Project Date: 18.01.2017 Title Cooling Water Pressure Loss: Tarun Engineering Department
This document is a project report from Tarun in the Engineering Department dated January 18, 2017. It analyzes the pressure loss in a pipe with a diameter of 0.0254 meters carrying a flow rate of 2.4 cubic meters per hour of water at 1000 kg/m3 density. It calculates the velocity, Reynolds number, friction coefficient from a Moody diagram, and resulting head and pressure losses of 10.8595 meters and 1.0642 bars, respectively, over an equivalent length of 100 meters.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
34 views1 page
Project Date: 18.01.2017 Title Cooling Water Pressure Loss: Tarun Engineering Department
This document is a project report from Tarun in the Engineering Department dated January 18, 2017. It analyzes the pressure loss in a pipe with a diameter of 0.0254 meters carrying a flow rate of 2.4 cubic meters per hour of water at 1000 kg/m3 density. It calculates the velocity, Reynolds number, friction coefficient from a Moody diagram, and resulting head and pressure losses of 10.8595 meters and 1.0642 bars, respectively, over an equivalent length of 100 meters.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 1
Tarun
Engineering Department
Project Date : 18.01.2017
Title Cooling Water Pressure Loss
Pipe Size DN25, d 0.0254 m
Flow Rate, q 2.4000 m3/h Equivalent Length, l 100.0000 m Density, 1000.0000 Kg/m3 Dynamic Viscosity, 0.0010 Ns/m2 at 20C Velocity, v 1.3164 m/s Reynolds No., Re 33368.5739 *v*d/ Roughness, e 0.1000 mm Relative Roughness, e/d 0.0039 Friction Coeff., f 0.0312 to be calculated From moody diagram
Head Loss, P 10.8595 m (f*l*v*v)/(2*d*g)
Pressure Loss, P 1.0642 Bar (f*l**v*v)/(2*d) or 106.4227 kN/m2