VLC Install Guide
VLC Install Guide
Installation Guide
May 2011
Document Number: 13718_04
Part Number: 18935
VESDA VLC Installation Guide VESDA by Xtralis
This document is subject to copyright owned by Xtralis AG (Xtralis). You agree not to copy, communicate to the public, adapt, distribute, transfer, sell,
modify or publish any contents of this document without the express prior written consent of Xtralis.
Disclaimer
The contents of this document is provided on an as is basis. No representation or warranty (either express or implied) is made as to the completeness,
accuracy or reliability of the contents of this document. The manufacturer reserves the right to change designs or specifications without obligation and
without further notice. Except as otherwise provided, all warranties, express or implied, including without limitation any implied warranties of merchantability
and fitness for a particular purpose are expressly excluded.
General Warning
This product must only be installed, configured and used strictly in accordance with the General Terms and Conditions, User Manual and product
documents available from Xtralis. All proper health and safety precautions must be taken during the installation, commissioning and maintenance of the
product. The system should not be connected to a power source until all the components have been installed. Proper safety precautions must be taken
during tests and maintenance of the products when these are still connected to the power source. Failure to do so or tampering with the electronics inside
the products can result in an electric shock causing injury or death and may cause equipment damage. Xtralis is not responsible and cannot be held
accountable for any liability that may arise due to improper use of the equipment and/or failure to take proper precautions. Only persons trained through an
Xtralis accredited training course can install, test and maintain the system.
Liability
You agree to install, configure and use the products strictly in accordance with the User Manual and product documents available from Xtralis.
Xtralis is not liable to you or any other person for incidental, indirect, or consequential loss, expense or damages of any kind including without limitation,
loss of business, loss of profits or loss of data arising out of your use of the products. Without limiting this general disclaimer the following specific warnings
and disclaimers also apply:
You agree that you have been provided with a reasonable opportunity to appraise the products and have made your own independent assessment of the
fitness or suitability of the products for your purpose. You acknowledge that you have not relied on any oral or written information, representation or advice
given by or on behalf of Xtralis or its representatives.
Total Liability
To the fullest extent permitted by law that any limitation or exclusion cannot apply, the total liability of Xtralis in relation to the products is limited to:
(i) in the case of services, the cost of having the services supplied again; or
(ii) in the case of goods, the lowest cost of replacing the goods, acquiring equivalent goods or having the goods repaired.
Indemnification
You agree to fully indemnify and hold Xtralis harmless for any claim, cost, demand or damage (including legal costs on a full indemnity basis) incurred or
which may be incurred arising from your use of the products.
Miscellaneous
If any provision outlined above is found to be invalid or unenforceable by a court of law, such invalidity or unenforceability will not affect the remainder
which will continue in full force and effect. All rights not expressly granted are reserved.
www.xtralis.com i
VESDA by Xtralis VESDA VLC Installation Guide
Document Conventions
The following typographic conventions are used in this document:
Convention Description
Convention Description
Contact Us
UK and the Middle East Tel: +44 (0) 1442 242 330
www.xtralis.com
ii www.xtralis.com
VESDA VLC Installation Guide VESDA by Xtralis
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the instruction, may cause harmful interference to radio communications. However,
there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television
reception, the user is encouraged to try to correct the interference by one or more of the following measures; re-orientate or relocate the receiving antenna,
increase the separation between the equipment and receiver, connect the equipment to a power outlet which is on a different power circuit to the receiver
or consult the dealer or an experienced radio/television technician for help.
FDA
This VESDA product incorporates a laser device and is classified as a Class 1 laser product that complies with FDA regulations 21 CFR 1040.10. The laser
is housed in a sealed detector chamber and contains no serviceable parts. The laser emits invisible light and can be hazardous if viewed with the naked
eye. Under no circumstances should the detector chamber be opened.
FM
3611 Hazardous Approval Warning: Exposure to some chemicals may degrade the sealing of relays used on the detector. Relays used on the detector are
marked TX2-5V, G6S-2-5V or EC2-5NU.
VESDA detectors must not be connected or disconnected to a PC while the equipment is powered in an FM Division 2 hazardous (classified) location
(defined by FM 3611).
ONORM F3014
ONORM F3014, transport times for all tubes (including capillaries) must not exceed 60 seconds from any hole. This means that the pre- designed pipe
networks that include capillaries cannot be used.
AS1603.8
The performance of this product is dependent upon the configuration of the pipe network. Any extensions or modifications to the pipe network may cause
the product to stop working correctly. You must check that ASPIRE2 approves alterations before making any changes. ASPIRE2 is available from your
VESDA ASD distributor.
AS1851.1 2005
Maintenance Standards. Wherever this document and the AS1851.1 differ, AS1851.1 should be followed in preference to this document.
FM Approved Applications
For open area protection the fire alarm threshold (signal) that initiates an evacuation procedure via the Fire Alarm Panel must not be set less sensitive than
0.625%/ft. The detector can send this signal via the Fire Alarm Panel Output signal or the Pre-alarm output signal.
European Installations
www.xtralis.com iii
VESDA by Xtralis VESDA VLC Installation Guide
EN54-20
The product must use a power supply conforming to EN 54-4.
The product is compliant with EN 54-20 sensitivity requirements provided the following conditions are met:
For a Class A detector, hole sensitivity must be better than 1.5% obscuration/m and transport time less than 60 seconds
For a Class B detector, hole sensitivity must be better than 4.5% obscuration/m and transport time less than 90 seconds
For a Class C detector, hole sensitivity must be better than 10% obscuration/m and transport time less than 120 seconds
These limits should be verified using ASPIRE2 during the design of the sampling pipe network.
The product is compliant with EN 54-20 flow monitoring requirements provided the following conditions are met:
The minor low and minor high flow thresholds should be set at 85% and 115% respectively
The flow through the detector predicted by ASPIRE2 should be in the range 20 to 65 lpm
Additional information:
Class A detectors passed EN 54-20 approvals testing with 30 holes and 0.05% obscuration/m detector sensitivity
Class B detectors passed EN 54-20 approvals testing with 36 holes and 0.09% obscuration/m detector sensitivity
Class C detectors passed EN 54-20 approvals testing with 40 holes and 0.165% obscuration/m detector sensitivity
Approvals
UL
ULC
FM
LPCB
VdS
CFE
ActivFire
AFNOR
VNIIPO
CE - EMC and CPD
EN 54-20
Regional approvals listings and regulatory compliance vary between Xtralis VESDA product models. Refer to www.xtralis.com for the latest product
approvals matrix.
Publication history
Last Update December 2009
Document Number 13718_03
Part Number: 18935
iv www.xtralis.com
VESDA VLC Installation Guide VESDA by Xtralis
Contents
1 Introduction .......................................................................................................................................... 3
2 Cabling Requirements ........................................................................................................................ 4
2.1 Power Cables ................................................................................................................................ 4
2.2 Data Cables ................................................................................................................................... 4
3 Product Specifications........................................................................................................................ 5
4 Product Dimensions ............................................................................................................................ 6
5 Battery Backup Calculations .............................................................................................................. 8
6 Installation ............................................................................................................................................ 9
6.1 Check Procedure Before Installation ............................................................................................. 9
6.2 Removal of Front Cover............................................................................................................... 10
6.3 Removal of Plastic Plugs for Cable Entry .................................................................................... 10
6.4 Securing the Mounting Bracket ................................................................................................... 11
6.5 Attaching the Detector onto the Bracket ...................................................................................... 12
6.6 Connecting the Air Sampling Pipe ............................................................................................... 13
6.7 Cabling Using Glands and Conduits ............................................................................................ 14
6.7.1 Using Glands ..................................................................................................................... 14
6.7.2 Using Conduits .................................................................................................................. 14
6.8 Procedure to Terminate Wires to the Termination Card .............................................................. 15
6.9 Terminating the Power Wires to the Termination Card ............................................................... 15
6.10 Connecting the VESDAnet Wires to the Termination Card (VN model only) .............................. 16
6.11 Terminating the Relay Wires to the Termination Card ................................................................ 17
6.12 Terminating the Auxiliary Wires to the Termination Card ............................................................ 18
6.13 Closing Up the VLC ..................................................................................................................... 18
6.14 Pipe Bonding Check .................................................................................................................... 18
7 Power Up ............................................................................................................................................ 19
7.1 Power Up the System .................................................................................................................. 19
8 Preliminary System Checks ............................................................................................................. 20
8.1 Logging On to the System ........................................................................................................... 20
8.1.1 Logging On with a PC ....................................................................................................... 20
8.1.2 Logging On with a LCD Programmer (For VN Model Only) .............................................. 20
8.2 Normalise the Air Flow and Clearing Air Flow Faults .................................................................. 21
8.2.1 Using a LCD Programmer (For VN Model only) ............................................................... 21
8.2.2 Using a PC ........................................................................................................................ 21
8.3 VESDAnet Communication Check (For VN Model only) ............................................................. 21
8.3.1 Using LCD Programmer .................................................................................................... 22
8.3.2 Using a PC ........................................................................................................................ 22
8.4 Basic Pass/Fail Smoke Test ........................................................................................................ 22
9 Installation Checklist ......................................................................................................................... 23
10 Maintenance and Parts Replacement .............................................................................................. 24
10.1 Exploded view of VLC components ............................................................................................. 25
10.2 Opening the Detector ................................................................................................................... 26
10.3 Closing the Detector .................................................................................................................... 26
10.4 Replacing the Air Filter Cartridge ................................................................................................ 26
10.5 Replacing the Aspirator ............................................................................................................... 27
www.xtralis.com 1
VESDA by Xtralis VESDA VLC Installation Guide
2 www.xtralis.com
VESDA VLC Installation Guide VESDA by Xtralis
1 Introduction
Scope of this Guide
This guide is intended for installation technicians to be able to install, perform basic power and
preliminary device checks for the VLC detector. It does not cover information for commissioning. All
VESDA equipment is to be commissioned by personnel who have attended a VESDA accreditation
course.
Use the checklist in Section 9 to verify that the installation has been correctly completed. Fill out the
details in the checklist sheet for the site and submit it to the appropriate personnel.
CAUTION
* The Detector must only be installed by VESDA accredited personnel.
* The performance of the system depends on the pipe network that was designed for the site.
Any alteration to the pipe network may alter the performance of the system. The ASPIRE2
design tool is to be used to verify the suitability of any pipe network design and subsequent
alterations. ASPIRE2 is available from your distributor.
* The IP rating for the VLC is IP 30. This rating indicates the device is not to be installed
where there is the possibility of any water or liquid falling onto the device.
www.xtralis.com 3
VESDA by Xtralis VESDA VLC Installation Guide
2 Cabling Requirements
The terminals on the termination card in the VLC will accept wire sizes up to 2.5 sq mm (12 AWG).
Use the power ratings for the detector to determine the required wire sizes.
The power requirements for the detector to operate are as follows:-
The recommended RS485 data cable for interconnecting to other detector units on the VESDAnet
loop is Belden 9841 (or equivalent). The cable characteristics are as follows:-
The maximum specified length for the RS485 cable between any two devices on the VESDAnet
network is 1300m (4000ft).
4 www.xtralis.com
VESDA VLC Installation Guide VESDA by Xtralis
3 Product Specifications
Key Software Features Event log: up to 12,000 events stored on FIFO basis
Smoke level, alarms and faults with time and date stamp
AutoLearn: Minimum 15 minutes, maximum 15 days.
Recommended minimum period 14 days. During
AutoLearn thresholds are NOT changed from pre-set values.
www.xtralis.com 5
VESDA by Xtralis VESDA VLC Installation Guide
4 Product Dimensions
205
(8.07)
Mounting
Bracket
225
(8.86)
112.5
(4.43) 95
(3.74)
112.5
(4.43)
225
(8.86)
Figure 1 Dimensions in mm (inches) of VLC with mounting Bracket (Rear View). E=Cable Entry Point on
Rear of Enclosure
6 www.xtralis.com
VESDA VLC Installation Guide VESDA by Xtralis
www.xtralis.com 7
VESDA by Xtralis VESDA VLC Installation Guide
Use Table 1 to calculate and to determine the battery backup requirements for your fire detection
system.
Remote Display
TOTAL CAPACITY =
STANDBY + ALARM
(mAHr)
DIVIDE BY 1000
MULTIPLY BY BATTERY
FACTOR 1.25 AHr
8 www.xtralis.com
VESDA VLC Installation Guide VESDA by Xtralis
6 Installation
6.1 Check Procedure Before Installation
(a) Do not install your VLC if there are any signs of shipping damage to the product. Inform your
distributor if there is any damage.
(b) Check the model of the VLC is correct as per the design specifications for the site. Refer to the
model number located on the bottom of the detector enclosure.
(c) Identify the location where the detector is to be mounted. The VLC can be mounted on a wall or a
suitable secure surface. There are two allowable mounting positions (see Figure 3) for the VLC:
Mounting the device with the air inlet pipe on the top of the box and with the air exhaust pipe
at the bottom. (Normal Orientation)
Mounting the device with the air inlet pipe at the bottom of the box and with the air exhaust
pipe on the top. (Inverted Orientation)
(d) Verify that the selected mounting location is suitable to fit the detector by test fitting the VLC onto
the actual mounting position. Ensure there is 150mm (6in) of clear space around the air inlet pipe
and cable entry points to allow for pipe and conduit entry.
(e) Verify that the cable entry points and the sampling air pipes are at the correct locations.
(f) Determine the type of fasteners required to attach the mounting bracket onto the mounting
surface. The size of the screw holes on the mounting plate is 8mm (1/3in).
Air Exhaust
Cable Entry Port
(One entry point
Air Inlet Port on rear of
enclosure, not
shown)
Air Exhaust
Port Cable Entry
www.xtralis.com 9
VESDA by Xtralis VESDA VLC Installation Guide
(a) Unscrew the two Philips head screws located on the left and right hand sides of the front cover.
(b) Remove the cover. The front cover is held to the main enclosure with a plastic tie. There is a
cable loom labelled LED CARD that connects the termination card in the enclosure to the LED
card located behind the front cover. If you need to separate the front cover from the main
enclosure perform steps (c) to (d), otherwise go to step 6.3.
(c) Remove the LED CARD cable connector from its socket on the termination card.
(d) Twist the plastic tie by 90 degrees on the cover side and slip the tie out through the slot.
Air Inlet
Cable Entry (One entry
point on rear of
enclosure. Not shown.)
Termination
Card
Aspirator
Enclosure
Cover
Screws
(b) Use your thumb to push out the hole plugs from inside the enclosure.
10 www.xtralis.com
VESDA VLC Installation Guide VESDA by Xtralis
Warning Make sure that there are no electrical wires or plumbing behind the mounting
position before drilling. Ensure the mounting position is flat.
(a) Place the mounting bracket onto the surface and mark out the two mounting screw holes. Refer to
Figure 5 for dimensions. Use a spirit level to ensure the bracket is level.
(b) Use the appropriate fasteners to suit the mounting surface. Secure the bracket to the surface.
www.xtralis.com 11
VESDA by Xtralis VESDA VLC Installation Guide
(b) Mount the detector onto the bracket by placing the four rectangular slots located on the rear of the
detector onto the four bracket tabs. Refer to Figure 6.
(c) Slide the device downwards until it locks onto the tabs and screw in the anti tamper screw. Refer
to Figure 7 for screw location.
(d) Check the unit does not slide off its bracket.
Rectangular Slots X 4
Mounting bracket
Bracket tab X 4
12 www.xtralis.com
VESDA VLC Installation Guide VESDA by Xtralis
Termination
Card
Anti Tamper
Screw
Fuse 1.6A
VESDAnet
Number Aspirator
Air Filter
Cartridge
Figure 7 Location of Anti Tamper Screw and other Components inside the Enclosure
The air inlet port is designed to fit a standard pipe of 25mm (1in) OD. A tapering of the air inlet port
prevents the pipe from being inserted beyond 15mm (5/8in).
Note Where it is common practice to use inch pipe which has a 1 1/16 inch OD, a suitable
adaptor should be used to connect the pipe to the inlet manifold. Such an adaptor is
supplied with the VLC in the appropriate territories.
a) De-burr and square off the end of the sampling air pipe. Ensure the pipe is free from swarf.
c) Insert the pipe into the inlet port ensuring a firm fit. DO NOT glue this connection.
Caution DO NOT GLUE THE AIR INLET AND EXHAUST PIPE CONNECTION THIS ACTION
WILL VOID YOUR WARRANTY
Glued connections makes disconnecting the air sampling pipe from the VLC for
maintenance extremely difficult and will result in damage to the equipment.
www.xtralis.com 13
VESDA by Xtralis VESDA VLC Installation Guide
(a) If using cable glands, use the correct gland size to fit the 25mm (1in) cable entry hole.
(b) Run the wires through the glands and into the VLC enclosure. Use your local codes and electrical
standards for cabling.
(a) Terminate the conduits at the cable entry holes on the sides of the box using the appropriate
conduit connectors.
(b) Run the wires through the conduits and into the VLC enclosure. Use your local codes and
electrical standards for cabling.
Terminal A Terminal B
1 Bias (-) (GND) 1 Shield
2 Reset (-) 2 VESDAnet A (-)
3 Reset (+) 3 VESDAnet A (+)
4 Bias (+) 4 Shield
5 LED (-) (GND) 5 VESDAnet B (-)
6 LED (+) 6 VESDAnet B (+)
7 FIRE (NO) 7 Power (-)
8 FIRE (C) 8 Power (+)
9 PRE-ALARM (NO) 9 Power (-)
10 PRE-ALARM (C) 10 Power (+)
11 FAULT (NO)
12 FAULT (C)
13 FAULT (NC)
Terminal A Terminal B
1 FIRE (NO) 1 Bias (-) (GND)
2 FIRE (C) 2 Reset (-)
3 PRE-ALARM (NO) 3 Reset (+)
4 PRE-ALARM (C) 4 Bias (+)
5 FAULT (NO) 5 LED (-) (GND)
6 FAULT (C) 6 LED (+)
7 FAULT (NC) 7 Power (-)
8 Power (+)
9 Power (-)
10 Power (+)
NC = Normally Close
NO = Normally Open
C = Common
14 www.xtralis.com
VESDA VLC Installation Guide VESDA by Xtralis
Use the appropriate wiring standards for your country or use the following suggested procedure listed
below.
(a) Strip off 5 to 10mm (1/5 to 2/5 in) of outer insulation from each wire.
(b) Twist wire strands together for multi-stranded wire only.
(c) Insert wire into terminal.
(d) Tighten terminal screw.
(e) Check the wire is firmly attached to the terminal.
(f) Ensure no bare wires are exposed at the terminals. The wire insulation must reach to the end of
the terminal.
(g) Check the terminations are correct by referring to the appropriate circuit diagrams in this guide.
a) Refer to Figure 8 or Figure 9 for the power terminals location on the termination card.
b) Connect the power wires to the Power terminals as shown in Figure 10.
Terminal B
GND 7
From 24V Power (-)
Power +24V 8
Supply Power (+)
9 GND
Power (-)
24V Power to
Power (+) 10 +24V Next Device
www.xtralis.com 15
VESDA by Xtralis VESDA VLC Installation Guide
6.10 Connecting the VESDAnet Wires to the Termination Card (VN model only)
a) Refer to Figure 8 for the network terminals location on the termination card.
b) Connect the VESDAnet wires as shown in Figure 11. This diagram is only an example for five
detectors. This wiring method is similar for two or more detectors.
c) Maintain the wiring polarity throughout the network and do not leave any VESDAnet terminals
unconnected.
NOTE: While an Open Loop configuration is possible (refer to System Design Manual), it is
strongly recommended that the Closed Loop configuration be installed to achieve a
fault tolerant loop
NOTE: When a VN model detector is not used in a VESDAnet loop and is to be used as a
stand-alone detector the VESDAnet terminals must be wired as per Figure 12.
Shield 4
Shield Shield 4
4
B- 5
B- B- 5
5
B+ 6
B+ B+ 6
6
Shield
1 Shield 1
A- A-
2 2
A+ A+ 3
3
Shield Shield
4 4
B- B-
5 5
B+ B+
6 6
Detector 5 Detector 4
Terminal B Terminal B
1
Shield
2
A-
3
A+
4
Shield
5
B-
6
B+
16 www.xtralis.com
VESDA VLC Installation Guide VESDA by Xtralis
a) Refer to Figure 8 or Figure 9 for the relay terminals location on the termination card.
b) Connect the relay wires to the terminals as per Figure 13 and your site requirements.
Terminal A Terminal A
1 NO
C 7 NO
C Fire C Fire
2 8
3 NO 9 NO
C Pre-Alarm 10 C Pre-Alarm
4
5 NO 11 NO
6 C 12 C
Fault Fault
7 NC 13 NC
www.xtralis.com 17
VESDA by Xtralis VESDA VLC Installation Guide
a) Refer to Figure 8 or Figure 9 for the Reset, LED and Bias terminals on the termination card for the
RO or VN model.
c) Terminate the RESET, LED and Bias wires as per your site requirements or with reference to
Figure 14
Reset Switch
1 Bias - RESET SWITCH
ISOLATE = CLOSED POSITION
2 Reset - RESET = OPENED POSITION
3 Reset +
4 Bias +
Remote
5 LED + LED
6 LED -
a) Tie all wires together into neat looms using cable ties.
b) Reattach the front cover to the plastic tie and connect the LED CARD connector to the socket on
the termination card if you have removed the cover and the connector.
c) Perform the power up as per section 7 and preliminary checks as per section 8.
d) Close up the VLC and secure the cover with the two screws.
a) Check all the plastic pipe connecting joints are fully sealed and bonded with glue to eliminate
unwanted air leaks. If applicable, check all metal pipe joints are sealed.
b) Check the pipe joint at the air inlet to the VLC in not bonded and fits firmly into the air inlet socket.
c) Check all pipes are securely attached to a mounting surface with the proper fasteners.
d) Check the number and sizes of the sampling air holes on the pipes are correct.
e) Check the routing of the pipes is correct with reference to the site plan.
18 www.xtralis.com
VESDA VLC Installation Guide VESDA by Xtralis
7 Power Up
Caution Powering up the system must be done by VESDA accredited personnel.
(c) Check the DC voltage at the Power terminals on the termination card is between 18 VDC to 30
VDC. Disconnect the power immediately if the supply voltage is above 30VDC or less than
18VDC and troubleshoot the fault.
(d) Replace the fuse when the measured voltage is OK. The system takes approximately 15
seconds to power up during which time an LED test sequence is performed.
Check all the power wires are securely connected to the Power terminals.
Check the polarities of the power wires are correctly terminated.
Check for a blown fuse on the termination card. Refer to Figure 7 for the fuse location.
Note: The detector may show faults immediately after power up and this is normal. Reset the
unit by pressing the RESET switch on the front cover of the detector to unlatch the
relays and fault lights. The fault light on the front cover will light up and this is normal.
Proceed to section 8.
www.xtralis.com 19
VESDA by Xtralis VESDA VLC Installation Guide
(a) Logging onto the system with a PC or a LCD Programmer. See section 8.1.
(c) VESDAnet communication checks for VN models only. See section 8.3
Check with your distributor for the User level and PIN number to log on to the system.
a) Connect the RS232 data cable from the PC output port to the 9 pin programming socket on the
termination card in the detector.
a) A PC-LINK HLI device must be connected between the PC and the 15-pin VESDAnet socket to
program the VN model detector.
b) Connect the RS232 data cable from the PC output port to the 9-pin socket on the PC-Link HLI
device.
c) Connect the 15-pin output port of the PC-LINK HLI device to the 15-pin VESDAnet socket on the
termination card in the detector or to any remote VESDAnet sockets if wired to the detector.
OR
Wait for the programmer to power up. Log in your User level and PIN number into the programmer.
20 www.xtralis.com
VESDA VLC Installation Guide VESDA by Xtralis
8.2 Normalise the Air Flow and Clearing Air Flow Faults
c) It takes approximately 11 minutes for the system to normalise during which time the Green OK
LED flashes twice every second to indicate that normalisation is in progress.
e) Press the Reset/Isolate button on the front cover to reset the detector after Normalisation. All the
fault lights should go off. If any of the fault lights are lit consult the Status menu on the
programmer or the Active Event List on the VSC program to determine the faults and consult your
System Design Manual to rectify.
f) If the unit fails to normalise it is because the measured airflow may be too low. Check for
blockages in the sampling air pipe and check that the exhaust plug has been removed.
a) Refer to the LCD menu tree supplied with each VLC (VN) detector.
d) To check the airflow level, go to the Normalise or Status menu after normalising.
8.2.2 Using a PC
c) From the Device menu, select Normalize Air Flow to start the function.
d) To check the airflow level, select the Current Flow command under Device menu after
normalising.
Note: This test verifies the VESDAnet system is functioning and all devices connected on
VESDAnet are communicating.
a) List all VESDAnet numbers for all devices connected onto the communication loop.
c) Verify the VESDAnet number for each device on the network is shown on the list.
d) If there are some devices not found on the display list, check the VESDAnet cabling to all the
devices is correct.
www.xtralis.com 21
VESDA by Xtralis VESDA VLC Installation Guide
b) Check the displayed list shows all the connected devices and the VESDAnet number for each
device is correct.
8.3.2 Using a PC
b) Check the displayed list shows all the connected devices and the VESDAnet number for each
device is correct.
Note: This test verifies the detector will sense smoke. It does not replace any appropriate
commissioning test.
(a) Isolate the detector by pressing the Reset key for more than 2 seconds.
(d) Wait for one of the red LEDs on the front panel to light up.
(e) If the LED does not light up contact a fully trained accredited VESDA engineer.
(f) Reset the detector by pressing the Reset switch once when the smoke test passes.
22 www.xtralis.com
VESDA VLC Installation Guide VESDA by Xtralis
9 Installation Checklist
Site Name:
Zone:..
Detector Serial Number/s:.
Perform the following checks listed below to ensure that all the necessary items are completed before
handing over to a commissioning engineer.
Name of Installer:..
Signature:...........................................................................
Date: .
www.xtralis.com 23
VESDA by Xtralis VESDA VLC Installation Guide
To work effectively the VLC Detector needs to be supported by a well designed Pipe Network.
The Maintenance Schedule includes the maintenance required for the Pipe Network.
NOTE: The frequency of maintenance checks could vary depending upon local codes and
standards and the environment of the installation.
WARNING: While a VESDA Zone has been isolated, no fire warnings will be issued by the VLC
and any fire will go unreported. Prior to any maintenance or testing:
1. Inform appropriate supervising authority about the risk associated with
isolating a VESDA Zone.
2. Ensure that any ancillary devices dependent on the VLC Detector is/are
enabled by the isolation before work is begun.
24 www.xtralis.com
VESDA VLC Installation Guide VESDA by Xtralis
B
C
J
E
A H
www.xtralis.com 25
VESDA by Xtralis VESDA VLC Installation Guide
Disassembly
Assembly
26 www.xtralis.com
VESDA VLC Installation Guide VESDA by Xtralis
Screws (E)
(F)
(G)
Assembly
1. Check the new aspirator has a gasket on the inlet flange and three attached screws
2. Wipe manifold outlet flange surface (J) if dirty.
3. Do the reverse of disassembly
4. Secure aspirator with three screws
5. Connect removed air hose to pipe on aspirator. Ensure a tight fit over the pipe.
6. Insert Termination Card (B) into interface card (C)
7. Secure the termination card with four screws
8. Connect aspirator cable connector to socket on aspirator. Connector is polarised and only be
inserted one way
9. Check all wires are secured to their connectors or terminals
10. Power ON the detector and check the aspirator is running
11. Close the detector.
END OF GUIDE
www.xtralis.com 27
VESDA by Xtralis VESDA VLC Installation Guide
28 www.xtralis.com