Basic Fire Protection Systems Used in Oil
Basic Fire Protection Systems Used in Oil
In any oil & gas plant or refinery unit there are many hazardous fluids & gases
present or generated. These fluids & gases can be flammable or inflammable in
nature and can cause fire in the facility destructing the assets, pollution to the
environment & fatality to human life.
To prevent fire from happening the facility is to be protected with some fire
protection system is provided based on the hazardous nature of the fluids &
gases. The normal fire protection system which are generally present in the
plant are explained below:
1. Firewater Systems
Firewater systems shall be in accordance with NFPA 13 Standard for
the Installation of Sprinkler Systems and the Technical Requirements.
Risers or vertical pipe 3 NPS and larger shall have a flanged joint or a
mechanical coupling at each deck level.
Changes in pipe size shall be made with a one piece reducing fitting.
Reducing bushings, couplings and unions shall not be acceptable.
All sprinkler pipe and fittings shall be designed and installed so that the
firewater system can be drained completely, including both wet and dry
type systems. Branch lines shall include a minimum slope of 1/2 for
each 10-0 of pipe run. Cross and feed mains shall include a minimum
slope of 1/4 for each 10-0 of pipe run.
Firewater systems shall minimize low point traps to make the system as
self draining as reasonably possible. Where unavoidable, low point
traps shall be provided with drain valves. Drain valves shall also be
provided at the ends or remote points in the system. The minimum size
for drain valves shall be 1 NPS.
2. Foam Systems
General
o The water line to each high back-pressure foam maker inlet shall
be valved separately.