Banco de Transformadores y Grupos de Conexión
Banco de Transformadores y Grupos de Conexión
GRUPOS DE CONEXIN
Brito Wilson
Facultad de Ingeniera Elctrica y Electrnica.
Quito, Ecuador
[email protected]
Conexin
Abstract Most Common used transformer is the three phase
transformer and it is because the transmission and distribution of TABLA I
electrical energy in Ac Three Phase System this because its CONEXIN YY0
possible to distribute more power with this system. There are two
alternatives in order to make a three phase transformer, the first
choice is build a single one using only one core and the second
choice consist in using three single phase transformer. Using the
Yy0
first choice there are different kind of connections, the first letter Primario Vl1 Vl2 Vl3 Vf iL
means how the High voltage side is connected, the number means
how many times there is out of phase 30 degrees, and the second
Carga 1 212 209 212,2 120 2,39
letter means how the low voltage side is connected, in this inform Carga 2 211 207,5 211,3 119 4,01
we will test the Yy0, Dy5 and Yd11. We will see that the single core
transformer has a better performance than using a transformer
Carga 3 210 206,2 210,6 119 5,96
bank, however using the transformer bank has some advantages. Secundario Vl1 Vl2 Vl3 Vf iL
Carga 1 195 215 197,3 119 1,7
Index Terms Hysteresis, Magnetic Circuits, Magnetic Flux.
Carga 2 184 231,8 189,9 117 3,63
Carga 3 166 205,6 186,4 116 6,34
I. INTRODUCCION
Carga 3 sin 168 207,1 189,4 137 6,36
E L transformador ms utilizado actualmente es el trifsico y
esto se debe a que la transmisin y distribucin de energa
elctrica se realiza en un sistema de corriente alterna trifsica.
Neurto
II. INFORME
= (1) = cos() (3)
3
Y ya que las cargas del banco de cargas eran resistivas:
En el momento que se retira un transformador el circuito
equivalente sera algo similar a esto:
cos() = 1 (4)
= (5)
Yy0
Entrada Pl1 Pl2 Pl3
1252,20 1228,95 1255,18
Salida con 1049,90 1303,50 1181,78
Neutral
Rendimiento 83,85 106,07 94,15
Salida sin 1069,12 1317,16 1204,58
Neutral
Rendimiento 85,38 107,18 95,97
Fig. 2. Conexin Delta/Delta
TABLA V
RENDIMIENTO CONEXIN DY5
Conexin Y/Delta
TABLA VI
RENDIMIENTO CONEXIN YD11
Yd11
Entrada Pl1 Pl2 Pl3
331,36 337,12 336,32
Salida 310,80 311,08 316,13
Rendimiento 93,80 92,28 94,00
Este arreglo es muy til cuando los voltajes no son muy altos y
es usada debido a que incluso cuando no se tiene cargas
balanceadas los voltajes de fase permaneces substancialmente
iguales
Desventajas del transformador de un solo cuerpo
Dificultad de reparacin
Mayor peligro de dao colateral
V. REFERENCIAS