Control Compresor
Control Compresor
MAM-KY02S B -
Monitor-200
USER
MANUAL
1
VOTE OF THANKS
Thank you for your trustworthy and select of PLOT air compressor controller !
Shenzhen Plot Electronic Co., Ltd specializes on the manufacture and R&D of air
compressor controller. We are devoted to win customer trust through our high
We try our best to ensure the completeness and correctness of the manual, but
PLOT Company shall reserve the rights for continuous research and improvement on
its products and assume no obligation for the modification and improvement on the
without notice.
Please feel free to contact our after-sale service center if you encounter any
2
NOTICE
Please read all the operation manual before operating the set and keep this manual for further
reference.
Installation position shall be considered carefully in order to ensure good ventilation and reduce
electromagnetic interference.
Wiring shall be performed respectively according to regulations for heavy and weak current to reduce
electromagnetic interference.
RC snubber must be connected to the two terminals of coil (such as AC contactor ,valve, etc),which
are controlled by relay output.
Correct ground connection (the third ground)can help increase product capacity of resisting signal
interference.
Features
Chinese / English display.
Short circuit, current block, current open phase, current overload, current unbalance protection for motor
On-off control and running control of motor.
Prevention for air compressor reversal
Temperature measurement , control and protection
Control pressure balance by adjust load rate automatically
High integration , high reliability ,high cost performance.
Remote control/Local control.
Block mode/Independent mode.
RS-485 communication function,
3
Contents
1,Basic Operation..................................................................................................................................................... 5
1.1, Button Explanation................................................................................................................................... 5
1.2, Status Display and Operation .................................................................................................................. 6
2, Contoller Function and Technical Parameter ................................................................................................. 12
3, Model and Specification .................................................................................................................................... 12
3.1, Model explanation .................................................................................................................................. 12
3.2Power specification sheet for corresponding motor. .............................................................................. 13
4, Installation.......................................................................................................................................................... 13
4.1, Mechanical Installation .......................................................................................................................... 13
4.2, Electrical Connections............................................................................................................................ 15
5, Alarm Function .................................................................................................................................................. 16
5. 1Monitor Indication............................................................................................................................... 16
5.2,Controller Indicator ................................................................................................................................ 16
6,Controller Protection.......................................................................................................................................... 17
7, Troubleshooting ................................................................................................................................................. 18
7.1This Fault Review ................................................................................................................................. 18
7.2Common Failures and Causes:............................................................................................................ 18
8, Schematic Diagram........................................................................................................................................ 20
4
1,Basic Operation
1.1, Button Explanation
Picture 1
IStart Button:
1,When compressor is at stop status, press this button to start the compressor.
2,When compressor is set as master ( No.1 ) in block mode ,press this button to start the compressor
and activate block mode function at the same time.
OStop Button
1,When the compressor is at running status, press this button to stop the compressor;
2,When compressor is set as master (No.1 ) in block mode ,press this button to stop compressor and
block mode function as well.
SSet Button:
1. When modifying data, press this button after modification to save and confirm the modified data.
2. When the compressor is at password setting status ,press this button to save and confirm the
password
SCREW COMPRESSOR
RUN PARAMETER
CALENDAR
CUSTOMER
PARAMETER
Press or to move the cursor to RUN PARAMETER, then press to switch to secondary
menu:
MOTORFAN CURR
TOTAL RUN TIME
THIS RUN TIME
MAINTENANCE PARA
CURR(A)R S T
6
MOTOR 56.1 56.2 56.0
FAN 4.1 4.1 4.1
Press RESET to return to the previous menu or the main menu. If no operation at the current menu for 120
seconds , controller will automatically return to the main menu and turn off the back light simultaneously.
According to above method, use move down ,move up button , enter button and return button
RESET to check TOTAL RUN TIME,THIS RUN TIME,MAINTENANCE PARA,FAULT RECORD,
PROD.DATESERIAL,THIS FAULT and return to previous menu.
1.2.2, Calendar
Check and set time of controller
TIME
2004-2-22
WEEK0
12:46:59
The check and modification of CUSTOMER PARAMETER is similar with RUN PARAMETER. Take
UNLOAD P as example: Move or to CUSTOMER PARAMETER and then press to switch to below
menu
SET PT
SET TIME
OPERATION MODE
BLOCK PARAMETER SET
LOAD P00.65MPa
UNLD P00.80MPa
FAN START T0080
FAN STOP T0070
Move the cursor to item LOAD P, then press to switch to the following menu which requires a user
password input.
INPUT PASSWORD
****
Note: User password can be modified in customer parameter and FACTORY PARAMETER
7
is fixed as
In this menu, the first data bit of password starts blinkingpress or to modify the first bit of
passwordPress to move the cursor to the next data bit, modify the second data of password in
accordance with the above , and modify the third and fourth data of password in sequence. PressS to
confirm the input data and the menu will switch to the following menu after verification:
9
In BLOCK mode, one compressor will stop or
BLOCK UNLD P 00.78MPa unload when master AIR P is above this set
data
In BLOCK mode, when master sends two
BLOCK DELAY 0020S commands continuously, second command
signal delays for this set data
Record total running time of oil filter. If
OIL FILTER 0000H changing new oil filter, the data should be reset
by manual operation.
Record total running time of O/A separator. If
O/A
0000H changing new O/A separator, the data should
SEPERATOR
be reset by manual operation
CLR
Record total running time of air filter .If
MAINTENANCE
AIR FILTER 0000H changing new air filter, the data should be reset
TIME
by manual operation
Record total running time of lubricant. If
LUBE 0000H changing new lubricant, the data should be
reset by manual operation
Record total running time of grease. If
GREASE 0000H changing new grease, the data should be reset
by manual operation
1, Alarm prompt when total running time of oil
filter is above the set data .
OIL FILTER 2000H
2,Set this data to 0000 , alarm function for
oil filter running time is not activated
1, Alarm prompt when total running time of
O/A O/A separator is above the set data.
2000H
SEPERATOR 2,Set this data to 0000 ,alarm function for
O/A separator running time is not activated
1, Alarm prompt when total running time of air
MAX LIFE TIME filter is above the set data.
AIR FILTER 2000H
2,Set this data to 0000 , alarm function for
air filter running time is not activated
1, Alarm prompt when total running time of
lubricant is above the set data.
LUBE 2000H
2, Set this data to 0000, alarm function for
lubricant running time is not activated.
1, Alarm prompt when total running time of
grease is above the set data.
GREASE 2000H
2,Set this data to 0 , alarm function for
grease running time is not activated
CHINESE/ ENGLISH: Displays in English
LANGUAGE ENGLISH
ENGLISH CHINESE: Displays in Chinese
ENABLE/ Enable: PHASE PRO function is activated
PHASE PRO
DISABLE Disable: PHASE PRO function is not activated
10
NEW USER User could modify the user password by old
**** ****
PASSWORD user password or factory password
1.2.4,Factory Parameter
The view and modification of factory parameter requires a factory password, The modification step is
same as customer parameter modification. Main function is as below:
11
2, Contoller Function and Technical Parameter
2.1,Digital input &output9 points of digital input10 points of digital relay output
2.2,Analog input& output 2 points of Pt100 temperature input2 points of 420mA pressure signal input,2
groups of three phases current input (CT provided
2.3,Input voltage of phasesthree phase 380V
2.4,Controller operation power220V50/60Hz12VARecommond20VA
2.5,Measurement :
2.5.1Oil temperature20150Accuracy1
2.5.2Discharge temperature20150Accuracy1
2.5.3Running time0999999H
2.5.4Current0999.9A
2.5.5Pressure01.60MPa Accuracy:0.01Mpa
2.6,Phase protection: When compressor is at stop mode and detects open phase, response time2s
2.7,Motor protection: This controller provides open phase, unbalance and overload protection to motor and
fan.
2.7.1Open phase protectionWhen any phase opens, the response time equals to set timeThis function is not
activated when OPEN PHASE PROTECTION time is set over 20s
2.7.2Unbalance protection: when MAX-MIN current >= SET DATA *MIN current/10 ,respond time is
5s
2.7.3Protection features of overload (time unit: second)please see following tabletable 2.1.1for your
reference. MultipleIactualIset ,response time is shown in following table (table 2.1.1) according to
Response timeS 60 48 24 8 5 1
12
3.2Power specification sheet for corresponding motor.
Corresponding
Current range
Specification main motor Remark Description
(A)
power (KW)
KY0220 820 Below 11 Fan has three
KY0240 1640 11-18.5 levels of current,
KY02100 100 22-45 such as 0.2-2.5A,
KY02200 200 55-90 1-5A and 4-10A,
KY02400 400 110 determined-by
KY02600/5 600/5 200-250 With CT current of motor
4, Installation
4.1, Mechanical Installation
4.1.1, CT Installation
The CT shall be installed at a place where the current of motor cable can be measured, thus, controller can
be set according to instructions on motor nameplate, and the detailed dimension is shown as below:
A
B
13
4.1.2,Controller Installation
When install the controller, room should be left around controller for wiring. The specific dimension is
shown as below:
1IndicatorIN
The corresponding digital input terminal of 00010203
04050607 is 20 1918
1716151413.
2IndicatorOUT
The corresponding digital input terminal of 00010203
040506070809 is 2728 29303135
36373839
3Power IndicatorPWR
4Run indicatorRUN
5Error indicatorERR
250
50
I
:80C
0.80MPa
: O
150
138
S 14 22
14
4.2, Electrical Connections
* Note : Electromagnetism coil shall be connected nearest with RC snubber during wiring, Dotted line is
15
5, Alarm Function
5. 1Monitor Indication
5.1.1, Air Filter Alarm
The text displays LUBE TIME END when running time of the lubricant is exhausted.
The text displays GREASE TIME END when running time of the grease is exhausted.
5.1.6, Discharge Temperature High Alarm
The text displays DISC T HIGH when DISC T is higher than ALARM DISC T set in FACTORY
PARAMETER.
5.2,Controller Indicator
Terminal 394041424346
Digital output OUT00~09 corresponding indicator on
47495051digital output
16
6,Controller Protection
6.1,,Motor protection
MAMKY02Scompressor controller provide short circuit ,block, overload, lack phase, unbalance
protection to motor.
Electronic
Failure display Reason
failure
Short circuit Display Motor/FAN OVER LOAD Short circuit or wrong current set
Overload, bearing wear and other mechanica
Current Block Display Motor/FAN BLOCK
l failure
Overload, bearing wear and other mechanica
Overload Display Motor/FAN OVERLOAD
l failure
Power supply, contactor and open phase of
Lack phase Display Motor/FAN *LACK PHASE
motor
Poor contact of contactor, inside open-loop of
Unbalance Display Motor/FAN UNBALANCE
motor
17
7, Troubleshooting
7.1This Fault Review
Alarm and stop caused by the external parts of controllers may be removed by checking THIS FAULT or
FAULT RECORD, method is shown as below:
Press to move the cursor to RUN PARAMETER menu, then press ,the secondary menu will show as
below:
MOTOR FAN CURR
TOTAL RUN TIME
THIS RUN TIME
MAINTENANCE
FAULT RECORD
PROD.DATESERIAL
THIS FAULT
Move the cursor to THIS FAULT menu Then press to switch to the following menudisplay failure
High discharge Bad vent condition, Oil shortage Check the vent condition and lubricant amount
temperature etc. etc.
Temperature Sensor
Cable broken or PT100 failure Check the wiring and PT100
Failure
Pressure too high or the pressure
High Pressure Check the pressure and the pressure sensor
sensor failure
Cable broken, Sensor failure or
Pressure Sensor Failure Check the wiring and pressure transmitter
the cables connect reversely
Lack water Water pressure switch failure Check water pressure switch
18
mechanical failure or wrong set
data etc.
Current unbalance, contactor
Unbalance failure or the internal open loop of Check the power, contactor and the motor
the motor
Phase sequence reversal or open
Wrong Phase Sequence Check the wiring
phase
Fan failure, contactor failure,no
Fan fail to run Check wiring
control output
Motor overload during Master start time set to less than Reset the master start time longer than star
start the star delta delay time delay + 2 seconds
The emergency stop button is
Main Contactor shakes Check if the coil of contactor connects with
loose or controller is reset by
frequently RC snubber or not
interference
19
8, Schematic Diagram