The PM1200 is a power meter that measures voltage, current, frequency, power factor, active and reactive power, and energy. It has accuracy of ±1% for power, current, voltage, energy, and power factor measurements. Communication is via an RS485 port using Modbus protocol. It is designed for indoor installation and has an IP51 rating. Key specifications include a measurement range of 50mA to 6A for current and 80 to 480V for voltage.

Uploaded by

Adhyartha Keraf
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
110 views

METSEPM1200: Product Datasheet

The PM1200 is a power meter that measures voltage, current, frequency, power factor, active and reactive power, and energy. It has accuracy of ±1% for power, current, voltage, energy, and power factor measurements. Communication is via an RS485 port using Modbus protocol. It is designed for indoor installation and has an IP51 rating. Key specifications include a measurement range of 50mA to 6A for current and 80 to 480V for voltage.

Uploaded by

Adhyartha Keraf
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Product datasheet METSEPM1200

Characteristics PM1200 power meter with energy and demand - with


communication

Main
Range of product PowerLogic PM1000
Device short name PM1200
Product or component type Power meter

Complementary
Power quality analysis Up to the 9th harmonic

Itisthedutyofanysuchuserorintegratortoperformtheappropriateandcompleteriskanalysis,evaluationandtestingoftheproductswithrespecttotherelevantspecificapplicationorusethereof.
Type of measurement Voltage
Current
Frequency
Power factor
Active and reactive power
Active and reactive energy
[Us] rated supply voltage 44...277 V DC
44...277 V AC (50/60 Hz)

Theinformationprovidedinthisdocumentationcontainsgeneraldescriptionsand/ortechnicalcharacteristicsoftheperformanceoftheproductscontainedherein.
Thisdocumentationisnotintendedasasubstituteforandisnottobeusedfordeterminingsuitabilityorreliabilityoftheseproductsforspecificuserapplications.
Network frequency 50/60 Hz

NeitherSchneiderElectricIndustriesSASnoranyofitsaffiliatesorsubsidiariesshallberesponsibleorliableformisuseoftheinformationcontainedherein.
Power consumption in VA < 3 VA at 240 V AC
Display type LED
Display resolution 3 lines with 4 digits
Sampling rate 20 samples/cycle
Measurement current 50 mA...6 A
Analogue input type Current 0...5 A (impedance <= 0.1 Ohm)
Current 0...1 A (impedance <= 0.1 Ohm)
Measurement voltage 80...480 V AC 50/60 Hz phase to phase
0 V...999 kV AC 50/60 Hz with external VT
Measurement accuracy 1 % power
1 % current
1 % voltage
1 % energy
0.1 % frequency
1 % power factor
1 % apparent power
Accuracy class Class 2 (reactive energy according to IEC 62053-23)
Class 1 (active energy according to IEC 62053-21)
Communication port protocol Modbus: 19.2 kbauds,
Communication port support RS485

Environment
Electromagnetic compatibility Electrostatic discharge immunity test, conforming to IEC 61000-4-2
Susceptibility to electromagnetic fields, conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test, conforming to IEC 61000-4-4
1.2/50 s shock waves immunity test, conforming to IEC 61000-4-5
Conducted RF disturbances, conforming to IEC 61000-4-6
Immunity to impulse waves, conforming to IEC 61000-4-12
Immunity to microbreaks and voltage drops, conforming to IEC 61000-4-11
Conducted and radiated emissions class class A, conforming to CISPR 11
Mounting mode Flush-mounted
Mounting support Panel
Type of installation Indoor installation

1/2
Overvoltage category III
IP degree of protection IP51 (front face) conforming to IEC 60529
IP40 (back) conforming to IEC 60529
Relative humidity 5...95 %
Ambient air temperature for operation -10...60 C
Ambient air temperature for storage -25...70 C
Operating altitude 0...2000 m
Standards IEC 62053-21
IEC 62052-11
Width 96 mm
Depth 80 mm (embedded)
Height 96 mm
Product weight 0.4 kg