 V measured with
standard built-in motor coils which ensure a 20 m unscreened motor cable
Acoustic noise The acoustic noise from the frequency Below are the typical values measured at a
converter is generated from 3 sources: distance of 1 metre from the unit and at full
1. D.C. (DC link) and AC coils load:
(motor coils).
2. RFI filter (acoustic noise increases
with the length of the motor cable).
3. Built-in fan.
VLT type 3002 3003 3004 3006 3008 3011 3016 3022 3032 3042 3052
IP 00 (dBA) 38 38 38 53 57 - - - - - -
IP 20/21 (dBA) 38 38 38 53 (60) 57 (55) 60 (59) 61 (63) 62 (64) 67 63 67
IP 54 (dBA) 38 59 57 57 (58) 57 (58) 63 (66) 63 (66) 67 (66) 67 66 72
( ): 200 V units
All units with built-in RFI filter and 100 m For VLT 3011-52 the values will decrease
screened motor cable. by approx. 2 dBA for units without RFI filter.
1. VLT 3002-08: IP 00 / IP 54
2. VLT 3002-08: IP 21 mounted with top fan.
VLT 3004 (200 V), 3006 (400 V, VT) and 3008 (400 / 500 V)
has a fan in IP 21 version, following curve 1.
1. VLT 3011-52: IP 20
2. VLT 3011-52: IP 54, VLT 3060-3250: IP 54; VLT 3032-3052, 230 V: IP 21 / IP54
Motor derating for running at low speed teristic for centrifugal pumps/fans. Motors
When a centrifugal pump or fan is con- running constant load torque applications
trolled by the VLT Series 3000 it is not at low speed must be derated or force-
necessary to reduce the output current at cooled (see graph).
low speed because of the load charac-
Derating for higher switching frequencies Derating for higher switching frequencies
Applies only to VLT types 3002-52 as the
maximum switching frequency is 4.5 kHz
set in the VLT types 3060-3250.
A higher switching frequency (para. 224)
results in greater loss and stronger heat
formation in the frequency converters tran-
sistors and motor coils.
The frequency converter therefore auto-
matically derates the maximum permitted
constant output current IVLT,N, when the
switching frequency exceeds 4.5 kHz.
Linear reduction is performed down to 60%
at 14 kHz (see graph).
Derating for installing long motor cables or The VLT 3000 Series is designed to run
larger cable cross-section with a motor cable of a rated cross-section. If
The VLT 3002-3052 is tested with 300 m a cable with a larger cross-section is to be
unscreened cable and 150 m screened used it is recommended to reduce the out-
cable (for types 3002-3004 this only put current by 5% for each step the
applies to fSWITCH 4.5 kHz. At fSWITCH > 4.5 cable cross-section is increased.
kHz, max. 40 m). (Higher cable cross-section gives
increased capacity to earth and thereby in-
creased earth current).
1 1
4.5 kHz yes ye 1, 4
EN55014 1
14 kHz yes ye 1, 4
1, 2 1 1
4.5 kHz yes ye
EN55011 Class A Gr.1 1 1
14 kHz yes ye
1, 3 1, 3
4.5 kHz yes ye 1, 3, 4
EN55011 Class B Gr.1 1, 3
14 kHz yes ye 1, 3, 4
1
Using the RFI option/module
2
Without the RFI option/module the cable borne part of EN55011 class A gr. 1
(150kHz-30MHz) is complied with.
3
Radiated emission (30MHz-1GHz) in accordance with EN55011 class A group 1.
4
Using the brake module, please contact Danfoss.
With the purpose of minimising the cable-borne interference to the mains supply and the
radiated interference from the frequency converter system, the motor cables should be
kept as short as possible. According to experience, most installations represent only a
slight risk of any interference from radiation.
Acceptance criterion B B B A
Port connection CM DM CM
Line OK OK OK - -
Motor OK - - - -
Brake OK - - - -
Control lines OK - OK - -
PROFIBUS option OK - - - -
Enclosure - - - OK OK
Basic specification:
Line 2kV/5kHz/DCN 2kV/2 4kV/12 - - N
Motor 2kV/5kHz/CCC - - - -
Brake 2kV/5kHz/CCC - - - -
8 kV AD
Enclosure - - - 10V
6 kV CD
Acceptance criterion B B B A
Port connection CM DM CM
Line OK OK OK - -
Motor OK - - - -
Brake OK - - - -
Control lines OK - OK - -
PROFIBUS option OK - - - -
Enclosure - - - OK OK
Motor 2kV/5kHz/CCC - - - -
Brake 2kV/5kHz/CCC - - - -
8 kV AD
Enclosure - - - 10V/m
6 kV CD
Acceptance criterion B B B A
Port connection CM DM CM
Line OK OK OK - -
Motor OK - - - -
Control lines OK - OK - -
PROFIBUS option OK - - - -
Enclosure - - - OK OK
Motor 2kV/5Hz/CCC - - - -
8 kV AD
Enclosure - - - 10V/m
6 kV CD
Vibration and shock The VLT 3000 Series is tested according VLT 3002-3008 meet the requirements
to a procedure based on the following equal to conditions when mounted close to
standards: or directly on heavy production equipment.
IEC 68-2-6: Vibration (sinusoidal) - 1970 VLT 3011-3052 meet the requirements
IEC 68-2-34: Random vibration wide equal to conditions when mounted directly
band-general requirement on wall or floor and in panels in factory
IEC 68-2-35: Random vibration wide buildings.
band-reproducibility high
IEC 68-2-36: Random vibration wide
band-reproducibility medium
Air humidity The VLT frequency converter has been The IP 54 versions can tolerate more
designed to meet the IEC 68-2.3 standard. moisture, because less dust and dirt are
The VDE 160, 5.2.1.2./7.2.1/ DIN 40040, deposited on the insulating surfaces, and
class E, 40 C, IP 54, is obtained according the enclosure allows no moisture inside.
to IEC 68-2-30.
Efficiency To reduce energy consumption it is very im- Normally the motor efficiency drops when
portant to optimise the efficiency of a sys- the load is lower than rated torque, com-
tem. The efficiency of each single pared to operation on the mains.
element in the system should be as high
as possible. In the range 75-100% of rated torque the
efficiency of the motor will be almost con-
Efficiency of the VLT 3000 Series (VLT) stant both when operated by the frequency
The load on the frequency converter has converter and when running directly on the
little effect on its efficiency. In general the mains.
efficiency at rated motor frequency fM,N is
the same whether the motor supplies a In general the internal switching frequency
100% rated shaft torque or only 75%. does not affect the efficiency of small
motors. Motors from 11 kW and upwards
The variable switching frequency influ- achieve better efficiency (1-2%). The effi-
ences the losses in the VLT 3000 Series. ciency is improved, because the sine shape
The efficiency will drop a little when the of the motor current is near perfect at high
switching frequency is set to a value higher switching frequency.
than 4.5 kHz.
System efficiency (SYSTEM)
Efficiency of the motor (MOTOR) To calculate the system efficiency you can
The efficiency of a motor connected to the multiply the efficiency of the units of the
frequency converter is dependent on the VLT 3000 Series (VLT) by the efficiency of
sine shape of the current. In general we can the motor (MOTOR):
say that efficiency is just as good as at SYSTEM = VLT x MOTOR
mains operation. The motor efficien-cy de-
pends on the make of the motor.
Harmonic currents compared to the RMS The voltage distortion of the mains supply
input current: depends on the size of the harmonic
currents multiplied by the internal imped-
Input current ance for the relevant frequency.
IRMS 1.0
The total voltage distortion THD is calcu-
I1 0.9
lated on the individual voltage harmonics
I5 0.4
according to the following formula:
I7 0.2
I11-49 < 0.1 THD% = U1 + U5+ ..... UN (UN% of U)
The value of I1 is equivalent to the power
factor.
Power factor The power factor is the ratio between Furthermore, a high power factor indicates
power (kW) and total (kVA). that the different harmonic currents are low.
Power factor for 3-phased supply
3 x V x I1 x cos1 IRMS = I 1 2 + I 5 2 + I 7 2 + . . . + In 2
=
3 x V x IRMS
I1 x cos1
Power factor =
IRMS
I1
cos1 1 power factor
IRMS
Ground fault
Ground failure on the VLT frequency con-
verter output. Another reason might be that
the motor cable is too long.
Consult the data sheets for permitted
cable length.
Check the motor and the motor cable
for earth leakage.
Electrostatic discharge Important! Many electronic components It is therefore important to take static
(ESD) are sensitive to static electricity. Even electricity into account when servicing elec-
voltages so low that they cannot be felt, tronic equipment.
seen or heard can impair components or
damage them completely. When performing field service on Danfoss
VLT frequency converters the following
Electronic discharge can, among other precautions must be taken:
things, result in the following: A portable ESD field service kit
consisting of a wrist strap and a
Drastic reduction in component conductive mat must be used.
operating life The portable ESD field service kit must
Periodic faults - as a rule concurrently be connected to the same potential as
with varying temperature, vibration or the VLT frequency converter.
varying load. Replaced defective control cards must
Faults that are difficult to trace and that be placed in antistatic packing. The
cannot be located by testing. packing from the new card could be
used for this purpose.
Use the flow charts The fault location procedure on the The flow chart layout is generally in a
following flow charts takes as its starting form applicable to all VLT frequency con-
point the main faults affecting the motor, verters, although at certain points it is
i.e. necessary to distinguish between some of
Motor runs unevenly the types.
Motor does not run
Motor does not brake
1) 2)
Symptom If the motor runs unevenly,
but no fault is indicated,
Motor runs unevenly the cause can be incorrect
setting of the VLT
frequency converter. Set
the frequency converter
correctly.
If the new settings cannot
make the motor run
evenly, call for Danfoss
assistance.
3) 4)
Symptom Is there backlight in the
display ? 6)
Motor does not run
No Yes Are fault messages
displayed?
5) No Yes
see: 8)
7)
Symptom
8) 9)
Symptom Have pre-fuses for the
VLT frequency converter
No message or blown?
backlight in display 10)
No Yes Call Danfoss
for assistance
11)
only VLT types 3060 - 3250
Have the built-in mains
fuses blown?
Yes
12)
Call Danfoss
for assistance
13)
Is the control card
overloaded? Disconnect
all control signal plugs
on the control card.
Does the fault disappear?
14)
No Yes Ensure that the previous
points are OK:
15) The fault can be caused
by short-circuiting on the
Call Danfoss control signals.
for assistance The 24 V supply might
be short-circuited.
19) 20)
Symptom Start the VLT frequency
converter by pressing Start
21) 22)
Is the display frozen, Check whether the
i.e. the display cannot following precautions have
be changed or is been taken!
undefinable? Have screened cables
been used?
No Yes Are the screened cables
connected correctly?
23) Yes
Is the motor connected
correctly and are all
motor phases OK?
Yes
24)
The frequency converter
must be set to run using
local references.
25)
Check whether the control
signals to the control card
are OK.
29) 30)
31)
Are both LEDs "braking"
and "overload" on the
brake control card active
during braking period
(yellow and red LEDs)?
33)
Yes Are the connections to
the brake control card
OK?
32) Yes
Connection of Beside the control card of the VLT The electrical connection between the
option cards frequency converter you will see a free option card and the standard control card
space. is done by means of the plugs FK1 - FK4.
This space is used for option cards.
The number of option cards is increasing
Mount the option card using the groove in and the functions of specific option cards
the right-hand side of the aluminium tray, will be described in a separate manual.
and the two screws.
Mounting of Unplug the ribbon connector, the small The next card has a two-pin molex connec-
fan option cable and the card ground wire. tor placed as shown. Plug the fan
Remove the control card and the shield cable into the molex connector.
together.
Place the fan option on the extrusion, mak- Replace the control card carefully, and
ing sure that the fan-option mounting holes plug in the ribbon connector, the small
are aligned with the enclosure. cable and the cards ground wire.
001 SETUP OPERATIO S) 101 SPEED CONTROL 4,S) 201 MIN. FREQUENCY 4,S)
SETUP 1 SLIP COMPENSATED 0
002 MENU SET COPY 102 SET CUR.LIMIT S) 202 MAX. FREQUENCY 4,S)
DO NOT COPY PREPROGRAMMED VALUE DEPENDING ON UNIT
003 LOCAL / REMOTE S) 103 MOTOR POWER 203 JOG FREQUENCY 4,S)
REMOTE DEPENDING ON UNIT 10
004 LOCAL SPEED S) 104 MOTOR VOLTAGE 204 DIG. REF. TYPE 4,S)
DEPENDING ON UNIT SUM
005 VALUE AT MAX S)
4,S)
105 MOTOR FREQ 205 REF. 1 DIGITAL
006 LOCAL RESET S) DEPENDING ON UNIT 0
ENABLE
106 AUTO MOTOR SET 206 REF. 2 DIGITAL 4,S)
007 LOCAL STOP S) OFF 0
ENABLE
107 MOTOR CURRENT 4,S) 207 REF. 3 DIGITAL 4,S)
008 LOCAL FWD/REV S) DEPENDING ON UNIT 0
DISABLE
108 MOTOR MAG. AMP 4,S) 208 REF. 4 DIGITAL 4,S)
009 LOCAL JOG S) DEPENDING ON UNIT 0
DISABLE
109 START VOLTAGE 4,S) 209 CURRENT LIMIT 4,S)
010 LOC REFERENCE S) DEPENDING ON UNIT DEPENDING ON UNIT
ENABLE
110 START COMP. 4,S) 210 LO FREQ. WARN 4,S)
011 ENERGY COUNTER S) DEPENDING ON UNIT 0
NO RESET
111 U/f RATIO 4,S) 211 HI FREQ. WARN 4,S)
012 HOUR COUNTER S) DEPENDING ON UNIT 132 Hz
NO RESET
112 SLIP COMP. 4,S) 212 LO CURR. WARN 4,S)
4
) Available in all 4 setups.
S
) Can be changed in start mode (running motor).
*) Where Depends on VLT is stated, the factory setting pa-
rameters are shown on the tables on the following pages.
304 POWER FAIL S) 404 INPUT 27 S) 504 Q-STOP S) 605 DISPLAY SELECT S)
STOP MTR. COAST LOGIC OR STANDARD DISPLAY
4)
305 FLYING START 405 INPUT 29 S) 505 DC-BRAKE S) 650 VLT TYPE
DISABLE JOGGING LOGIC OR
4
) Available in all 4 setups.
S
) Can be changed in start mode (running motor).
*) Where Depends on VLT is stated, the factory setting pa-
rameters are shown on the tables on the following pages.
Factory settings
3002 3003 3004 3006 3008 3011 3016 3022 3032 3042 3052 3060 3075 3100 3125 3150 3200 3250
Parameter
MG.30.A7.02 - VLT is a registered Danfoss trademark
103 Motor power 0.75 1.5 2.2 4 5.5 7.5 11 15 22 30 37 45 55 75 90 110 132 160
104 Motor voltage 380 380 380 380 380 380 380 380 380 380 380 380 380 380 380 380 380 380
107 Motor current 2 3.7 5.3 9.1 12.2 15.8 22.8 31.1 42.8 59.3 72 86.2 106.3 134.1 166.8 197.8 230 272.4
108 Motor magnetizing current 1.1 2 2.4 3.6 4.6 5.4 8.6 10.2 13.1 20 20.3 28 34.5 40.1 53.6 60.3 67.8 77.5
109 Start voltage 40 39.1 36.8 35.6 35.4 35.2 35 34.9 34.9 36.8 36.2 36.8 36.7 36.7 36.7 36.7 36.7 36.7
110 Start compensation 16 5 5 2.3 1.6 1.19 0.7 0.46 0.28 0.21 0.23. 0 0 0 0 0 0 0
111 U/F ratio 6.84 6.94 7.03 7.13 7.13 7.18 7.2 7.28 7.3 7.32 7.22 7.33 7.31 7.3 7.3 7.3 7.3 7.3
112 Slip compensation 4.86 3.8 3.2 2.6 2.08 1.72 1.24 1.14 0.84 0.74 0.52 0.56 0.52 0.36 0.32 0.28 0.26 0.24
113 Negative slip comp. 4.86 3.8 3.2 2.6 2.08 1.72 1.24 1.14 0.84 0.74 0.52 0.56 0.52 0.36 0.32 0.28 0.26 0.24
209 Current limit 3.5 6.6 9 16 20.8 25.6 38.4 51.2 70.4 97.6 116.8 129 158 209 252 308 365 453
232 Current, min. value 0.6 1 1.2 1.8 2.3 2.7 4.3 5.1 6.6 10 10.2 14 17.3 20.1 26.8 30.2 33.9 38.8
308 D.C. brake voltage 28 25 28 21 14 13 11 12 11 21 20 20 0.0 0.0 0.0 0.0 0.0 0.0
151
Factory settings
460/500 V
3002 3003 3004 3006 3008 3011 3016 3022 3032 3042 3052 3060 3075 3100 3125 3150 3200 3250
Parameter
103 Motor power 0.75 1.5 2.2 4 5.5 7.5 11 15 22 30 37 55 75 90 110 132 160 200
MG.30.A7.02 - VLT is a registered Danfoss trademark
104 Motor voltage 460 460 460 460 460 460 460 460 460 460 460 460 460 460 460 460 460 460
107 Motor current 1.8 3.4 4.8 7.6 10.0 13.7 20.0 25.0 35.5 48.5 61.8 84.7 110.8 137.8 163.4 190.0 225.0 285
108 Motormagnetizingcurrent 1.1 2.2 3.4 4 4.8 6.0 9.3 10.6 11.1 16.2 20.8 29.5 33.1 44.3 49.8 56.0 64.0 79
109 Start voltage 49.1 46.3 45.8 45.2 45.0 44.9 44.7 44.3 43.8 44.6 44.5 47.0 47.0 47.0 47.0 47.0 47.0 47.0
110 Start compensation 12.30 8.40 5 2.8 1.5 0.85 0.85 0.75 0.51 0.31 0.32 0 0 0 0 0 0 0
111 U/F ratio 7.30 7.30 7.10 7.40 7.46 7.30 7.40 7.30 7.30 7.40 7.40 7.50 7.40 7.50 7.50 7.50 7.50 7.50
112 Slip compensation 3.33 2.50 2.67 2.50 1.08 1.42 1.75 1.13 0.52 0.60 0.62 0.30 0.30 0.27 0.23 0.22 0.20 0.18
113 Negative slip comp. 3.33 2.50 2.67 2.50 1.08 1.42 1.75 1.13 0.52 0.60 0.62 0.30 0.30 0.27 0.23 0.22 0.20 0.18
202 Max. frequency 60.0 60.0 60.0 60.0 60.0 60.0 60.0 60.0 60.0 60.0 60.0 60.0 60.0 60.0 60.0 60.0 60.0 60.0
209 Current limit 3.4 5.4 .7. 13.1 17.6 23.2 34.7 44.6 67.2 86.4 104.0 116.0 144.0 186.0 234.0 270.0 360.0 453.0
232 Current, min. value 0.6 1.1 1.7 2.0 2.4 3.0 4.7 5.3 5.6 8.1 10.4 14.8 16.6 22.2 24.9 28.0 32.0 39.5
200/230 V
3002 3003 3004 3006 3008 3011 3016 3022 3032 3042 3052
Parameter
104 Motor voltage 200 200 200 200 200 200 200 200 230 230 230
107 Motor current 3.8 7.8 10.0 17.2 25.0 32.0 46.0 57.2 80.0 104.0 130.0
108 Motor magnetizing current 2.4 3.2 4.6 6.8 8.8 10.0 14.4 21.6 28.8 27.1 37.4
109 Start voltage 21.3 20.2 19.3 19.4 19.5 19.4 19.4 19.5 22.3 21.9 22.2
110 Start compensation 4.2 2.10 1.86 0.79 0.50 0.35 0.21 0.11 0.00 0.00 0.00
111 U/F ratio 3.75 3.70 3.80 3.80 3.80 3.80 3.80 3.80 3.70 3.65 3.70
112 Slip compensation 4.6 2.56 2.80 1.60 2.00 1.90 1.80 1.66 0.75 0.37 0.42
113 Negative slip comp. 4.6 2.56 2.80 1.60 2.00 1.90 1.80 1.66 0.75 0.37 0.42
209 Current limit 6.7 12.5 17.0 30.0 40.0 51.2 73.6 97.6 120.0 156.0 195.0
215 Ramp-up time 1 1 1 10 10 10 10 10 30 30 30
232 Current, min. value 1.2 1.6 2.3 3.4 4.4 5.0 7.2 10.8 14.4 13.6 18.7
308 D.C. brake voltage 22 16 21 17 14 11 10 10 0.0 0.0 0.0
Continued
P T
Parallel connection of motors ......... 50 Technical data ................................. 23
Parameter description ............. 82, 83 Technology ....................................... 9
PARAMETER MODE ...................... 61 Terminal 53Analogue input voltage 111
Parameternumbering ...................... 65 Terminal 60Analogue input current 111
Personal display select ................. 122 The control panel ............................ 60
Pre-fuses ........................................ 45 Thermal motor protection ............. 130
Product range ................................. 14 These rules concernyour safety ....... 2
Programmable control inputs Time out .......................................... 64
andsignal outputs in 4 ..................... 11 Time out function .......................... 112
Programming keys ............................ 6 Time out(Time out) ....................... 112
Proportional gain ............................ 93 Travelling the menu ........................ 65
Protected against mains Travelling throughthe menu ............ 65
disturbance ..................................... 11 Trip delay at current limit ................ 99
Trip delay at inverter fault ............. 100